Mikro MK300A, MK300EA User Manual

INDICATORS
Pre-fault alarm................................................................ Red indicator
Leakage trip delay time.................................................. Red indicator
Leakage trip....................................................................7-segment display and red indicators
Manual test trip............................................................... 7-segment display and red indicators
ZCT connection fault...................................................... 7-segment display and red indicators
Trip records.................................................................... 7-segment display
Real-time leakage current.............................................. 7-segment display
ZERO-PHASE CURRENT TRANSFORMERS
MECHANICAL
Mounting.........................................................................Standard DIN 96x96mm panel mount
Approximate weight........................................................ 0.58kg (excluding ZCT)
9. CONNECTION DIAGRAMS
AUX
LN
TRIP CONTACT
NC
NO
C
9 11 12 13 14 15
62 3 4 5 71
MK300A
8
1610
L1 L2 L3 N PE
MIKRO ZCT
SHUNT TRIP
The EARTH wire must not pass through the ZCT
MK300A & MK300EA Earth Leakage Relay User's Manual
A BRIEF OVERVIEW
k j
a b
c d
e f
AUX
TRIP CONTACT
NC
9 11 12 13 14 15
REMOTE
LN
RESET
ALARM CONTACT
NO
NO
C
10. CASE DIMENSION
96mm
96mm
* Applicable to MK300EA series only
FRONT
62 3 4 5 71
POSITIVE SAFETY CONTACT
C
LOAD
L1 L2 L3 N PE
MK300EA
8
NC
NO
C
1610
LOAD
MIKRO ZCT
CONTACTOR
The EARTH wire must not pass through the ZCT
i
a - DATA display b - Trip status indicator c - Alarm status indicator d - DP2 indicator e - Decrement button f - Increment button g - RESET button
Symbols
n
I - Sensitivity setting t - Time delay setting Flt 1 - Fault record #1 (Most recent) Flt 2 - Fault record #2
g h
h - TEST button i - Model
Flt 3 - Fault record #3 (Oldest)
j - DP1 indicator
90mm 70mm
91±0.5mm
k - FUNC display
1. DESCRIPTION
The MK300A and MK300EA are microprocessors based earth leakage relays designed for measure the low-level current flowing from the live part of the installation to the earth in the absent of the
SIDE
PANEL CUTOUT
91±0.5mm
insulation fault. A zero phase current transformer is connected to the relay and function as the sensor for sensing the leakage cu
rrent. All conductors of the circuit to be protected shall go through the ZCT.
For better fault preventive control of the system or equipment to be protected, MK300EA series comes with a pre-fault alarm contact and a positive safety contact. The pre-fault alarm contact is activated whenever the leakage current exceed 50% of the sensitivity setting. While the positive sa
fety contact is activated if the relay is power up and function correctly. The MK300EA series also built-in a digital input port for remotely reset the relay after leakage fault trip, manual test trip or ZCT connection fault.
2. LIGHT INDICATORS
LED
LED
display
indicator
display
00000
No auxiliary supply
00XX1
Normal condition, no tripping
0BXXX
Leakage current > 50% of the I∆n
0FBXXX
Leakage current > 85% of the I∆n. Trip time delay
XXXX“tSt”
Manual trip test
[FUNC]
[DP1]
[DP2]
Symbols
Description
Blank
Off
Note 1
Real-time leakage current display (Default)
1
OffXIn
Sensitivity setting (A)
2
OffX∆t
Trip time delay setting (second)
AOnNote 1
Flt 1
Fault record #1 (Most recent)
bOnNote 1
Flt 2
Fault record #2
cOnNote 1
Flt 3
Fault record #3 (Oldest)
Trip Contact
Activated and latch by leakage fault trip, manual test trip or ZCT connection fault
Positive Safety
Activated when the relay is power up and function correctly with no tripping.
