Midea MFE-60ARN1-RB4W, MFE-60AMN1-RB4W Service Manual

Page 1
EFEU-A-1312
SERVICE MANUAL
MIDEA AIRCONDITIONER
Model: MFE-60ARN1-RB4W MFE-60AMN1-RB4W
Code
Factory model
Model
Power supply
2T0043800005
CE-KFR160LW/SDN1Y-E(B4)
MFE-60AMN1-RB4W
3Ph, 380-420V, 50Hz
2T0043800026
CE-KFR160LW/SDN1Y-E(B4)-W[J]
MFE-60ARN1-RB4W
3Ph, 380-420V, 50Hz
2T0043800036
EU-KFR150LW/SDN1Y-E(B4)-W
MFE-60ARN1-RB4W
3Ph, 380-420V, 50Hz
Page 2
CONTENTS
1. Safety Precautions .................................................................................................................... 1
1.1 Precaution .................................................................................................................................................... 1
1.2 Installation .................................................................................................................................................... 1
1.3 Caution .......................................................................................................................................................... 1
1.4 Operational................................................................................................................................................... 2
2. Dimension .................................................................................................................................. 3
2.1 Indoor Unit ..................................................................................................................................................... 3
2.2 Outdoor Unit .................................................................................................................................................. 4
3. Refrigerant cycle diagram ........................................................................................................ 5
4. Wiring diagram .......................................................................................................................... 6
4.1 MFE-60AMN1-RB4W .................................................................................................................................. 6
4.2 MFE-60ARN1-RB4W(2T0043800026) .................................................................................................... 7
4.3 MFE-60ARN1-RB4W(2T0043800036) .................................................................................................... 8
5. Installation details ..................................................................................................................... 9
5.1 Installation place .......................................................................................................................................... 9
5.2 Installing ....................................................................................................................................................... 10
5.3 Refrigerant pipe connection ....................................................................................................................13
5.4 Drain pipe of the indoor unit ....................................................................................................................26
5.5 Wiring ............................................................................................................................................................ 27
5.6 Test run ......................................................................................................................................................... 27
6. External view and display ...................................................................................................... 28
6.1 Parts names ................................................................................................................................................28
6.2 Control panel ...............................................................................................................................................29
6.3 LED ...............................................................................................................................................................30
Page 3
7. Operation characteristics ...................................................................................................... 31
8. Electronic function ................................................................................................................. 32
8.1 Main data introduction ...............................................................................................................................32
8.2 Main Protection ...........................................................................................................................................32
8.3 Operation modes and functions ..............................................................................................................33
8.4 Other functions ............................................................................................................................................40
9. Trouble shooting ..................................................................................................................... 40
9.1 Self-diagnosis .......................................................................................................................... 40
9.2 LEDs for the indication of outdoor trouble .............................................................................. 41
9.3 Troubles and solutions ............................................................................................................ 42
Page 4
1
1. Safety Precautions
1.1 Precaution
To prevent injury to the user or other people and property damage, the following instruction s must be followed. Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2 Installation
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized servic e center. Do not disassemble or repair the product by yourself. Sharp edges could cause injury, be especially careful of the case edges and the fins on th e condenser and evaporator. Be sure the installation area does not deteriorate with age. Take care to ensure that power cable could not be pulled out or damaged during operatio n. Do not place anything on the power cable. Do not plug or unplug the power supply plug during operation. Do not store or use flammable gas or combustible near the product. When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on. If strange sounds, or small or smoke comes from product. Turn the breaker off or disconne ct the power supply cable as soon as possible. When the product is soaked (flooded or submerged), contact an Authorized service center. Be caution that water could not enter the product. Turn the main power off when cleaning or maintaining the product. When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
1.3 Caution
Always check for gas (refrigerant) leakage after installation or repair of product. Install the drain hose to ensure that water is drained away properly. Keep level even when installing the product. Do not install the product where the noise or hot air from the outdoor unit could damage t he neighborhoods. Use two or more people to lift and transport the product. Do not install the product where it will be exposed to sea wind (salt spray) directly.
Page 5
2
1.4 Operational
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draf t). Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system. Do not block the inlet or outlet of air flow. Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. Do not touch the metal parts of the product when removing the air filter. They are very sh arp. Do not step on pr put anything on the product. (outdoor units) Always insert the filter securely. Clean the filter every two weeks or more often if necessar y. Do not insert hands or other object through air inlet or outlet while the product is operated. Do not drink the water drained from the product. Use a firm stool or ladder when cleaning or maintaining the product.
Page 6
3
2. Dimension
2.1 Indoor Unit
Dimension Mode
W
(mm)
D
(mm)
H
(mm)
55K 600 358 1900
Page 7
4
2.2 Outdoor Unit
Dimension Model
W (mm)
D (mm)
H (mm)
W1 (mm)
A (mm)
B (mm)
MOI-60H-RB4W
940
360
1245
1020
602
380
MOU-60HN1-RB4W (2T0043800026)
900
350
1170
985
590
378
MOU-60HN1-RB4W (2T0043800036)
938
633.5
404
448
370
392
Page 8
5
3. Refrigerant cycle diagram
MOI-60H-RB4W MOU-60HN1-RB4W(2T0043800036)
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
T3 Condenser temp. sensor
Accumulator
T5 Discharge temp. sensor
INDOOR OUTDOOR
Low pressure switch
High pressure switch
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
For MOI-60H-RB4W, there is no low pressure switch.
