Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Emerson Flow customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
Index ................................................................................................................................................. 55
Installation Manual i
Page 4
Contents
iiMicro Motion® Model 1500 and Model 2500
Page 5
1Planning
Topics covered in this chapter:
•Meter components
•Installation types
•Maximum cable lengths between sensor and transmitter
•Output options
•Environmental limits
•Hazardous area classifications
•Power requirements
1.1Meter components
The transmitter is one component of a Micro Motion device. The other major component
is the sensor.
Planning
A third component, called the core processor, provides additional memory and processing
functions.
1.2Installation types
The transmitter was ordered and shipped for one of three installation types. The fifth
character of the transmitter model number indicates the installation type.
Installation type indication for Model 1500 and Model 2500 transmittersFigure 1-1:
The model number is located on the device tag on the side of the transmitter.
Installation types for Model 1500 and Model 2500 transmittersTable 1-1:
Model codeDescription
D4-wire remote 35 mm DIN rail
E4-wire remote 35 mm DIN rail transmitter with 9-wire remote enhanced core
processor
B4-wire remote 35 mm DIN rail with 9-wire remote core processor
The transmitter is installed remotely from the sensor. The 4-wire connection between the sensor and
transmitter must be field wired. Power supply and I/O must be field wired to the transmitter.
Remote core processor with remote sensor installation (model code B or
E)
The transmitter, core processor, and sensor are all mounted separately. The 4-wire connection between
the transmitter and core processor must be field wired. The 9-wire connection between the core processor
and the sensor must be field wired. Power supply and I/O must be field wired to the transmitter. This
configuration is sometimes called double-hop.
1.3Maximum cable lengths between sensor and
transmitter
The maximum cable length between the sensor and transmitter that are separately
installed is determined by cable type.
Maximum cable lengths between sensor and transmitterTable 1-2:
Cable typeWire gaugeMaximum length
Micro Motion 4-wireNot applicable• 1000 ft (300 m) without Ex-
approval
• 500 ft (150 m) with IIC rat-
ed sensors
• 1000 ft (300 m) with IIB rat-
ed sensors
Micro Motion 9-wireNot applicable60 ft (20 m)
User-supplied 4-wireVDC 22 AWG (0.35 mm2)300 ft (90 m)
Installation Manual 3
Page 8
Planning
Maximum cable lengths between sensor and transmitter (continued)Table 1-2:
Cable typeWire gaugeMaximum length
1.4Output options
The transmitter was ordered and shipped for one of up to three output options. You must
know your transmitter output option to correctly install the transmitter. The eighth
character of the transmitter model number indicates the output option.
VDC 20 AWG (0.5 mm2)500 ft (150 m)
VDC 18 AWG (0.8 mm2)1000 ft (300 m)
RS-485 22 AWG (0.35 mm2) or
larger
1000 ft (300 m)
Figure 1-4:
Output option model code indication for Model 1500 and Model 2500
transmitters
The model number is located on the device tag on the side of the transmitter.
Output options for Model 1500 transmittersTable 1-3:
Model codeDescription
AOne mA, one frequency, RS-485
(1)
C
(1) Output code C on the Model 1500 transmitter is used only with the filling and dosing application.
One mA, two DO, RS-485
Output options for Model 2500 transmittersTable 1-4:
Model codeDescription
BOne mA, two configurable I/O channels, RS-485 – default configuration of two
mA, one FO
COne mA, two configurable I/O channels, RS-485 – custom configuration
4Micro Motion® Model 1500 and Model 2500
Page 9
1.5Environmental limits
Environmental specificationsTable 1-5:
TypeValue
Ambient temperature limits
(Operating)
Ambient temperature limits
(Storage)
Humidity limits5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
If the ambient temperature is above 113 °F (45 °C) and you are mounting multiple
transmitters, mount the transmitters so they are at least 0.39 in (10 mm) apart.
Installation Manual 7
Page 12
A
B
Mounting and sensor wiring for 4-wire remote installations
Mounting multiple transmittersFigure 2-2:
A.0.39 in or greater (10 mm or greater)
B.End bracket or end stop; 0.33 in (8.5 mm) minimum spacing
2.2Prepare the 4-wire cable
Important
For user-supplied cable glands, the gland must be capable of terminating the drain wires.
Note
If you are installing unshielded cable in continuous metallic conduit with 360º termination shielding,
you only need to prepare the cable – you do not need to perform the shielding procedure.
