Midea MCA-24HRN2, MCA-24CRN2, MCA-36HRN2, MCA-36CRN2, MCA-42HRN2 Installation Manual

...
CASSETTE TYPE
Thank you very much for purchasing our air conditioner, please read this owner's manual carefully before using your air conditioner.
INSTALLATION MANUAL
AIR CONDITIONER
MODEL:
CONTENTS PAGE
1. PRECAUTIONS................................................................................................1
2. INSTALLATION INFORMATION.. ...2
3. ATTACHED FITTINGS.... ....3
4. INSTALLATION PLACE.. ...4
5. INDOOR UNIT INSTALLATION.. ....5
6. OUTDOOR UNIT INSTALLATION.. .9
7. INSTALL THE CONNECTING PIPE.. .10
8. CONNECT THE DRAIN PIPE. .....14
9. WIRING.... .16
10. TEST OPERATION..... ....20
.................................................................
.............................................................................
..............................................................................
.................................................................
................................................................
............................................................
..................................................................
.....................................................................................................
.............................................................................
PRECAUTIONS
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electric components. Only trained and qualified service personnel should install, repair or service air conditioning equipment. All other operations should be performed by trained service personnel. When working on air conditio­ning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply. Follow all safety codes. Wear glasses and work gloves. Use quen­ching cloth for brazing and unbrazing operations. There are fire extinguishers available for all brazing operations.
WARNING
WARNING
WARNING
This manual describes the installation of specified indoor and outdoor units. Do not install them conn­ected with any other indoor or outdoor unit .Mismatching of units and incompatibility between control devices in the two units could lead to damage of both units .
Before performing service or maintenance operations on system, turn off main power switch of the unit. Electrical shock could cause personal injury. This unit shall be installed in accordance with national wiring regulations.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or similarly qualified person in order to avoid a hazard. The means for disconnection from the supply having a contact separation of at least 3 mm in all poles.
CAUTION
1. Wire the outdoor unit, then wire the indoor unit. You are not allow to connect the air conditioner with the power source until wiring and piping the air conditioner is done.
2. For installation of the indoor unit, outdoor unit, and connection piping in between, follow the instru­ ctions given in this manual as strictly as possible.
3. Installation in the following places may cause trouble. If it is unavoidable using in such places, please consult with the dealer. (1) A place full of machine oil. (2) A saline place such as coast. (3) Hot-spring resort. (4) A place full of sulfide gas. (5) A place where there are high frequency machines such as wireless installation, welding machine, medical facilities. (6) A place of special environmental conditions.
4. Don't install this unit in the laundry.
1
Remark per EMC Directive 89/336/EEC For to prevent flicker impressions during the start of the compressor (technical process) ,following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance please refer to your contract with the power supplier, if restric­ tions do apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner refer to the rating plate of the product.
5. For any question contact your local dealer.
NOTE
INSTALLATION INFORMATION
2
1. Select the location;
2. Install the indoor unit;
3. Install the outdoor unit;
4. Install the connecting pipe ;
5. Connect the drain pipe;
6. Wiring;
7. Test operation.
To install properly, please read this "installation manual" at first. The air conditioner must be installed by qualified persons. When installing the indoor unit or its tubing, please follow this manual as strictly as possible. When all the installation work is finished, please turn on the power only after a thorough check. Regret for no further announcement if there is any change of this manual caused by product improvement.
CAUTIONS FOR THE REMOTE CONTROLLER OPERATION
Please do not throw the remote controller or beat it. Please use the remote controller within the allowed distance, and keep the transmitter toward the receiver of the indoor unit. Please keep the remote controller more than 1m away from TV or stereo set. Never put the remote controller at the place with humid or direct sunlight, or near heaters. Please insert the batteries properly.
INSTALLATION ORDER
Please check whether the following fittings are of full scope. If there are some attached fittings free from use, please restore them carefully.
Installation Fittings
Tubing & Fittings
1. Expansible hook..........................................4
2. Installation hook..........................................4
3. Installation paper board...............................1
4. Bolt M5 16 or M6 12.............................4
ATTACHED FITTINGS
5. Connecting pipe group...............................1
7. Soundproof / insulation sheath...................2
6. Binding tape................................................6
8. Out-let pipe sheath.......................................1
9. Out-let pipe clasp.........................................1
10. Tightening band.......................................20
11. Drain elbow.................................................1
12. Seal ring.....................................................1
13. Wall conduit..............................................1
14. Wall conduit cover....................................1
Power/Signal Wiring Group
15. Power wiring of the indoor unit.................1
16. Weak electrical wiring between
the indoor and outdoor units....................1
Drainpipe Fittings Protect Pipe Fittings
Remote controller & Its Frame
Others
21. Owner's manual.......................................1
22. Installation manual...................................1
17. Remote controller......................................1
18. Frame........................................................1
19. Mounting screw(ST2.9 10-C-H) .............2
20. Alkaline dry batteries (AM4)......................2
3
Liquid-side tubing
MCA-42(36,48)CRN2 MCA-42(36,48)HRN2
gas-side tubing
f9.53mm f12.7mm
f16mm f19mm
MCA-24CRN2 MCA-24HRN2
INSTALLATION PLACE
4
There is enough room for installation and maintenance. The air outlet and the air inlet are not impeded, and can not be reached by strong wind. It must be a dry and well ventilating place. The support is flat and horizontal and can stand the weight of the outdoor unit. And will no additional noise or vibration. Your neighborhood will not feel uncomfortable with the noise or expelled air. There is no leakage of combustible air. It is easy to install the connecting pipe or cables. Determine the air outlet direction where the discharged air is not blocked. A place free of a leakage of combustible gases. In the case that the installation place is exposed to a strong wind such as a seaside or high position, secure the normal fan operation by putting the unit lengthwise along the wall or using a duct or shield plates. If possible, do not install the unit where it is exposed to direct sunlight. If necessary, install a blind that does not interfere with the air flow. During the heating mode, the water drained off the outdoor unit ,The condensate should be well dr­ained away by the drain hole to an appropriate place, so as not to interfere other people or public. Select the position where it will not be subject to snow drifts, accumulation of leaves or other seasonal debris. It is important that the air flow for the outdoor unit is not impeded as this will result in reduction in heating or cooling performance.
CAUTIONS
Location in the following places may cause malfunction of the machine.(If unavoidable, please consult your local dealer) a. There is petrolatum existing. b. There is salty air surrounding (near the coast). c. There is caustic gas (the sulfide, for example) existing in the air (near a hot spring). d. The Volt vibrates violently (in the factories). e. In buses or cabinets. f. In kitchen where it is full of oil gas. g. There is strong electromagnetic wave existing. h. There are inflammable materials or gas. i. There is acid or alkaline liquid evaporating. j. Other special conditions.
NOTICES BEFORE INSTALLATION
1. Select the correct carry-in path.
2. Move this unit as originally packaged as possible.
3. If the air conditioner is installed on a metal part of the building, it must be electrically insulated acc­ ording to the relevant standards to electrical appliances.
1. The indoor unit
There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The air outlet and the air inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heaters.
2. The outdoor unit
INDOOR UNIT INSTALLATION
5
>1000mm
>1000mm
>1000mm
>1000mm
Chart 2
A
Drain side
Tubing side
(Unit: mm)
680(Hook-location)
780(Hook-location)
840(Body)
840(Body)
880(Ceiling hole)
880(Ceiling hole)
950(Panel)
950(Panel)
1. Install the main body A. The existing ceiling (to be horizontal)
a. Please cut a quadrangular hole of 880 880mm in the ceiling according to the shape of the installation paper board. (Refer to Chart3, 4) The center of the hole should be at the same position of that of the air conditioner body. Determine the lengths and outlets of the connecting pipe, drainpipe and cables. To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary. b. Please select the position of installation hooks according to the hook holes on the installation board.
Drill four holes of f12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings). Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the installation hooks from the height of ceiling, then cut off the unnecessary part. If the ceiling is extremely high, please determine the length of the installation hook according to facts.
Necessary room
>2500mm
outlet intlet outlet
ground
A
Chart 1
Note:
MCA-24CRN2 MCA-24HRN2
MCA-42(36,48)CRN2
MCA-42(36,48)HRN2
Chart 3
A 330mm
Series A 260mm
Series