MOU-60HN1-RB4W(2T0043800026)
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
T3 Condenser temp. sensor
T5 Discharge temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
Oil return Capillary
Oil separator
Low pressure switch
High pressure switch
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
Page 9
6
4. Wiring diagram
4.1 MFE-60AMN1-RB4W
Indoor Unit
Outdoor Unit
Page 10
7
4.2 MFE-60ARN1-RB4W(2T0043800026)
Indoor Unit
Outdoor Unit
Page 11
8
4.3 MFE-60ARN1-RB4W(2T0043800036)
Indoor Unit
Outdoor Unit
Page 12
9
5. Installation details
5.1 Installation place
5.1.1 Indoor Unit a.Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. b.There should not be any heat source or steam near the unit. c.There should not be any obstacles blocking the air circulation. d.A place where air circulation in the room is good. e.A place where drainage can be easily done. f.Do not install the unit near the door way. g.There should not be any direct sunlight. Otherwise, the sun will fade the plastic cabinet and affect its appearance. If unavoidable, sunlight prevention should be taken into consideration.
5.1.1.1 Please stand the unit in hard and flat ground; Please reserve space for installation and maintenance.
5.1.2 Outdoor Unit The outdoor unit should be put in a position that guarantees the minimum space for
sufficient air circulation and to allow maintenance work and the connections of electrical and refrigerant circuit lines. It may be installed on a floor or flat roof or wall-mounted, provided its weight is properly supported and there is no transmission of vibration to the adjacent rooms.
5.1.2.1 Before installing the outdoor unit, you should: a).If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat
radiation from the condenser is not obstructed.
b).Select a place that is easy to connect indoor unit's pipe and electric wires. c).Avoid a place where combustible gas may leak or stay. d).Keep it in mind that water may drain out of the outdoor unit while in "Heat" mode. e).Ensure the space around the back and sides and the front of the unit. f).Take the air conditioner weight into account and select a place where noise and
vibration are minimum.
5.1.2.2 If the outdoor unit is to be installed on a roof or where no constructions are around, you should avoid hard wind blows directly to the air outlet, because
Page 13
10
it may cause trouble for air-flow shortage.
5.1.2.3 Reserve enough space for installation, maintenance and unit-functioning. Remove as many obstacles as possible nearby.
Caution:
Installation in the following places may cause trouble. If it is unavoidable to use in such places,please consult with the dealer. (1) A place full of machine oil. (2) A saline place such as coast. (3) Hot-spring resort. (4) A place full of sulfide gas. (5) A place where there are high frequency machines such as wireless installation, welding machine, medical facility. (6) A place of special environmental conditions.
5.2 Installing
5.2.1 Indoor Unit:
1. Anti-falling; To prevent the indoor unit from falling, you must: a. Pay full attention to the unit because its long outer shape makes it easy to fall; b. Firmly fix the unit to the wall or in the ground to avoid accidental falling.
Page 14
11
2. Dismounting the air-inlet grid Please take off the air-inlet grid before connecting the pipes/wires. Pull down the two knobs marked "PULL" on the grid, take off the two straps, then the air-inlet grid goes free.
3. Take the Pipe Clip off before connecting the pipes and wiring; fit it when these finished. Use accessories to connect the pipes/wires on both sides and back side.
Page 15
12
5.2.2 Outdoor Unit:
1. Ship the a/c to the installation place originally packed;
2. Be careful while hanging the unit because the center of gravity of the unit is not centralized;
3. Do not make the angle of inclination more than 45 degrees while shipping;(Avoid horizontal storage)
4. Be sure the electric insulation work is well done if installed on metal ceiling / wall.
5. Fix the unit feet with bolts (M10). Be sure the unit is fixed strongly enough to against
blast or earthquake.
6. Make a concrete basement to the unit by the above references.
Page 16
13
For the value of A and B, please refer to the dimension part.
5.3 Refrigerant pipe connection
5.3.1 Pipe length and the elevation
The correct refrigerant quantity filled in the 5-meter-long pipe of the outdoor unit is marked on the Product Data Plate. If you have to use longer pipe for every meter plus pipe, the refrigerant should be added according to the following calculation.
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional refrigerant
(g/m)
Gas
Liquid
60K
3/4’’
(Ф19)
1/2’’
(Ф12.7)
5
20
30
60
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability. Oil trap should be installed per 5-7 meters.
