Midea MSMBBU-12HRFN1-QRD0GW, MOB01-18HFN1-QRD0GW, MOB01-12HFN1-QRD0GW, MSMBCU-18HRFN1-QRD0GW, MSMBDU-24HRFN1-QRD0GW Service Manual

...
Page 1
Mission 3D Inverter Series
Service Manual 2014
MBSEU-A-1412
Page 2
CONTENTS
1. Precaution .................................................................................................................................................... 3
1.1 Safety Precaution .......................................................................................................................... 3
1.2 Warning ......................................................................................................................................... 3
2. Function ........................................................................................................................................................ 6
3. Dimension .................................................................................................................................................... 7
3.1 Indoor Unit ..................................................................................................................................... 7
3.2 Outdoor Unit ................................................................................................................................ 10
4. Refrigerant Cycle Diagram ....................................................................................................................... 13
5 Installation Details ...................................................................................................................................... 14
5.1 Wrench torque sheet for installation ........................................................................................... 14
5.2 Connecting the cables ................................................................................................................ 14
5.3 Pipe length and the elevation ..................................................................................................... 15
5.4 Installation for the first time ......................................................................................................... 16
5.5 Adding the refrigerant after running the system for many years ................................................ 17
5.6 Re-installation while the indoor unit need to be repaired ........................................................... 18
5.7 Re-installation while the outdoor unit need to be repaired ......................................................... 19
6. Operation Characteristics ......................................................................................................................... 21
7. Electronic function .................................................................................................................................... 22
7.1 Abbreviation ................................................................................................................................ 22
7.2 Display function ........................................................................................................................... 22
7.3 Main Protection ........................................................................................................................... 23
7.4 Operation Modes and Functions ................................................................................................. 24
8. Troubleshooting ......................................................................................................................................... 28
8.1 Indoor Unit Error Display ............................................................................................................. 29
8.2 Trouble shooting.......................................................................................................................... 30
Page 3
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other
people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring
instruction will cause harm or damage.
Before service the unit, be sure to
read this service manual at first.
1.2 Warning
Installation
Do not use a defective or underrated
circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer,
seller, a qualified electrician, or an authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of
control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and
breaker.
Improper wiring or installation may cause fore or electric shock.
Use the correctly rated breaker of
fuse.
There is risk of fire or electric shock.
Do not modify or extend the power
cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the
unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and
installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the
dealer or an authorized service center.
Do not install the product on a
defective installation stand.
Be sure the installation area does not
deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a
long time when the humidity is very high and a door or a window is left open.
Take care to ensure that power cable
could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power
cable.
There is risk of fire or electric shock.
Do not plug or unplug the power
supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product
with wet hands.
Do not place a heater or other
appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into
electrical parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or
combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly
closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off
the gas and open a window for ventilation before turn the product on.
If strange sounds or smoke comes
from product, turn the breaker off or disconnect the power supply cable.
Page 4
There is risk of electric shock or fire.
Stop operation and close the window
in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the
product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked, contact
an authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter
the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to
time when operating it together with a stove etc.
There is risk of fire or electric shock.
Turn the main power off when
cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a
long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody
could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION
Always check for gas (refrigerant)
leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that
water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the
product.
It can avoid vibration of water leakage.
Do not install the product where the
noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and
transport the product.
Do not install the product where it will
be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operational
Do not expose the skin directly to
cool air for long time. (Do not sit in the draft).
Do not use the product for special
purposes, such as preserving foods, works of art etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air
flow.
Use a soft cloth to clean. Do not use
harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the
product when removing the air filter. They are very sharp.
Do not step on or put anything on the
product. (outdoor units)
Always insert the filter securely.
Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects
through air inlet or outlet while the product is operated.
Do not drink the water drained from
the product.
