Midea MFJ-24ARN1-QB8, MFJ-48ARN1-RB6 Service Manual

Page 1
Model:
MFJ-24ARN1-QB8 MFJ-48ARN1-RB6
Floor Standing Type Air Conditioner
Page 2
Content
CONTENT
1
Safety Precautions .......................................................................................... 1
1.1 Precaution .................................................................................................................... 1
1.2 Installation ................................................................................................................... 1
1.3 Caution ......................................................................................................................... 1
1.4 Operational .................................................................................................................. 1
3
Out Dimensions ............................................................................................... 3
3.1 Indoor Unit ................................................................................................................... 3
3.2 Outdoor Unit ................................................................................................................. 4
4
External view and display ............................................................................... 5
4.1 External view ................................................................................................................ 5
4.2 Display panel ............................................................................................................... 6
5
Refrigerant cycle diagram .............................................................................. 7
5.1 Cooling only .................................................................................................................. 7
5.2 Heat pump mode ......................................................................................................... 7
6
PCB drawing & wiring diagram ...................................................................... 8
6.1 MFJ-24ARN1-QB8 ........................................................................................................ 8
6.2 MFJ-48ARN1-RB6 ........................................................................................................ 9
7
Installation detail ........................................................................................... 10
7.1 Installation place ....................................................................................................... 10
7.2 Installing ..................................................................................................................... 11
7.3 Refrigerant pipe connecting .....................................................................................13
7.4 Drain Pipe of The Indoor Unit ...................................................................................15
7.5 Wiring .........................................................................................................................15
7.6 Test operation ............................................................................................................ 16
8
Electronic function ........................................................................................ 17
8.1 Performance Index .................................................................................................... 17
8.2 Main data Introduction.............................................................................................. 17
8.3 Operation Modes and Functions .............................................................................. 17
8.4 Other Functions .........................................................................................................19
9
Characteristic of temperature sensor ......................................................... 20
10 Trouble shooting ........................................................................................... 21
10.1 Protective Function .................................................................................................... 21
10.2 Self-diagnosis ............................................................................................................ 21
10.3 Troubles and Solutions ............................................................................................. 22
Page 3
Safety Precautions
1
1 Safety Precautions
1.1 Precaution
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2 Installation
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service
center.
Do not disassemble or repair the product by yourself.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the
condenser and evaporator.
Be sure the installation area does not deteriorate with age.
Take care to ensure that power cable could not be pulled out or damaged during operation.
Do not place anything on the power cable.
Do not plug or unplug the power supply plug during operation.
Do not store or use flammable gas or combustible near the product.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the
product on.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the
power supply cable as soon as possible.
When the product is soaked (flooded or submerged), contact an Authorized service center.
Be caution that water could not enter the product.
Turn the main power off when cleaning or maintaining the product.
When the product is not be used for a long time, disconnect the power supply plug or turn off the
breaker.
1.3 Caution
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
Keep level even when installing the product.
Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
Use two or more people to lift and transport the product.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
1.4 Operational
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigerant system.
Do not block the inlet or outlet of air flow.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Page 4
Safety Precautions
2
Do not touch the metal parts of the product when removing the air filter. They are very sharp.
Do not step on pr put anything on the product. (outdoor units)
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
Do not insert hands or other object through air inlet or outlet while the product is operated.
Do not drink the water drained from the product.
Use a firm stool or ladder when cleaning or maintaining the product.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old
and mew batteries or different types of batteries.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not
use the remote of the batteries have leaked.