8Micro Motion® Model 1500 and Model 2500
Page 13
Mounting and sensor wiring for 4-wire remote installations
4-wire cable preparationFigure 2-3:
Remove the core processor
cover
Cable glands
Micro Motion
cable gland
Pass the wires through the gland nut and clamping insert.
Gland nut
1. Strip 4-1/2 inch (115 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 3/4 inch (19 mm) of shielding.
Clamping
insert
NPT
Wrap the drain wires twice around the shield and cut off
Gland supplier
Gland type
the excess drain wires.
Cable layout
through the gland.
Terminate the drain
wires inside the
M20
1. Strip 4-1/4 inch (108 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 1/2 inch (12 mm) of shielding.
User-supplied
cable gland
Pass the wires
gland.
Metal conduit
Run conduit to
sensor
Lay cable in conduit
Done
(do not perform the
shielding procedure)
Drain wires
wrapped around
shield
Go to the shielding
procedure
Installation Manual 9
Page 14
Mounting and sensor wiring for 4-wire remote installations
4-wire cable shieldingFigure 2-4:
From the preparation
procedure
Micro Motion
cable gland
Braided
(armored cable)
Apply the Heat Shrink
1. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
2. Apply heat (250 °F or 120 °C) to shrink the tubing. Do not burn the
cable.
3. Position the clamping insert so the interior end is flush with the braid
of the heat shrink.
Assemble the Gland
1. Fold the shield or braid back over the clamping insert and 1/8 inch
(3 mm) past the O-ring.
2. Install the gland body into the conduit opening on the core processor housing.
3. Insert the wires through gland body and tighten the gland nut onto the gland body.
Cable shield
type
Shielded heat
shrink
Foil
(shielded cable)
NPT
Gland supplier
Gland typeM20
After heat applied
User-supplied
cable gland
Trim 7 mm from the shielded
heat shrink
Trim
Terminate the shield
and drain wires in the
Assemble the gland
according to vendor
gland
instructions
Shield folded back
Done
Gland body
2.2.14-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain
shield drain wires.
The 4-wire cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.75 mm2) wires for the VDC connection, and one pair of white and green 22 AWG
(0.35 mm2) wires for the RS-485 connection.
10Micro Motion® Model 1500 and Model 2500
Page 15
Mounting and sensor wiring for 4-wire remote installations
User-supplied 4-wire cable must meet the following requirements:
•Twisted pair construction.
•Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
•Wire gauge appropriate for the cable length between the core processor and the
transmitter.
Wire gaugeTable 2-1:
Wire gaugeMaximum cable length
VDC 22 AWG (0.35 mm2)300 ft (90 m)
VDC 20 AWG (0.5 mm2)500 ft (150 m)
VDC 18 AWG (0.8 mm2)1000 ft (300 m)
RS-485 22 AWG (0.35 mm2) or larger1000 ft (300 m)
2.3Wire the transmitter to the sensor
1.Connect the cable to the sensor-mounted core processor as described in the sensor
documentation.
2.Connect the four wires from the core processor to terminals 1–4 on the transmitter.
Important
Do not ground the shield, braid, or drain wires at the transmitter.
Installation Manual 11
Page 16
RS-485B
RS-485A
VDC –
VDC+
Mounting and sensor wiring for 4-wire remote installations
Terminal connections for 4-wire cableFigure 2-5:
2.4Ground the flowmeter components
In 4-wire remote installations, the transmitter and sensor are grounded separately.
Prerequisites
CAUTION!
Improper grounding could cause inaccurate measurements or meter failure.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
Mounting and sensor wiring for remote core processor with remote sensor installations
3.1.1Mounting multiple transmitters
If the ambient temperature is above 113 °F (45 °C) and you are mounting multiple
transmitters, mount the transmitters so they are at least 0.39 in (10 mm) apart.
Mounting multiple transmittersFigure 3-2:
A.0.39 in or greater (10 mm or greater)
B.End bracket or end stop; 0.33 in (8.5 mm) minimum spacing
3.2Mount the remote core processor
This procedure is required only for remote core processor with remote transmitter
installations.
Prerequisites
For mounting the remote core processor to a wall:
•Micro Motion recommends the use of 5/16-18 (8 mm–1.25) fasteners that can
withstand the process environment. Micro Motion does not supply bolts or nuts as
part of the standard offering (general purpose bolts and nuts are available as an
option).
•Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
•Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
For mounting the remote core processor to an instrument pole:
•Use two 5/16-inch U-bolts for 2-inch pipe, and four matching nuts, that can
withstand the process environment. Micro Motion does not supply U-bolts or nuts.