Page 17
14
5.3.2 Piping connection
5.3.2.1 Connecting Of Refrigerant Pipe a) Only the correctly installing of indoor and outdoor unit done, can the refrigerant
pipe be connected.
b) The cut-off valves are completely close before ex-work. Before connecting the
refrigerant pipe, be careful to check whether the valves are completely close.
c) The connecting procedure of refrigerant pipe: first, unscrew the two valves on the
outdoor unit and the pipe-jointing nut on the indoor unit(please keep them carefully). Please connect the refrigerant pipe according to the manual, the pipe-jointing nut should be screw tightly and no leakage. Note: you need two wrenches to make balance.
d) When the connecting of refrigerant pipe is finished, before power on the system,
you should vacuum the indoor unit through the maintenance port on the cut-off valves, or open the high-pressure valve, and exhaust the air through the maintenance port on the low-pressure valve(closed). It will take about ten seconds. Then screw tightly the maintenance port. (When supplement the refrigerant, fill through the maintenance port of the low-pressure valves on the outdoor unit).
e) Open all the valves completely before power on the system, or it will be sick for
low efficiency.
f) Gas leak check. Make sure no gas from connections with leak detector or soap
water.
5.3.2.2 Pipe Connecting Procedures Completely shut the cut-off valves of the outdoor unit (as ex-work status). Unscrew the
nuts on the cut-off valves and immediately connect the reamer joint (in 5 minutes). If it last too long, dust, vapor and other obstacles may enter the pipe and cause trouble later on. Before connecting the pipe, the air in the pipe should be removed in advance by releasing refrigerant R-410A.
Notes for the bendable pipe
a. The bendable pipe should be used on the indoor side; b. Bend angel may not exceed 90 degrees; c. The bend location should be made on the center of the pipe if possible, as for bend
radius, the bigger the better;
Page 18
15
d. The bendable pipe may not be bent for more than 3 times.
Bend the thin pipe
a. While bending, expose the pipe by cutting the concave gap on the bending heat-insulation pipe(roll it with soft band after bent).
b. To avoid pipe deformation, the radius is the bigger the better. c. Use a pipe-bending device to make the compact bending pipe.
5.3.2.3 Using bronze pipe selling in market
Completely shut the cut-off valves of the outdoor unit (as ex-work status). After t he refrigerant pipe has been connected with both the indoor and outdoor unit, let th e air exhaust out from the maintenance gap on he low-pressure cut-off valves of the outdoor unit. Screw the nuts tightly on the maintenance gap after the air has been drained.
5.3.2.4 To make the refrigerant pipe unblocked completely
You should keep the cut-off valves of the outdoor unit completely open after you have finished the above steps (5.3.2.2 or 5.3.2.3) Note:
1.Before screwing the reamer nut, smear the pipe and the connecting surface with r
efrigerant oil;
2.Check and make sure there is no leakage by soap-water or leakage-checker after
connecting;
3.Be sure the connecting joint on the indoor side is insulated.
4.Use two wrenches to connecting the pipes.
Page 19
16
Outside diameter
Torque
Additional tightening
torque
mm
inch
N.cm
N.cm
Ф12.7
1/2
4950
6030
Ф19
3/4
9720
11860
5.3.3 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be
leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
Page 20
17
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the
2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas
service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa.
If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes
more. If the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are
some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Page 21
18
after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way
valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way
valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening
Page 22
19
the flare nut on the 2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way
valves to the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m.
Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the
3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
Electronic scale
Page 23
20
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid
refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
5.3.4 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
Electronic scale
Page 24
21
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
5.3.5 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
Page 25
22
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened
position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge
hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa. Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of
18N.m.
Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
Page 26
23
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way
valves to the open position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
5.3.6 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Page 27
24
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter
indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
Page 28
25
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1
Electronic scale
Page 29
26
minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose
from the 3-way valve’s service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage
5.4 Drain pipe of the indoor unit
1.Make sure the drain pipe is connected to the outdoor side downward;
2.The hard polyvinyl chloride(PVC)plastic pipe (external diameter 26 mm) sold is the market is suitable for the attached soft drain pipe;
3.Please connect the Soft Drain Pipe with the Drain Pipe, then fix it with band;
4.If you have to connect the Drain Pipe indoors, to avoid condensing caused by air intake, you must cover the pipe with heat-insulation material (polyethylene with Spe cific Gravity of 0.03, at least 9 mm in thickness), and use Glue Band to fix it.
5.After the Drain Pipe has been connected, please check if the water drains out of the pipe efficiently and has no leakage.
6.Refrigerant pipe and Drainpipe should be heat-insulated to avoid condensing and water-dropping later on.
Page 30
27
5.5 Wiring
Please refer to the Wiring Diagram.
Note: The power supply of the air conditioner is different according to the models. Please refer to the WIRING DIAGRAM pasted on the indoor and outdoor units befo re wire connection.
5.6 Test run
1. Make sure the resistance between the socket of the electric system and the grounded line, when detected by a 500 V million-ohmmeter, is at least 2 million ohms. If the resistance is less than the number, please do not use the air conditioner;
2. Check again if the air conditioner is properly installed, especially for the anti-fallin g device;
3. When accomplished all the above procedures, service people should explain and test the air conditioner for the customer according to the "User's Manual".
