GD Midea Refrigeration Equipment Co.,Ltd
SPLIT TYPE, HEAT PUMP AIR CONDITIONERS
Technical & service manual 2005
Elite Series(7000-18000) R22 Wall Mounted
[Models]
MSE-07CR
MSE-07HR
MSE-09CR
MSE-09HR
MSE-12CR
MSE-12HR
MSE-18CR
MSE-18HR

1
Elite SERIES (R22)
Contents
1. Features………………………………………………………………… 02
2. Specification………………………………………………………..……03
3. Dimensions…………………………………………………………..… 05
4. Refrigeration cycle diagram……………………………………………08
5. Capacity table…………………………………………………………...09
6. Wiring diagram…………………………………………………..………15
7. Electronic function………………………………………….…………...20
8. Troubleshooting……………………………………………………….…28
9. Characteristic of temp. sensor…………………………………………31

3
2.Specification
MSE-07CR MSE-07HR MSE-09CR MSE-09HR
Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h
7000 7000
9000 9000
Input W 800 800 1050 1050
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h, w/w
8.8,2.6 8.8,2.6
8.6,2.5 8.6,2.5
Capacity Btu/h 8000 10000
Input W 800 1020
Rated current A 3.5 4.45
COP W/W 2.93 2.88
L/h 0.8 0.8 1.0 1.0
W 1300
1000
1350 1350
A 6.8 5.0 6.0 6.0
A 17.2 17.2 18.0 18.0
Model
2P14C225ANA 2P14C225ANA
2P18S225ANK 2P18S225ANK
T
Brand GD Matsushita GD Matsushita GD Matsushita GD Matsushita
Ca
acity Btu/h 7500 7500 9920 9920
ut W 725 7 25 9 70 97 0
Rated current
RL A 3.4 3.4 4.5 4.5
Locked rotor Am
rotector B160-135-141E MRA98854
acitor uF 25 25 30 30
Refri
erant oil ml ATOMOS M60 270 ATOMOS M60 270 SUNISO 350 SUNISO 350
Model
RPG13H RPG13H RPG13H RPG13H
Brand Wellin
ut W
39.5 39.5 39.5 39.5
Ca
acitor uF
1.2 1.2 1.2 1.2
S
eed(hi/mi/lo) r/min 1050/950/800 1050/950/800 1250/1100/850 1250/1100/850
m3/h
400/35/300 400/35/300
450/400/350 450/400/350
dB(A)
35/32/30 35/32/30 37/34/32 37/34/32
Dimension (W*H
mm
710×250×195 710×250×195 710×250×195 710×250×195
Packing (W*H*
mm
800×340×270 800×340×270 800×340×270 800×340×270
Net/Gross weight Kg
Model
YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Brand Welling Welling Welling Welling
Input W
70 70 70 70
Capacitor uF
3333
Speed r/min
850 850 850 850
m3/h 1500 1500 1800 1800
dB(A)
49 49
50 50
Dimension(W*H*
mm
700X535X235 700X535X235 700X535X235 700X535X235
Packing (W*H*D mm
815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg
28/31 28/31 28/31 28/31
g 530 570 580 800
MPa
2.6 2.6 2.6 2.6
Liquid side/ Gas
mm(inch)
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Max. refrigerant
m10101010
Max. difference i
m5555
16A 16A 16A 16A
Electrolic control Electrolic control Electrolic control Electrolic control
℃
17-30 17-30 17-30 17-30
℃
18?-45 -7 -? 45 18?-45 -7 -? 45
m2 10-14 10-14 14-21 14-21
set 126/272/298 126/272/298 126/272/298 126/272/298
Ambient temp
Application area
Qty’per 20’ /40’ /40'HQ
Connection wiring
Plug type
Thermostat type
Operation temp
Outdoor unit
Refrigerant type R22(R407C)
Design pressure
Refrigerant piping
Indoor unit
Outdoor fan moto
Outdoor air flow
Outdoor noise level
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Moisture Removal
Max. input consumption
Max. current
Starting current
Model
Power supply
Cooling
Heating
★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient
condition.