14Micro Motion® Model 1500 and Model 2500
Page 19
A
B
Mounting and sensor wiring for remote core processor with remote sensor installations
•Ensure the instrument pole extends at least 12 inches (305 mm) from a rigid base,
and is no more than 2 inches (50.8 mm) in diameter.
Procedure
1.If desired, reorient the core processor housing on the bracket.
a. Loosen each of the four cap screws (4 mm).
b. Rotate the bracket so that the core processor is oriented as desired.
c. Tighten the cap screws, torquing to 30 to 38 in-lbs (3 to 4 N-m).
Components of a remote core processorFigure 3-3:
A. Mounting bracket
B. Cap screws
2.Attach the mounting bracket to an instrument pole or wall.
3.3Prepare the 4-wire cable
Important
For user-supplied cable glands, the gland must be capable of terminating the drain wires.
Note
If you are installing unshielded cable in continuous metallic conduit with 360º termination shielding,
you only need to prepare the cable – you do not need to perform the shielding procedure.
Installation Manual 15
Page 20
Mounting and sensor wiring for remote core processor with remote sensor installations
4-wire cable preparationFigure 3-4:
Remove the core processor
cover
Cable glands
Micro Motion
cable gland
Pass the wires through the gland nut and clamping insert.
Gland nut
1. Strip 4-1/2 inch (115 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 3/4 inch (19 mm) of shielding.
Clamping
insert
NPT
Wrap the drain wires twice around the shield and cut off
Gland supplier
Gland type
the excess drain wires.
Cable layout
through the gland.
Terminate the drain
wires inside the
M20
1. Strip 4-1/4 inch (108 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 1/2 inch (12 mm) of shielding.
User-supplied
cable gland
Pass the wires
gland.
Metal conduit
Run conduit to
sensor
Lay cable in conduit
Done
(do not perform the
shielding procedure)
Drain wires
wrapped around
shield
Go to the shielding
procedure
16Micro Motion® Model 1500 and Model 2500
Page 21
Mounting and sensor wiring for remote core processor with remote sensor installations
4-wire cable shieldingFigure 3-5:
From the preparation
procedure
Micro Motion
cable gland
Braided
(armored cable)
Apply the Heat Shrink
1. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
2. Apply heat (250 °F or 120 °C) to shrink the tubing. Do not burn the
cable.
3. Position the clamping insert so the interior end is flush with the braid
of the heat shrink.
Assemble the Gland
1. Fold the shield or braid back over the clamping insert and 1/8 inch
(3 mm) past the O-ring.
2. Install the gland body into the conduit opening on the core processor housing.
3. Insert the wires through gland body and tighten the gland nut onto the gland body.
Cable shield
type
Shielded heat
shrink
Foil
(shielded cable)
NPT
Gland supplier
Gland typeM20
After heat applied
User-supplied
cable gland
Trim 7 mm from the shielded
heat shrink
Trim
Terminate the shield
and drain wires in the
Assemble the gland
according to vendor
gland
instructions
Shield folded back
Done
Gland body
3.3.14-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain
shield drain wires.
The 4-wire cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.75 mm2) wires for the VDC connection, and one pair of white and green 22 AWG
(0.35 mm2) wires for the RS-485 connection.
Installation Manual 17
Page 22
A
B
Mounting and sensor wiring for remote core processor with remote sensor installations
User-supplied 4-wire cable must meet the following requirements:
•Twisted pair construction.
•Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
•Wire gauge appropriate for the cable length between the core processor and the
transmitter.
Wire gaugeTable 3-1:
Wire gaugeMaximum cable length
VDC 22 AWG (0.35 mm2)300 ft (90 m)
VDC 20 AWG (0.5 mm2)500 ft (150 m)
VDC 18 AWG (0.8 mm2)1000 ft (300 m)
RS-485 22 AWG (0.35 mm2) or larger1000 ft (300 m)
3.4Wire the transmitter to the remote core
processor
1.If you are installing a Micro Motion-supplied cable gland at the core processor
housing, identify the cable gland to use for the 4-wire cable conduit opening.
Cable gland identificationFigure 3-6:
A. Cable gland used with 4-wire conduit opening
B. 3/4"–14 NPT cable gland used with 9-wire conduit opening
2.Connect the cable to the core processor as described in the sensor documentation.
3.Connect the four wires from the core processor to terminals 1–4 on the transmitter.
Important
Do not ground the shield, braid, or drain wires at the transmitter.