Page 5
Outer Dimensions
3
2 Out Dimensions
2.1 Indoor Unit
Dimension Mode
Width
(mm)
Height
(mm)
Depth
(mm)
24K 500 1700 290 48K 540 1825 410
Page 6
Outer Dimensions
4
2.2 Outdoor Unit
Dimension Mode
W idth
(mm)
Height
(mm)
Depth
(mm)
A
(mm)
B
(mm)
24K
840
695
335
560
335
Dimension Mode
W idth
(mm)
Height
(mm)
Depth
(mm)
A
(mm)
B
(mm)
48K
940
1245
360
602
380
Page 7
External view and display
5
3 External view and display
3.1 External view
1
2
3
4
5
6
7
8
11
10
9
Ou tdoor unit
1
Air outle t
2
Operation panel
3
Hori zo ntal airf lo w co nt ro l l ouve r
4
Vertical ai rflo w co ntr ol louve r
5
Remote con troller holder( on so me mod els)
6
Air inl et(2 sides )
7
Drain pi pe , vent pip e
8
Co nn ectio n cabl e
9
Co nn ectio n pipe
10
Refrigerant pipe po rt
11
Air outlet
In door un i t
Note: All the pictures in this manual are for explanation purpose only. They may be slightly
different from the air conditioner you purchased(depend on model). The actual shape shall prevail.
Page 8
External view and display
6
3.2 Display panel
au to
T2
T3
T4
T1
OFF
ON
AUX IL IARY FU NCT ION
M ODE
FA N S PEED
A DJU ST
M ODE
A DJU ST
LOCK
TE ST RUN NING
ON /OF F
1
2 3 4 5 6
57
In di c ators
Auto op eration display
Co ol ing op er at ion d i sp l ay
Dry op era tio n display
Heating operati on di sp lay
Fa n op era tion di s play
Vert ical ai r f low di spl ay
Hor i zontal airflo w disp lay
Slee p opera ti on display
Turbo ope rat io n displa y On t imer op eration display
Of f timer operati on dis play Loc k oper a tion di s pl ay
Fa n spe ed operat io n display
Room Te mp/Set Temp
/Set Tim er displa y
Page 9
Refrigerant cycle diagram
7
4 Refrigerant cycle diagram
4.1 Cooling only
4.2 Heat pump mode
Page 10
PCB drawing & Wiring diagram
8
5 PCB drawing & wiring diagram
5.1 MFJ-24ARN1-QB8
Indoor unit
Outdoor unit
Page 11
PCB drawing & Wiring diagram
9
5.2 MFJ-48ARN1-RB6
Indoor unit
Outdoor unit
Page 12
Installation detail
10
6 Installation detail
6.1 Installation place
6.1.1 Indoor Unit
A place which provides the spaces around the indoor unit as required above in the diagram.
A place where is no obstacle near the inlet and outlet area.
A place which can bear the weight of the indoor unit.
A place which allows the air filter to be removed downward.
A place where the reception range is not exposed to direct sunlight.
In the center of the room where possible.
6.1.1.1 Please stand the unit in hard and flat ground;
Please reserve space for installation and maintenance.
6.1.1.2 Please check the elevation difference between the indoor unit and the outdoor unit, the length of the refrigerant pipe, and the curved places (bend) of the pipe are no more than the following numbers:Elevation difference: no more than 10 M (if the elevation difference between indoor and outdoor unit is more than 10 meters, it is recommended that the outdoor unit be placed above the indoor unit.)
Pipe length: no more than 20 M
Bends: no more than 5 places
6.1.2 Outdoor Unit
6.1.2.1 Before installing the outdoor unit, you should:
Select a place where no direct sunlight or other heat-radioactivity may reach. A sunshade is
needed if it is unavoidable.
Select a place that is easy to connect indoor unit's pipe and electric wires.
Avoid a place where combustible gas may leak or stay.
Keep it in mind that water may drain out of the outdoor unit while in "Heat" mode.
Page 13
Installation detail
11
6.1.2.2 If the outdoor unit is to be installed on a roof or where no constructions are around, you should avoid hard wind blows directly to the air outlet, because it may cause trouble for air-flow shortage.
6.1.2.3 Reserve enough space for installation, maintenance and unit-functioning.
Remove as many obstacles as possible nearby.
6.2 Installing
6.2.1 To prevent the indoor unit from falling, you must:
Pay full attention to the unit because its long outer shape makes it easy to fall;
Safety Lock
Screws
3.9 25
×
M8 Screws
Screws
3.9 25
×
Air Outlet
Air Inlet
Screw hole
(on the unit
)
2
Firmly fix the unit to the wall and in the ground to avoid accidental falling.
6.2.2 Dismounting the air-inlet grid
Please take off the air-inlet grid before connecting the pipes/wires.