Page 31
28
6. External view and display
6.1 Parts names
This unit consists of indoor unit and outdoor unit.
Note: All the pictures in this manual are for explanation purpose only. They may be slightl y different from the air conditioner you purchased(depend on model). The actual sh ape shall prevail.
Air Outlet Let the conditioned air go out from it. Control Panel (inserted) Consists of indicators and control buttons. Air Inlet Where a filter is settled, absorbing the air in the room and clean it. Drain Pipe From which the condensed water is drained. Refrigerant Pipe In which the refrigerant passes through, connects the outdoor unit with the indoor unit. Outdoor(condensing)Unit Consists of compressor, fan motor, heat-exchanger and other electric parts. Decorative LED Displays green or red lights according to running mode.
Page 32
29
6.2 Control panel
On/Off button: Power-on and power-off the A/C(Air conditioner) LED indicator :Lights when unit runs normally ,flashes one time per second when the unit
is waiting for orders ,flashes two times per second when the unit is sick. Mode select button : Use this button to select among the following 5 modes : Auto :automatically adjust the temperature (17~30) Cool :normal cooling operation(17~30) Heat :(for cooling and heating only)normal heating operation(17~30) Dry :dehumidify the room air and keep the indoor temperature(17~30) Fan :fan only ,no cooling Temp .adjusting buttons : warm:push this button to raise the setting temperature cool:push this button to lower the setting temperature. Fan Speed button : Auto: automatically adjust the fan speed Low: Low fan speed. Med: Medium fan speed High: High fan speed Swing /fresh button :push this button to make the air-flow blow left or right and anion
producer open.
Time/clock Alter button (Short form :ALT button):use this button to alter the modes between timeand clock’.
Page 33
30
Time adjusting button: Hour: set the hour of current time Minute: set the minute of current time Confirm/Cancel button :Push this button to confirm or cancel the timer setting Test Running button :Push this button to make the unit run for an hour of test ,this function
is specially designed for maintenance technicians.
6.3 LED
A. Operation modes B. Timer setting clock or trouble display C. Timer display D. Types of clock E. Room temperature setting display F. Fan speed of the indoor unit display G. Status display
Page 34
31
7. Operation characteristics
Mode
Temperature
Cooling
operation
Heating operation
Drying
operation
Room temperature
17℃~32℃
0~30
17℃~32℃
Outdoor temperature
18℃~43℃
-7℃~43℃:
For the models
with low
temperature
cooling system
-7~24
18℃~ 43℃
CAUTION:
1. If air conditioner is used outside of the above conditions, certain safety protection
features may come into operation and cause the unit to function abnormally.
2. Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. Optimum performance will be achieved within this operating temperature.
Page 35
32
8. Electronic function
8.1 Main data introduction
Ts : Set temperature, T1 : Room temperature T2: Evaporator pipe temperature T3: Condenser pipe temperature T4: Outdoor ambient temperature
8.2 Main Protection
8.2.1 Time delay for the compressor start-up
At the beginning of energizing or after the stop of the compressor, certain time delay will be needed to start the compressor. When switching over between cooling/heating/dehumidifying mode, the compressor st ops automatically.
8.2.2 Sensor protection at open circuit and breaking disconnection.
8.2.3 Phase check function
If the phase sequence is detected wrong or lack of 1 or 2 phase, the unit won’t st
art and there is error code displayed on outdoor PCB.
8.2.4 Over-current protection
When compressor is running, if the current is over twice of the rated for 3 seconds, the compressor will stop and an error code will be displayed on the outdoor PCB. If the current becomes normal for 3 minutes, the indoor sends signal to the outdoor, the outdoor will display normally.
8.2.5 Outdoor protection
When outdoor protection signal is high level, outdoor unit will perform protection: the whole machine will be shut down while the indoor unit will indicate the correspondi ng protection signal. The A/C will recover if outdoor protection signal is low level.
8.2.6 Air outlet of indoor unit high temperature protection
When the temperature of air outlet of indoor unit is up to 70°C, protection signal is high level, then the unit will perform protection: electric heaters will be shu t down at once, indoor fan speed will be high and four-way valve, compressor and outdoor fan are shut down. The A/C will recover if the temperature of air outlet of indoor unit is down to 55°C.
Page 36
33
8.3 Operation modes and functions
8.3.1 Manual operation
8.3.2 Heating mode
8.3.2.1 Four-way valve opens at once and anti-cold air function opens at the same time,
electric heaters starts or stops according to 8.3.2.4.
8.3.2.2 Condition for the compressor and outdoor fan action: MFE-60ARN1-RB4W(2T0043800036)
When compressor is on, outdoor fan will follow the below rules: Fan(below): When compressor is on, the outdoor fan runs all the time. Fan(above):
18
T4
Off
On
16
The others modes:
When compressor is on, outdoor fan will follow the below rules: When T416, the two fan run at the same time. When T418, the below fan is on, the above fan is off.
