ODMI-A-1110
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drop s.
● Moisture in the refrigerant circuit may freeze and block capillary t ubing.
● Water may lead to corrosion of par ts in the refrigerant syst em.
Therefore, the indoor units and t he pipes between i ndoor and out d oor unit s m ust be lea k tested and
evacuated to remove gas and mo ist ur e from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come
out, the pipes have leakage.
1. Air pur ging with vacuum pum p
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose w it h t he push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of ha ndle hi connection to the vacuu m pu mp.
4) Fully open the handle Lo of the ma ni fold valve.
5) Operate the vacuum pum p t o evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it sh oul d be pumped 20 minutes more. If
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage