Micro Motion 4200 Operating Manual

Installation Manual
MMI-20058013, Rev AB
Micro Motion® 4200 2-Wire Transmitter
April 2019
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +41 (0) 41 7686
111
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Europe and Middle East Asia Pacific
666
France 0800 917 901 India 800 440 1468
Central & Eastern +41 (0) 41 7686
111
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
New Zealand 099 128 804
Japan +81 3 5769 6803
2
Installation Manual Contents
MMI-20058013 April 2019

Contents

Chapter 1 Planning........................................................................................................................ 5
1.1 About this document........................................................................................................................5
1.2 Related documentation....................................................................................................................5
1.3 Meter components...........................................................................................................................5
1.4 Installation types.............................................................................................................................. 6
1.5 Installation checklist.........................................................................................................................7
1.6 Maximum cable lengths between sensor and transmitter.................................................................9
Chapter 2 Mounting and sensor wiring........................................................................................ 11
2.1 Mounting and sensor wiring for integral-mount transmitters......................................................... 11
2.2 Mount the transmitter to a wall or instrument pole........................................................................ 11
2.3 Wire the 9-wire remote-mount transmitter to the sensor...............................................................14
2.4 Ground the meter components...................................................................................................... 16
2.5 Rotating the transmitter on the sensor (optional)...........................................................................17
2.6 Rotating the display orientation..................................................................................................... 18
2.7 Rotate the sensor wiring junction box on a remote-mount transmitter (optional).......................... 19
Chapter 3 Wiring the channels.....................................................................................................21
3.1 Installation types for the 4200 transmitter......................................................................................21
3.2 Available channels.......................................................................................................................... 22
3.3 Barriers verified by Micro Motion.................................................................................................... 23
3.4 Channel power requirements .........................................................................................................24
3.5 Access the wiring channels............................................................................................................. 28
3.6 Wire the Channel A mA HART output............................................................................................. 29
3.7 Wire the Channel B mA output....................................................................................................... 30
3.8 Wire Frequency/Discrete output (Channel B)..................................................................................30
3.9 Wire the mA/SIL output..................................................................................................................31
Chapter 4 Power up the transmitter.............................................................................................33
Chapter 5 Configuring the transmitter with Guided Setup............................................................35
Chapter 6 Using the display controls............................................................................................ 37
6.1 Configure the display backlight...................................................................................................... 38
Chapter 7 Communicating with the transmitter...........................................................................39
Installation Manual 3
Contents Installation Manual
April 2019 MMI-20058013
4 Micro Motion® 4200 2-Wire Transmitter
Installation Manual Planning
MMI-20058013 April 2019

1 Planning

1.1 About this document

This manual provides information on planning, mounting, wiring, and initial setup of the transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand:
Basic transmitter and sensor installation, configuration, and maintenance concepts
and procedures
All corporate, local government, and national government safety standards and
requirements that guard against injuries and death

1.2 Related documentation

See the approval documentation shipped with the transmitter, or download the appropriate documentation from the Micro Motion web site (www.emerson.com/
flowmeasurement):
Micro Motion 4200 2-Wire Transmitter: Configuration and Use Manual
Micro Motion 4200 2-Wire Transmitter: Product Data Sheet
Micro Motion 4200 2-Wire Transmitter: Safety Manual for Safety Instrumented Systems
Micro Motion ProLink III User Manual
Sensor installation manual, which is shipped with the sensor
FMEDA report for Coriolis Flowmeter with 4200 Transmitter, Prepared for Emerson by
exida.com LLC

1.3 Meter components

A 4200 meter consists of the following components:
A transmitter
A sensor
Installation Manual 5
Planning
April 2019 MMI-20058013
Installation Manual

