
SERVICE MANUAL
MIDEA AIRCONDITIONER
North America MARKET
DC INVERTER MULTI TYPE
M2OC-18HRDN1-M
M3OC-27HRDN1-M
M4OC-36HRDN1-M

ODMI-A-1110
CONTENTS
1. General information of Outdoor Units ................................................. 3
2.Features .................................................................................................. 4
3. Dimensions ............................................................................................ 5
4. Wiri ng Diagram ...................................................................................... 6
5. Refrigeration Cycle Diagram ................................................................ 8
6. I ndoor units combination .................................................................... 10
7. I nstallation De tails ............................................................................... 11
8. Electronic control function ................................................................. 20
9. Troubleshooting .................................................................................. 25

ODMI-A-1110
1. General information of Outdoor Unit s
Model name Dimension (mm(in)) Compressor
M2OC-18HRDN1-M 845x320x700(33.3x12.6x27.6) DA130S1C-20FZ
M3OC-27HRDN1-M 845x320x700(33.3x12.6x27.6) DA150S1C-20FZ
M4OC-36HRDN1-M 990x345x965(39x13.6x38) TNB306FPGMC-L

The hydrophilic fin can improve the heating efficiency at operation mode.
It is only operated in the heating operation mode except defrosting operation.
It protects the valves and prevents water from dripping.
Outdoor unit
Power relay control
Hydrophilic aluminum fin
4 way valve control
Low noise air flow system
Discharge pipe temperature protection
Compressor crankcase heater

ODMI-A-1110
3. Dimensions
mm(in)
Model W D H W1 A B
M2OC-18HRDN1-M
845((33.3) 320(12.6) 700(27.6) 908(35.7) 560(22) 335(13.2)
M3OC-27HRDN1-M
M4OC-36HRDN1-M 990(39) 345(13.6) 965(38) 1075(42.3) 624(24.6) 366(14.4)

ODMI-A-1110
5. Refrigeration Cycle Diagram
8.1 Refrigeration circuit drawing of inverter dual zone
5.2 Refrigeration circuit drawing of inverter tri-zone
8.3 Refrigeration circuit drawing of inve r t e r qua-zone

ODMI-A-1110
6. Indoor units combination
6.1 Indoor unit combination for M2OC-18HRDN1-M
Comb.
6.2 Indoor unit combination for M3OC-27HRDN1-M
Comb.
6.3 Indoor unit combination for M4OC-36HRDN1-M
Comb.

ODMI-A-1110
7. Installation Details
7.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
mm inch N.cm N.cm
$6.35 1/4 1500(153kgf.cm) 1600(163kgf.cm)
$9.52 3/8 2500(255kgf.cm) 2600(265kgf.cm)
$12.7 1/2 3500(357kgf.cm) 3600(367kgf.cm)
7.2 Connecting the cables
The power cord of connect s houl d be selected according to the follow ing specifications sheet.
For power line:
Unit AWG
dual-zone(18K outdoor unit) 14
tri-zone (27K outdoor unit). 14
qua-zone(36K outdoor unit) 12
For indoor unit and outdoor unit connection line, 16AWG is ok for all.
7.3 Pipe length and the elevation
Unit
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas Liquid
9K 3/8•• ($9.53) 1/4•• ($6.35)
5
(16.4ft)
8
(26.2ft)
20
(65.6ft)
20
(0.212
ozs/ft)
12K/18K 1/2•• ($12.7) 1/4•• ($6.35)
Caution:
Capacity test is based o n standard length and maxi mu m allowance length is based on rel iability.
Oil trap should be install ed per 3-5 meters.

ODMI-A-1110
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drop s.
● Moisture in the refrigerant circuit may freeze and block capillary t ubing.
● Water may lead to corrosion of par ts in the refrigerant syst em.
Therefore, the indoor units and t he pipes between i ndoor and out d oor unit s m ust be lea k tested and
evacuated to remove gas and mo ist ur e from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come
out, the pipes have leakage.
1. Air pur ging with vacuum pum p
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose w it h t he push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of ha ndle hi connection to the vacuu m pu mp.
4) Fully open the handle Lo of the ma ni fold valve.
5) Operate the vacuum pum p t o evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it sh oul d be pumped 20 minutes more. If
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage

ODMI-A-1110
points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump.
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, and then tighten the flare nut again. Make sure the pressure display in the pressure
indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3
way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purgi ng by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a char ging cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purg e t he air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 second s t hen closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refr igerant by loosening the flare nut on t he

