Mikro NX330A User Manual

9. RECORDS
a. Record the 3 latest tripped faults current or “tSt” for manual trip test. b. The records are stored in non-volatile memory. c. To clear the entire record database:
Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or [FUNC] digit shown “A”.
Step 2: Press [ ] and [ ] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will clear the e
10.
TECHNICAL DATA
AUXILIARY SUPPLY RECORDS
NX330A-230A(6)....................184~276 VAC Fault record....................... 3 latest trip fault current or “tSt”
NX
330A-110A(6)....................94~127 VAC for manual trip test
Rated frequency.....................50Hz or 60Hz Storage.............................. Non-volatile memory
VA Rating...............................3 VA typical
SETTING RANGES DIGITAL INPUT PORT
Sensitivity adjustment............ 30mA, 50mA, Remote re
Delay time adjustment........... Instantaneous, Contact rating.................... 5A 240V ACI
Number of shots.....................0~30 (step=1) Expected electrical life.......50,000 at rated current
Dead time.....................
Persistent fault time............... 0~500sec (step=1sec) ZERO-PHASE CURRENT TRANSFORMERS
Reclaim time.......................... 0~500min (step-1min)
Lockout self reset time........... 0~200hrs (step=1hour) Mounting............................Standard DIN 96x96mm panel
Programmable contact...........0~6 (step=1) Approximate we
INDICATORS
Pre-fault alarm....................... Red indicator
Leakage trip delay time..........Red indicator
Leakage trip........................... 7-segment display and red indicators
Manual test trip...................... 7-segment display and red indicators
ZCT connection fault..............7-segment display and red indicators
Trip records............................7-segment display
Real-time leakage current......7-segm
11.
CONNECTION DIAGRAM
12. CASE DIMENSION
..........1~500sec (step=1sec)
AUX
LN
TRIP SAFE CONTACT*
NC
NO
COM
9 11 12 13 14 15
96mm
96mm
FRONT
0.10~1.00A (step=50mA),
1.00~10.0A (step=1.00A) OUTPUT CONTACTS
0.1~3.0s (step=0.1s) Contact arrangement.........Change over
0=Disable reclose function Expected mechanical life...5,000,000 operations
0=Disable To operate with Mikro's ZCT series of current transformers
0=Disable MECHANICAL
0=Disable mounting
ent display
REMOTE RESET
62 3 4 5 71
ALARM CONTACT
NC
NX330A
8
NO
COM
1610
L1 L2 L3 N PE
set..................... N.O. Dry contact
ight........... 0.58kg (excluding ZCT)
MIKRO ZCT
CONTACTOR
LOAD
The EARTH wire must not pass through the ZCT
90mm 70mm
SIDE
91±0.5mm
PANEL CUTOUT
91±0.5mm
NX330A Self-Reclosing Earth Leakage Relay User's Manual
A BRIEF OVERVIEW
a
k
j
i
NX 330A
TE S T
a - DATA display
b - Trip status indicator
c - Alarm status indicator
d - DP2 indicator
e - Decrement button
f - Increment button
g - RESET button
h - TEST button
i - Model
j - DP1 indicator
k - FUNC display
1. DESCRIPTION
The NX330A is microprocessors based earth leakage relay with built in self-reclosing function.
The earth leakage protection module is designed for measure the low-level current flowing from the live part of the installation to the earth in the absent of the insulation fault. A zero is connected to the relay and function as the sensor for sensing the leakage current. All conductors of the circuit to be protected shall go through the ZCT.
While the self reclosing module provide multiple number of shots operation. It also incorporates intelligent to differentiate the transient fault or persistent fault.
Flt 1 - Fault record #1(Most recent)
Flt 2 - Fault record #2
Flt 3 - Fault record #3(Oldest)
RE S E T
Symbols
n
I - Sensitivity setting
- Time time delay setting
t
SHOTS - Nos of reclose operations
tDEAD - Dead time
tPF - Persistent fault monitoring time
tREC - Reclaim time
tLAR - Lockout auto reset time
RLY2 - Programmable Output contact
b
c
d
e
f
g
h
phase current transformer
2. LIGHT INDICATORS
LED
LED
display
indicator
display
00000
No auxiliary supply
00XX1
Normal condition, no tripping
0BXXX
Leakage current > 50% of the I∆n
0FBXXX
Leakage current > 85% of the I∆n. Trip delay time running.
