Midmark VetPro1000 Mobile Service manual

4.4 (5)

Midmark VetPro® 1000

Veterinary Dental Cart

Model Numbers:

8000-001

8000-002

8000-003

8000-004

8000-005

8000-006

8000-006S

8000-007

8000-007S

8000-008

8000-008S

Service and

Parts Manual

Present Production Model Shown

FOR USE BY MIDMARK TRAINED TECHNICIANS ONLY

SF-1928

Part No. 004-0586-00 Rev. AA8 (4/3/19)

Table of Contents

Section A General Information

Section B

Symbols.....................................

iii

Ordering Parts...........................

iii

Serial Number Location............

iii

Specifications............................

iv

Model Description.....................

iv

Scheduled Maintenance............

v

Troubleshooting

Compression Cycle.................

A-2

Electrical .................................

A-3

Troubleshooting Chart............

A-5

Testing & Adjustments

Checking for Air Leaks...........

B-2

Water Relay..............................

B-3

Tri-block...................................

B-4

Line Voltage.............................

B-5

Compressor Head...................

B-7

Capacitor..................................

B-8

Check Valve & Solenoid.......

B-10

Pressure Switch....................

B-12

Air Regulator.........................

B-14

Air Tank .................................

B-16

Water System.........................

B-17

Air Intake Filter......................

B-18

Exhaust Muffler.....................

B-20

Foot Control...........................

B-21

LED Light (Scaler).................

B-22

Standard Scaler.....................

B-23

Air/Oil Separator....................

B-24

Fiber Optics (Early Units).....

B-25

Fiber Optics (Current)...........

B-26

Handpiece Holder Adjust......

B-28

Foot Control...........................

B-29

C

Access procedures

 

Upper Compartment

C-2

Section

Middle Compartment..............

C-3

Delivery System......................

C-6

 

Lower Compartment...............

C-3

 

Water System...........................

C-5

 

 

 

D

Wiring & Tubing diagrams

Wiring Diagram

D-2*

Section

Tubing Diagrams

D-7*

 

 

Tri-Block Diagram...............

D-12*

 

Quad-Block Diagram.............

D-13

 

 

 

E

exploded views & parts lists

Section

VetPro® 1000.............................

E-2

 

 

 

 

 

(*) Indicates multiple pages due to model / serial number break(s).

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

ii

General Information

Symbols

warning

Indicates a potentially hazardous situation which could result in serious injury if not avoided.

Caution

Indicates a potentially hazardous situation which may result in minor or moderate injury if not avoided. It may

also be used to alert against unsafe practices

Equipment Alert

Indicates a potentially hazardous situation which could result in equipment damage if not avoided.

The symbols below may be used in this manual to represent the operational status of table functions and components.

Indicates the function / component is working properly. No action required.

Indicates the function / component is working, but a problem exists.

Indicates the function is not working at all, or that the component is faulty.

Ordering Parts

The following information is required when ordering parts:

Serial number & model number

Part number for desired part

(Refer to Section E: Exploded Views & Parts Lists)

Non-warranty parts orders may be faxed to Midmark using the Fax Order Form.

For warranty parts orders, call Midmark’s Technical Service Department with the required information.

Hours: 8:00 am to 5:00 p.m. EST (Monday thru Friday) Phone: 1-800-Midmark

Serial Number Location

Serial Number

Label

Past Production Model Shown

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

iii

Specifications

warning

Equipment not suitable for use in the presence of

a flammable anesthetic mixture.

Go To Table Of Contents

Cart

Width

23 inches (58.42 cm)

Length

18 1/2 inches (46.99 cm)

Height

36 1/2 inches (92.71 cm)

Weight

130 lbs (58.97 kg)

 

 

Shipping Weight

150 lbs (68.04 kg)

 

 

Top of Cart Weight Restriction

25 lbs (11.33 kg)

 

 

Electrical (See Regulatory Compliance Chart - Next Page)

Fuse (Scaler Transformer)

 

800mA, 250 V, 3AG SLO BLO

 

 

 

Power Cord Length

 

10 ft. Hospital Grade

Handpiece

Connection Type

 

Midwest 4-Hole Type Handpiece

Compressor

Motor

 