ODMI-A-1110
2-way valve approximatel y 45’ until the gauge indi cates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and t h e char ging cy lin der, and set the 2-way and 3-way valv es to the ope n
position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to t ighten the service port cap to a torque 18 N·m.
Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe lengt h >5m
Procedure:
1). Connect the charge hose to t he c har ging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410 A, m ake the cylinder bottom up to ensur e the liquid charge.
2). Purge the air from the charge h ose.
Open the valve at the bott om of th e cylinder and pr es s the ch eck v alve on th e charge set to pur ge t he air
(be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at t he c ool ing mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnec t t he char ge hose
Electronic scale

ODMI-A-1110
from the 3-way valve’ s ser vice port immediately and turn off the air conditioner before disconnecting the
hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque o f 18 N.m.
Be sure to check for gas lea kage.
7.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to t he 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the
cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge h ose.
Open the valve at the bott om of th e cylinder and pr es s the ch eck v alve on th e charge set to pur ge t he air
(be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record t he w eight.
4) Operate the air conditioner at t he c ool ing mode.
5) Open the valves (Low side) on the charge set and charge the sy st em with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air
conditioner before discon nec t in g the hose.
Electronic scale

ODMI-A-1110
7). Mount the valve stem caps and the service port
Use torque wrench to tight en t he ser vice port cap to a torque of 18N. m.
Be sure to check for gas lea kage.
7.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve st ems are in the opened position.
Be sure to use a hexagonal wr ench t o operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the ma ni fold valve slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditi oner at t he cooling cycle and stop it when the gaug e indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.

ODMI-A-1110
Use a torque wrench to tight en t he 3-way valves service port cap to a t or que of 1.8 kgf.m.
Be sure to check for gas leakage.
2. Air purgi ng by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a char ging cylinder to the service port of t he 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purg e t he air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 second s t hen closing it for 1 minute; repeat 3 ti me s.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on t he
2-way valve approximatel y 45’ until the gauge indi cates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and t h e char ging cy lin der, and set the 2-way and 3-way valv es to the ope n
position

ODMI-A-1110
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to t ighten the service port cap to a torque 18 N.m.
Be sure to check the gas leakage.
7.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump t o 3-way valve’s service port.
3). Evacuation for approxi mately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that t he gauge
needle does not move (appr oximately 5 minutes afte r t ur ning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.

ODMI-A-1110
2. Refrigerant charging
Procedure:
1). Connect the charge hose to t he c har ging cylinder; open the 2-w ay valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410 A, m ake the cylinder bottom up to ensur e liquid charge.
2). Purge the air from the charge hose
Open the valve at the bott om of th e cylinder and pr es s the ch eck v alve on th e charge set to pur ge t he air
(be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record t he w eight.
4). Open the valves (Low side) o n t he charge set and charge the syst em with liquid refrigerant
If the system cannot be char ge w ith the specified amount of refrigerant, or can be charged with a litt le at
a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; how ever, one
time is not sufficient, w ait approximately 1 minute and then r epeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve’s service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
6). Mounted the valve stem cap s and the service port
Use torque wrench to tight en t he ser vice port cap to a torque of 18N. m.
Be sure to check for gas leaka ge

8. Electronic control function
8.1 Abbreviation
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of out door heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Set t ing temp.
8.2 Electric control working environment.
8.2.1 Input voltage: 230V.
8.2.2 Input power frequency:60Hz.
8.2.3 Indoor fan normal working a mp. is less than 1A.
8.2.4 Outdoor fan. Normal working amp. is less than 1.5A.
8.2.5 Four-way valve normal wor king amp. is less than 1A.
8.2.6 Swing motor: DC12V.
8.3 Outdoor unit’s digital display tube
There is a digital display t ube i n outdoor PCB.
Digital display tube display function
• In standby , the LED displays “- -”
• In compressor operation, the LED display t he r unning frequency,
• In defrosting mode, The LED displays “dF” or alternative displays between running frequency and
“dF”(each displays 2s)
• In compressor pre-heating, The LED displays “- -”
• In protection or malfunction, the LED displ ays error code or protection code.
8.4 Outdoor unit point check function
There is a check switch in outdoor PCB.
Push the switch SW1 to check the st ates of un it when the unit is running. The digita l displ ay t ube will display
the follow procedure when push SW1 each time.
Indoor unit capacity demand code
2 Outdoor unit running mode code
Off:0, Cooling:1, Heating:2
Amendatory capacity demand code
4 Outdoor unit fan motor state
Off:0, Low speed:1, High speed:2
Evaporator outlet temp. for 1# indoor unit
Evaporator outlet temp. for 2# indoor unit
Evaporator outlet temp. for 3# indoor unit
Evaporator outlet temp. for 4# indoor unit
Compressor discharge temp.
EXV open angle for 1# indoor unit