18Micro Motion® Model 1500 and Model 2500
Page 23
RS-485B
RS-485A
VDC –
VDC+
Mounting and sensor wiring for remote core processor with remote sensor installations
Terminal connections for 4-wire cableFigure 3-7:
3.5Prepare the 9-wire cable
Micro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. The
type of cable you are using determines how you will prepare the cable.
Perform the cable preparation procedure appropriate for your cable type.
Installation Manual 19
Page 24
Mounting and sensor wiring for remote core processor with remote sensor installations
Preparing jacketed cableFigure 3-8:
Prepare jacketed
cable at the sensor
end
1. Trim 4 ½ inches (115 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Remove the foil that is around the insulated wires
and separate them.
Trim cable jacket
4. Identify the drain wires in the cable. Clip off each
drain wire as close as possible to the cable jacket.
Drain wires clipped
5. Slide the 1 ½ inch (40 mm) heat-shrink tubing over
the wires and cable jacket. The tubing should
completely cover the clipped ends of the drain wires.
Prepare jacketed
cable at the
transmitter end
1. Trim 4 inches (100 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Remove the foil that is around the insulated wires
and separate them.
Trim cable jacket
4. Identify the drain wires in the cable and bring them
together. Fan the other wires to the outside of the
cable. Twist the drain wires together.
5. Slide the 3-inch (75 mm) heat-shrink tubing over
the drain wires. Push the tubing as close as possible
to the cable jacket.
6. Slide the 1 ½ inch (40 mm) long heat-shrink tubing
over the cable jacket. The tubing should
completely cover all portions of the drain wires that
remain exposed next to the cable jacket.
Heat-shrink
tubing
6. Without burning the cable, apply heat to shrink all
tubing. Recommended temperature is 250 °F (121
°C).
7. Allow the cable to cool, then strip ¼ inch (5 mm) of
insulation from each wire.
Heat-shrink tubing over
cable jacket
Heat-shrink tubing over drain
wires
7. Without burning the cable, apply heat to shrink all
tubing. Recommended temperature is 250 °F (121
°C).
8. Allow the cable to cool, then strip ¼ inch (5 mm) of
insulation from each wire.
20Micro Motion® Model 1500 and Model 2500
Page 25
Mounting and sensor wiring for remote core processor with remote sensor installations
Preparing shielded or armored cableFigure 3-9:
Prepare shielded or
armored cable at the
sensor end
1. Without cutting the shield, strip 7 inches (175 mm)
of outer jacket.
2. Strip 6 ½ inches (165 mm) of braided shield, so ½
inch (10 mm) of shield remains exposed.
3. Remove the foil shield that is between the braided
shield and inner jacket.
4. Strip 4 ½ inches (115 mm) of inner jacket.
Trim outer jacket
Trim braided shield
Trim inner jacket
5. Remove the clear wrap and filler material.
6. Remove the foil that is around the insulated wires
and separate them.
7. Identify the drain wires in the cable. Clip each drain
wire as close as possible to the cable jacket.
Drain wires clipped
8. Slide the 1 ½ inch (40 mm) long heat-shrink tubing
over the cable jacket. The tubing should completely
cover the clipped ends of the drain wires.
Prepare shielded or
armored cable at the
transmitter end
1. Without cutting the shield, strip 9 inches (225 mm) of
cable jacket.
2. Strip 8 ½ inches (215 mm) of braided shield, so ½
inch (10 mm) of shield remains exposed.
3. Remove the foil shield that is between the braided
shield and inner jacket.
4. Strip 4 inches (100 mm) of inner jacket.
Trim outer jacket
Trim braided shield
Trim inner jacket
5. Remove the clear wrap and filler material.
6. Remove the foil that is around the insulated wires and
separate them.
7. Identify the drain wires in the cable and bring them
together. Fan the other wires to the outside of the
cable. Twist the drain wires together.
8. Slide the 3-inch (75 mm) long heat-shrink tubing over
the drain wires. Push the tubing as close as possible to
the inner jacket.
9. Slide the 1 ½ inch (40 mm) long heat-shrink tubing
over the cable jacket. The tubing should completely
cover all portions of the drain wires that remain
exposed next to the cable jacket.
Heat-shrink tubing
9. Without burning the cable, apply heat to shrink all
tubing. Recommended temperature is 250 °F (121
°C).
10. Allow the cable to cool, then strip ¼ inch (5 mm) of
insulation from each wire.
Heat-shrink tubing over cable
Heat-shrink tubing over drain wires
10. Without burning the cable, apply heat to shrink all
tubing. Recommended temperature is 250 °F (121
°C).