8.3.2.3 Indoor fan action Auto fan in heating mode MFE-60ARN1-RB4W(2T0043800036):
Condition
Compressor and outdoor fan
Ts-T1≥1°C
On
T1-Ts>0°C
Off
Condition
Compressor and outdoor fan(High)
Ts-T1≥1°C and compressor is off reaches up to over 4 minutes
On T1-Ts>2°C
Off
Page 37
34
-2
T1-Ts
-3
High
Low
-5
Medium
-4
The others modes:
8.3.2.4 Electric heaters (only available to some modes) Electric heaters only opens in heating mode
MFE-60ARN1-RB4W(2T0043800036)
The others modes:
8.3.2.5 Defrost (only available to heating mode)
MFE-60ARN1-RB4W(2T0043800036)
---Defrosting Conditions
Starting Of Defrosting Condition (meet one of the following is ok):
(1)Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 40 minutes, then consecutive 3 minutes less than -5 degrees (Just for the AC is turn on , whether or not the heating mode the temperature was detected, start to statistical time when reach the temperature condition . Shut down or defrosting calculate time again). (2) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 60 minutes, then consecutive 3 minutes less than -4 degrees (Just for the AC is turn on , whether or not the heating mode the temperature was detected, start to statistical time when reach the temperature condition . Shut down or defrosting
Condition
Fan speed
Ts-T1≥4°C
High
2°C Ts-T1 < 4°C
Med
Ts-T1 < 2°C
Low
Condition
Electric heaters
T4<5℃
On
T4>7℃
Off
Condition
Electric heaters
Ts-T1 > 6°C and indoor fan opens,T2 < 50 °C
On
T1≥Ts or indoor fan closes or T2 > 52 °C
Off
Page 38
35
calculate time again). (3) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C reaches to 80 minutes, then consecutive 3 minutes less than -2 degrees (Just for the AC is turn on , whether or not the heating mode the temperature was detected, start to statistical time when reach the temperature condition . Shut down or defrosting calculate time again). (4) Under evaporator high temperature protection, the accumulated time when outdoor fan motor is off and compressor is on reaches up to over 90 minutes .( Shut down or defrosting or T3 is over 15°C, calculate time again.)
--- Defrosting Action
Four-way valve, indoor fan, outdoor fan are shut down. Compressor keeps on.
--- Ending Of Defrosting Condition (meet one of the following is ok): (1)Time of defrosting lasts 10 minutes. (2) Temperature of outdoor coil T3 is up to 8°C and continues to 80 seconds. (3) Temperature of outdoor coil T3 is up to 15°C.
The others modes:
---Defrosting Conditions Starting Of Defrosting Condition: T3< 0°C and the compressor keeps running over 45 minutes. Meanwhile T3-3°C for
3minutes.
--- Defrosting Action Four-way valve, indoor fan, outdoor fan are shut down. Compressor keeps on.
Page 39
36
--- Ending of defrosting condition (meet one of the following is ok): (1)Time of defrosting lasts 10 minutes. (2) Temperature of outdoor coil T3 is up to 20°C.
8.3.2.6 High evaporator coil temp.T2 protection:
Model
TE7
TE8
TE9
MFE-60AMN1-RB4W
60
56
54
MFE-60ARN1-RB4W (2T0043800026)
60
56
54
MFE-60ARN1-RB4W (2T0043800036)
62
56
50
8.3.3 Cooling mode
8.3.3.1 Conditions for the compressor and outdoor fan action MFE-60ARN1-RB4W(2T0043800036)
When compressor is on, outdoor fan will follow the below rules: Fan(below): When compressor is on, the outdoor fan runs all the time. Fan(above):
33
T3
On
Off
30
Condition
Compressor and outdoor fan
T1-Ts>1°C
On
T1-Ts0°C
Off
Page 40
37
The others modes:
When compressor is on, outdoor fan will follow the below rules: When T333, the two fan run at the same time. When T330, the above fan is on, the below fan is off.
8.3.3.2 Action of Indoor Fan HIGH/ MED /LOW/AUTO fan can be switched over by your comfort. Auto fan under cooling mode. MFE-60ARN1-RB4W(2T0043800036)
5.0
4.0
High
Low
2.0
Medium
3.0
The others modes:
8.3.3.3 Low evaporator coil temperature T2 protection MFE-60ARN1-RB4W(2T0043800036) AC will enter T2 protection if any of the following conditions is satisfied. Condition 1:
T2CoolExit
T2
On
Off
T2CoolIn
Condition
Compressor and outdoor fan
T1-Ts≥1°C and compressor is off reac hes up to over 3 minutes
On Ts-T1>1°C
Off
Condition
Fan speed
T1-Ts≥4°C
High
2°C T1-Ts < 4°C
Med
T1-Ts < 2°C
Low
Page 41
38
When the evaporator coil temp.T2 keeps lower than T2CoolIn for 30 minutes, the compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the compressor and outdoor fan will restart up.