Oil Free 1/3 HP

Working Pressure

 

70-100 PSI

Flow Rate

 

2.5 scfm @ 40 PSI

Sound Level (full load)

 

40 dB

Air Tank

 

1 Gallon

Water Module

Reservoirs

 

Two - 1 Liter - Toggled

Pressurized System

 

30-40 PSI

Handpiece Flush System

 

Manual

Air and Water Connections

 

External Quick Connects

Other

 

Duty Cycle

 

Continuous Operation

 

 

Note: Exception, Units with LED

 

 

Scaler, 10 min. ON, 5 min. OFF

Classifications

 

Class 1, Type B Applied Part,

 

 

Ordinary Equipment [IPXO]

warning

The Acteon Newtron® LED scaler complies with current electromagnetic compatibility standards. However, it must not be used by or on those with cardiac stimulators or other active implants unless adequate electromag-

netic interference shielding is present. Check with a cardiologist to verify the EMI shielding capabilities of the implant. See enclosed Newtron® LED manual for further advisories.

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: 2/14/14]

iv

Go To Table Of Contents

Model Identification / Compliance Chart

 

 

 

Complies To:

 

 

Electrical Ratings:

 

 

 

 

 

 

 

 

 

Model

Description

UL

CAN / CSA22.2,

IEC 60601-1,

 

VAC

 

Cycles

 

 

60601-1,

CE

Amps

 

 

#601.1-M90

Ed. 2

+/- 10%

(Hz)

 

 

Ed. 1

 

 

 

 

 

 

 

 

 

 

8000-001

VetPro 1000 w/ Scaler

115

6

60

8000-002

VetPro 1000 w/o Scaler

115

6

60

8000-003

VetPro 1000 w/ Scaler and Fiber

115

6

60

 

Optics

8000-004

VetPro 1000 w/o Scaler and w/

115

6

60

 

Fiber Optics

8000-005

VetPro 1000 w/ Scaler, Export

 

 

 

230

3

50

8000-006

VetPro 1000 w/ LED Scaler and

 

 

 

230

3

50

 

Fiber Optics. Export

 

 

 

8000-007

VetPro 1000 w/ LED Scaler and

115

6

60

 

2 Position Fiber Optics

8000-008

VetPro 1000 w/ LED Scaler and

115

6

60

 

Fiber Optics

8000-006S

VetPro 1000 w/ LED Scaler and

 

 

 

230

3

50

 

Swivel Fiber Optics. Export

 

 

 

8000-007S

VetPro 1000 w/ LED Scaler and

115

6

60

 

2 Position Swivel Fiber Optics

 

 

 

 

 

 

 

 

 

8000-008S

VetPro 1000 w/ LED Scaler and

115

6

60

 

Swivel Fiber Optics

Note

Refer to Section E For Serial Number Breaks

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: 11/03/15]

v

Scheduled Maintenance Chart

 

 

Scheduled Maintenance

 

 

 

Interval

Inspection / Service

Description

 

 

 

Daily

Clean System

Refer to: Operating and Care Guide Tri-fold or CD, located in sleeve inside door on back of cart.

 

 

 

 

DrainAir Regulator

Refer to: Operating and Care Guide Tri-fold or CD, located in sleeve inside door on back of cart.

 

 

 

 

Drain Condensation from

Refer to: Operating and Care Guide Tri-fold or CD, located in sleeve inside door on back of cart.

 

Air Tank

 

 

Empty Water System

Refer to: Operating and Care Guide Tri-fold or CD, located in sleeve inside door on back of cart.

 

 

 

After Each Procedure

Clean Handpieces

Follow manufacturer’s of handpieces recommendations.

 

 

 

 

Flush Handpieces

Refer to: Operating and Care Guide Tri-fold or CD, located in sleeve inside door on back of cart.

 

 

 

 

Fill Water Bottles

Refer to: Water Bottles in this manual.

 

 

 

 

Change Mufflers

 

Annually

and

Refer to: Mufflers andAir Regulator in this manual.