Pull down the two knobs on the grid, take off the two screws, then the air-inlet grid goes free.
Page 14
Installation detail
12
6.2.3 Take the Pipe Clip off before connecting the pipes and wiring; fit it when these finished.
Use accessories 4 and 9 to connect the pipes/wires on both sides and back side.
Drain Pipe
Reamer Joint
Pipe/wire-hole positions on both sides
Wiring Hole 35
φ
Refrigerant/drain Pipe hole 80
φ
Reamer Joint
Refrigerant Pipe
Pipe/wire-hole position on the bottom
Wiring Hole 35
φ
Refrigerant/drain Pipe hole
Refrigerant/drain
Pipe hole
6.2.4 Ship the a/c to the installation place originally packed;
Be careful while hanging the unit because the center of gravity of the unit is not centralized;
Do not make the angle of inclination more than 45 degrees while shipping;(Avoid horizontal
storage)
Be sure the electric insulation work is well done if installed on metal ceiling / wall.
Fix the unit feet with bolts (M10/M8). Be sure the unit is fixed strongly enough to against blast or
earthquake.
Page 15
Installation detail
13
Make a concrete basement to the unit by the above references.
6.3 Refrigerant pipe connecting
6.3.1 Pipe length and the elevation
The correct refrigerant quantity filled in the 5-meter-long pipe of the outdoor unit is marked on
the Product Data Plate. If you have to use longer pipe for every meter plus pipe, the refrigerant
should be added according to the following calculation.
Standard
length
Max. Max. A dditional
(m) E lev ation Elev ation refrigerant
Btu/h GAS LIQUID B (m) A (m) (g/m)
24K
5/8’’ (φ16)
1/4’’ (φ9.53)
51020
65
48K
3/4’’ (φ19)
1/2’’ (φ12.7)
51530
90
Pipe sizeC apacity
6.3.2 Piping connection
6.3.2.1 Connecting Of Refrigerant Pipe
a.
Only the correctly installing of indoor and outdoor unit done, can the refrigerant pipe be connected.
b.
The cut-off valves are completely close before ex-work. Before connecting the refrigerant pipe, be careful to check whether the valves are completely close.
c.
The connecting procedure of refrigerant pipe: first, unscrew the two valves on the outdoor unit and the pipe-jointing nut on the indoor unit(please keep them care fully). Please connect the refrigerant
pipe according to the manual, the pipe-jointing nut should be screw tightly and no leakage. Note:
you need two wrenches to make balance.
d.
When the connecting of refrigerant pipe is finished, before power on the system, you should
Page 16
Installation detail
14
vacuum the indoor unit through the maintenance port on the cut-off valves, or open the
high-pressure valve, and exhaust the air through the maintenance port on the low-pressure
valve(closed). It will take about ten seconds. Then screw tightly the maintenance port. (When
supplement the refrigerant, fill through the maintenance port of the low-pressure valves on the
outdoor unit ).
e.
Open all the valves completely before power on the system, or it will be sick for low efficiency.
f.
Gas leak check. Make sure no gas from connections with leak detector or soap water.
6.3.2.2 Using bronze pipe selling in market
Completely shut the cut-off valves of the outdoor unit (as ex-work status). After the refrigerant
pipe has been connected with both the indoor and outdoor unit, let the air exhaust out from the
maintenance gap on he low-pressure cut-off valves of the outdoor unit. Screw the nuts tightly
on the maintenance gap after the air has been drained.
6.3.2.3 To make the refrigerant pipe unblocked completely
you should keep the cut-off valves of the outdoor unit completely open after you have finished
the above steps (step1) or step 2))
Note: Before screwing the reamer nut, smear the pipe and the connecting surface with
refrigerant oil; Check and make sure there is no leakage by soap-water or leakage-checker after
connecting;
Be sure the connecting joint on the indoor side is insulated.
Use two wrenches to connecting the pipes.
Tubing size Torque
9.52 3270~3990N.cm(333~407kgf.cm)
12.7 4950~6030N.cm(504~616kgf.cm)
16 6180~7540N.cm(630~770kgf.cm)
19 9720~11860N.cm(990~12106kgf.cm)
6.3.3 Air Purging
When Using the Vacuum Pump
(For method of using a manifold valve, refer to its operation manual.)
a.
Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a
charge port of the low-pressure valve on the gas pipe side.
b. Connect the charge hose connection to the vacuum pump.
c. Fully open the handle Lo of the manifold valve.
d. Operate the vacuum pump to evacuate. After starting evacuation, slightly loose the flare nut of
the Lo valve on the gas pipe side and check that the air is entering.(Operation noise of the
vacuum pump changes and a compound meter indicates 0 instead of minus)
e. After the evacuation is complete, fully close the handle Lo of the manifold valve and stop the
operation of the vacuum pump. Make evacuation for 15 minutes or more and check that the
compound meter indicates -76cmHg (-10x106Pa).
Page 17
Installation detail
15
f. Turn the stem of the packed valve B about 45 counterclockwise for 6~7 seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure
indicator is a little higher than the atmosphere pressure.
g. Remove the charge hose from the low pressure charge hose.
h. Fully open the packed valve stems B and A.
i. Securely tighten the cap of the packed valve.
6.4 Drain Pipe of The Indoor Unit
Make sure the drainpipe is connected to the outdoor side downward;
The hard polyvinyl chloride(PVC)plastic pipe (external diameter 26 mm) sold is the market is
suitable for the attached soft drain pipe;
Please connect the Soft Drain Pipe with the Drain Pipe, then fix it with band;
If you have to connect the Drain Pipe indoors, to avoid condensing caused by air intake, you
must cover the pipe with heat-insulation material (polyethylene with Specific Gravity of 0.03, at least
9 mm in thickness), and use Glue Band to fix it.
After the Drain Pipe has been connected, please check if the water drains out of the pipe
efficiently and has no leakage.
Refrigerant pipe and Drainpipe should be heat-insulated to avoid condensing and
water-dropping later on.
6.5 Wiring
Please refer to the Wiring Diagram.
Page 18
Installation detail
16
(Wiring size: 2.5mm )
2
(Wiring size: 2.5mm )
2
Note: Some models is equipped with a cord having a plug, So a wall outlet shall be properly
installed.
6.6 Test operation
Perform test operation after completing gas leak and electrical safety check. The test operation
time should last more than 30 minutes.
1). Open the panel and lift the panel up to angle which remains fixed. Do not lift the panel any
further when it stops with a "click"sound.
2). Press the manual switch button twice until the operation indicator lights, the unit will operate on
Manual Cool mode.
3). Check if all the functions work well while testing the air conditioner. Especially check whether
the drainage of indoor unit is smooth or not.
4). Press the manual switch button again till the operation indicator turns dark after finishing the
test operation and the unit stops operation.
Page 19
Electronic function
17
7 Electronic function
7.1 Performance Index
No. Item Index
1 Applicable Voltage Range 185-253V, 342-418V
2 A/C Frequency 50Hz
3 Working environment temperature -7°C- +45°C
7.2 Main data Introduction
Ts : Set temperature,
T1 : Room temperature
T2: Evaporator pipe temperature
7.3 Operation Modes and Functions
7.3.1 Manual Operation
7.3.2 Heating Mode
7.3.2.1 Four-way valve opens at once, while defrosting process closes.
7.3.2.2 Condition for the compressor action: (Ts=set temperature, T1=room temperature)
7.3.2.3 Indoor Fan Action
Anytime remote switchover for fan speed among high/low/auto, anti-cold air function takes
priority.
Auto fan in heating mode
Anti-cold air:
Switchover between fan speed and fine tune can be set according to temperature of evaporator
pipe (T2).
Condition Compressor and outdoor fan
Room temperature up T1-Ts=0°C Off
T1-Ts>-1°C On
Room temperature down T1-Ts<-1°C On
T1-Ts=0°C Off
Condition Fan speed
Room temperature up T1-Ts>-1°C Low
T1-Ts<-1°C Hi.
Room temperature down T1-Ts<-2°C Hi.