4
MSE-12CR MSE-12HR MSE-18CR MSE-18HR
Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h
12000 12000
18000 18000
Input W
1350 1350 1960 1960
Rated current A
6.0 6.0
9.4 9.4
EER Btu/w.h, w/w
8.9,2.6 8.9,2.6 9.2,2.7 9.2,2.7
Capacity Btu/h 14000 / 20500
Input W
1350
/ 1890
Rated current A
6.0
/8.6
COP W/W 3.0 / 3.2
L/h 1.5 1.5 1.9
W
1700 1700
2200 2130
A 8.0 8.0 10.2 10.4
A
25 25 36 36
Model
PH225X2C-4FT PH225X2C-4FT PH290X2C-4FT1 PH290X2C-4FT1
T
Brand
GMCC GMCC
GD Toshiba GD Toshiba
Ca
acity Btu/h 13197/13299 13197/13299 17435 17435
ut W 1250/1285 1250/1285 1670 1670
Rated current
RL A 5.7/5.5 5.7/5.5 8.0 8.0
Locked rotor Am
A 29.9/33 29.9/33 41.2 41.2
Thermal
rotector UP3RE0591-T56 UP3RE0591-T56 Internal Internal
Ca
acitor uF
35 35 35 35
Refri
erant oil ml
480 480 520 520
Model
RPG13D RPG13D RPG25 RPG25
Brand Wellin
acitor uF 1.5uF/450V 1.5uF/450V
S
eed(hi/mi/lo) r/min 1180/1000/850 1180/1000/850 1180/1080/800 1180/1080/800
m3/h
580/500/420 580/500/420 80 0/730/60 0 800/730/600
dB(A)
37/32/28 37/32/28
42/40/38 42/40/38
Dimension (W*H
mm
790x265x195 790x265x195
920×292×225 920×292×225
Packing (W*H*
mm
875×375×285 875×375×285
1015X370X295 1015X370X295
Net/Gross weight Kg
9.0/11.5 9.0/11.5 13/15 13/15
Model
YDK24-6 YDK24-6 YDK36-6 YDK36-6
Brand Welling Welling WELLING WELLING
Input W
85 85 96 96
Capacitor uF
2.5μF/450V 2.5μF/450V 2.5μF/450V 2.5μF/450V
Speed r/min
900 900 900 900
m3/h 2000 2000 1800 1800
dB(A)
54 54
56 56
Dimension(W*H*
mm
780×540×250 780×540×250
780X540X250 780X540X250
Packing (W*H*D mm 910x575x335 910x575x335 9 10x575x335 910x575x335
Net/Gross weight Kg
34/37 34/37 37/40 40/43
g
850 900
1130 1400
MPa
2.6 2.6 2.6 2.6
Liquid side/ Gas
mm(inch)
Ф
6.35/φ12.7
Ф
6.35/φ12.7
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Max. refrigerant
m10101010
Max. difference i
m5555
No No No No
16A 16A No No
Electronic control Electronic control Electronic control Electronic control
℃
17-30 17-30 17-30 17-30
℃
18-45 —7-45 17-45 —7-45
m2 18-26 18-26 30-40 30-40
set 108/226/266 108/226/266 100/210/245 100/210/245
Ambient temp
Application area
Qty’per 20’ /40’ /40'HQ
Connection wiring
Plug type
Thermostat type
Operation temp
Outdoor unit
Refrigerant type R22(R407C)
Design pressure
Refrigerant piping
Indoor unit
Outdoor fan moto
Outdoor air flow
Outdoor noise level
Compressor
Indoor fan motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Moisture Removal
Max. input consumption
Max. current
Starting current
Model
Power supply
Cooling
Heating
★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient
condition.

5
3.Dimensions
3.1 Indoor unit
MSE-07CR, MSE-07HR
MSE-09CR, MSE-09HR
MSE-12CR, MSE-12HR

7
3.4 Outdoor unit
MSE-07CR, MSE-07HR
MSE-09CR, MSE-09HR
3.5 Outdoor unit
MSE-12CR, MSE-12HR
MSE-18CR, MSE-18HR

8
4.Refrigeration cycle diagram

9
5. Capacity table
5.1 MSE-07CR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
21ºC D
15ºC W
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
24ºC D
17ºC W
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
Total capacity kW 2.32 2.27
2.15
1.98 1.81 1.65
Sensitive capacity kW 1.65 1.62
1.56
1.48 1.41 1.34
27ºC D
19ºC W
Input kW. 0.72 0.79
0.85
0.92 0.99 1.05
Total capacity kW 2.36 2.39 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
32ºC D
23ºC W
Input kW. 0.71 0.19 0.87 0.95 1.03 1.10
5.2 MSE-07HR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
21ºC D
15ºC W
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
24ºC D
17ºC W
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
Total capacity kW 2.32 2.27
2.15
1.98 1.81 1.65
Sensitive capacity kW 1.65 1.62
1.56
1.48 1.41 1.34
27ºC D
19ºC W
Input kW. 0.72 0.79
0.85
0.92 0.99 1.05
Total capacity kW 2.36 2.39 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
32ºC D
23ºC W
Input kW. 0.71 0.19 0.87 0.95 1.03 1.10