Page 5
Use a firm stool or ladder when
cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote
control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the
batteries. Do not dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets
onto your skin or clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
Page 6
2. Function
Model Names of Indoor/Outdoor Units
3D inverter
Capacity
Indoor units
Outdoor units
9k
MSMBAU-09HRFN1-QRD0GW
MOB01-09HFN1-QRD0GW
12k
MSMBBU-12HRFN1-QRD0GW
MOB01-12HFN1-QRD0GW
18k
MSMBCU-18HRFN1-QRD0GW
MOB01-18HFN1-QRD0GW
24k
MSMBDU-24HRFN1-QRD0GW
MOF2-24HFN1-QRD0GW
Page 7
3. Dimension
3.1 Indoor Unit
Model
W D H
MSMBAU-09HRFN1-QRD0GW
730
198
293
MSMBBU-12HRFN1-QRD0GW
810
200
300
MSMBCU-18HRFN1-QRD0GW
980
225
325
MSMBDU-24HRFN1-QRD0GW
1090
235
338
Page 8
For MSMBAU-09HRFN1-QRD0GW:
For MSMBBU-12HRFN1-QRD0GW:
For MSMBCU-18HRFN1-QRD0GW:
For MSMBDU-24HRFN1-QRD0GW:
Page 9
Page 10
3.2 Outdoor Unit
More than 30cm
More than 60cm
More than 200cm
More than 30cm
More than 60cm (Service space)
Fence or
obstacles
Page 11
For MOB01-09HFN1-QRD0GW, MOB01-12HFN1-QRD0GW, MOB01-18HFN1-QRD0GW,
Page 12
For MOF2-24HFN1-QRD0GW,
Model
W D H
W1 A B
MOF2-24HFN1-QRD0GW
845
320
700
908
560
335
Page 13
4. Refrigerant Cycle Diagram
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
ACCUMULATOR
INDOOR OUTDOOR
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
Page 14
5 Installation Details
5.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
5.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
Page 15
5.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MSMBAU-09HRFN1-QRD0GW + MOB01-09HFN1-QRD0GW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSMBBU-12HRFN1-QRD0GW + MOB01-12HFN1-QRD0GW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSMBCU-18HRFN1-QRD0GW + MOB01-18HFN1-QRD0GW
1/2’’
12.7)
1/4’’
(Ф6.35)
5
20
30
15
MSMBDU-24HRFN1-QRD0GW + MOF2-24HFN1-QRD0GW
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5
25
50
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the system reliability.
Page 16
5.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi
connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates
-0.1Mpa. If the meter does not indicate
-0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves
are set to the closed position.
2). Connect the charge set and a charging
cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the
Page 17
charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage. Check the flare connections for gas leakage.
5). Discharge the refrigerant. Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m. Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose. Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4) Operate the air conditioner at the cooling
mode.
5) Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper
weight (refer to the table), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service
port Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
5.5 Adding the refrigerant after running
the system for many years
Procedure:
1). Connect the charge hose to the 3-way service
port, open the 2-way valve and the 3-way valve. Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
Page 18
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
5.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose. Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle
and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position
immediately Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa. Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m. Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves
are set to the closed position.
2). Connect the charge set and a charging
cylinder to the service port of the 3-way valve Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging
cylinder, and set the 2-way and 3-way valves to the open position
Page 19
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m. Be sure to check the gas leakage.
5.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates
-0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way valve Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper
weight, disconnect the charge hose from the 3-way valve’s service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service
port Use torque wrench to tighten the service port cap to a torque of 18N.m.
Page 20
Be sure to check for gas leakage
Page 21
6. Operation Characteristics
Mode
Temperature
Cooling operation
Heating operation
Drying operation Room temperature
17℃~32℃ (62~90)
0~30 (32~86)
10℃~32℃ (50~90)
Outdoor temperature
0~50 (32~122)
-20~30 (-4℉~86℉)
0~50 (32~122)
-15~50(5~122) (For the models with low temperature cooling system)
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features
may come into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
Page 22
7. Electronic function
7.1 Abbreviation
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature
7.2 Display function
7.2.1 Icon explanation on indoor display board.
Digital display: Displays the temperature settings when the air conditioner is operational. Displays the room temperature in FAN mode. Displays the self-diagnostic codes.
Dispalys for three seconds when Timer ON, Fresh, Swing, Turbo or Silence feature is activated.
Dispalys for three seconds when Timer OFF is set.
Dispalys for three seconds when Fresh,
Swing, Turbo or Silence feature is cancelled.
Dispalys under deforsting operation.
Dispalys when anti-cold air feature is activated under heating mode.
Dispalys during self clean operation (if aplicable).
Dispalys under 8 heating operation (if aplicable).
When ECO function(optional) is actived,the
illuminates gradually one by one as
In one second interval.
WIFI control display(optional) Displays when the WIFI control feature is acticated.(Not available when the unit does not have this function)
NOTE: A guide on using the infrared remotr is included in this literature package.
Page 23
7.3 Main Protection
7.3.1 Three minutes delay at restart for compressor
Less than 1 minute delay for the 1st time stand-up and 3 minutes delay for others.
7.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the compressor top temp. protector restart.
7.3.3 Temperature protection of compressor discharge
Compressor discharge temp. T5>115for 5s, compressor stops.