 

Air Regulator Filter

 

Date of Service:

 

Model Number:

Location:

 

Serial Number:

Service Technician:

 

Notes:

 

 

 

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

vi

Section A

Operation &

Troubleshooting

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

A-1

Compression Cycle & Air Flow

Atmospheric air is drawn in through the intake filter to the compressor head where air is compressed and exhausted. Air travels though the check valve, which prevents air flushing back into the head, then flows through the solenoid. The solenoid allows air to escape for approximately two seconds during start-up to relieve pressure from the head, then closes sending pressurized air to the storage tank. Air from the storage tank activates the pressure switch. As the storage tank fills the pressure switch opens at a preset pressure and stops the compressor.

The air regulator adjusts air from the storage tank to 65 PSI. Storage tank air also supplies the quick disconnect. Air going to the quick disconnect is not regulated and pressure is at 100 PSI. Accessories connected to the quick disconnect will need to have it’s own regulator installed if the manufacture recommends less than 100 PSI.

The regulated air (65 PSI) flows to the foot control and water bottles. When user activates the throttle valve by depressing the foot control, air is sent through the tri-block and each instrument manifold. When the instrument is removed from the holder the holder valve is activated allowing air to flow through the handpiece. There are drive air adjustment valves to adjust air pressure for the instruments.

The air/water syringe is activated by pressing on the instrument’s air and water buttons. The user can make drive air, coolant air and water flow adjustments. Air flows though the gauge to show pressure readings. Regulated air also pressurizes the water bottles. Air to the water bottles is adjusted to 40 PSI by the water pressure regulator and can be lowered by adjusting the water pressure regulator.

Water Flow

VetPro® 1000 has a self-contained water system with two, one-liter bottles. The toggle switch opens and closes the use of the bottles. When the toggle switch is set in the middle, both valves to the bottles are closed depressurizing the bottles and stopping flow. When toggle switch is flipped

toward a bottle that bottles valve opens and allows water flow to each needle valve’s instrument. The needle valve is the users way to control water flow to instruments.

VA1245

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 03/20/12]

A-2

Always verify model & serial number

Electrical Flow

• Supply line voltage is always present at the Dental Cart power cord receptacle when plugged into a wall receptacle.

When the On/Off switch is turned on, line voltage, 115 VAC, is supplied to the Terminal Block and Pressure Switch.

• 115 VAC comes from the Terminal Block and energizes the Accessory Receptacles, Timer, Motor, Fan and Transformer.

•The Timer keeps the solenoid turned off until the compressor is running at full RPM. The Solenoid is normally opened when not energized. The Solenoid allows air to escape for approximately two seconds to relieve pressure from the head, then closes sending pressurized air to the storage tank.

• The system will continue to run until the pressure inside the system reaches

100 PSI (+ / - 5 PSI) (Cut-out time)

It will turn back on at 65 PSI (+ / - 5 PSI)

(Cut-In time).

• When the Pressure Switch is at 65 PSI (+ / - 5 PSI) or below it’s

contacts are closed and the compressor is energized.

• Transformer supplies 24 VAC to Scaler (if applicable).

Models:

All

All

Serial Numbers:

TGC001000Thru TGC001254

V796868 thru V933242

 

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 8/9/10]

A-3

Always verify model & serial number

Electrical Flow - Current Units

• Supply line voltage is always present at the Dental Cart power cord receptacle when plugged into a wall receptacle. When the On/Off switch is turned on, line voltage, 115 VAC, is supplied to the Terminal Block and Pressure Switch.

• 115 VAC comes from the Terminal Block and energizes the Timer, Motor, Fan and Transformer.

•The Timer keeps the solenoid turned off until the compressor is running at full RPM. The Solenoid is normally opened when not energized. The Solenoid allows air to escape for approximately two seconds to relieve pressure from the head, then closes sending pressurized air to the storage tank.

• The system will continue to run until the pressure inside the system reaches

100 PSI (+ / - 5 PSI) (Cut-out time)

It will turn back on at 65 PSI (+ / - 5 PSI)

(Cut-In time).

• When the Pressure Switch is at

65 PSI (+ / - 5 PSI) or below it’s contacts are closed and the compressor is energized.

• Transformer supplies 24 VAC to Scaler (if applicable).