10
WINTER OUTDOOR CONDITIONS
Indoor
Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-8ºC W
Capacity kW 2.75 2.45 2.17 1.40 1.17 1.13
15ºC
Input kW. 0.97 0.86 0.77 0.67 0.62 0.65
Capacity kW 2.60 2.33 2.10 1.33 1.23 1.09
18ºC
Input kW. 0.99 0.86 0.78 0.71 0.68 0.68
Capacity kW 2.58
2.35
2.08 1.27 1.14 1.11
20ºC
Input kW. 1.02
0.90
0.81 0.71 0.67 0.64
Capacity kW 2.40 2.29 1.99 1.07 1.15 1.07
22ºC
Input kW. 0.94 0.89 0.81 0.70 0.68 0.63
5.3 MSE-09CR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.44 2.32 2.16 1.98 1.82 1.70
Sensitive capacity kW 1.68 1.63 1.56 1.48 1.40 1.34
21ºC D
15ºC W
Input kW. 0.87 0.95 1.02 1.09 1.17 1.24
Total capacity kW 2.62 2.50 2.36 2.20 2.07 1.94
Sensitive capacity kW 1.78 1.73 1.67 1.61 1.56 1.54
24ºC D
17ºC W
Input kW. 0.87 0.95 1.03 1.11 1.20 1.28
Total capacity kW 2.80 2.75
2.60
2.40 2.18 1.99
Sensitive capacity kW 1.93 1.89
1.82
1.73 1.64 1.57
27ºC D
19ºC W
Input kW. 0.89 0.97
1.05
1.14 1.22 1.30
Total capacity kW 2.85 2.90 2.86 2.76 2.63 2.50
Sensitive capacity kW 1.83 1.85 1.84 1.81 1.78 1.79
32ºC D
23ºC W
Input kW. 0.88 0.98 1.07 1.17 1.27 1.37

11
5.4 MSE-09HR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.44 2.32 2.16 1.98 1.82 1.70
Sensitive capacity kW 1.68 1.63 1.56 1.48 1.40 1.34
21ºC D
15ºC W
Input kW. 0.87 0.95 1.02 1.09 1.17 1.24
Total capacity kW 2.62 2.50 2.36 2.20 2.07 1.94
Sensitive capacity kW 1.78 1.73 1.67 1.61 1.56 1.54
24ºC D
17ºC W
Input kW. 0.87 0.95 1.03 1.11 1.20 1.28
Total capacity kW 2.80 2.75
2.60
2.40 2.18 1.99
Sensitive capacity kW 1.93 1.89
1.82
1.73 1.64 1.57
27ºC D
19ºC W
Input kW. 0.89 0.97
1.05
1.14 1.22 1.30
Total capacity kW 2.85 2.90 2.86 2.76 2.63 2.50
Sensitive capacity kW 1.83 1.85 1.84 1.81 1.78 1.79
32ºC D
23ºC W
Input kW. 0.88 0.98 1.07 1.17 1.27 1.37
WINTER OUTDOOR CONDITIONS
Indoor
Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-8ºC W
Capacity kW 3.58 3.18 2.80 1.82 1.52 1.47
15ºC
Input kW. 1.18 1.05 0.94 0.81 0.75 0.80
Capacity kW 3.37 3.02 2.72 1.73 1.60 1.41
18ºC
Input kW. 1.20 1.05 0.96 0.86 0.83 0.84
Capacity kW 3.35
3.05
2.70 1.64 1.48 1.44
20ºC
Input kW. 1.24
1.08
0.98 0.86 0.82 0.82
Capacity kW 3.11 2.97 2.57 1.40 1.50 1.39
22ºC
Input kW. 1.14 1.07 0.98 0.86 0.82 0.79