-2°C <T1-Ts <-1°C Low
Condition Fan speed
Room temperature up T2<25°C Off
25°C <T2<32°C Low
T2>32°C Set fan speed
Room temperature down T2>22°C Set fan speed
20°C <T2<22°C Low
Page 20
Electronic function
18
7.3.3 Defrost (only available to heating mode)
7.3.3.1 Defrosting Conditions
Starting Of Defrosting Condition (meet one of the following is ok):
(1)Accumulated compressor operating time when temperature of outdoor heat exchanger coil
T3 is below -2°C reaches up to over 46 minutes.(When T3 is over 20°C, calculate time again.)
(2) Under evaporator high temperature protection, the accumulated time when outdoor fan
motor is off and compressor is on reaches up to over 90 minutes .(When T3 is over 20°C, calculate
time again.)
High temperature defrosting condition:
Under high temperature protection of evaporator, the time when outdoor fan is shut down but
compressor is not has been accumulated for up to 90 minutes.
7.3.3.2 Defrosting Action
Four-way valve, indoor fan, outdoor fan are shut down. Compressor keeps on.
7.3.3.3 Ending Of Defrosting Condition (meet one of the following is ok):
(1)Time of defrosting lasts 10 minutes.
(2)Temperature of outdoor coil T3 is up to 20°C.
7.3.4 Cooling Mode
7.3.4.1 Four-way valve is closed.
If four-way valve is open before the machine enters cooling mode, then four-way valve will be
closed at the first time, the compressor starts under the cooling mode.
7.3.4.2 Conditions for the compressor and outdoor fan action (Ts = set temperature)
7.3.4.3 Action of Indoor Fan
HIGH/LOW/AUTO fan can be switched over by your comfort.
Auto fan under cooling mode.
7.3.5 Dehumidifying Mode
7.3.5.1 Indoor fan speed is low.
7.3.5.2 If certain protective condition is met, operation will be carried out.
T2<20°C Off
Condition Compressor and outdoor fan
Room temperature up T1-Ts=0°C Off
T1-Ts>1°C On
Room temperature down T1-Ts>0°C On
T1-Ts=0°C Off
Condition Fan speed
Room temperature up T1-Ts>2°C Hi.
1°C < T1-Ts <2°C Low
Room temperature down T1-Ts>1°C Hi.
T1-Ts <1°C Low
Page 21
Electronic function
19
7.3.6 Auto Mode
7.3.6.1 Under auto mode, the indoor fan is set to be auto.
7.3.6.2 When entering auto mode, the heating, fan only or cooling operation will be automatically chosen according to the room temperature T1 and the set temperature Ts.
Condition Mode
T1-Ts>1°C Cooling
-1°C< T1-Ts<1°C Fan
T1-Ts<-1°C Heating(fan for cooling only type)
7.3.6.3 After one mode is chosen, if the condition lasts for 15 minutes, meanwhile the compressor doesn't start up within consecutive 15 minutes, the operation mode will be re-chosen according to the T1and Ts.
7.3.6.4 If certain condition is met, then the corresponding protective function will be executed.
7.3.7 Fan Only Mode
7.3.7.1 Under this mode, four-way valve, compressor and outdoor fan are shut down.
7.3.7.2 High/Low/Auto fan can be switched over through manual control. Auto fan will be controlled in line with cooling auto fan with temperature set to be 24C.
7.4 Other Functions
7.4.1 LCD display
Mode, Set temp.,fan speed, time, timer, protection etc.
7.4.2 Timer
The machine should be provided with max. Interval of 24h and min. resolution ratio of 15
minutes.