[Trip]
[Alarm]
[FUNC]
1 1 0 0 B Relay tripped 0 0 1 0 1 Scroll through setting 0 0 1 1 1 Scroll through records 0 0 B 0 1 [DATA] programming mode 1 1 X X “Ct” ZCT connection fault
Table 1: Relay status displayed
1 = ON 0 = OFF X = Don't care B = Normal blink FB = Fast blink
[DP1]
[DATA]
running.
3. PUSH BUTTONS OERATION
a.
Integral Trip Test:
Press the [TEST] button and hold for 3.5s to perform an integral test on the relay ranging from the
analog sensing circuitry to output contact(s) of the relay as well as the relay indicators and display.
During the testing process, the first 2s is to simulate the pre-fault alarm condition then follow by 1.5s
testing on the trip time delay. End of time delay, relay trip.
b. Leakage Fault Trip Reset: / Manual Test Trip Reset:
Press the [RESET] button once or through digital input port.
c. ZCT Connection Fault Reset:
Press the [RESET] button once or through digital input port.
Reset is inhabited if the fault is not rectify.
d. Parameters Viewing:
When the relay is operate normal and healthy condition, press the [RESET] button to step through
the various functions.
When step through the parameters, press [RESET] button and hold for 1.5 second to jump direct to
the default [FUNC].
Table 2: List of [FUNC] code displayed Note 1: If DP2 is OFF. The unit for the [DATA] displayed is in mA.
If DP2 is ON. The unit for the [DATA] displayed is in ampere (A).
Status
e. Parameters Setting
Step 1: Press [RESET] button to step to desired [FUNC] or parameter.
Step 2: Press [ ] and [ ] buttons simultaneously and hold for 1.5s to enter programming mode.
The [FUNC] digit blink to indicates the relay has enter into the programming mode.
Step 3: Press [ ] or [ ] button to increase or decrease the parameter value.
Step 4: To save the selected value, press [ ] and [ ] buttons simultaneously and hold for 1.5s. It
will exit the programming mode with [DATA] displaying the new setting.
To exit programming mode without saving the selected setting, press the [RESET] button once.
4. DIGITAL INPUT PORT *
a.
These digital port is for remotely reset the relay when tripped or ZCT connection fault.
b. To reset the relay, make a connection between terminals 4 and 5 of the relay.
5. OUTPUT CONTACTS
Contact * Pre-fault Alarm
Contact *
Table 3: Output contact description
6. RECORDS
a.
Record the 3 latest tripped faults current or “tSt” for manual trip test.
b. The records are stored in non-volatile memory. c. To clear the entire record database:
Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or
[FUNC] digit shown “A”.
Step 2: Press [ ] and [ ] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will
clear the entire fault records database.
7. TECHNICAL DATA
AUXILIARY SUPPLY
MK300A-230(6) / MK300EA-230(6)............................... 184~276 VAC
MK300A-110(6) / MK300EA-110(6)............................... 94~127 VAC
MK300A-240AD(6) / MK300EA-240AD(6)..................... 85~265VAC/110~340VDC
Rated fr
equency............................................................. 50Hz or 60Hz
VA rating.........................................................................3 VA typical
SETTING RANGES
Sensitivity adjustment.....................................................30mA, 50mA,
Delay time adjustment.................................................... Instantaneous,
RECORD
Fault record.................................................................... 3 latest trip fault current or “tSt” for manual trip test
Storage........................................................................... Non-volatile memory
DIGITAL INPUT PORT
Remote reset.................................................................. N.O. Dry contact
OUTPUT CONTACTS
Contact rating................................................................. 5A(NO) / 3A(NC) / 250V AC1
Contact arrangement......................................................Change over
Expected electrical life....................................................10,000 at rated current
Expected mechanical life................................................5,000,000 operations
Activated when the measured leakage current > 50% of the In and self reset when the measured leakage current < 45% of the In. Activated and latch when the relay is tripped.
0.10~1.00A (step=50mA),
1.00~10.0A (step=1.00A)
0.1~3.0s (step=0.1s)