12
5.5 MSE-12CR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 3.38 3.21 2.99 2.75 2.52 2.35
Sensitive capacity kW 2.53 2.28 2.18 2.07 1.96 1.88
21ºC D
15ºC W
Input kW. 1.20 1.30 1.41 1.51 1.61 1.72
Total capacity kW 3.62 3.46 3.26 3.06 2.86 2.68
Sensitive capacity kW 2.50 2.42 2.34 2.25 2.19 2.16
24ºC D
17ºC W
Input kW. 1.20 1.31 1.43 1.54 1.65 1.76
Total capacity kW 3.88 3.80
3.60
3.32 3.02 2.76
Sensitive capacity kW 2.71 2.65
2.55
2.42 2.30 2.19
27ºC D
19ºC W
Input kW. 1.23 1.34
1.45
1.57 1.68 1.80
Total capacity kW 3.95 4.01 3.95 3.82 3.64 3.46
Sensitive capacity kW 2.56 2.59 2.57 2.53 2.50 2.51
32ºC D
23ºC W
Input kW. 1.22 1.35 1.48 1.62 1.75 1.89
5.6 MSE-12HR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 3.38 3.21 2.99 2.75 2.52 2.35
Sensitive capacity kW 2.53 2.28 2.18 2.07 1.96 1.88
21ºC D
15ºC W
Input kW. 1.20 1.30 1.41 1.51 1.61 1.72
Total capacity kW 3.62 3.46 3.26 3.06 2.86 2.68
Sensitive capacity kW 2.50 2.42 2.34 2.25 2.19 2.16
24ºC D
17ºC W
Input kW. 1.20 1.31 1.43 1.54 1.65 1.76
Total capacity kW 3.88 3.80
3.60
3.32 3.02 2.76
Sensitive capacity kW 2.71 2.65
2.55
2.42 2.30 2.19
27ºC D
19ºC W
Input kW. 1.23 1.34
1.45
1.57 1.68 1.80
Total capacity kW 3.95 4.01 3.95 3.82 3.64 3.46
Sensitive capacity kW 2.56 2.59 2.57 2.53 2.50 2.51
32ºC D
23ºC W
Input kW. 1.22 1.35 1.48 1.62 1.75 1.89

13
WINTER OUTDOOR CONDITIONS
Indoor
Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-8ºC W
Capacity kW 4.81 4.28 3.78 2.45 2.04 1.97
15ºC
Input kW. 1.61 1.44 1.29 1.11 1.03 0.99
Capacity kW 4.53 4.06 3.66 2.32 2.14 1.98
18ºC
Input kW. 1.65 1.44 1.31 1.18 1.14 1.02
Capacity kW 4.50
4.10
3.63 2.21 1.98 1.94
20ºC
Input kW. 1.69
1.48
1.34 1.18 1.12 1.03
Capacity kW 4.20 3.99 3.46 1.87 2.00 1.87
22ºC
Input kW. 1.78 1.48 1.35 1.12 1.13 1.07
5.7 MSE-18CR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 4.69 4.45 4.15 3.81 3.50 3.27
Sensitive capacity kW 3.28 3.18 3.04 2.88 2.74 2.62
21ºC D
15ºC W
Input kW. 1.70 1.84 1.99 2.14 2.28 2.43
Total capacity kW 5.03 4.81 4.53 4.25 3.97 3.73
Sensitive capacity kW 3.47 3.37 3.25 3.13 3.04 3.00
24ºC D
17ºC W
Input kW. 1.70 1.86 2.02 2.17 2.33 2.50
Total capacity kW 5.38 5.28
5.00
4.61 4.20 3.83
Sensitive capacity kW 3.77 3.69
3.55
3.38 3.20 3.06
27ºC D
19ºC W
Input kW. 1.73 1.90
2.05
2.22 2.38 2.54
Total capacity kW 5.68 5.57 5.49 5.30 5.06 4.81
Sensitive capacity kW 3.57 3.61 3.58 3.52 3.48 3.50
32ºC D
23ºC W
Input kW. 1.72 1.91 2.10 2.29 2.48 2.67

14
5.8 MSE-18HR
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 4.69 4.45 4.15 3.81 3.50 3.27
Sensitive capacity kW 3.28 3.18 3.04 2.88 2.74 2.62
21ºC D
15ºC W
Input kW. 1.70 1.84 1.99 2.14 2.28 2.43
Total capacity kW 5.03 4.81 4.53 4.25 3.97 3.73
Sensitive capacity kW 3.47 3.37 3.25 3.13 3.04 3.00
24ºC D
17ºC W
Input kW. 1.70 1.86 2.02 2.17 2.33 2.50
Total capacity kW 5.38 5.28
5.00
4.61 4.20 3.83
Sensitive capacity kW 3.77 3.69
3.55
3.38 3.20 3.06
27ºC D
19ºC W
Input kW. 1.73 1.90
2.05
2.22 2.38 2.54
Total capacity kW 5.68 5.57 5.49 5.30 5.06 4.81
Sensitive capacity kW 3.57 3.61 3.58 3.52 3.48 3.50
32ºC D
23ºC W
Input kW. 1.72 1.91 2.10 2.29 2.48 2.67
WINTER OUTDOOR CONDITIONS
Indoor
Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-8ºC W
Capacity kW 6.92 6.15 5.44 3.52 2.94 2.83
15ºC
Input kW. 2.45 2.19 1.96 1.69 1.57 1.45
Capacity kW 6.52 5.84 5.27 3.35 3.09 2.78
18ºC
Input kW. 2.51 2.19 1.99 1.80 1.73 1.48
Capacity kW 6.48
5.90
5.22 3.18 2.86 2.79
20ºC
Input kW. 2.57
2.25
2.04 1.79 1.70 1.51
Capacity kW 6.02 5.74 4.98 2.70 2.88 2.75
22ºC
Input kW. 2.38 2.25 2.05 1.79 1.71 1.53