7.3.4 Fan speed is out of control
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure
7.3.5 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections happen, the corresponding code will display on indoor unit and the unit will stop working.
7.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 7s later. If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
7.3.7 Compressor preheating functions
Preheating permitting condition: When T4(outdoor ambient temperature)3°C , the preheating function will be activated.
7.3.8 Sensor protection at open circuit and breaking disconnection.
When there’s only one temperature sensor in malfunction , the air conditioner will keep working but show the error code, in case of any emergency use. When there’s more than one temperature sensor in malfunction, the air conditioner will stop working
7.3.9 Refrigerant leakage detection
This function is only active in cooling mode. It can better prevent the compressor being damaged by refrigerant leakage or compressor overload. Open condition: When compressor is active, the value of the Coil temperature of evaporator T2 has no change or very little change.
Page 24
7.4 Operation Modes and Functions
7.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan:
a
b
c
d
T1
e
7.4.2 Cooling Mode
7.4.2.1 Compressor running rules
When T1-Ts<-2, the compressor will stop, when T1TS>-0.5℃,the compressor will be activated. When the AC run in mute mode, the compressor will run with low frequency. When the current is more than setting value, the current protection function will be activated, and the compressor will stop.
7.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
T4
A+
A
B
C
D
E
7.4.2.3Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. When the setting temp. is reached,if the compressor stop running,indoor fan motor will run in Minimum speed or setting speed. The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H+(H+=H+G) A H(=H) B C
M+(M+=M+Z) D M(M=M) E F
L+(L+=L+D) G L(L=L) H I
T1-Td (°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
a
b
c
d
T1
e
7.4.2.4 Condenser temperature protection
Page 25
Resume
Off
Decrease
Hold
When condenser temperature temp. is more than setting value, the compressor will stop.
7.4.2.5 Evaporator temperature protection
When Evaporator temperature temp.is less than setting value, the compressor will stop.
7.4.3 Heating Mode
7.4.3.1 Compressor running rules
When T1-Ts><-ΔT, the compressor will stop, when T1—TS<ΔT-1.5 时,the compressor will be on.
ΔT is the programmed parameter of
temperature compensation. When the AC run in mute mode,the compressor will run with low frequency. When the current is more than setting value,the current protection function will be activated and the compressor will stop.
7.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
T4
E
D
C
B
A
A+
7.4.3.3 Indoor fan running rules When the compressor is on, the indoor fan can
be set to high/med/low/auto/mute. When indoor unit coil temp. is low,the anti-cold air function will start and indoor fan motor will run at low speed,the speed cant be changed ,when the temp. is lower than setting value,the indoor fan motor will stop. When the indoor temp reaches the setting temp.,the compressor will stop,the indoor fan motor will run at the minimum speed or setting speed.(The anti-cold air function is valid). The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H=H
H+(H+=H+G)
M(M=M)
M+(M+=M+Z)
L(L=L)
L+(L+=L+D)
H-(H-=H-G)
M-(M-=M-Z)
L-(L-=L-D)
T1-Td
L
H
M
Auto fan action in heating mode:
Page 26
T1-Td+ΔT
7.4.3.4Defrosting mode
AC will enter the defrosting mode according to the value of temp. of T3 and the value range of temp. change of T3 and also the compressor running time. During the defrosting mode, the compressor keep running, indoor and outdoor motor will stop, defrost lamp of the indoor unit will be lighted
. Will be displayed.
7.4.3.5 Evaporator coil temperature protection
Resume
Off
Decrease
Hold
When evaporator temperature temp. is more than the setting protection value, the compressor will stop.
7.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between 17°C ~30°C In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
T1-Ts
Cooling
Heating*
Fan only
Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode. If the machine switches mode between heating and cooling, the compressor will keep stopping for certain time and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again.
7.4.5 Drying mode
Indoor fan speed is fixed at breeze and can’t be
changed. The louver angle is the same as in cooling mode. All protections are active and the same as that in cooling mode.
7.4.6 Forced operation function
Forced cooling mode: The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for 30 minutes, AC will turn to auto mode with 24 setting temperature. Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24 setting temperature. When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting, fan speed setting, sleeping mode setting, follow me setting, it will quit the forced operation.
Page 27
7.4.7 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including swing function) automatically after 3 minutes when power returns. If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes and turn to auto mode as 24 setting temp. If AC is off before power off and AC is required to start up now, the compressor will have 1 minute delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
7.4.8 8 Heating(optional)
When the compressor is running, the indoor fan motor will run without anti-cold air function. When the compressor is off, the indoor fan motor is off .