Models:

 

Please refer to Section D

 

 

 

 

 

 

 

 

 

 

 

Serial Numbers:

 

for Wire Diagrams Listed Under Serial Numbers

 

 

 

 

 

 

 

 

 

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: ]

A-4

Always verify model & serial number

Troubleshooting Chart

Problem

Probable Cause

Check

Correction

Syringe has no

Empty water bottles.

Water level in bottles.

Fill water bottles.

water when button

 

 

 

 

Toggle not seated to

Check toggle location.

Push toggle completely to left or right side.

depressed.

right or left side.

 

 

 

 

 

 

 

 

Water Regulator

Check Water regulator.

Verify bottles are pressurized. Regulator should be adjusted all the way

 

 

 

 

 

to the right.

 

 

Quick disconnect.

Check water (blue)

Depress quick disconnect with a screwdriver and hold for serveral

 

 

 

 

disconnect.

seconds. Hold rag underneath screwdriver for any water flow. If no water

 

 

 

 

 

flow, change syringe check valve.

 

 

Tubing Crimped.

Check for crimped tubing.

Replace tubing.

 

 

 

 

 

 

 

 

Syringe.

Check Syringe tip and

Change syringe tip. Check syringe cartridge for water, repair or replace.

 

 

 

 

cartridge.

 

 

 

 

 

 

Handpiece has no

Needle Valves closed.

Check needle valves.

Verify needle valves are open.

water flow but

 

 

 

 

Handpieces.

Remove handpieces and verify you have water

If you have water coming from syringe, remove handpieces and recheck

syringe is still working.

 

 

 

 

through tubing.

water flow from tubing, if none repair or replace handpieces.

 

 

Kinked Tubing.

Check for kinked tubing from foot control to water

Replace tubing.

 

 

 

 

relay.

 

 

 

 

 

 

 

 

 

Water Relay

Remove air tubing from foot control going to water

If air is present, repair water relay membrane or replace water relay.

 

 

 

 

relay, depress foot control and check for air.

Refer to: Section B Water Relay.

 

 

 

 

Remove water tubing from tri-block coming from

If water is present, repair or replace tri-block. If no water is present,

 

 

 

 

water relay, depress foot control.

repair or replace water relay. Refer to: Section B Tri-Block or Water

 

 

 

 

 

Relay.

Handpiece leaking in

Incorrect holder

Check location of handpiece.

Place handpiece in correct holder position.

holder.

location.

 

 

 

 

Membrane

If foot control is not depressed while handpieces

Change membrane (diaphragm) in block.

 

 

(Diaphragm)

are hanging in holders, membrane in (tri or dual)

Refer to Section B Tri-Block.

 

 

 

 

block is leaking.

 

Water bottle or toggle

Check valve.

Check, check valve.

Toggle over to one side and fill water bottle. Observe other side for leak-

leaking.

 

 

 

ing. If it is leaking , replace check valve. Repeat for other side.

Handpiece in holder

Handpiece in wrong

Verify handpiece is in correct holder position.

Move handpiece to correct position.

and is still running

holder.

 

 

when another hand-

 

 

 

 

Holder switch out of

Check set screw adjustment.

Adjust set screw on holder. Refer to Section B: Handpiece Holder

piece is in use.

adjustment.

 

Adjustment.

 

 

 

 

 

Tri-block.

Check air to tri-block supply.

Pinch tubing off with pliers, handpiece should stop, if not check pilot

 

 

 

 

 

valve.

Models:

 

 

 

 

 

 

All

 

 

 

Serial Numbers:

 

all

 

 

 

 

 

 

 

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 5/21/13]

A-5

Always verify model & serial number

Troubleshooting Chart

Problem

Probable Cause

Check

Correction

Compressor will not start.

Power cord unplugged.

Verify power cord is plugged in cart and outlet.

Plug power cord into cart and/or outlet.

 

 

 

 

 

On/Off switch is off.

Check that the on/off switch is turned on.

Turn on/off switch on.

 

 

 

 

 

Circuit breaker tripped.

Check to see if circuit breaker needs reset.

Reset circuit breaker.

 

 

 

 

 

No power at outlet.

Check for voltage at outlet and/or move to

Reset circuit breaker. Assure outlet is on dedicated circuit

 

 

another room.

capable of handling cart requirements.

 

Loose wire connection.