1100B
Relay tripped
00101
Scroll through setting
00111
Scroll through records
00B01
[DATA] programming mode
11XX“Ct”
ZCT connection fault
XXXX“tSt”
Manual trip test
XXXX“Loc”
Transient fault lockout by reclose function
XXXX“PLo”
Persistent fault lockout by reclose function
[FUNC]
[DP1]
[DP2]
Symbols
Description
Blank
Off
Note 1
Real-time leakage current display (Default)
1
OffOnI∆n
Sensitivity setting (A)
2
Off
On∆t
Trip time delay setting (second)
3
Off
Off
SHOTS
Nos of shots / reclose operations
4
Off
Off
tDEAD
Dead time (sec)
5
Off
Off
tPF
Persistent fault monitoring time (sec)
6
Off
Off
tREC
Reclaim time (min)
7
Off
Off
tLAR
Lockout automatic reset time (hours)
8
Off
Off
RLY2
Programmable contact
AOnNote 1
Flt 1
Fault record #1 (Most recent)
bOnNote 1
Flt 2
Fault record #2
cOnNote 1
Flt 3
Fault record #3 (Oldest)
[DATA]
Pre-fault Alarm
Leakage Trip
Manual Test Trip
Re-close Lockout
ZCT Connection Fault
1
2XXXX
3X√√√
X
4XX
X√X
5
X
6XXX√
Terms
Description
Dead time
Time when the trip safe contact de-activated due to leakage fault or manual test trip to the Reclaim time
Time required by the recloser to reset back to initial state since the last reclose operation
Lockout automatic
Time required for unlock and reset the self-reclosing module during lockout state. The
[Trip]
[Alarm]
[FUNC]
Table 1: Relay status displayed
1 = ON 0 = OFF X = Don't care B = Normal blink FB = Fast blink
3.
PUSH BUTTONS OERATION
a. Integral Trip Test:
Press the [TEST] button and hold for 3.5s to perform an integral test on the relay ranging from the analog sensing circuitry to output contacts of the relay as well as the relay indicators and display.
During the testing process, the first 2s is to simulate the pre-f the trip time delay. End of time delay, relay trip.
b. Trip Reset; Lockout Reset and ZCT Connection Fault Reset:
Press the [RESET] button once or through digital input port.
ZCT connection fault reset is inhabited if the fault is not rectify
c. Parameters Viewing:
When the relay is operate normal and no tripping, press [RESET] button to step through th
When step through the parameters, press [RESET] button and hold for 1.5 second to jump direct to the default
[FUNC].
[DP1]
[DATA]
Status
ault alarm condition then follow by 1.5s testing on
e various parameters.
Step 2: Press [ ] and [ ] buttons simultaneously and hold for 1.5s to enter programming mode. The [FUNC] digit blink to indicate the relay has enter into t
Step 3: Press [ ] or [ ] button to increase or decrease the parameter value.
Step 4: To save the selected value, press [ ] and [ ] buttons simultaneously and hold for 1.5s. It will exit the
programming mode with [DATA] displaying the new setting.
To exit programming mode without saving the selected setting, press the [RESET] button once.
4.
DIGITAL INPUT PORT
a. The digital port is for remotely reset the relay when tripped, lockout or ZCT connection fault. b. To reset the relay, make a connection between terminals 5 and 6 of the relay.
5.
OUTPUT CONTACTS
a. Trip Safe Contact:
Activated and latch when the relay is in normal power-up condition with the measured leakage current less than
0.85 In. De-activated during leakage trip, manual test trip or ZCT connection fault.
b. Programmable Contac
0 X X X X X
Table 3: Programmable contact selection table
X = Disable = Enable
6.
SELF-RECLOSE
Shots Nos of self-reclosing operation before lockout.
Persistent fault monitoring time
t:
time when the trip safe contact is activated by the recloser.
Fault detected immediately after the trip safe contact is activated by the recloser is called persistent fault. An time frame for monitor the persistent fault is called persistent fault time.
he programming mode.
Table 2: List of [FUNC] code displayed Note 1: If DP2 is OFF. The unit for the [DATA] displayed is in mA.
d. Parameters Setting
Step 1: Press [RESET] button to step to desired parameter.
If DP2 is ON. The unit for the [DATA] displayed is in ampere (A).
reset time
Transient fault lockout When the number of self reclosing operations match the number of shots setting, further
Persistent fault lockout Relay lockout when the tripping is initiated by the persistent fault
Table 4: Self reclose function explanation
a) Shots, Dead Time and Reclaim Time b) Persistent Fault Monitoring Time
Leakage
Trip Safe Contact
Dead Time
Reclaim Time
Shots Counter
0
unlock operation is carry out when no operators attended the relay during lockout state.
fault trip will perform the l ockout.
Leakage
Trip Safe Contact
Dead Time
Persistent Fault
1
2
0
Lockout
Loading...