Condition 2:
T2CoolExit
T2
On
Off
T2CoolIn-2
When the evaporator coil temp.T2 keeps lower than T2CoolIn-2 for 20 minutes, the compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the compressor and outdoor fan will restart up.
Condition 3:
T2CoolExit
T2
On
Off
T2CoolIn-4
When the evaporator coil temp.T2 keeps lower than T2CoolIn-4 for 8 minutes, the compressor and outdoor fan will shut off. When T2 is higher than T2CoolExit, the compressor and outdoor fan will restart up.
The others modes: When T2-1 and lasts for 4 minutes, the indoor has no capacity demand and resume
till T210.
8.3.3.4 Condenser high temperature T3 protection When T3T3CoolStop_ADD for 3 seconds, the compressor will shut off. When T3 T3CoolRts_ADD,the compressor will restart.
Model
T3CoolStop_ADD
T3CoolRts_ADD
MFE-60AMN1-RB4W
65
60
MFE-60ARN1-RB4W (2T0043800026)
65
60
MFE-60ARN1-RB4W
65
48
Page 42
39
(2T0043800036)
8.3.4 Dehumidifying mode
8.3.4.1 Indoor fan speed is low.
8.3.4.2 Four-way valve is closed, the compressor and outdoor fan will operate the same as in cooling mode.
8.3.5 Auto Mode
MFE-60ARN1-RB4W (2T0043800036):
8.3.5.1. Under auto mode, the indoor fan is set to be auto.
8.3.5.2 When entering auto mode, the heating, fan only or cooling operation will be automatically chosen according to the room temperature T1 and the set temperature Ts.
Condition
Mode
T1-Ts>1°C
Cooling
-1°C T1-Ts1°C
Fan
T1-Ts<-1°C
Heating(fan for cooling only type)
Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode. If the machine switches mode between heating and cooling, the compressor will keep stopping for 15 minutes and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again.
The others models:
8.3.5.1. Under auto mode, the indoor fan is set to be auto.
8.3.5.2 When entering auto mode, the heating, fan only or cooling operation will be automatically chosen according to the room temperature T1 and the set temperature Ts.
Condition
Mode
3°C T1-Ts
Cooling
-3°C T1-Ts3°C
Fan
T1-Ts<-3°C
Heating(fan for cooling only type)
8.3.5.3. After one mode is chosen, the operation mode will be re-chosen according to the T1 and Ts.
Condition
Mode
3°C T1-Ts
Cooling
-3°C T1-Ts3°C
Former mode
T1-Ts<-3°C
Heating(fan for cooling only type)
8.3.6 Fan Only mode
MFE-60ARN1-RB4W (2T0043800036):
8.3.6.1 Temperature setting function is disabled, and no setting temperature is displayed.
8.3.6.2 Under this mode, four-way valve, compressor and outdoor fan are shut down.
8.3.6.3 High/Low/Auto fan can be switched over through manual control. Auto fan will be
Page 43
40
controlled in line with cooling auto fan with temperature set to be 24°C.
The others models:
8.3.6.1 Under this mode, four-way valve, compressor and outdoor fan are shut down,
indoor fan keeps on.
8.3.6.2 High/Med/Low/Auto fan can be switched over through manual control.
8.3.6.3 Under auto mode, the indoor fan is set to be Med.
8.4 Other functions
8.4.1 LCD display
Mode, Set temperature, fan speed, time, timer, etc.
8.4.2 Timer
The machine should be provided with max. Interval of 24h.
9. Trouble shooting
9.1 Self-diagnosis
MFE-60ARN1-RB4W (2T0043800036):
Codes
Contents
P4
Protection of temperature of indoor evaporator
P5
Protection of temperature of outdoor condenser
P7
Compressor discharge temperature protection
P9
Protection of anti-cold wind
P10
Low pressure protection
P11
High pressure protection
P12
Current overload protection
E1
Open- or short-circuit of T1 temperature sensor
E2
Open- or short-circuit of T2 temperature sensor
E3
Open- or short-circuit of T3 temperature sensor
E4
Open- or short-circuit of T4 temperature sensor
E5
Communication malfunction between indoor unit and outdoor unit
E10
Low pressure failure of compressor
E13
Lack of phase
E14
Default phase of compressor
E15
Indoor fan speed is out of control
EC
Refrigerant Leakage Detection
Page 44
41
The others models:
Codes
Contents
E01
The temp. sensor is open or short-circuit.