1.4 Installation types

The 4200 transmitter was ordered and shipped for one of two installation types. The fifth character of the transmitter number indicates the installation type.
Figure 1-1: Installation type indication for 4200 transmitters
The number is located on the device tag on the side of the transmitter.
Table 1-1: Installation types for 4200 transmitters
Code Description
I Integral mount
C Remote mount
Figure 1-2: 4200 transmitter -- Integral mount
A. Conduit openings
B. Clamping ring C. Sensor case D. Transmitter housing cover (hidden from view)
The transmitter is installed directly on the sensor.
6 Micro Motion® 4200 2-Wire Transmitter
Installation Manual
MMI-20058013 April 2019
The connections between the transmitter and sensor are 9-wire, and do not require field wiring on the integral mount version.
The I/O connections consist of 2 channels, each channel being 2-wire. Power must be supplied to Channel A for the transmitter to operate, while Channel B connections are optional.
Figure 1-3: 4200 transmitter -- Remote mount
Planning
A. Transmitter housing cover
B. Clamping ring C. Junction box
The transmitter is installed remotely from the sensor. The 9-wire connection between the sensor and transmitter must be field wired. Power supply and I/O must be field wired to the transmitter. The sensor connection is in the junction box.

1.5 Installation checklist

Safety messages are provided throughout this content to protect personnel and
equipment. Read each safety message carefully before proceeding to the next step.
When choosing a location for components, refer to the following guidelines:
See the sensor installation manual for information on locating the sensor with
remote-mount or extended-mount electronics.
Installation Manual 7
Planning Installation Manual
April 2019 MMI-20058013
Do not install a component in a location where its temperature, humidity, or
vibration limits will be exceeded.
Maximum distance between components depends on the wire size, the wire type,
and the power supply. Ensure that sufficient power is supplied to the transmitter terminals.
If you plan to mount the transmitter in a hazardous area:
Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter housing.
Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
For ATEX/IECEx installations, you must strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the product documentation DVD shipped with the product or at www.emerson.com/
flowmeasurement.
Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable length does not exceed 60 ft (20 m).
The transmitter can be mounted in any orientation as long as the conduit openings do
not point upward.
CAUTION
Installing the transmitter with the conduit openings or transmitter display facing upward risks condensation moisture entering the transmitter housing, which could damage the transmitter.
Minimize the amount of moisture or condensation inside the transmitter housing.
Moisture inside the transmitter housing can damage the transmitter and cause measurement error or flowmeter failure. To do this:
Ensure the integrity of all gaskets and O-rings
Install drip legs on conduit or cable
Seal unused conduit openings
Ensure that all covers are fully tightened
Mount the meter in a location and orientation that satisfies the following conditions:
Allows sufficient clearance to open the transmitter housing cover. Install with 8–10
inches (200–250 mm) clearance at the wiring access points.
Provides clear access for installing cabling to the transmitter.
Provides clear access to all wiring terminals for troubleshooting.
8 Micro Motion® 4200 2-Wire Transmitter
Installation Manual Planning
MMI-20058013 April 2019

1.6 Maximum cable lengths between sensor and transmitter

The maximum cable length between the sensor and transmitter that are separately installed is determined by cable type.
Cable type Wire gauge Maximum length
Micro Motion 9-wire remote mount
Not applicable 60 ft (18 m)
Installation Manual 9
Planning Installation Manual
April 2019 MMI-20058013
10 Micro Motion® 4200 2-Wire Transmitter
Installation Manual Mounting and sensor wiring
MMI-20058013 April 2019

2 Mounting and sensor wiring

2.1 Mounting and sensor wiring for integral­mount transmitters
There are no separate mounting requirements for integral transmitters, and no need to connect wiring between the transmitter and the sensor.

2.2 Mount the transmitter to a wall or instrument pole

There are two options available for mounting the transmitter:
Mount the transmitter to a wall or flat surface.
Mount the transmitter to an instrument pole.
Prerequisites
If you are mounting the transmitter to a wall or flat surface:
Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
If you are mounting the transmitter to an instrument pole:
Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base,
and is no more than 2 in (51 mm) in diameter.
Confirm that you have the necessary tools, and the instrument-pole mounting kit
shipped with the transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws.
Installation Manual 11
Mounting and sensor wiring Installation Manual
April 2019 MMI-20058013
Figure 2-1: Mounting bracket to transmitter
2. Using a wall-mount or pole-mount:
For wall-mount installations, secure the mounting bracket to the prepared
surface.
Figure 2-2: Wall-mounting bracket dimensions
A. 2.8 in (71.4 mm) B. 2.8 in (71.4 mm)
12 Micro Motion® 4200 2-Wire Transmitter
Loading...
+ 28 hidden pages