EXV open angle for 2# indoor unit
EXV open angle for 3# indoor unit
EXV open angle for 4# indoor unit
Power supply of outdoor unit AD data
The indoor unit can communicate with outdoor unit well.
The last error or protection code
Ambient temp. of 1# indoor unit
Condenser pipe temp. of 1# indoor unit
Ambient temp. of 2# indoor unit
Condenser pipe temp. of 2# indoor unit
Ambient temp. of 3# indoor unit
Condenser pipe temp. of 3# indoor unit
Ambient temp. of 4# indoor unit
Condenser pipe temp. of 4# indoor unit
The following items from 6.4.1 to 6.4.6 are for the explanation of the point check functions.
8.4.1 Frequency of compressor :
Display Frequency of compressor (Hz)
30 30
-- Stand by
60 60
8.4.2 Running mode:
Display Corresponding mode
0 Off
1 Cooling mode
2 Heating mode
8.4.3 Capacity demand:
Cooling mode
Capacity 2000-2
500
2000-2
500
3000-3
800
4500-5
000
5000-5
500
5500-6
100
6100-7
000
7000-7
500
7500-8
000
>7500
Correspondi
ng Code
1 2 3 4 5 6 7 8 9 >=10
Heating mode
Capacity 2000-2
500
2000-2
500
3000-3
800
4500-5
000
5500-6
100
6100-7
000
6100-7
000
7000-7
500
7500-8
000
>8000
Correspondin
g Code
1 2 3 4 5 6 7 8 9-10 >=11
Note:
The capacity is just for ref er enc e.

8.4.4Number of indoor unit
Display Number of indoor unit
1 1
2 2
3 3
8.4.5 Outdoor ambient t emp:
Display Corresponding temp. Display
Corresponding
temp.
Display
Corresponding
temp.
15 -7.5 50 10 80 25
16 -7 51 10.5 81 25.5
17 -6.5 52 11 82 26
18 -6 53 11.5 83 26.5
19 -5.5 53 11.5 84 27
20 -5 54 12 85 27.5
21 -4.5 55 12.5 86 28
22 -4 56 13 87 28.5
23 -3.5 57 13.5 88 29
24 -3 58 14 89 29.5
26 -2 59 14.5 90 30
27 -1.5 60 15 91 30.5
28 -1 61 15.5 92 31
29 -0.5 62 16 93 31.5
30 0 63 16.5 93 31.5
31 0.5 63 16.5 94 32
32 1 64 17 95 32.5
33 1.5 65 17.5 96 33
34 2 65 17.5 97 33.5
35 2.5 66 18 98 34
36 3 67 18.5 99 34.5
37 3.5 68 19
10.
35~40
38 4 69 19.5
11.
40~45
39 4.5 70 20
12.
45~50
40 5 71 20.5
13.
50~55
41 5.5 72 21
14.
55~60
42 6 73 21.5
15.
60~65
43 6.5 74 22
16.
65~70
44 7 75 22.5
45 7.5 75 22.5
46 8 76 23
47 8.5 77 23.5
48 9 78 24
49 9.5 79 24.5