E02
Compressor is over current
E04
Outdoor unit protection
P02
Compressor is over load
P03
The temperature of evaporator coil of indoor unit is too low (when coo ling)
P04
The temperature of evaporator coil of indoor unit is too high (when he ating)
P05
The temperature of air outlet of indoor unit is too high (when heating)
9.2 LEDs for the indication of outdoor trouble
In normal operation, LEDs emit no light and they will flash at a frequency of 2Hz w hen trouble occurs. Their codes are listed in the following table:
MFE-60ARN1-RB4W (2T0043800036):
Type
Contents
LED2(green)
LED3(yellow)
LED4(red)
Normal
Normal running
Light
Off
Off
Normal
Normal standby
Off
Light
Off
Trouble
Phase sequence
Off
Flash
Off
Trouble
Lack of phase
Off
Off
Flash
Trouble
Protection of low pressure
Flash
Off
Flash
Trouble
Protection of high pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Flash
Light
Trouble
Communication malfunction
Off
Flash
Flash
Trouble
Open- or short-circuit of T3
temperature sensor
Off
Off
Light
Trouble
Open- or short-circuit of T4
temperature sensor
Flash
Off
Off
Trouble
Discharge temperature protection of
compressor
Light
Off
Light
Trouble
High temperature protection of condenser
Flash
Flash
Light
Trouble
Fan jump selection error
Flash
Flash
Flash
The others models:
Type
Contents
LED1
LED2
LED3
Trouble
Phase sequence or Lack of phase(A ,B)
Flash
Off
Off
Page 45
42
Trouble
Lack of phase(C)
Off
Off
Off
Trouble
Protection of low pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Off
Flash
Trouble
Communication malfunction
Flash
Off
Flash
Trouble
Open- or short-circuit of T3 temperature sensor
Off
Flash
Flash
Trouble
Open- or short-circuit of T4 or T5 temperature sensor or
protection of high pressure
Off
Flash
Off
Trouble
High temperature protection of condenser
Flash
Flash
Flash
Note: When the machine stands by, LED1- LED3 flashes in low speed.
9.3 Troubles and solutions
Before calling for service, please review the following list of common problems and solutions.
Problem
Possible Cause
Solutions
Unit Idleness
No electric power supply
Wait for power recovery
Power Switch turned off
Turn on the switch
Fuse blew
Replace the fuse
Air flow but poo r cooling (heatin g)
Improper temperature setting
Readjust the temp. to a lo
wer degree. See ‘OPERAT
IONS’ for details
The air -filter blocked
Clean the air- filter
Air inlet/outlet blocked
Clear the air inlet/outlet
Windows/door are open
Close windows/door
Air flow but no cooling (heating) The air inlet/outlet of indoor/outdoor unit are blocked up by something
Remove the obstacles whi ch blocks the air inlet/outl et
Too much dust or dirt on the air­filter
Clean the air-filter
Page 46
43
9.3.1 Open or short circuit of temperature sensor
Open or short circuit of
temperature sensor
Check the connections
between temperature sensor and PCB. Are
the connections good?
Correct the connections.No
Yes
Yes Replace indoor or outdoor PCB.
Replace the sensor
Check the resistance value
of the sensor via Appendix 1
Is it normal?
No
9.3.2 Default phase of compressor
Page 47
44
9.3.3 Phase sequence error
9.3.4 High temperature protection of condenser
High temperature protection of condenser
Check the resistance of the temp. sensor
according to Appendix 1, is it normal?
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
6. Outdoor PCB is defective
Replace the sensor
No
Yes
Phase sequence error
Change the order of the wires to power supply.
Switch on the unit again.
If the problem cannot be solved, the outdoor PCB is defective
Page 48
45
9.3.5 High pressure protection
9.3.6 Low temperature protection
9.3.7 Low pressure protection
Low temperature protection
Possible reason 1: The outdoor ambient temp. is low. 2: The wires are loose to the temp. sensor. 3: The temp. sensor is defective. 4: The evaporator or the filter is dirty. 5: System has block.
Low pressure protection
Possible reason 1: The wires are loose to the pressure switch. 2: The pressure switch is defective. 3: System has refrigerant leakage. 4: The evaporator or the filter is dirty. 5: System has block.
Page 49
46
9.3.8 Overload of current
Page 50
47
9.3.9 Indoor / outdoor unit communication error
Page 51
48
Yes
Yes
Measure Vs, is it moving alternately between positive value and negative value? (Vs is the voltage between S and N of outdoor unit.)
Yes
Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes?
No
Yes
Change the outdoor main PCB.
Power on. Is the error extinguished?
Check all the wirings between indoor and outdoor, indoor PCB and outdoor PCB following the wiring diagram. Are all the wirings connected correctly?
Change the indoor main PCB.
Yes
Change the outdoor main PCB.
No
Is the wiring to the outdoor PCB connected correctly?
Power on. Is the error extinguished?
Change the indoor main PCB.
No
Is the wiring to the indoor PCB connected correctly?
Page 52
49
9.3.10 Refrigerant Leakage Detection
Is there cool air blowing out from indoor air outlet?
Yes
Yes
Check if T2 sensor is well
fixed. Correct the installation
or replace T2 sensor. Does the problem remain again?
No
Is there any leakage? Especially the connection parts, such as the gas valve and the liquid valve.
No
Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code?
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
Clear the blocking.
Yes
Is there any block i n g ? (Such as the capillary or the welded points of the pipes.)
Page 53
50
9.3.11 Indoor fan speed has been out of control
Shut off the power supply
and turn it on 5 seconds
later. Is it still displaying
the error code?
Shut off the power supply, rotate the fan by hand. Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.No
Yes
Yes
Check whether the fan
motor is normal through
index 1?
