Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
Please read this manual before installing your Enterprise Plus Series UPS,
models E750RM2U, E1000RM2U, E1500RM2U, E1500RMT2U, E2000RM2U,
E3000RM2U, E3000RMT2U as it provides important information that should be
followed during installation and maintenance of the UPS and batteries allowing
you to correctly set up your system for the maximum safety and performance.
Included is information on customer support and factory service if it is required.
If you experience a problem with the UPS please refer to the Troubleshooting
guide in this manual to correct the problem or collect enough information so
that the Technical Support Department can rapidly assist you.
This symbol indicates "ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply Phase"
This symbol indicates "Alternating Current Supply"
2
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electrical codes. Do not use extension cords, adapter plugs, or surge
strips.
CAUTION! T o reduce the risk of electrical shock with the installa-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
the UPS from the AC wall outlet before inst alling a computer interface
cable. Reconnect the power cord only after all signaling connections
are made.
English
WARNING:This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond
the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed
by QUALIFIED SERVICE PERSONNEL ONL Y.
WARNING: Risk of Electrical Shock. Hazardous live p arts inside
these power supplies are energized from the battery even when the
AC input is disconnected.
CAUTION! T o de-energize the outputs of the UPS:
1. If the UPS is on press and release the On/Off/T est button. NOTE:
For the 208V models; turn the input circuit breaker to the off position.
2. Disconnect the UPS from the AC wall outlet.
3. To de-energize the UPS completely, disconnect the battery .
3
NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions
English
from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly ,
that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
Re-orient the receiving antenna.
Relocate the computer with respect to the receiver.
Move the computer away from the receiver.
Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authority to operate the equipment.
Receiving Inspection
After removing your UPS from its carton, it should be inspected for damage that
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrier will not be honored. The packing materials that your UPS was shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SA VE THE PACKING MA TERIALS!
NOTE: These UPSs are shipped with the batteries disconnected. The batteries must be connected before putting these UPSs into service. Refer to Section 3 "Installation" for connecting the batteries.
4
Life Support Policy
As a general policy , we do not recommend the use of any of our products in life
support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect
its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examples of devices considered to be life support devices are neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis
systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options
on many of our UPS systems. We do not claim that units with this modification
are certified or listed as Hospital Grade by us or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
English
5
English
CONTROL PANEL
The AC normal (green) LED illuminates in a steady st ate when the
UPS is on and operating in the AC normal mode. The AC normal
LED will extinguish when operating in the Battery mode.
The On-Battery (green) LED illuminates in a steady state when the
UPS is operating in the Battery mode. The On-Battery LED will
extinguish when operating in the AC normal, Boost and Buck modes.
The Boost (yellow) LED illuminates in a blinking state when the
UPS is operating in the Boost mode. The Boost LED will extinguish
when operating in the AC normal, Buck and Battery modes.
The Buck (yellow) LED illuminates in a blinking state when the UPS
is operating in the Buck mode. The Buck LED will extinguish when
operating in the AC normal, Boost and Battery modes.
The Fault (red) LED illuminates in a steady state when the UPS
detects an internal fault. The Fault LED is extinguished when the
UPS is operating properly .
The Weak/Bad Battery (red) LED illuminates in a steady state when
the UPS detects a weak battery, bad battery or if the battery is
disconnected. The Weak/Bad Battery LED is extinguished when
the battery's condition is good.
The Site Wiring Fault (red) LED (120V models) illuminates in a steady
state when the UPS detects a site wiring problem. The SWF LED is
extinguished when the UPS is connected to proper site wiring.
6
The Load Level Bar Graph (AC mode only) operates as follows:
LED #10: >10% load (green/red/yellow) LED will be green and illuminated when there is at least 10% of the rated capacity .
LED #30: >30% load (green/yellow) LED will be green and illuminated when there is at least 30% of the rated capacity .
LED #50: >50% load (green/yellow) LED will be green and illuminated when there is at least 50% of the rated capacity .