Page 22
Characteristic of temperature sensor
20
8 Characteristic of temperature sensor
Temp.Resistance KΩ Temp.Resistance KΩ Temp.Resistance K
-10 62.2756 17 14.6181 44 4.3874
-9 58.7079 18 13.918 45 4.2126
-8 56.3694 19 13.2631 46 4.0459
-7 52.2438 20 12.6431 47 3.8867
-6 49.3161 21 12.0561 48 3.7348
-5 46.5725 22 11.5 49 3.5896
-4 44 23 10.9731 50 3.451
-3 41.5878 24 10.4736 51 3.3185
-2 39.8239 25 10 52 3.1918
-1 37.1988 26 9.5507 53 3.0707 0 35.2024 27 9.1245 54 2.959 1 33.3269 28 8.7198 55 2.8442 2 31.5635 29 8.3357 56 2.7382 3 29.9058 30 7.9708 57 2.6368 4 28.3459 31 7.6241 58 2.5397 5 26.8778 32 7.2946 59 2.4468 6 25.4954 33 6.9814 60 2.3577 7 24.1932 34 6.6835 61 2.2725 8 22.5662 35 6.4002 62 2.1907 9 21.8094 36 6.1306 63 2.1124
10 20.7184 37 5.8736 64 2.0373 11 19.6891 38 5.6296 65 1.9653 12 18.7177 39 5.3969 66 1.8963 13 17.8005 40 5.1752 67 1.83 14 16.9341 41 4.9639 68 1.7665 15 16.1156 42 4.7625 69 1.7055 16 15.3418 43 4.5705 70 1.6469
Page 23
Exploded view & spare-part
21
9 Trouble shooting
9.1 Protective Function
9.1.1 3-minute delay for the compressor start-up
At the beginning of energizing or after the stop of the compressor, 3-minute delay will be needed
to start the compressor.
When switching over between cooling/heating mode, the compressor stops automatically.
9.1.2 Evaporator protection against high temperature
9.1.2.1 Only available under heating mode.
9.1.2.2 The operation principle is as follows: (T2 = evaporator temperature)
Condition Outdoor fan Compressor
T2>56°C Off On
T2>62°C Off Off
T2<62°C On Off
T2<50°C On On
Note: During protection, the indoor fan continues operating at a set speed, while the anti-cold air
function of heating and the compressor will be 3 minute delayed to shut down for protection.
9.1.3 Evaporator Protection against low temperature
9.1.3.1 Only available under cooling and dehumidifying status.
9.1.3.2 Protection principle:
Condition Outdoor fan Compressor
T2<2°Clast 3 minute Off Off
T2>8°C On On
9.1.3.3 The restart of the compressor shall execute the delay protection.
9.1.4 Condenser high temperature protection
9.1.4.1 Only available to cooling and dehumidifying mode.
9.1.4.2 Action condition
Condition Outdoor fan Compressor
Condenser temp.>62°C Off Off
Condenser temp.<48°C On On
9.1.4.3 Delay protection should be performed when the compressor restarts.
9.1.5 Outdoor protection
When outdoor protection signal is high level, outdoor unit will perform protection: the whole
machine will be shut down while the indoor unit will indicate the corresponding protection signal.
The A/C will recover if outdoor errors are eliminated after the outdoor protection occurs.
9.2 Self-diagnosis
Codes Contents
P4 Protection of temperature of indoor evaporator
P5 Protection of temperature of outdoor condenser
P9 Protection of defrosting or anti-cold wind
E1 Open-circuit and short-circuit of temperature sensors T1
E2 Temp. sensor T2 on indoor evaporator is open circuit or short circuit
Page 24
Exploded view & spare-part
22
E3 The condenser temperature sensor T3 is open or short
E6 Protection of outdoor unit
9.2.1 LEDs for the indication of outdoor trouble
In normal operation, LEDs emit no light and they will flash at a frequency of 5 Hz when trouble
occurs. Their codes are listed in the following table:
LED1 LED2 LED3 Contents
Off Off On Ok
On Off On Phase sequence error
Off On On Overload of current
On On On Lack of phase
9.3 Troubles and Solutions
Before calling for service, please review the following list of common problems and solutions.
If any of the following conditions occur, check your unit and resolve corresponding problems referring
to given remediation. If the trouble can't be settled contact our dealer.
Trouble Cause Solutions
Unit does not start Power failure. Wait for the comeback of power
Power switch is open. Switch on the power
Fuse of power switch may have blown. Replace the fuse
Batteries remote controller are exhausted. Replace the batteries
The time is not start-up time you have set. Wait or cancel the time set.
Air flowing normally
with low
cooling(heating)
effect
Temperature is not set correctly. Set the temperature properly.
Door or window is open. Close door and window.
Air filter is blocked with dust or dirtiness. Clean the air filter.