11. Allow the cable to cool, then strip ¼ inch (5 mm) of
insulation from each wire.
jacket
Installation Manual 21
Page 26
Mounting and sensor wiring for remote core processor with remote sensor installations
3.5.19-wire cable types and usage
Cable types
Micro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. Note
the following differences between the cable types:
•Armored cable provides mechanical protection for the cable wires.
•Jacketed cable has a smaller bend radius than shielded or armored cable.
•If ATEX compliance is required, the different cable types have different installation
requirements.
Cable jacket types
All cable types can be ordered with a PVC jacket or Teflon® FEP jacket. Teflon FEP is
required for the following installation types:
•All installations that include a T-series sensor.
•All installations with a cable length of 250 ft (75 m) or greater, a nominal flow less
than 20 percent, and ambient temperature changes greater than +68 °F (+20 °C).
Cable jacket material and temperature rangesTable 3-2:
Mounting and sensor wiring for remote core processor with remote sensor installations
3.6Wire the remote core processor to the sensor
using jacketed cable
Prerequisites
For ATEX installations, the jacketed cable must be installed inside a user-supplied sealed
metallic conduit that provides 360° termination shielding for the enclosed cable.
CAUTION!
Sensor wiring is intrinsically safe. To keep sensor wiring intrinsically safe, keep the sensor
wiring separated from power supply wiring and output wiring.
CAUTION!
Keep cable away from devices such as transformers, motors, and power lines, which produce
large magnetic fields. Improper installation of cable, cable gland, or conduit could cause
inaccurate measurements or flow meter failure.
CAUTION!
Improperly sealed housings can expose electronics to moisture, which can cause measurement
error or flowmeter failure. Install drip legs in conduit and cable, if necessary. Inspect and
grease all gaskets and O-rings. Fully close and tighten all housing covers and conduit openings.
Procedure
1.Run the cable through the conduit. Do not install 9-wire cable and power cable in
the same conduit.
2.To prevent conduit connectors from seizing in the threads of the conduit openings,
apply a conductive anti-galling compound to the threads, or wrap threads with PTFE
tape two to three layers deep.
Wrap the tape in the opposite direction that the male threads will turn when
inserted into the female conduit opening.
3.Remove the junction box cover and core processor end-cap.
4.At both the sensor and transmitter, do the following:
a. Connect a male conduit connector and waterproof seal to the conduit opening
for 9-wire.
b. Pass the cable through the conduit opening for the 9-wire cable.
c. Insert the stripped end of each wire into the corresponding terminal at the
sensor and transmitter ends, matching by color. No bare wires should remain
exposed.
Installation Manual 25
Page 30
D
I
H
F
E
A
B
C
G
Mounting and sensor wiring for remote core processor with remote sensor installations
Sensor and remote core processor terminal designationsTable 3-6:
Wire color Sensor terminal Remote core processor terminal Function
BlackNo connectionGround screw (see note)Drain wires
Brown11Drive +
Red22Drive –
Orange33Temperature –
Yellow44Temperature return
Green55Left pickoff +
Blue66Right pickoff +
Violet77Temperature +
Gray88Right pickoff –
White99Left pickoff –
d. Tighten the screws to hold the wire in place.
e. Ensure integrity of gaskets, grease all O-rings, then replace the junction-box and
transmitter housing covers and tighten all screws, as required.
3.7Wire the remote core processor to the sensor
using shielded or armored cable
Prerequisites
For ATEX installations, shielded or armored cable must be installed with cable glands, at
both the sensor and remote core processor ends. Cable glands that meet ATEX
requirements can be purchased from Micro Motion. Cable glands from other vendors can
be used.
CAUTION!
Keep cable away from devices such as transformers, motors, and power lines, which produce
large magnetic fields. Improper installation of cable, cable gland, or conduit could cause
inaccurate measurements or flow meter failure.
CAUTION!
Install cable glands in the 9-wire conduit opening in the transmitter housing and the sensor
junction box. Ensure that the cable drain wires and shields do not make contact with the
junction box or the transmitter housing. Improper installation of cable or cable glands could
cause inaccurate measurements or flow meter failure.
28Micro Motion® Model 1500 and Model 2500
Page 33
ABCDEF
GHI
Mounting and sensor wiring for remote core processor with remote sensor installations
CAUTION!
Improperly sealed housings can expose electronics to moisture, which can cause measurement
error or flowmeter failure. Install drip legs in conduit and cable, if necessary. Inspect and
grease all gaskets and O-rings. Fully close and tighten all housing covers and conduit openings.
Procedure
1.Identify the components of the cable gland and cable.