Check back panel wire connections.

Reconnect wires to back panel if loose.

 

 

 

Check voltage on circuit breaker, power cord bracket and

 

 

 

on/off switch. Refer to: Section B Line Voltage

 

Capacitor.

Check Capacitor.

Test capacitor. Replace if needed.

 

 

 

Refer to Section B: Capacitor

 

Pressure Switch Frozen

Check Pressure Switch.

Replace Pressure Switch. Refer to: Section B Pressure

 

 

 

Switch.

 

Motor/Compressor Frozen

Unplug cart. Can you manually move

If you are unable to move compressor fans, replace com-

 

 

compressor fans?

pressor. Refer to: Section B Compressor

Compressor will not shut off or will

Air leaks in system and/or

Check for air leaks.

Refer to: Section B Checking for Air Leaks

recycle often.

foot control.

 

 

Compressor will not recycle or

Room temperature too high.

Ambient room temperature.

Move to another room. Try running unit.

stalls and or breaker tripping

 

 

 

Check Valve.

See if check valve is sticking.

Spray soapy water on solenoid muffler, if it bubbles while

causing air to deplete.

 

 

compressor is running, replace check valve.

 

 

 

 

 

 

Refer to: Section B Check Valve

 

Solenoid.

Check Solenoid.

Turn off unit and drain air tank. Turn on unit and see if

 

 

 

solenoid bubbles for a few seconds, if not replace sole-

 

 

 

noid.

 

 

 

Refer to: Section B Solenoid

Compressor makes humming noise

To much back pressure.

See if check valve is sticking.

Spray soapy water on solenoid muffler, if it bubbles while

and or smells like it is burning.

 

 

compressor is running, replace check valve.

 

 

 

Refer to: Section B Check Valve

LED light not working on scaler.

LED light not installed

Check polarity.

Check polarity ( + & - ) connection of LED bulb.

(Models 8000-007, 8000-007S, 8000-

properly.

 

Refer to: Section B LED Scaler

008 & 8000-008S ONLY)

 

 

 

Tubing connection bad.

Check tubing connection.

Check continuity between tubing connection and scaler

 

 

 

plug. Refer to: Section B LED Scaler

 

Poor contact with pins.

Clean pins.

Clean pins with alcohol and allow to dry before use.

 

 

 

 

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: [11/03/15]

A-6

Always verify model & serial number

Troubleshooting Chart

Problem

Probable Cause

Check

Correction

Scaler running intermittently or low

Poor power supply

Check power supply.

Verify VetPro 1000 is plugged into wall and not loose.

power, or not vibrating for no

connection.

 

 

apparent reason.

Air pressure not set

Check air pressure.

Check air pressure. Refer to: Section B Air Regulator

 

correctly.

 

 

 

Not drive air.

Check drive air adjustment knob.

Verify Drive air adjustment knob is all the way open.

 

 

 

 

 

Tubing.

Check tubing continuity.

Check continunity in black and orange wires of the tubing.

 

 

 

Refer to: Section B Scaler Tubing

 

 

Check HI resistance.

Check HI resistance between the black and orange tubing

 

 

 

wires. Refer to: Section B Scaler Tubing

 

Tip not tight enough.

Check tip.

Verify tip is tightened. Tip must be tightened for scaler

 

 

 

operation to work.

 

Tip is worn.

Check tip.

Tip must be within tolerance as per tip chart for scaler

 

 

 

operation to work. Change tip.

 

Potentiometer Harness bad

Check for proper setting. Service tip: if setting

If you have 24 V AC or 31 V DC, Check potentiometer for

 

or misadjusted.

is correct move on to Ώ check.

proper resistance sweep of 4 to 4.7K Ώ when turned from

 

 

 

Min to Max on Ohmmeter measuring between the white

 

 

 

and brown/blue wires on molex.

 

 

 

If resistance is not ok, replace potentiometer harness. If

 

 

 

resistance is ok, check all wiring and pins for continuity.

 

 

 

Repair any wiring that does not pass continuity check.

 

 

 

If you do not have 24V AC or 31 V DC Check power sup-

 

 

 

ply and air/electric switch for failure.

 

 

 

Replace potentiometer harness if power supply or air-

 

 

 

electric switch has failed.

