Minuteman UPS MCP-E User Manual

MCP-E Series
User's Manual
TABLE OF CONTENTS
MCP-E Series
User's Manual
1. Introduction 2
2. Controls and Indicators 4
4. Operation 13
5. Troubleshooting 17
6. Replacing the Battery 20
English
7. Obtaining Service 24
8. Specifications 25
9. Configurable Parameters & Settings 26
10. Limited Product Warranty 28 1 1. Declaration of Conformity 29
© Copyright Para Systems, Inc., 2001
1
INTRODUCTION
English
Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
Please read the manual before installing your UPS. It provides the information that should be followed during installation and maintenance of the UPS and the batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the MINUTEMAN Technical Support Department can rapidly assist you.
This symbol indicates "A TTENTION"
This symbol indicates "Risk of Electrical Shock"
NOTICE: This equipment has been tested and found to comply with the limits
for a Class A computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital
apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
n Re-orient the receiving antenna n Relocate the computer with respect to the receiver n Move the computer away from the receiver n Plug the computer into a different outlet so that the computer and receiver are on
different branch circuits.
n Shielded communications interface cables must be used with this product
WARNING: Changes or modifications to this unit not expressly approved by the
party responsible for compliance could void the user's authority to operate the equipment.
Receiving Inspection
After removing your MINUTEMAN UPS from it's carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored.
2
This symbolt
The packing materials that your UPS was shipped in, are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to MINUTEMAN, please use the original packing material. Since MINUTEMAN is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE PACKING MA TERIALS!
WARNING: Risk of electrical shock. Hazardous live parts inside
this power supply are energized from the battery even when the AC input power is disconnected.
To de-energize the outputs of the UPS:
1. If the UPS is on press the on/off button for 1 second
2. Disconnect the UPS from the AC power outlet
3. To deenergize the UPS completely, disconnect the battery.
This uninterruptible power source contains potentially hazardous voltages. DO NOT attempt to disassemble the unit. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by AUTHORIZED SERVICE PERSONNEL ONL Y .
CAUTION! To reduce the risk of electrical shock in conditions where load
equipment grounding cannot be verified, disconnect the UPS from the AC power outlet before installing a computer interface cable. Reconnect the power cord only after all signaling connections are made.
CAUTION! Connect the UPS to a two pole, three wire grounding AC
power outlet. The receptacle must be connected to appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes
CAUTION! "High Leakage Current". The UPSs must be connected to the
appropiate building ground.
Para Systems Life Support Policy
As a general policy, Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend the use of any of its products in direct patient care. Para Systems will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Para Systems that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of Para Systems Inc. is adequately protected under the circumstances.
English
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemak­ers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim that units with this modification are certified or listed as Hospital Grade by PARA SYSTEMS or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
3
CONTROLS AND INDICATORS
English
FRONT PANEL (LCD Units)
Primary Power Switch: Press and release the ON/OFF button to turn the unit ON or OFF .
Normal Mode Icon: This icon will illuminate when the utility power is within safe operating range.
Battery Mode Icon: This icon will illuminate when the Utility power is outside safe operating range and the unit is operating in the battery mode.
Bypass Mode Icon: This icon will illuminate when the unit is in bypass mode and you do not have battery backup protection.
Unit Fault Icon: The Fault icon illuminates when the UPS has detected an internal fault. (see section 5)
Unit Fault Icon: This icon and error code will illuminate when the self diagnostics are able to determine the problem.
Unit Charger Icon: This icon will illuminate when the unit is charging the batteries.
Unit Overload Icon: This icon will illuminate when the unit load has exceed the rating of the UPS. The UPS will transfer to bypass mode if the overload is not removed.
Estimated Time Remaining icons: These combination of LCD icons will illuminate when selected and the UPS is operating in the battery mode. The first time icon will appear as ">" if the estimated time remaining is greater than ten (10) minutes. This symbol will turn off when the estimated time remaining is less than 10 minutes and the remaining time will appear in the display.
Unit Audible Alarm Icon: This alarm will illuminate when audible alarm is silenced.
4
Unit Input Icon: When selected, this will display the selected item for the input from utility.
Unit Output Icon: When selected, this will display the selected item for the output from unit.
Unit Amperage Icon: When selected, this will display the amps from either the input or output based on selection of input or output as described previously.
Unit Voltage Icon: When selected, this will display the voltage from either the input or output based on selection of input or output as described previously.
Unit Frequency Icon: When selected, this will display the frequency from either the input or output based on selection of input or output as described previously.
Unit Load in Watts Icon: When selected, this will display the load from either the input or output based on selection of input or output as described previously.
English
!
Unit Battery Percentage Status Icon: When selected, this will display the percentage of battery capability remaining.