Replace the fan
motor
No
If the
malfunction is
still existing,
replace the
main PCB
Page 54
51
Index 1:
1 DC Fan Motor(control chip is in PCB)
NO. 1 2 3 4
5
Color
Orange
Grey
White
Pink
Black
Signal
Hu
Hv
Hw
Vcc
GND
Color
Red
Blue
Yellow
Signal
W V U
1) Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the
resistance is not equal to each other, the fan motor must has problems and need to be replaced. Otherwise, go to step 2.
2) Power on and when the unit is in standby, measure the voltage of pin4-5 in feedback
signal connector. If the value is not 5V, change the PCB. Otherwise, go to step 3.
3) Rotate the fan by hand, measure the voltage of pin1-5, pin 2-5 and pin 3-5 in feedback
signal connector. If any voltage is not positive voltage fluctuation, the fan motor must has problems and need to be replaced.
Page 55
52
9.3.12 Temperature protection of compressor discharge
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp.
is more than 115°C ?
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Method: Check whether the
resistance of compressor
discharge temp. sensor is
right refer to the Appendix 2
No
Yes
Yes
Trouble is solved
No
Judge: The discharge temp. sensor is broken
Check whether the
refrigerant is leak
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace outdoor main board
Yes
Page 56
53
Appendix Temp. Sensor Resistance Value Table (℃--K)
K Ohm
K Ohm
K Ohm
K Ohm
-20
115.266
20
12.6431
60
2.35774
100
0.62973
-19
108.146
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
-15
84.2190
25
10.000
65
1.96532
105
0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10
62.2756
30
7.97078
70
1.64691
110
0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5
46.5725
35
6.40021
75
1.38703
115
0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
0
35.2024
40
5.17519
80
1.17393
120
0.35982
1
33.3269
41
4.96392
81
1.13604
121
0.35042
2
31.5635
42
4.76253
82
1.09958
122
0.3413
3
29.9058
43
4.57050
83
1.06448
123
0.33246
4
28.3459
44
4.38736
84
1.03069
124
0.32390
5
26.8778
45
4.21263
85
0.99815
125
0.31559
6
25.4954
46
4.04589
86
0.96681
126
0.30754
7
24.1932
47
3.88673
87
0.93662
127
0.29974
8
22.5662
48
3.73476
88
0.90753
128
0.29216
9
21.8094
49
3.58962
89
0.87950
129
0.28482
10
20.7184
50
3.45097
90
0.85248
130
0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15
16.1156
55
2.84421
95
0.73119
135
0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
Page 57
54
Appendix 2
Unit: ---K Discharge temp. sensor table
-20
542.7
20
68.66
60
13.59
100
3.702
-19
511.9
21
65.62
61
13.11
101
3.595
-18
483
22
62.73
62
12.65
102
3.492
-17
455.9
23
59.98
63
12.21
103
3.392
-16
430.5
24
57.37
64
11.79
104
3.296
-15
406.7
25
54.89
65
11.38
105
3.203
-14
384.3
26
52.53
66
10.99
106
3.113
-13
363.3
27
50.28
67
10.61
107
3.025
-12
343.6
28
48.14
68
10.25
108
2.941
-11
325.1
29
46.11
69
9.902
109
2.86
-10
307.7
30
44.17
70
9.569
110
2.781
-9
291.3
31
42.33
71
9.248
111
2.704
-8
275.9
32
40.57
72
8.94
112
2.63
-7
261.4
33
38.89
73
8.643
113
2.559
-6
247.8
34
37.3
74
8.358
114
2.489
-5
234.9
35
35.78
75
8.084
115
2.422
-4
222.8
36
34.32
76
7.82
116
2.357
-3
211.4
37
32.94
77
7.566
117
2.294
-2
200.7
38
31.62
78
7.321
118
2.233
-1
190.5
39
30.36
79
7.086
119
2.174
0
180.9
40
29.15
80
6.859
120
2.117
1
171.9
41
28
81
6.641
121
2.061
2
163.3
42
26.9
82
6.43
122
2.007
3
155.2
43
25.86
83
6.228
123
1.955
4
147.6
44
24.85
84
6.033
124
1.905
5
140.4
45
23.89
85
5.844
125
1.856
6
133.5
46
22.89
86
5.663
126
1.808
7
127.1
47
22.1
87
5.488
127
1.762 8 121
48
21.26
88
5.32
128
1.717
9
115.2
49
20.46
89
5.157
129
1.674
10
109.8
50
19.69
90 5 130
1.632
11
104.6
51
18.96
91
4.849
12
99.69
52
18.26
92
4.703
13
95.05
53
17.58
93
4.562
14
90.66
54
16.94
94
4.426
15
86.49
55
16.32
95
4.294
B(25/50)=3950K
16
82.54
56
15.73
96
4.167
17
78.79
57
15.16
97
4.045
R(90)=5KΩ±3%
18
75.24
58
14.62
98
3.927
19
71.86
59
14.09
99
3.812
Loading...