
Air-Conditioners For Building Application
INDOOR UNIT
CMB-WP108V-G
GB
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.

2
22.2 2.3
2.4
[Fig. 2.4.1]
33.2
[Fig. 3.2.1]
C
D
E
B
B
E
AA
H Indoor unit side
G Service space
GService space
(FSub drain pan)
(700)
250120 100
*1
89
A200
B265
450 450
300400
<B>
<A>
G Service space
[Fig. 2.3.1]
<A> Top view
<B> Front view
Model name A B
CMB-WP108V-G 1600 –
*1 Dimensions with which pipe connection can be handled at site
A Inspection hole
B Side of outdoor unit piping
C Control box
D Side of indoor unit piping
E Water inlet
F Sub drain pan
G Service space
H Indoor unit side
E
A
B
G
H
F
D
J
K
D
A
c
def
b
a
H
H1
h1
h2
A Outdoor unit B HBC controller
C Indoor unit
D Less than H=50 m (when the outdoor unit is higher than the indoor unit)
E Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
F Twinning pipe (field supply)
G Less than 110 m H Less than 60 m
I Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)
J Less than 15 m K Less than 15 m
CMB-WP108V-G
Notes:
*1 Indoor units that are connected to the same branch joint cannot be si-
multaneously operated in different operation modes.
(Unit: m)
Item Piping portion Allowable value
Between outdoor unit and
HBC controller (refrigerant pipework)
A 1 10 or less
Water pipework between indoor units
and HBC controller
f 60 or less
Between
indoor and
outdoor units
Above outdoor unit H 50 or less
Below outdoor unit H1 40 or less
Between indoor units and HBC controller h1 15 or less
Between indoor units h2 15 or less
Difference of ele vat ion
1 Hanging method
A: Min. 30 mm
A Hanging bolt ø10 (field supply)
B Washer (field supply)

3
44.1
[Fig. 4.1.2]
4.2 4.3
[Fig. 4.2.1] [Fig. 4.3.1]
4.4
[Fig. 4.4.1] [Fig. 4.4.2]
D
DD
DDFD
A
B
E
*1
C
HBC CONTROLLER
Unit model Model name
High pressure
side
Low pressure
side
PURY-WP200
(HBC CONTROLLER)
CMB-WP108V-G
ø15.88
(Brazing)
ø19.05
(Brazing)
PURY-WP250
ø19.05
(Brazing)
ø22.2
(Brazing)
Connection to water circuit by screw
connections
Note:
*1. Connection of multiple indoor units with one connection (or joint pipe)
• Total capacity of connectable indoor units: Less than 80
• Number of connectable indoor units: Maximum 3 Sets
• Twinning pipe is field supplied.
A To outdoor unit
B End connection (brazing)
C HBC controller
D Indoor unit
E Twinning pipe (field supply)
F Up to three units for 1 branch hole; to tal cap acity: below 80 (but same in cooling/
heating mode)
A Cut here
B Remove brazed cap
A Locally procured insulating material
for pipes
B Bind here using band or tape.
C Do not leave any opening.
D Lap margin: more than 40 mm
E Insulating material (field supply)
F Unit side insulating material
A: 25 cm B: 1.5 – 2 m
A Downward gradient of more than 1/100
B Insulating material C Supporting bracket
D Drain discharge port E Drain hose (200 mm long, accessory)
F Cable tie (accessory) G Hose band (accessory)
A HBC controller B Indoor unit
C Collecting pipe D Please ensure this length is at least 10 cm.

4
55.1
[Fig. 5.1.1]
5.2
6
E
C
D
B
F
G
ATo
HBC controller sample installation
A Expansion tank B Shutoff valve
C Strainer D Pressure reducing valve
E Water inlet F Refrigerant pipes
G Drain pipe
F
E
D
C
B
A
D
DD
DDFD
A
B
E
*1
C
B C ED
A
A Locally procured insulating material
for pipes
B Bind here using band or tape.
C Do not leave any opening.
D Lap margin: more than 40mm
E Insulating material (field supply)
F Unit side insulating material
A To ou tdoor unit
B End connection (brazing)
C HBC controller
D Indoor unit
E Twinning pipe (field supply)
F Up to three units for 1 branch hole; total capacity: below 80 (but in same mode,
cooling/heating)
Water pipework is screw
connections
Note:
*1. Connection of multiple indoor units with one connection (or joint pipe)
• Total capacity of connectable indoor units: Less than 80
• Number of connectable indoor units: Maximum 3 Sets
• Selection of water piping
Select the size according to the total capacity of indoor units to be installed
downstream.
• Please group units that operate on 1 branch.
[Fig. 5.2.2]
[Fig. 5.2.3]
[Fig. 5.2.1]
A HBC controller
B Water pipe
C Pressure reducing valve
D Strainer
E Shut off valve
Indoor unit
Connection size Pipe size
Water inlet Water outlet Water out Water return
PEFY-WP·VMA
Rc 3/4
screw
Rc 3/4
screw
I.D. 20 mm I.D. 20 mm
A Control box
B Power source wiring
C ø21 hole (closed rubber bushing)
D Transmission wiring
E Clip cables here
[Fig. 6.0.1]