Cable gland and cable (exploded view)Figure 3-17:
A. Cable
B. Sealing nut
C. Compression nut
D. Brass compression ring
E. Braided shield
F. Cable
G. Tape or heat-shrink tubing
H. Clamp seat (shown as integral to nipple)
I. Nipple
2.Unscrew the nipple from the compression nut.
3.Screw the nipple into the conduit opening for the 9-wire cable. Tighten it to one turn
4.Slide the compression ring, compression nut, and sealing nut onto the cable. Make
5.Pass the cable end through the nipple so the braided shield slides over the tapered
6.Slide the compression ring over the braided shield.
7.Screw the compression nut onto the nipple. Tighten the sealing nut and
8.Use a 25-mm (1-inch) wrench to tighten the sealing nut and compression nut to
Installation Manual 29
past hand-tight.
sure the compression ring is oriented so the taper will mate properly with the
tapered end of the nipple.
end of the nipple.
compression nut by hand to ensure that the compression ring traps the braided
shield.
20–25 foot-pounds (27–34 N-m) of torque.
Page 34
A
B
C
E
D
F
GA
Mounting and sensor wiring for remote core processor with remote sensor installations
Cross-section of assembled cable gland with cableFigure 3-18:
A. Cable
B. Sealing nut
C. Seal
D. Compression nut
E. Braided shield
F. Brass compression ring
G. Nipple
9.Remove the junction box cover and remote core processor end-cap.
10.At both the sensor and remote core processor, connect the cable according to the
following procedure:
a. Insert the stripped end of each wire into the corresponding terminal at the
sensor and remote core processor ends, matching by color. No bare wires should
remain exposed.
Sensor and remote core processor terminal designationsTable 3-7:
Wire color Sensor terminal Remote core processor terminal Function
BlackNo connectionGround screw (see notes)Drain wires
Brown11Drive +
Red22Drive –
Orange33Temperature –
Yellow44Temperature return
Green55Left pickoff +
Blue66Right pickoff +
Violet77Temperature +
Gray88Right pickoff –
White99Left pickoff –
b. Tighten the screws to hold the wires in place.
30Micro Motion® Model 1500 and Model 2500
Page 35
D
I
H
F
E
A
B
C
G
Mounting and sensor wiring for remote core processor with remote sensor installations
c. Ensure integrity of gaskets, grease all O-rings, then replace the junction box
cover and remote core processor end-cap and tighten all screws, as required.
Connect the power supply to terminals 11 and 12. Terminals 13 and 14 are used to jumper
power to another Model 1500 or Model 2500 transmitter. A maximum of five transmitters
can be jumpered together.
Power terminalsFigure 4-1:
A.Primary power supply (VDC)
B.Power supply jumper to 1–4 additional Model 1500 or Model 2500 transmitters
34Micro Motion® Model 1500 and Model 2500
Page 39
I/O wiring for Model 1500 transmitters
5I/O wiring for Model 1500
transmitters
Topics covered in this chapter:
•Basic analog wiring
•HART/analog single loop wiring
•HART multidrop wiring
•Internally powered frequency output wiring
5.1Basic analog wiring
Model 1500 basic analog wiringFigure 5-1:
A
A.Terminals 21 and 22 to mA receiving device; 820 Ω maximum loop resistance
5.2HART/analog single loop wiring
Note
For HART communications:
•600 Ω maximum loop resistance
•250 Ω minimum loop resistance
Installation Manual 35
Page 40
A
B
B
A
C
E
D
F
I/O wiring for Model 1500 transmitters
HART/analog single loop wiringFigure 5-2:
A.820 Ω maximum loop resistance
B.HART-compatible host or controller
5.3HART multidrop wiring
Tip
For optimum HART communication, single-point ground the output loop to an instrument-grade
ground.