Page 28
8. Troubleshooting
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, ­terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
Page 29
8.1 Indoor Unit Error Display
Operation
lamp
Timer lamp
Display
LED STATUS
1 time
X
E0
Indoor unit EEPROM parameter error
2 times
X
E1
Indoor / outdoor units communication error
4 times
X
E3
Indoor fan speed has been out of control
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short circuit
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
7 times
X
EC
Refrigerant leakage detection
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or short circuit
4 times
O
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
5 times
O
F4
Outdoor unit EEPROM parameter error
6 times
O
F5
Outdoor fan speed has been out of control
1 times
P0
IPM malfunction or IGBT over-strong current protection
2 times
P1
Over voltage or over low voltage protection
3 times
P2
High temperature protection of compressor top diagnosis and solution
5 times
P4
Inverter compressor drive error
Olight Xoff ☆(flash
Page 30
8.2 Trouble shooting
8.2.1 EEPROM parameter error diagnosis and solution(E0/F4)
Error Code
E0/F4
Malfunction decision conditions
Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Supposed causes
Installation mistake
PCB faulty
Trouble shooting:
Yes
Replace the indoor/outdoor
main PCB.
Power off, then restart the
unit 2 minutes later.
EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos.
Note: The two photos above are only for reference, its may be not same totally with the ones on your side.
Indoor PCB
Outdoor PCB
Page 31
8.2.2 Indoor / outdoor unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision conditions
Indoor unit does not receive the feedback from outdoor unit during
110 seconds and this condition happens four times continuously.
Supposed causes
Wiring mistake
Indoor or outdoor PCB faulty
Trouble shooting:
Measure Vs, is it positive fluctuation? (Vs is the voltage between S and N of outdoor unit. Red pan-S, Black pan-N)
Measure Vs, is it positive fluctuation? (Vs is the voltage between S and N of outdoor unit. Red pan-S, Black pan-N)
Yes
Power off, then restart the unit 2 minutes later
Power off, then restart the unit 2 minutes later
No
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Check the outdoor wiring connection
Check the outdoor wiring connection
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Yes
Replace the outdoor main PCB.
Replace the outdoor main PCB.
No
Replace the indoor main PCB.
Replace the indoor main PCB.
No
Check the indoor wiring connection
Check the indoor wiring connection
Yes
Yes
Check whether reactor is normal?
Check whether reactor is normal?
Yes
Replace the reactor
Replace the reactor
No
Page 32
8.2.4 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3/F5
Malfunction decision conditions
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.
Supposed causes
Wiring mistake
Fan ass’y faulty
Fan motor faulty
PCB faulty
Trouble shooting:
Power off, then restart the
unit 2 minutes later
Shut off the power supply, Rotate the fan by hand.
The unit operates normally.
Find out the cause and have
it solved
Check the wiring of fan
motor
No
Yes
No
Correct the connections.
No
NoReplace the fan motor
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB
Yes
Replace the main PCBNo
Page 33
Index1: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
280V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
14-17.5V
5
Yellow
Vsp
0~5.6V
6
Blue
FG
14-17.5V
2. Outdoor DC Fan Motor (control chip is in outdoor PCB) Power on ,and check if the fan can run normally, if the fan can run normally, the PCB must has problems and need to be replaced, If the fan cant run normally, measure the resistance of each two pins. If the resistance is not equal to each other, the fan motor must have problems and need to be replaced, otherwise the PCB must has problems and need to be replaced.
3. Indoor AC Fan Motor Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V power supply), the PCB must has problems and need to be replaced.
Page 34
8.2.4 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code
EC
Malfunction decision conditions
Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 Tcool2 does not keep continuous 4 seconds and this
situation happens 3 times, the display area will show “EC” and
AC will turn off.
Supposed causes
T2 sensor faulty
Indoor PCB faulty
System problems, such as leakage or blocking.
Trouble shooting:
Check cool air blowing out from indoor air outlet
Yes
Yes
Check if T2 sensor
No
Check leakage of system
No
Power off, then restart the
unit 2 minutes later.
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
check blockIng of system and
clear the blocking
Page 35
8.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5)
Error Code
E4/E5/F1/F2/F3
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Supposed causes
Wiring mistake
Sensor faulty
Trouble shooting:
Check the connection between temperature
sensor and PCB.