 

Tubing is damaged.

Check tubing.

Check continuity in black and orange wires of the tubing.

 

 

 

Refer to: Section B Scaler Tubing

 

Handpiece is damaged.

Swap out handpieces.

If scaler operates properly with different handpiece, old

 

 

 

one is damaged.

 

Transducer in scaler.

Check transducer in scaler.

Replace with a known working handpiece. If the replace-

 

 

 

ment handpiece works, then the transducer is bad in

 

 

 

the problem handpiece. Return handpiece to Acteon for

 

 

 

service or replace with new handpiece.

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 5/21/13]

A-7

Always verify model & serial number

Testing & Repair

Section B

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

B-1

Testing & Repair

Checking for Leaks

Use Soapy Water to check for leaks...

A)Listen to foot control for air leaks.

B)Tubing inside back of cart.

C)Air regulator and “T” fittings.

D)Storage air tank and tank fittings.

E)Tri-block and instrument manifolds.

F)Air and water quick disconnects.

G)Handpiece docks.

H)Water bottles.

I)Solenoid muffler, check valve and compressor fittings.

Note: Refer to: Section C for Access Procedures

Tri-Block

& Manifolds

Handpiece

Docks

Water Bottles

Models:

All

Serial Numbers:

all

 

 

Quick Disconnects

Foot

Control

Air Tank & Fittings

Regulator & Fittings

Tubing

Solenoid & Check Valve

VA1252

 

Compressor Fittings

 

Earlier Production Model Shown

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 5/21/13]

B-2

Always verify model & serial number

Testing & Repair

Water Relay - Function and Location

The water relay is located inside the delivery panel.

The water relay stops the water flow to the needle valves until the foot control (throttle valve) is pressed, then air flows to the water relay and opens the needle valves allowing water to flow to the instruments. It also supplies water directly to the syringe.

Earlier Production Model Shown

Models:

All

Serial Numbers:

all

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-3

Always verify model & serial number

Midmark VetPro1000 Mobile Service manual

Testing & Repair

Water Relay - Testing

Step 1: Disconnect power.

Remove delivery panel.

 

 

Note: Refer to Section C Access Procedures

 

 

Step 2: Disconnect orange tubing from water relay .

Depress foot control.

Foot Control

Tube

Incoming

Water

Supply

Tri-block

Manifold

Tube

Syringe

Tube

Step 3: Disconnect tubing from water relay manifold.

Depress foot control.

Models:

All

Serial Numbers:

all

 

 

 

 

 

 

 

 

 

Results

 

Status

 

Required Action

 

 

 

 

No water when foot control not

 

 

 

Water flow good.

 

depressed.

 

 

 

 

 

 

 

 

 

Water when foot control is

 

 

 

Water flow good.

 

depressed.

 

 

 

 

 

 

 

 

 

No air flow when orange tube is

 

 

 

Tubing clogged or damaged. Change

 

disconnected.

 

 

 

orange tubing.

 

No water flow when manifold

 

 

 

Water relay is bad. Replace water

 

tubing is disconnected.

 

 

 

relay.

 

 

 

 

 

 

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 5/21/13]

B-4

Always verify model & serial number

Testing & Repair

Tri-Block (Dual Block in Models without Scaler 8000-002 & -004)

Function and Location

The tri-block is located behind the delivery instruments.

It is a manifold that the air and water source travel through and is routed to different components in the delivery system. When the foot control is activated, air flows into the tri-block through two tubes, one for coolant air and one for drive air. Coolant air flows from the tri-block to each instrument manifold. Drive air flows though the adjustment valve on the tri-block to each instrument. The tri-block also supplies air to the air pressure gauge.

Water flows from the water relay valve through the tri-block and to each water needle valve. The tri-block has a membrane seal that provides a fluid-tight seal between the two walls. To access the membrane for repair, remove allen screws from the front of the block to separate the block. Also Refer to: Section C Access Procedures to access the block and to Section D for a tubing diagram of the tri-block. Replacement kit for the membrane is available.

Note: The air/water supply for the syringe does not flow through the tri-block.

Membrane

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-5

Always verify model & serial number

Testing & Repair

Line Voltage Testing - 115 VAC

Components to check line voltage are listed in the chart below.