Unit Load Percentage Status Icon: When selected, this will display the percentage of load on the unit.
5
INSTALLATION
English
INST ALLATION PLACEMENT
Install the UPS in a temperature controlled environment that is free of conductive contami­nants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged. Operating Temperature: 700VA-5000VA: 0 to 40°C, 7000VA: 0 to 32°C Storage Temperature: -15 to +45°C Operating Elevation: 0 to 3,000 Meters Storage Elevation: 0 to 15,000 Meters Operating and Storage Relative Humdity: 95%, non-condensing
REAR PANEL (120Vac models shown)
Tower Models
1. Smart slot for optional cards
2. Switch, momentary switch used to change displays or silence alarm
3. Dip switches used to configure unit parameters
4. Simple Communications port (AS400)
5. RS232 intelligent communications port
6. Network protection (lan only)
7. External battery connection point
8. Output load receptacles
9. Output load circuit breakers
10. Incoming utility power cord
11. Incoming utility circuit breaker
6
Rackmount Models
1. Incoming utility power cord
2. Incoming utility circuit breaker
3. External battery connection point
4. Network protection (lan only)
5. Smart slot for optional cards
6. Switch, momentary switch used to change displays or silence alarm
7. Dip switches used to configure unit parameters
8. Simple Communications port (AS400)
9. RS232 intelligent communications port
10. Output load circuit breakers
11. Output load receptacles
1
2
3 4
5
6
7 8
9
10
English
MCP 5000iE and MCP 7000iE
1. Fans: Internal Cooling Fans.
2. Maintenance Bypass Switch: In normal operation the switch must be in the UPS position. When doing routine maintenance the switch must be in the BPS position.
3. Output Circuit Breakers: Turn OFF/ON the output of the UPS.
4. Alarm Silencer: Silences the Alarm in the Battery Mode.
5. Configuration Switches: Must be set before turning the UPS ON (see page 8).
6. Input Circuit Breakers: Turn OFF/ON the input of the UPS.
7. RS232 Port: Intelligent Communications Port.
8. Contact Closure Port: Simple Communications Port (AS400).
9. External Battery Pack Connector: Remove the panel for external Battery Pack Connection.
10. Access Panel for Input/Output Terminals: Remove the panel for Input/Ouptut Connections.
7
INSTALLATION (Must be performed by Authorized Service Personnel ONLY)
English
Be sure to read the installation placement and all the cautions before installing the UPS. The MCP-E series UPS has external Battery Pack capability, please observe the following warning when connecting the Battery Pack(s). WARNING! DO NOT PLUG THE BATTERY PACK'S CONNECT OR INTO THE UPS's BA TTERY CONNECTOR WHILE THE UPS IS TURNED ON. NOTE: The red connectors/wires are the battery positive(+) and the black connectors/ wires are the battery negative(-) on all MINUTEMAN configurations.
MCP 5000iE and MCP 7000iE Input/Output/Battery Pack Connections
(Must be performed by Authorized Service Personnel ONLY)
Installation instructions for hardwiring the Input/Output Connections:
1. Crimp M6 ring terminals (part number R14-6 or equivalent) to the appropriate size input and output cables (see page 9) using the appropiate Crimp tool (part number Crimpers RYO­14 or equivalent). Ring T erminal: Size: M6 (or equivalent) Part Number: R14-6 (or equivalent) Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent) Crimp tool: Part number: Crimpers RYO-14 (or equivalent) Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent)
2. Remove the access panel on the rear panel of the UPS.
3. Install the appropriate size strain relief into the input and output access holes.
4. Push the input cable through the strain relief nearest the input terminal block.
5. Connect L1 to the AC Input's "L" terminal, connect L2 to theAC Input's "N" terminal, connect AC ground to the AC Input's ground terminal. Be sure that all the connections and the strain relief are tightly secured.
6. Push the output cable through the strain relief nearest the output terminal block.
7. Connect L1 to the AC Output's "L" terminal, connect L2 to the AC Output's "N" terminal, connect AC ground to the AC Output's ground terminal. Be sure that all the connections and the strain relief are tightly secured.
8. Reinstall the access panel on the rear panel of the UPS.
9. Now the UPS is ready for the normal start-up procedure.
8
NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker
which will provide for an emergency power off. (Must be performed by Authorized
Service Personnel ONLY)
Model MCP 5000iE MCP7000iE Input Circuit Breaker 40 Amp 50 Amp Input Wire Size/Temp 8 AWG/min75°C 6 AWG/min75°C Wire Conductor Three conductor, copper wire only Tightening torque for pressure wire connectors having screws
Torque 17.6Lbs (8kg)
English
Block diagram of the MCP 5000iE and MCP 7000iE input and output wiring.
9
Loading...
+ 22 hidden pages