HART multidrop wiringFigure 5-3:
A.250–600 Ω resistance
B.HART-compatible host or controller
C.HART-compatible transmitters
D.Model 1500 or Model 2500 transmitter
E.SMART FAMILY™ transmitters
F.24 VDC loop power supply required for passive transmitters
36Micro Motion® Model 1500 and Model 2500
Page 41
Open circuit output voltage = 15 VDC ±3%
Load resistance (Ohms)
High level output voltage (Volts)
I/O wiring for Model 1500 transmitters
5.4Internally powered frequency output wiring
Internally powered frequency output wiringFigure 5-4:
C
A
000042
A.Counter
B.Channel C – Terminals 31 and 32
Output voltage versus load resistance (Channel C)Figure 5-5:
Installation Manual 37
Page 42
I/O wiring for Model 2500 transmitters
6I/O wiring for Model 2500
transmitters
Topics covered in this chapter:
•mA/HART wiring
•Frequency output wiring
•Discrete output wiring
•Discrete input wiring
6.1mA/HART wiring
6.1.1Basic analog wiring
Model 2500 basic analog wiringFigure 6-1:
AB
A.Channel A – Terminals 21 and 22 to mA receiving device; 820 Ω maximum loop resistance
B.Channel B – Terminals 23 and 24 to mA receiving device; 420 Ω maximum loop resistance
6.1.2HART/analog single loop wiring
Note
For HART communications:
•600 Ω maximum loop resistance
•250 Ω minimum loop resistance
38Micro Motion® Model 1500 and Model 2500
Page 43
HART/analog single loop wiringFigure 6-2:
A
B
A.820 Ω maximum loop resistance
B.HART-compatible host or controller
A.PLC or other device
B.External DC Power Supply (VDC)
C.Direct DC input
Power is supplied by either a PLC/other device or by direct DC input.
Input voltage ranges for external powerTable 6-1:
VDCRange
3–30High level
0–0.8Low level
0.8–3Undefined
46Micro Motion® Model 1500 and Model 2500
Page 51
7Specifications
Topics covered in this chapter:
•Electrical connections
•Input/output signals
•Environmental limits
•Physical specifications
7.1Electrical connections
Electrical connectionsTable 7-1:
TypeDescriptions
Input/output connectionsThree pairs of wiring terminals for transmitter outputs. Screw ter-
minals accept stranded or solid conductors, 24 to 12 AWG (0.40
to 3.5 mm2).
Power connectionsThe transmitter has two pairs of terminals for the power connec-
tion:
• Either pair accepts DC power
• The remaining pair is used for making a jumper connection to
a second transmitter
Plug terminals accept solid or stranded conductors, 24 to
12 AWG (0.40 to 3.5 mm2).
Digital communications maintenance connections
Core processor connectionThe transmitter has two pairs of terminals for the 4-wire connec-
Two clips for temporary connection to the service port. One pair
of terminals supports Modbus/RS-485 signal or service port
mode. On device power-up, user has 10 seconds to connect in
service port mode. After 10 seconds, the terminals default to
Modbus/RS-485 mode.
tion to the core processor:
• One pair is used for the RS-485 connection to the core pro-
cessor
• One pair is used to supply power to the core processor
Plug terminals accept solid or stranded conductors, 24 to
12 AWG (0.40 to 3.5 mm2).
Specifications
Installation Manual 47
Page 52
Specifications
7.2Input/output signals
I/O and digital communication for Model 1500 transmittersTable 7-2:
Description
One active 4–20 mA output, not intrinsically safe:
• Isolated to ±50 VDC from all other outputs and Earth ground
• Maximum load limit: 820 ohms
• Can report mass flow or volume flow
• Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 Version 03.02.2003
One active frequency/pulse output, not intrinsically safe:
• Can report mass flow or volume flow, which can be used to indicate flow rate or total
• Reports the same flow variable as the mA output
• Scalable to 10,000 Hz
• Voltage is +15 VDC ±3% with 2.2 kohm internal pull-up resistor
• Linear with flow rate to 12,500 Hz
• Configurable polarity: active high or active low
• Can be configured as a discrete output to report five discrete events, flow direction, flow
switch, calibration in progress, or fault
Service port, Modbus/RS-485 (terminals 33-34)
• After device power up, terminals 33 and 34 are available in service port mode for 10 seconds:
-Modbus RTU protocol
-38,400 baud
-No parity
-One stop bit
-Address = 111
• After 10 seconds, terminals 33 and 34 default to Modbus/RS-485:
-Modbus RTU or Modbus ASCII protocol (default: Modbus RTU)
-1200 to 38,400 baud rate (default: 9600)
-Stop bit configurable (default: one stop bit)
-Parity configurable (default: odd parity)
HART/Bell 202:
• HART Bell 202 signal is superimposed on the primary milliamp output, and is available for host
system interface. Frequency 1.2 and 2.2 kHz, Amplitude: to 1.0 mA, 1200 baud, Requires 250
to 600 ohms load resistance
• HART revision 5 as default, selectable to HART revision 7
One zero button that can be used to start the flowmeter zeroing procedure