8.4.6 Opening degree of electronic ex pansion valve:
Actual opening degree equals the display data divided 8
8.5 Protection
8.5.1 Three minutes delay at restart for compressor.
8.5.2 T emperature prot ection of compressor discharge.
When the compressor discharge te mp. is getting higher, the running frequency will be limited as below rules:
----If 102℃<T5<115℃, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115 ℃ for 10 seconds, the co mpressor will stop and restar t t ill T5<90℃.
8.5.3 Low voltage protection
VOLLIMT1
VOLTAGE
No limit
VOLLIMT2
VOLLIMT3
Off
VOLFRE2
VOLFRE1
VOLREL1
VOLREL2
VOLREL3
Model VOLLIMT1 VOLLIMT2 VOLLIMT3 VOLREL1 VOLREL2 VOLREL3 VOLFRE1 VOLFRE2
M2OC-18HRDN1-M 230 200 120 260 210 135 62 54
M3OC-27HRDN1-M 245 220 120 265 240 135 78 45
M4OC-36HRDN1-M 200 185 120 210 195 135 54 42
Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always
after restart t he mac hi ne.
8.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
Cooling mode :
Current frequency(Hz) Current limit value(A) Frequency limit
COOL_F10 ICOOLLMT6
Decrease the frequenc
COOL_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3
minutes
(When the frequency>COOL_F4 via capacity demand).
COOL_F9 ICOOLLMT5
COOL_F8 ICOOLLMT4
COOL_F7 ICOOLLMT3
COOL_F6 ICOOLLMT2
COOL_F5 ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later.
Heating mode:
Current frequency(Hz) Current limit value(A) Frequency limit
HEAT_F12 IHEATLMT8 Decrease the frequency to HEAT_F4 and run at HEAT_F4
for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3
minutes
HEAT_F11 IHEATLMT7
HEAT_F10 IHEATLMT6
HEAT_F9 IHEATLMT5
HEAT_F8 IHEATLMT4

(When the frequency>Heat_F4 via capacity demand).
HEAT_F6 IHEATLMT2
HEAT_F5 IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display t he failure for 30 seconds and stop. The AC will restart 3
minutes later.
8.5.5 Indoor / out door units c om munication protection
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
8.5.6 High condenser coil temp. protection.
When T3>65℃ for 3 seconds, the compressor will stop while the indoor fan and outd oor f an will continue.
When T3<52 ℃, the protection w ill relea se and the compressor will restart after 3 minutes.
8.5.7 Outdoor unit anti -freezing protection
When T2B <0 ℃ for 250 seconds, the indoor unit capacity demand will be zero and resume to normal when
T2B>10 ℃.
8.5.8 Oil return
Running rules :
1. If the compressor frequency keeps lower than RECOILINFRE for 2hours,the AC will rise the frequency
to RECOILFRE for 3mins and then resume to former frequenc y.
M2OC-18HRDN1-M 45
M3OC-27HRDN1-M 45
M4OC-36HRDN1-M 40
2. During the oil return process, the EXV and indoor units keep the current running mode, the frequency
will not be limited by the compressor discharge temp. and t he cur r ent .
8.5.9 Compressor pre heating functions
----Preheating permitting c ondition:
If T4(outdoor ambient temperature)<3 ℃ and newly powered on or if T4<3 ℃
for over 3 hours, the compr essor heating cable will work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
----Preheating release condition:
If T4>5 ℃ o r the compressor starts running, preheating function will stop.
8.5.10 Compressor crankcase heater
When T4<3℃ and the compressor is not runnin g, the crankcase heater will be ac t iv e.
When T4≧5℃ or the compressor starts up, the cr ankcase heater will stop work.

9. Troubleshooting
9.1 Indoor unit error code explanation:
Vertu series & 9A series:
Display LED STATUS
E0 EEPROM parameter error
E1 Communication malfunction between indoor and outdoor units
E2 Zero-crossing signal error
E3 Indoor fan speed out of control
E5
Open or short circuit of outdoor temperat ure sensor
E6
Open or short circuit of room or evaporator coil temperature sensor
P0 Inverter module protection
P1 Over voltage or too low voltage protection
P2 Tempe rat ure protection of compressor top.
P3 Outdoor temp. too low protection
P4 Inverter compressor drive error
9.2 Outdoor unit error code explanation:
Display LED STATUS
E0 EEPROM parameter error
E1 No 1 Indoor units pipe temp. sensor or conne ctor of pipe te mp . sens or is defective
E2 No 2 Indoor units pipe temp. sensor or conne ctor of pipe te mp . sens or is defective
E3 No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E6 No 4 Indoor units pipe temp. sensor or conne ctor of pipe te mp . sens or is defective
E4 Open or short circuit of outdoor te mp erat ure sensor
E5 Compressor volt protection
E7 Communication error between outdoor IC and DSP
P0 Temperature protection of compressor top.
P1 High pressure protection (just for 36K 1x4 units.)
P2 Low pressure protection (just for 36K 1x4 units.)
P3 Compressor current protection
P4 Inverter module protection
P5 Outdoor temp. too low protection
P6 Condenser high-temper atu re protection
P7 Compressor driving protection
PF PFC protection ( jus t for 36K 1x 4 units.)