115 VAC Models Only Reference Serial Numbers Below

Meter Reading

Status

Required Action

 

 

 

< 115 VAC On / Off Switch

 

Replace On / Off Switch

 

 

 

< 115 VAC Pressure Switch

 

Replace Pressure Switch

 

 

 

< 115 VAC Terminal Block

 

Replace Terminal Block

 

 

 

< 115 VAC Fiber Optic

 

Replace Receptacle

Receptacles

 

 

 

< 115 VAC Timer

 

Replace Timer

 

 

 

< 115 VAC Fan

 

Replace Fan

 

 

 

< 115 VAC Transformer

 

Replace Transformer

 

 

 

115 VAC = On / Off Switch

 

On / Off Switch OK

 

 

 

115 VAC = Pressure Switch

 

Pressure Switch OK

 

 

 

115 VAC = Terminal Block

 

Terminal Block OK

 

 

 

115 VAC = Fiber Optic

 

Accessory Receptacles OK

Receptacles

 

 

 

115 VAC = Timer

 

Timer OK

 

 

 

115 VAC = Fan

 

Fan OK

 

 

 

115 VAC = Transformer

 

Transformer OK

 

 

 

Caution

When testing components with power on use care to prevent electrical shock.

To check line voltage...

Set multi-meter to v

Use multi-meter to verify voltage.

Models:

All

All

Serial Numbers:

TGC001000Thru TGC001254

V796868 thru V933242

 

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 8/9/10]

B-6

Always verify model & serial number

Testing & Repair

Line Voltage Testing - 230 VAC

Components to check line voltage are listed in the chart below.

230 VAC Models Only

Reference Serial Numbers Below

Meter Reading

Status

Required Action

< 230 VAC On / Off Switch

 

Replace On / Off Switch

< 230 VAC Pressure Switch

 

Replace Pressure Switch

< 230 VAC Terminal Block

 

Replace Terminal Block

< 230 VAC Timer

 

Replace Timer

< 230 VAC Fan

 

Replace Fan

< 230 VAC Transformer

 

Replace Transformer

< 230 VAC Fiber Optic Receptacle

 

Replace Receptacle

230 = VAC On / Off Switch

 

On / Off Switch OK

230 = VAC Pressure Switch

 

Pressure Switch OK

230 = VAC Terminal Block

 

Terminal Block OK

230 = VAC Timer

 

Timer OK

230 = VAC Fan

 

Fan OK

230 = VAC Transformer

 

Transformer OK

231 = VAC Fiber Optic Receptacle

 

Fiber Optic Receptacle OK

Models:

All

Serial Numbers:

V933243 thru Present

 

 

Caution

When testing components with power on use care to prevent electrical shock.

To check line voltage...

Set multi-meter to v

Use multi-meter to verify voltage.

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 8/9/10]

B-7

Always verify model & serial number

Testing & Repair

Compressor Head - Function and Location

The Compressor Head is located in the lower compartment.

Atmospheric air is drawn in though the intake filter to the compressor head where air is compressed and exhausted to the storage tank. Heat is generated from the compression process. The compressor head has a fan on both ends. There is also a fan located above the compressor head to pull hot air up and out though a vent on the back middle compartment of the cart. If you are unable to manually move the fans on the compressor (when power supply is completely shut-down), the compressor head needs replaced. There is a head rebuild kit available.

Compressor Head

Earlier Production Model Shown

Models:

All

Serial Numbers:

all

 

 

Intake Filter

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 09/24/08]

B-8

Always verify model & serial number

Testing & Repair

Capacitor - Function and Location

The capacitor is located in the lower compartment.

The run capacitor aids in running efficiency. It creates a phase shift to give more power to the compressor.

Capacitor

Earlier Production Model Shown

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-9

Always verify model & serial number

Testing & Repair

Capacitor - Testing

Step 1: Disconnect power.

Access run capacitor in lower compartment.

Note: Refer to: Section C - Lower Compartment.

Step 2: Discharge capacitor by touching screwdrivers

to both contacts on the capacitor and to each other.

Step 4: Place meter probes on capacitor connectors.

Reverse the leads, this should produce the same reading.