48Micro Motion® Model 1500 and Model 2500
Page 53
Specifications
Table 7-3:
I/O and digital communication for Model 1500 transmitters with filling
and dosing application
Description
One active 4–20 mA output, not intrinsically safe:
• Isolated to ±50 VDC from all other outputs and Earth ground
• Maximum load limit: 600 ohms
• Can report mass flow or volume flow, or can control a two-position discrete valve or three-posi-
tion analog valve
• Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 Version 03.02.2003
One or two discrete outputs:
• Can report fill in progress or fault, or can control discrete valve
• Maximum sink capability is 500 mA
• Configurable for internal or external power
-Internally powered to 15 VDC ±3%, internal 2.2 kΩ pull-up, or
-Externally powered 3-30 VDC max., sinking up to 500 mA at 30 VDC maximum
One discrete input (can be configured instead of one of the discrete outputs):
• Configurable for internal or external power
• Can be used to begin fill, end fill, pause fill, resume fill, reset fill total, reset mass total, reset
volume total, or reset all totals (includes fill total)
Service port, Modbus/RS-485 (terminals 33-34):
• After device power up, terminals 33 and 34 are available in service port mode for 10 seconds:
-Modbus RTU protocol
-38,400 baud
-No parity
-One stop bit
-Address = 111
• After 10 seconds, terminals 33 and 34 default to Modbus/RS-485:
-Modbus RTU or Modbus ASCII protocol (default: Modbus RTU)
-1200 to 38,400 baud rate (default: 9600)
-Stop bit configurable (default: one stop bit)
-Parity configurable (default: odd parity)
One zero button that can be used to start the flowmeter zeroing procedure
Installation Manual 49
Page 54
Specifications
I/O and digital communication details for Model 2500 transmittersTable 7-4:
Description
Three input/output channels (A, B, and C) that can be configured from the following choices:
• One or two active 4–20 mA outputs (Channels A and B):
-Not intrinsically safe
-Isolated to ±50 VDC from all other outputs and earth ground
-Maximum load limits of mA1: 820 ohms; of mA2: 420 ohms
-Can report mass flow, volume flow, density, temperature, or drive gain
-Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 Version 03.02.2003
• One or two active or passive frequency/pulse outputs (Channels B and C):
-Not intrinsically safe
-Can report mass flow or volume flow, which can be used to indicate flow rate or total
-If configured as a dual pulse output, the channels are electrically isolated but not independ-
(2)
ent
-Scalable to 10,000 Hz
-If active, output voltages is +15 VDC ±3% with a 2.2 kohm internal pull-up resistor
-If passive, output voltage is 30 VDC maximum, 24 VDC typical, sinking up to 500 mA at 30
VDC
-Output is linear with flow rate to 12,500 Hz
• One or two active or passive discrete outputs (Channels B and C):
-Not intrinsically safe
-Can report five discrete events, flow switch, forward/reverse flow, calibration in progress,
or fault
-If active, output voltage is +15 VDC ±3% with a 2.2 kohm internal pull-up resistor
-If passive, output voltage is 30 VDC maximum, 24 VDC typical, sinking up to 500 mA at 30
VDC
• One discrete input (Channel C)
Service port, Modbus/RS-485 (terminals 33-34):
• After device power up, terminals 33 and 34 are available in service port mode for 10 seconds:
-Modbus RTU protocol
-38,400 baud
-No parity
-One stop bit
-Address = 111
• After 10 seconds, terminals 33 and 34 default to Modbus/RS-485:
-Modbus RTU or Modbus ASCII protocol (default: Modbus RTU)
-1200 to 38,400 baud rate (default: 9600)
-Stop bit configurable (default: one stop bit)
-Parity configurable (default: odd parity)
HART/Bell 202:
• HART Bell 202 signal is superimposed on the primary milliamp output, and is available for host
system interface. Frequency 1.2 and 2.2 kHz, Amplitude: to 1.0 mA, 1200 baud, Requires 250
to 600 ohms load resistance
• HART revision 5 as default, selectable to HART revision 7
(1)
(1) When output option B is ordered, the channels are configured at the factory for two mA and one frequency
output; When output option C is selected, the channels are custom configured at the factory.
50Micro Motion® Model 1500 and Model 2500
Page 55
(2) For custody transfer using double-pulse frequency output, the transmitter can be configured for two
frequency outputs. The second output can be phase shifted –90, 0, 90, or 180 degrees from the first output,
or the dual-pulse output can be set to quadrature mode
7.3Environmental limits
Environmental specificationsTable 7-5:
TypeValue
Ambient temperature limits
(Operating)
Ambient temperature limits
(Storage)
Humidity limits5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Process
Management family of companies. All other marks are property of
their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.