15
6. Schematic diagram and wiring diagram
6.1 Schematic diagram
1 2 3 4 5 6 78
A
B
C
D
8
7654321
D
C
B
A
C1
104
Vin
1
GND
2
Vout
3
IC3 780 5
+5V
E3
470uF/16V
E1
2200uF/25V
C4
104
D4
D3
D2
D1
Vin
1
GND
2
Vout
3
IC1 781 2
+12V-a
E2
1000uF/16V
C3
104
X14MR7
1M
A0
1
A1
2
A2
3
GND4SDA
5
SCL
6
WC
7
VCC
8
IC2
24C04
+5V C2
104
R2
10KR110K
SDA
SDA
SCL
SCL
C5
104
+5V
R412K
1
2
3
IC5 KIA70 42
RST
RST
BUZ1
BUZZER1
R5
1K
+12V
R27
2K
Q3
9014
BUZ
BUZ
E4
10uF/16V
R8
8.1K/1%
C6
104
R10 2K
D6
IN4148
D5
IN4148
+5V
1
2
CN2
T1_roo m
T1_roo m
T1_roo m
E5
10uF/16V
R9
8.1K/1%
C7
104
R11 2K
D8
IN41 48
D7
IN41 48
+5V
1
2
CN3
T2_I.p ipe
T2_I. pip e
T2_I. pip e
CT1
0057h
D10
1N4148
R14
1.4K/1%
R6
1K/1%
R13
16K
E6
10uF/16V
D9
1N4148
R12 2K
C8
104
+5V
Current
Cu rrent
Q2
9014
R15
12K
C9
104
D11 1N414 8
D12 1N414 8
R16 12K
R17
12K
R18 10K
+5V ZERO
ZERO
A
B
B
A
E7
10uF/16V
C10
102
R19 1 50
+5V
R20 1K
C11
104
REC
REC
R215.1K
D13
IN41 48
C12
103
+5V
1
2
3
CN4
FAN_BACK
+12V-a
FANSP_FEEDBAC K
FANSP_FEEDBAC K
REC
V
GND
REC1
RECEIVER_V
JR7
10K
C13
104
R23 2 K
+5V
AUTO_SELECT
AUTO_SELECT
C14
1.2uF/450V
IC6 PC 81 7
T1T2
G
TR1
BT131
L2
?
C15
333
R242K
+12V-a
R26
1K
E9
470uF/25V
R28
11K/2W
Z1
12V
D15
IN4 007
R29
11K/2W
L1
N
R25 51/1W
FAN_IN '
FAN_IN
IN1
1
IN2
2
IN3
3
IN4
4
IN5
5
IN6
6
IN7
7
VSS8VDD
9
OUT7
10
OUT6
11
OUT5
12
OUT4
13
OUT3
14
OUT2
15
OUT1
16
IC7
UJN2003
STEP_I2
STEP_I1
STEP_I3
STEP_I4
STEP_I2
STEP_I1
STEP_I3
STEP_I4
+12V-a
C19
104
1
2
3
4
5
CN12
SWING
FAN_IN '
FAN_IN
BUZ '
BUZ '
COMP
COMP
COMP '
COMP '
RY2
RELAY-SPST
+12V-a
D21
IN4148
R33
2K
Q5
9014
RY3
RELAY-SPST
+12V-a
D22
IN4 148
R34
2K
Q6
9014
RY4
RELAY-SPST
+12V-a
D23
IN4148
R35
2K
Q7
9014
RY5
RELAY-SPST
+12V-a
D24
IN4148
C20
333
R36
51/1W
VALVE
VALVE
FAN_OUT
FAN_OUT
HEAT
HEAT
RY6
COMP
C21
333
R37
51/1W
+12V-a
1
CN14
N
L(POWER_IN PORT)
LOAD_COMP
N
FUSE1
3.15A/250V
L1
L1
FRESH
FUSE2
10A
LOAD_VALVE
LOAD_FAN OUT
LOAD_HEAT L
LOAD_HEAT N
1
CN11
N
1
CN10
HEAT_L
1
CN9
HEAT_N
1
2
CN13
ZR1
10D471K
C23
0.1uF/275VAC
1
2
CN15
TRANS_IN
SW1
t
PTC
82RM
R39
5.1K
C22
104
R38
10K
+5V
SW_TEST
SW_TEST
Onl y For He at Pum p
Dsa
1
Dsb
2
Q0
3
Q1
4
Q2
5
Q3
6
GND
7
CP
8
MR9Q4
10
Q5
11
Q6
12
Q7
13
Vcc
14
IC8
74HC164
+5V
+5V
COM1
COM2
COM3SEG1
SEG2
SEG3
SEG4
R60
10K
R59
10K
+5V
C24
104
SEG3
SEG4
Q8
9012Q99012
Q10
9012
R44
330
R45 330
R46 330
R47 330
R48 330
R49 330
R54 330
R55 330
R412KR422KR43
2K
LED6
自动
LED7
化霜
LED8
定时
+5V
abcde
f
g
h
com1
com2
DIS1
WT4021BG
COM1 COM2 COM3
LED9
运行灯
1
2
3
4
5
CN6
FAN_IN
+12V-a
COM1
COM2
COM3SEG1
SEG2
SEG3
SEG4
SCL
SDA
T1
T2
CURRENT
AUTO_SELECT SW
STEP_I1
STEP_I2
STEP_I3
STEP_I4
FAN_IN
BUZ
COMP
VALVE
FAN_OUT
ZERO
FANSP
REC
HEAT
FRESH
RST
X2
X1
C25
104
+5V
IN40 07 *4
VSS0
1
VDD0
2
P25
3
P26
4
P00
5
P01
6
P02
7
P03
8
P04
9
VSS1
10
P05
11
P50
12
P51
13
P52
14
P53
15
AVDD
16
AVREF
17
AN10
18
AN11
19
AN12
20
AN1321AN14
22
AN15
23
AVSS
24
P10
25
P11
26
P30
27
P31
28
P32
29
P33
30
P20
31
VDD1
32
P21
33
P22
34
P23
35
P24
36
Vpp/ IC
37
XT2
38
XT1
39
RESET
40
X2
41
X1
42
IC4
UPD789 166
+5V
C26
104
JR1
10K
JR3 10K
JR2
10K
JR5 10K
JR4
10K
+5V
C16
102
C17
102
JR6
10K
JR8
10K
JR9
10K
+5V
R41
10K
R41
10K
R41
10K
+5V +5V
FRESH
R61
2K
Q11
9014
R62
1K
IC9
PC817
SW2
+12V-a +12V-b
R63
5.1K
Q12
9014
GNDB
+12V-b 1
2
CN16
C23
104
E10
2200uF/25V
D19
D18
D17
D16
Vin
1
GND
2
Vout
3
IC10 7812
+12V-b
E11
1000uF/16V
C24
104
C
D
IN40 07 *4
1
2
3
4
CN1
TRANS
GNDB