9.3 Trouble shooting
9.3.1 Indoor unit trouble shooting
Indoor unit display LED STATUS
E0 EEPROM parameter error
Shut off the power supply and turn on it 1 minute later
The problem comes out again
Is the EEPROM chip plugged in indoor PCB
Replace the main PCB of indoor unit

Indoor unit display LED STATUS
E1 Communication malfunction between indoor and outdoor units
No
Yes
No
Yes
The unit does not work normally
Check the wiring between indoor and outdoor
unit. Is the connection of L, N, S and G N D good?
No
Is the LED4(red) bright and LED1(yellow)
blinking on outdoor P C B?
The power supply for outd oor PCB is fail.
Check the wiring on outdoor PCB
comparing with wiring plate. Is the
connection good?
The unit does not
work normally
Turn off the power supply, after 1 minute, connect the
power supply, turn on the unit with remote controller
Replace indoor PCB and repower
Replace outdoor e-box.

Indoor unit display LED STATUS
E2 Zero-crossing signal error
Indoor unit display LED STATUS
E3 Indoor fan speed out of control
Indoor unit display LED STATUS
E5 Open or short circuit of outdoor temperature sensor
Is the outdoor temperature
check if E5 display again?
NO
YES
Replace outdoor e-box
YES
Is the indoor fan motor
connector and connection
Is voltage being applied to
the fan motor?
(rang 90v-160v between
mid pin and N on CN1
Indoor PCB is defective. Replace
Be sure the power supply is good
and correct the connection

Indoor unit display LED STATUS
E6 Open or short circuit of room or evaporator coil temperature sensor
Indoor unit display LED STATUS
P0 Inverter module protection
Indoor unit display LED STATUS
P1 Over voltage or too low voltage protection
Is the power supply good?
Be sure the power supply is
NO
YES
Replace the outdoor e-box.
Is the indoor temperature
connector and connection
good?
Repair the connector and
check if E6 display again?
NO
YES
Replace the.indoor PCB
YES
No
Yes
No
Yes
Yes
Check the connectors in outdoor PCBs。Is connection to connector
Is the wires to compr essor right
Check the outdoor inverter module。
P-N,P-U,P-V; P-W;N-W,N-U,N-V
At inverter module
Normally, P-N: ~1.0MΏ, P-U: ~2.0MΏ
P-V: ~2.0MΏ, P-V: ~2.0MΏ; N-W: ~1.0MΏ
Check compressor
Check the resistance between the terminal U, V, W with multimeter, if Ruv=Ruw=Rwv, it is
OK. Otherwise, to replace the compressor.
Inverter module is defective,

Indoor unit displ a y LED STATUS
P2 Temperature protection of compressor top.
Indoor unit displ a y LED STATUS
P3 Outdoor temp. too low protection
The trouble shooting is same with one of outdoor unit P3 protection.
Indoor unit displ a y LED STATUS
P4 Inverter compressor drive error
Yes
Replace inverter compressor.
No
Is the connection of compressor good?
Is the wiring sequence r ight? The v oltag e
range proper?
Yes
No,
Charge refrigerant
Is the abnormality the same
after gas charging?
Is refrigerant circulation
Does the compressor operate?
Replace it
There is block
welded points of the pipes.)

9.3.2 Outdoor unit trouble shooting
Outdoor unit displ ay LED STATUS
E0 EEPROM parameter error
Outdoor unit di splay LED STATUS
E1
No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Outdoor unit displ ay LED STATUS
E2
No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Shut off the power supply and turn on it 1 minute later
The problem comes out again
Is the EEPROM chip plugged in indoor PCB
Replace the main PCB of indoor unit
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor

Outdoor unit displ ay LED STATUS
E3
No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Outdoor unit displ ay LED STATUS
E6
No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor

Outdoor unit display LED STATUS
E4 Open or short circuit of outdoor temperature sensor
Outdoor unit displ ay LED STATUS
E5 Compressor volt protection
Yes
Check the voltage of power supply, if the voltage is about 220V, turn off the
power supply to indoor unit and turn it on again after 1 minute
Does the trouble occur again?
Check the DC voltage between pin P & N on the IPM, if the voltage is
310V~380V, it is OK.
No
Replace the outdoor power board
Yes
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Replace the sensor