Inlet/outlet of indoor/outdoor units are
blocked.
Clear all blockages.
Inlet/outlet of indoor/outdoor units are
blocked.
Clear the blockage, then restart
your operation.
Be in 3 minutes protection of compressor Wait
Page 25
Exploded view & spare-part
23
Number Display code Problem What to do
1 E1 E2 E3 E4 Temperature Sensor is off or short-circuit. Contact service people
2 E6 Outdoor unit protection Contact service people
3 E8 Electrostatic dust collection Contact service people
4
P4
The temperature of the evaporator of indoor
unit is too low or high (For the protection
feature, the compressor turns off
automatically)
Turn off the unit, clean the air
filter, then restart the unit. If this
operation does not work, please
contact service people.
5
P5
The temperature of condenser of the
outdoor unit is too high (For the protection
feature, the compressor turns off
automatically)
Turn off the unit, check if there is
any obstacle in the air-inlet,
otherwise call the service people.
6 P9 Defrosting protection or warm-air
controlling is off
The unit will auto restart after
finishing the defrosting or the
temperature of the Heat
Exchanger of indoor unit raise.
Page 26
Exploded view & spare-part
24
Specification
Model
ModelModel
Model
MFJ-24ARN1-QB8 MFJ-48ARN1-RB6
Factory Code
Factory CodeFactory Code
Factory Code
2T004330T031 2T004370T020
Electrical Data
Electrical DataElectrical Data
Electrical Data
Power supply Ph-V-Hz
1φ,220-240V,50HZ 3φ,380-420V,50HZ
Capacity
Cooling/Heating
Btu/h
24000/27000+7200 46000/49000+12000
Power consumption
Cooling/Heating
W
2500/2450+2100 5200/5100+3500
Rated current Coo
ling/Heating
A
12/11.5+9.6 8.6/8.5+5.6
EER
Cooling/Heating
Btu/w.h
9.5/10.9 8.9/10.2
System data
System dataSystem data
System data
Refrigerant type g
R410A/2000 R410A/4500
Design pressure MPa
4.2 4.2
Air flow m3/h
1100 1750
Noise level
Indoor dB(A)
48 50
Outdoor dB(A)
60 62
Dimension&Weight
Dimension&WeightDimension&Weight
Dimension&Weight
Indoor
Dimension (W*H*D)
mm
500x1700x290 540x1825x410
Packing (W*H*D) mm
615x1805x415 655x1935x555
Net/Gross weight
Kg
41.5/58.5 58/75
Outdoor
Dimension (W*H*D)
mm
840x695x335 940x1245x360
Packing (W*H*D) mm
965x755x395 1018x1380x435
Net/Gross weight
Kg
60/63 104/115
Refrigerant piping
Refrigerant pipingRefrigerant piping
Refrigerant piping
Liquid side/ Gas side mm
Ф9.53/Ф16 Ф12.7/Ф19
Max. refrigerant pipe length m
20 30
Max. difference in level m
10 15
Applicable ambient
Applicable ambientApplicable ambient
Applicable ambient
Ambient temp
-7-45 -7-45
Application area m2
40-56 80-112
Compressor
CompressorCompressor
Compressor
Compressor
Model
PA290X3CS-4MU1 C-SBN373H8D
Type
Rotary Scroll
Brand
GMCC Sanyo
Capacity Btu/h
24490 48109
Input W
2430 4750
Rated current(RLA) A
11.4 8.22
Locked rotor Amp(LRA)
A
61 66
Thermal protector
UP14SE5145 internal
Capacitor uF
50 No
Refrigerant oil ml
950 1700
Fan Motor
Fan MotorFan Motor
Fan Motor
Indoor Model
YDK75-8 YDK120-8T
Page 27
Exploded view & spare-part
25
Brand
Welling Welling
Input W
164 300
Capacitor uF
5UF/450V 6.5UF/450V
Speed(high/low) r/min
575/540/440 600/550/480
Outdoor
Model
YDK100-6D YDK65-6F/YDK65-6
Brand
Welling Welling
Input W
170 156/148
Capacitor uF
5UF/450V 3.5UF/450V
Speed r/min
900 800
Loading...