16
6.2 Wiring diagram
6.2.1 Cooling only
6.2.1.1 MSE-07CR, MSE-09CR MSE-12CR
2(N)
Y&G
BLUE
S
RED
C
BLACK
R
BLACK

18
6.2.2 Heating/cooling
6.2.2.1 MSE-07HR, MSE-09HR MSE-12HR
INDOOR UNIT
OUTDOOR UNIT

20
7 Electronic function
7.1 Electric Control working environment
7.1.1 input voltage: 175~253V
7.1.2 Input power frequency:50Hz
7.1.3 Ambient temperature: -7°C~+45°C
7.1.4 Indoor fan normal working amp is less than 1A,
7.1.5 Outdoor fan. Normal working amp is less than 1.5A
7.1.6 Four-way valve normal working amp is less than 1A.
7.1.7 Swing motor: DC12V.
7.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
7.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
I
RESTORE
: Amp self-protection return value
TH
DEFROST
: High wind, defrosting temperature difference
TM
DEFROST
: Middle wind, defrosting temperature difference
TL
DEFROST
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
7.3 Functions
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode

21
7.4 Protection
7.4.1 3 minutes delay at restart for compressor.
7.4.2 Sensor protection at open circuit and breaking disconnection
7.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
7.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
7.4.5 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark
I< I
RESTORE
On On On
On On Off Heating mode I
RESTORE
<I< I
FAN
Low speed On On Cooling mode
I
FAN
<I<I
5MIN
Off Off After 5 Minutes
Current up
I
5MIN
<I< I
3SEC
Off Off After 3 Seconds
I
5MIN
<I< I
3SEC
Off Off After 3 Seconds
I
FAN
<I<I
5MIN
Off Off After 5 Minutes
On On Off Heating mode I
RESTORE
<I< I
FAN
Low speed On On Cooling mode
Current down
I< I
RESTORE
On On On
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
7.5 Fan-only mode
Fan speed is high/mid/low/ Auto
7.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition
T=Indoor T emp.
Ts=Setting Temp.
Compressor Outdoor fan
T> T s+1 On On Room temp. up
T<Ts+1 Off Off
T> T s On On Room temp. down
T<Ts Off Off
Auto fan at cooling mode:
Condition
T=Indoor T emp.-Setting Temp.
Indoor fan speed
T<4℃ Low
4℃<T<5℃ Med.
Room temp. up
T>5℃ High
T> 4℃ High
1<T<℃ 4℃ Med.
Room temp. down
T<1℃ Low