Step 3: Set meter to Ω reading.

Meter Reading

Status

Required Action

 

 

 

“O” or “Open” Reading

 

Replace Capacitor

 

 

 

Start Low and Increases

 

Capacitor

 

 

 

Models:

 

All

 

 

 

 

 

Serial Numbers:

 

all

 

 

 

 

 

 

B-10

© Midmark Corporation 2008 SF-1928

004-0586-00 [Revised: dd/mo/yr]

Always verify model & serial number

Testing & Repair

Check Valve & Solenoid - Function and Location

The check valve and solenoid are located in the lower compartment.

Compressed air travels from the compressor head though the check valve, which prevents air flushing back into the head. Then air flows though the solenoid. The solenoid allows air to escape for approximately two seconds to relieve pressure from the head then closes sending pressurized air to the storage tank.

Solenoid

Models:

All

Serial Numbers:

all

 

 

Earlier Production Model Shown

Check Valve

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-11

Always verify model & serial number

Testing & Repair

Check Valve - Clean

Step 1: Disconnect power.

Step 2: Remove check valve from compressor head and solenoid.

Step 3: Blow out valve with air.

If valve is sticking, replace.

VA1261

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-12

Always verify model & serial number

Testing & Repair

Pressure SwitchFunction and Location

The pressure switch is located in the middle compartment accessed from the back of the cart. When the storage tank is filled to the preset pressure the pressure switch will open and stop the compressor.

Cut-In / Cut-Out time is the minimum and maximum discharge pressures at which the compressor will switch from unload to load operation (cut-in) or from load to unload (cut-out). The pressure switch controls the Cut-In and

Cut-Out times.

Pressure Switch

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-13

Always verify model & serial number

Testing & Repair

Pressure Switch - Adjustment

Step 1: Run compressor until pressure reaches 100 PSI.

Note: Compressor should shut off close to 100 lbs.

Step 2: If compressor didn’t shut down at 100 PSI, access pressure switch and remove cover.

Note: Refer to: Section C Middle Compartment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustment Screw “A”

 

Adjustment Screw “B”

 

 

 

 

 

 

Step 3: Make adjustment.

Adjustment screw “A” , turn clockwise to increase both Cut-In and Cut-Out pressure.

Differential pressure adjustment screw “B”, turn Clockwise to increase Cut-In pressure without affecting Cut-Out.

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-14

Always verify model & serial number

Testing & Repair

Air Regulator - Function and Location

The regulator is located in the upper compartment behind the rear door.

The air regulator regulates air from the storage tank from 100 PSI to 65 PSI. The regulator should only be set for 65 PSI. There is a button on the bottom of the regulator that will drain condensation by pressing on it at the end of each work day.

Air Regulator

Earlier Production Model Shown

Models:

All

Serial Numbers:

all

 

 

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-15

Always verify model & serial number

Testing & Repair

Air RegulatorAdjustment

Equipment alert

Do not adjust regulator over 65 PSI, it will overheat the compressor. Air pressure for the piezo electric scaler should be set to 60 PSI.

To Adjust Regulator...

A)Pull adjustment knob upward to unlock.

B)Rotate adjustment knob clockwise to increase pressure, counterclockwise to decrease pressure.

C)Push adjustment knob downward to lock.

Models:

All

Serial Numbers:

all

 

 

Decrease Increase

Adjustment

Knob

Unlock

Lock

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: dd/mo/yr]

B-16

Always verify model & serial number

Testing & Repair

Air Regulator & Air Tank - Maintenance

To Drain Air Regulator...

Place a cloth under the regulator and depress the button until there is no water coming out.

Button

Present Model Shown with Yellow Tubing Earlier Models have Red Tubing

Valve

Opened

Note

User should drain regulator and air tank daily.

Models:

Serial Numbers:

To Drain Condensation from Air Tank...

A) Turn power switch off.

B) Position end of yellow tube so it drains into a container.

C) Turn drain valve slowly to open.

D) When no water is coming out, slowly close valve.

All

all

© Midmark Corporation 2008 SF-1928 004-0586-00 [Revised: 6/16/10]

B-17

Always verify model & serial number

Loading...
+ 93 hidden pages