Correct the connectionNo
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Repalce the sensorNo
Yes
Page 36
8.2.6 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code
P0
Malfunction decision conditions
When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes
Wiring mistake
IPM malfunction
Outdoor fan ass’y faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of Fan
Speed Has Been Out Of Control
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
(Several MΩ)
(+)Red
(-)Black
(Several MΩ)
P
N
U N U V V
W
W
(+)Red
Page 37
8.2.7 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code
P1
Malfunction decision conditions
An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the power supply
Check the connections and wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Check the voltage between P
and N
Check the reactor
Yes
No
Replace outdoor main PCB
Page 38
8.2.8 High temperature protection of compressor top diagnosis and solution(P2)
Error Code
P2
Malfunction decision conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the air flow system
of indoor and outdoor units
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Power off, then restart the unit 10
minutes later
Check if the temperature
of compressor
No
Check refrigerant system
Yes
Check the overload
protector
Correct the connection.No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
Page 39
8.2.9 Inverter compressor drive error diagnosis and solution(P4)
Error Code
P4
Malfunction decision conditions
An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
Supposed causes
Wiring mistake
IPM malfunction
Outdoor fan ass’y faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of Fan
Speed Has Been Out Of Control
malfunction
Yes
Check the compressor resistance
values
No Replace the compressor.
Yes
Replace the outdoor main PCB
Page 40
Main parts check
1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor. Measure the resistance value of each winding by using the multi-meter.
Page 41
Appendix 1 Temperature Sensor Resistance Value Table (℃--K)
K Ohm
K Ohm
K Ohm
K Ohm
-20
115.266
20
12.6431
60
2.35774
100
0.62973
-19
108.146
21
12.0561
61
2.27249
101
0.61148
-18
101.517
22
11.5000
62
2.19073
102
0.59386
-17
96.3423
23
10.9731
63
2.11241
103
0.57683
-16
89.5865
24
10.4736
64
2.03732
104
0.56038
-15
84.2190
25
10.000
65
1.96532
105
0.54448
-14
79.3110
26
9.55074
66
1.89627
106
0.52912
-13
74.5360
27
9.12445
67
1.83003
107
0.51426
-12
70.1698
28
8.71983
68
1.76647
108
0.49989
-11
66.0898
29
8.33566
69
1.70547
109
0.48600
-10
62.2756
30
7.97078
70
1.64691
110
0.47256
-9
58.7079
31
7.62411
71
1.59068
111
0.45957
-8
56.3694
32
7.29464
72
1.53668
112
0.44699
-7
52.2438
33
6.98142
73
1.48481
113
0.43482
-6
49.3161
34
6.68355
74
1.43498
114
0.42304
-5
46.5725
35
6.40021
75
1.38703
115
0.41164
-4
44.0000
36
6.13059
76
1.34105
116
0.40060
-3
41.5878
37
5.87359
77
1.29078
117
0.38991
-2
39.8239
38
5.62961
78
1.25423
118
0.37956
-1
37.1988
39
5.39689
79
1.21330
119
0.36954
0
35.2024
40
5.17519
80
1.17393
120
0.35982
1
33.3269
41
4.96392
81
1.13604
121
0.35042
2
31.5635
42
4.76253
82
1.09958
122
0.3413
3
29.9058
43
4.57050
83
1.06448
123
0.33246
4
28.3459
44
4.38736
84
1.03069
124
0.32390
5
26.8778
45
4.21263
85
0.99815
125
0.31559
6
25.4954
46
4.04589
86
0.96681
126
0.30754
7
24.1932
47
3.88673
87
0.93662
127
0.29974
8
22.5662
48
3.73476
88
0.90753
128
0.29216
9
21.8094
49
3.58962
89
0.87950
129
0.28482
10
20.7184
50
3.45097
90
0.85248
130
0.27770
11
19.6891
51
3.31847
91
0.82643
131
0.27078
12
18.7177
52
3.19183
92
0.80132
132
0.26408
13
17.8005
53
3.07075
93
0.77709
133
0.25757
14
16.9341
54
2.95896
94
0.75373
134
0.25125
15
16.1156
55
2.84421
95
0.73119
135
0.24512
16
15.3418
56
2.73823
96
0.70944
136
0.23916
17
14.6181
57
2.63682
97
0.68844
137
0.23338
18
13.9180
58
2.53973
98
0.66818
138
0.22776
19
13.2631
59
2.44677
99
0.64862
139
0.22231
Page 42
2.Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
ASN98D22UFZ
ASM135D23UFZ
DA200S2C-10MT
Blue - Red
1.57Ω
(20/68)
1.75Ω
(20/68)
0.51Ω
(20/68)
Blue - Black
Red - Blue
Loading...