22
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Condition
Temp. Time
Compressor Outdoor fan
T> TE6 On On
Evaporator Temp. up
T< TE6 >5 Minutes Of f Off
T> TE5 On On
Evaporator Temp. down
T< TE5 >5 Minutes Of f Off
7.7 Dehumidifying mode
7.7.1 The 4-way valve is off in dehumidifying mode
7.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
1 TA ≥ TS+2
LOW
BREEZE
ON 6minutes
OFF 4minutes
2 TS ≤TA<TS+2
LOW
BREEZE
ON 5minutes
OFF 5minutes
3 TA < TS
LOW
BREEZE
ON 4minutes
OFF 6minutes
Repeat on and off cycle.
7.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
7.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of
cooling mode.
7.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
7.8 Heating mode
7.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
7.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
7.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
7.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
function prevails.
Anti-cold wind control function at heating mode
Condition Indoor fan speed

23
T= Indoor exchanger temp.
T<TE1 Off
TE1<T<TE2 Breeze
Indoor exchanger temp. up
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
Indoor exchanger temp. down
T<TE4 Off
7.8.5 Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2℃ High Room temp. up
T>2℃ Med.
T> 0℃ Med. Room temp. down
T<0℃ High
7.8.6 Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
7.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
7.9 Defrosting operation (Available for heating only).
7.9.1 Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
℃
Temp. of evaporator---room temp.
Fan speed is high ≤TH
DEFROST
Fan speed is mid ≤TM
DEFROST
Fan speed is low ≤TL
DEFROST
Breeze Meet only if it is Breeze
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
7.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.

24
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→7.5-minute defrost → 7.5-minute defrost→7.5-minute defrost→10-minute defrost→
7.10 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
DEROST
differs in different models.
7.11 Defrosting Actions:
7.12 utomatic operation mode
7.12.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan
only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode
TA—TS>2℃ Cooling
-1 ≤TA℃ -TS≤+2℃ Fan-only
TA-TS<-1℃ Heating (air-only for cooling only type)
7.12.2 The indoor fan blows automatically in corresponding selected mode.
7.12.3 The motion of indoor fan’s blade should accord with the selected operation mode.
7.12.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot
start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or
reselect when the set temp. varies.
7.13 orced cooling function
7.13.1 Select forced cooling function with the forced cooling button or the switch.
7.13.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is
set as low, the A/C operates at the DRY mode with a set temp. of 24℃.
Defrost 10or 6minutes
45S 25S
Compressor
4-way Valve 23S
40S
Outdoor Fan
Indoor Fan
10S

25
7.13.3 All protections of remote control cooling are available at forced cooling operation.
7.14 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
7.15 Timer Function
7.16 Economic Running
7.16.1 The economic running function is available at cooling, heating or auto mode.
7.17 Cooling: The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain
as a constant and the fan speed is kept at low speed.
7.18 Heating: The set temperature decrease 1℃ per hour. Two hours later, the set temperature will
maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes
precedence over all).
7.19 Auto: The economic running function operates in accordance with selected running mode by auto mode.
7.20 uto restart function: In case of a sudden power failure, this function automatically sets the unit to
previous settings before the power failure when power returns.

26
7.21 Models and Parameters
Model MSE-07CR MSE-07HR MSE-09CR MSE-09HR
I3SEC 8.5A 8.5A 10.0
TE1 28℃ 28℃
TE2 32℃ 32℃
TE3 30℃ 30℃
TE4 26℃ 26℃
TE5 4℃ 4℃ 4℃ 4℃
TE6 10℃ 10℃ 10℃ 10℃
TE7 60℃ 60℃
TE8 53℃ 53℃
TE9 50℃ 50℃
ANGLCOOL 88 88 88 88
ANGLHEAT 125 125
ANGLOFF 0 0 0° 0°
THDEFROST 15 17°C
TMDEFROST 16 18°C
TLDEFROST 17 19°C