LED #70: >70% load (green/yellow) LED will be green and illuminated when there is at least 70% of the rated capacity .
LED #90: >90% to approximately 109% load (red/yellow) LED will
be yellow and illuminated when there is approximately 90% of the
rated capacity to indicate that unit is near full capacity. The LED
will turn red at 110% load capacity to indicate an Overload condition.
The Battery Capacity Bar Graph (Battery mode only) operates as
follows:
LED #90: >90% battery capacity (red/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 80% capacity and then it will extinguish.
LED #70: >70% battery capacity (green/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 60% capacity and then it will extinguish.
LED #50: >50% battery capacity (green/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 40% capacity and then it will extinguish.
LED #30: >30% battery capacity (green/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 30% capacity and then it will extinguish.
LED #10: >30% battery capacity (green/red/yellow) LED will be yellow and illuminated until the unit issues a Low Battery Warning
Alarm and then it will turn red to indicate a Low Battery Warning.
English
The Multi-Function On/Off/T est Button functions as follows:
When the UPS is Off, press and release the On/Off/Test button
after one beep to turn the UPS On. NOTE: The input circuit
breaker MUST be in the on position for the 208V models.
When the UPS is On, press and release the On/Off/Test Button
after one beep to turn the UPS Off. NOTE: Turn the input circuit
breaker to the off position for the 208V models.
When the UPS is On, press and hold the On/Off/T est button for four
beeps, then release the button. The UPS will perform a 5-second
Self T est.
7
REAR PANEL
English
1. The RS232 Communications Interface Port is for UPS monitoring and control.
2. The USB Communications Interface Port is for UPS monitoring and control.
3. The RJ1 1 REPO (Remote Emergency Power Off) Port is for UPS control.
4. The option slot is for option cards.
5. The External Battery Connector is for connecting External Battery Packs.
6. The output circuit breaker will trip in the event the load exceeds the UPS’s power rating.
7. The Battery Backup output power receptacles. The output receptacles are electrically
wired into two segments to support the "Load Shedding Function". The locking receptacle
does not support the Load Shedding Function. NOTE: The locking recptacle is not on all
models.
8. The input circuit breaker will trip in the event the load exceeds the UPS’s power rating.
9. The input power cord (120V models). The AC Power Inlet IEC320 (208V models).
10. The dipswitch is for setting the Inverter (On-Battery) output voltage.
11. The External Ground Stud is for connecting an external ground wire.
12. The R-J1 1/R-J45 modular connectors are used for 10/100 Base-T Network/single line
Phone/Fax/Modem protection.
Model #
E750RM2U
E1000RM2U
E1500RM2U
E2000RM2U
E3000RM2U
E1500RMT2U
E3000RMT2U
8
Input Power Plug
(All power cords are 10ft)
NEMA 5-15P
NEMA 5-15P
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
NEMA 6-15P
NEMA L6-30P
Output Power Receptacles
6-NEMA 5-15R
6-NEMA 5-15R
6-NEMA 5-15R
6-NEMA 5-15/20R
1-NEMA L5-20R
6-NEMA 5-15/20R
1-NEMA L5-30R
6-NEMA 6-15R
6-NEMA 6-15/20R
1-NEMA L6-30R
INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a location which will
provide good air circulation for the UPS at all times. A void locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Route power cords so they cannot be walked on or damaged.
Operating T emperature (Maximum): 0 to 40 degrees C (+32 to +104 degrees F)
Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage T emperature: -15 to +45 degrees C (+5 to +1 13 degrees F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the UPS. Place the UPS in the final desired location and complete the rest of
the installation procedure. These UPSs are shipped with the internal batteries
disconnected. The batteries must be connected before putting these UPSs
into service. See the connecting the batteries procedure to connect the batteries and see the Rackmount Configuration to install the UPS into the rack. USECAUTION: The UPS is heavy . Use the appropriate number of personnel when
installing the UPS.
English
9