Outdoor unit displ ay LED STATUS
E7 Communication error between outdoor IC and DSP
Is the LED in outdoor main PCB light?
1.Is the +5 voltage in outdoor main board?
Power Board: CN4, Red wire and yellow (GND)
Outdoor main PCB: CZ1
2.Is the +12v voltage in outdoor main board?
Power Board: CN1, Purple wire and yellow (GND)
Inverter module defective.
Rectifier circuit i
defective when the voltage in outdoor is
abnormal .
P and N 310V~380V(DC)
No
Yes
No
Check the signal wires between outdoor
PCBs, is it connected good.
Replace the main control board
Replace the IPM module

Outdoor unit displ ay LED STATUS
P0 Temperature protection of compressor top.
Off: 105c; On: 90c
The trouble shooting is same with the one of indoor unit P2 protection.
Outdoor unit display
LED STATUS
P3 Compressor current protection
Outdoor unit displ ay
LED STATUS
P4
Inverter module protection
The trouble shooting is same with the one of indoor unit P0 protection
Check the resistance of compressor, normally
U and V is 0.6 ohm
U and W is 0.6 ohm
V and W is 0.6 ohm
Turn one ind oor unit only, Does the compressor start after
3 minutes?
Does the trouble occur again after compressor
running some time?
No
Yes
No
The compressor is defective
Check the refrigerant circulation volume and pressure
No
The compressor is defective
Yes
If refrigerant circulation volume and pressure is OK, change the outdoor main PCB.

Outdoor unit displ ay LED STATUS
P6 Condenser high-temperature protection
When outdoor pipe temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than
52°C.
Is the outdoor pipe temp. more than 65°C ?
Is the outdoor pipe temp sensor right according to the annex 1
Replace the outdoor main board
No
Yes
Replace the outdoor pipe temp sensor
No

Outdoor unit displ ay LED STATUS
PF PFC module protection
No
No
Yes
Check whether the power
supply of bridge rectifiers
output port is 325VDC
Replace bridge rectifiers
normally ?
No
Check whether the
power supply of bridge
rectifiers input port is
normal.
Replace the
outdoor PCB
Yes
Replace the PFC inductance
voltage between P and
N port in IPM is 380V.
No
Replace outdoor e-box.
Check whether the
wiring between PCB
and PFC module is
normal.
Yes
No
Check the voltage of power supply, if the voltage
is about 220V, turn off the power supply and
turn it on again after 1 minute
Yes
Check whether
the PFC
inductance is
normal.
Replace PFC

Annex 1
Characteristic of temp. se nsor
Temp. ℃ Resistan ce K© Temp. ℃ Resistance K© Temp. ℃ Resistance K©
-10 62.2756 17 14.6181 44 4.3874
-9 58.7079 18 13.918 45 4.2126
-8 56.3694 19 13.2631 46 4.0459
-7 52.2438 20 12.6431 47 3.8867
-6 49.3161 21 12.0561 48 3.7348
-5 46.5725 22 11.5 49 3.5896
-4 44 23 10.9731 50 3.451
-3 41.5878 24 10.4736 51 3.3185
-2 39.8239 25 10 52 3.1918
-1 37.1988 26 9.5507 53 3.0707
0 35.2024 27 9.1245 54 2.959
1 33.3269 28 8.7198 55 2.8442
2 31.5635 29 8.3357 56 2.7382
3 29.9058 30 7.9708 57 2.6368
4 28.3459 31 7.6241 58 2.5397
5 26.8778 32 7.2946 59 2.4468
6 25.4954 33 6.9814 60 2.3577
7 24.1932 34 6.6835 61 2.2725
8 22.5662 35 6.4002 62 2.1907
9 21.8094 36 6.1306 63 2.1124
10 20.7184 37 5.8736 64 2.0373
11 19.6891 38 5.6296 65 1.9653
12 18.7177 39 5.3969 66 1.8963
13 17.8005 40 5.1752 67 1.830
14 16.9341 41 4.9639 68 1.7665
15 16.1156 42 4.7625 69 1.7055
16 15.3418 43 4.5705 70 1.6469

Annex 2
1. Reference voltage data:
a) Rectifier : Input :220-230V(AC), output :310V(DC)
b) Inverter module: U,V, W 3ph.
Result
U-V 60-150V(AC)
U-W 60-150V(AC)
V-W 60-150V(AC)
P-N DC 310V
c) Photo-couple PC817, PC851: Control side <+5V, AC side :< 24V(AC)
d) S terminal and N: changeable from 0-24V
2. Check the Diode Bridge com ponent ( In wiring diagram, rect ifier)
Remark: If this part is abn or m al, the LED will not light.
Multi-meter Result
Forward Resistance Backward Resistance