27
Model MSE-12CR MSE-12HR MSE-18CR MSE-18HR
I3SEC 12.0A 12.0A 16.0A 16.0A
I5MIN 8.5A 8.5A 13.0A 13.0A
IFAN 7.5A 7.5A 11.0A 11.0A
IRESTORE 6.5A 6.5A 9.5A 9.5A
IDEFROST 5.0A 7.5A
TE1 34 34
TE2 37 36
TE3 33 30
TE4 22 20
TE5 4 4 3 3
TE6 10 10 14 14
TE7 63 60
TE8 53 52
TE9 52 50
ANGLCOOL 88 88 88 88
ANGLHEAT 125 125
ANGLOFF 0° 0° 0° 0°
THDEFROST 18 17°C
TMDEFROST 19 18°C
TLDEFROST 20 19°C

28
8.Troubleshooting
8.1 Display board
This indicator illuminates when the air conditioner is in AU TO operation.
AUTO indicator
DE FROST indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner s tarts defrosting a utomatically or
when the warm air control feature is activated in heating operat ion.
1
22
3
4
5
1
22
3
4
Displays the temperature settings when the air conditioner is operat ional.
This indicator flashes after po wer is on and illuminates when the unit is in operation.
This indicator illuminates when T IMER is set ON/OFF
O P ERATION i n d i c ator
TIMER indicator
TEMPER ATUR E indicator
5
Signal receptor
8.2 For all heat pump model
r Extinguish
☆ Flash at 5Hz
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On
Over current protection of the compressor occurs 4 times X ☆
EEROM error On ☆
No over-zero signal ☆ ☆

29
8.3 Diagnostic Chart
8.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated.
Yes
Yes No
No Yes
Yes
No
8.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status when
power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Yes
No Yes
No
fter energizing, the air conditione
can’t be operated
Check if AC220V power supply outputs to Indoor PCB.
Check if AC220V exists at the primary coil of transformer.
Indoor PCB is defective
Check if AC14.5V exists at the secondary coil of transformer.
Take off the secondary plug of transformer, and then check i
C14.5V exists at the secondary coil of transformer.
The transformer is defective. Indoor PCB is defective
Resetting phenomenon often occurs during operation.
fter changing indoor fan motor, check if the failure releases.
Indoor PCB is defective
Power supply circuit has problems.
fter changing Indoor PCB, check if the failure releases.

30
8.3.3 Failure phenomenon
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On
Over current protection of the compressor occurs 4 times X ☆
EEROM error On ☆
No over-zero signal ☆ ☆
r Extinguish
☆ Flash at 5Hz
8.3.3.1 Operation lamp flashes and Timer lamp off.
8.3.3.2 Operation lamp flashes and Timer lamp on.
8.3.3.3 Operation lamp off and Timer lamp flashes
No Yes
Yes No
8.3.3.4 Operation lamp on and Timer lamp flashes
EEROM error, indoor PCB is defective.
8.3.3.5 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main
control board must have fault.
Operation lamp off and Timer lamp flashes
Indoor PCB is defective
Power supply fault Outdoor unit fault (such as the compressor)
The voltage of power supply is too low (less than 187V)?
fter changing the main control board, check if the failure releases.
Is connector connection good?
Is voltage being applied to the fan motor?
Fan motor is defective
Repair the connector
Indoor PCB is defective
No Yes
Yes No
Is connection to connector good?
Replace the sensor
Repair connector
Yes
No
Yes

31
9. Characteristic of temp. sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ
-10 62.2756 17 14.6181 44 4.3874
-9 58.7079 18 13.918 45 4.2126
-8 56.3694 19 13.2631 46 4.0459
-7 52.2438 20 12.6431 47 3.8867
-6 49.3161 21 12.0561 48 3.7348
-5 46.5725 22 11.5 49 3.5896
-4 44 23 10.9731 50 3.451
-3 41.5878 24 10.4736 51 3.3185
-2 39.8239 25 10 52 3.1918
-1 37.1988 26 9.5507 53 3.0707
0 35.2024 27 9.1245 54 2.959
1 33.3269 28 8.7198 55 2.8442
2 31.5635 29 8.3357 56 2.7382
3 29.9058 30 7.9708 57 2.6368
4 28.3459 31 7.6241 58 2.5397
5 26.8778 32 7.2946 59 2.4468
6 25.4954 33 6.9814 60 2.3577
7 24.1932 34 6.6835 61 2.2725
8 22.5662 35 6.4002 62 2.1907
9 21.8094 36 6.1306 63 2.1124
10 20.7184 37 5.8736 64 2.0373
11 19.6891 38 5.6296 65 1.9653
12 18.7177 39 5.3969 66 1.8963
13 17.8005 40 5.1752 67 1.830
14 16.9341 41 4.9639 68 1.7665
15 16.1156 42 4.7625 69 1.7055
16 15.3418 43 4.5705 70 1.6469