MicroMod Automation & Controls is dedicated to improving customer efficiency by providing the most cost-effective, application-specific
process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design
and implementation.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivaled service and support.
The quality, accuracy and performance of the Company's products result from over 100 years experience, combined with a continuous
program of innovative design and development to incorporate the latest technology.
Use of Instructions
Warning. An instruction that draws attention to the risk of
injury or death.
Note. Clarification of an instruction or additional information.
! Caution. An instruction that draws attention to the risk of
the product, process or surroundings.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it
must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system
performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any
other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of MicroMod
Automation & Controls, Inc.
Licensing, Trademarks and Copyrights
MOD 30 and MOD 30ML are trademarks of MicroMod Automation & Controls, Inc.
MODBUS is a trademark of Modicon Inc.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
The relevant sections of these instructions must be read carefully before proceeding.
1. Warning Labels on containers and packages must be observed.
2. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the
information given or injury or death could result.
3. Normal safety procedures must be taken to avoid the possibility of an accident occurring when operating in conditions of high
pressure and/or temperature.
4. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling
procedures must be used.
5. When disposing of chemicals, ensure that no two chemicals are mixed.
SAFETY ADVICE CONCERNING THE USE OF THE EQUIPMENT DESCRIBED IN THIS MANUAL MAY BE OBTAINED FROM THE
COMPANY ADDRESS ON THE BACK COVER, TOGETHER WITH SERVICING AND SPARES INFORMATION.
i Information. Further reference for more detailed information
or technical details.
3 FRONT PANEL ......................................................................................................................................... 15
12.4ERROR AND HARDWARE MALFUNCTION MESSAGES ................................................................................ 84
12.5RESETTING THE INSTRUMENT................................................................................................................. 84
12.6PARTS LIST ........................................................................................................................................... 86
All software, including design, appearances, algorithms and source code is copyrighted by MicroMod
Automation & Controls, Inc. and is owned by MicroMod or its suppliers.
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
1 INTRODUCTION
1.1 Product Overview
The 53SL5100 Controller is capable of functioning as any one of four selectable application-specific
instruments. The instrument application is selected with the front panel push buttons by entering the
appropriate number (1 through 4 respectively) into a designated database location. The four instrument
selections are:
1. Single Loop (PID) Controller - a PID controller that fulfills the requirements of a majority of process
applications. It is used with other devices in a standard feedback control loop to automatically control
a process variable (PV) at a predetermined setpoint (SP). The proportional, integral, and derivative
(PID) terms can be activated as needed.
2. Analog Backup Controller - for operations requiring computer backup. It is used where a remote
computer is normally controlling the final element directly. In this configuration, the controller acts as a
control signal selector and as an automatic backup to the computer. The controller continually adjusts
its output to match the feedback signal from the final element so that transfer to on-line operation is
bumpless.
3. Ratio (PID) Controller - for applications where one variable must automatically be maintained in
definite proportion to another variable. The PID algorithm is executed to maintain a controlled line at a
predetermined proportion to the uncontrolled or wild line.
4. Automatic/Manual Station - for installations requiring a single station automatic/manual selector. In
Auto, the Auto input is passed directly through the station to the output. In Manual, the station acts as
a manual loader for direct operator control of the process.
Each of the four instrument selections has its own unique display of process attributes (e.g., process variable,
output, etc.) as well as a supplemental parameter display that is invoked by pressing a front panel push
button. The parameter display provides quick access to view and/or alter three values such as % Proportional
Band, Reset (integral action), and Rate (derivative action). The instrument is configured at the factory to
display these three values, but the parameter display selections can be altered.
1
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
1.2 Specifications
Item Specification(s)
Power
Range (as specified in model number) 22 - 26 V dc
Power Consumption (ac/dc operation) 36 VA maximum
Internal Power Supply:
Available Power Output for Transmitters
Output Ripple 200 mV p-p maximum
Analog Input (ANI0, ANI1) Signals (all analog in-puts are referenced to signal common)
Quantity 4 (ANI0, ANI1)
Signal Range 0 -5 V dc or 1 -5 V dc (0 -20 mA and 4 -20 mA dc respectively).
Input Impedance 1 megohm minimum for voltage inputs; value of ranging resistor for
Measurement Accuracy ± 0.1% of span
Contact Input CCI0 Signal (referenced to power common)
Quantity 1 (CCI0)
Type discrete input
Permitted Contact Resistance 100 ohm maximum
Open/Close Contact Duration for open recognition: 0.05 seconds minimum
Contact Recognition Level Closed
Contact Recognition Level Open 4 V dc to 24 V dc
Analog Output (ANO0) Signal (referenced to power common)
Quantity 1 (ANO0)
Signal Range 0 -20 mA dc (4 -20 mA dc typically)
Load Range 0 - 750 ohms
Accuracy ± 0.2% of span
Switch Output (CCO0) Signal (referenced to power common)
Quantity 1 (CCO0)
Type
Configuration solid state equivalent of a single pole single throw, normally open or
Voltage 30 V dc maximum
Current 50 mA dc maximum
Datalink Communication
Sampling and Update Attributes
Program Scan Rate 0.05 seconds
Analog Input Signal Sampling Rate 0.05 seconds
Contact Input Signal Sampling Rate 0.05 seconds
Display Update 0.10 seconds
Output Signal Update 0.05 seconds
Control Ranges
Proportional Band 2 - 1000% and OFF
Integral 0.02 -200 minutes/repeat or Manual Reset from 0-100%
Derivative 0.01 - 8 minutes and OFF
108 - 132 V rms
216 - 264 V rms
50/60 Hz
25 V dc ± 1 V dc @ 80 mA maximum, short circuit protected.
NOTE: The rear terminal board has the appropriate resistors for
ANI0 and ANI1.
current signals.
for closed recognition: 0.05 seconds minimum
1 V dc maximum
solid state switch output
normally closed contacts referenced to common.
RS485, four wire, asynchronous; baud rates 300 to 28,800
2
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Item Specification(s)
Environmental Characteristics
Controlled Environment Enclosed temperature controlled location (Class A and B per ISA-
Ambient Temperature Limits 4 -52°C (40 - 125°F)
Relative Humidity Limits 10 - 90% maximum
Temperature Effects on Accuracy ± 0.28% per 28°C (50°F) change from reference temperature 25°C
Dimensions 2.844W x 5.656H x 12.906L (inches) 73W x 144H x 329L (mm)
Flush Panel Mounting 0.125 inch - 1 inch thickness (3.2 mm - 25.4 mm)
Electrical Connections Screw type terminal block at rear of casework
Weight 5 lbs (2.3 kg)
Front Panel Display 96 x 48 dot addressable
Front Panel Push Buttons 10 membrane type switches
S71.01 1985)
(77°F)
60 pulses/s for 2.0 s
and 446 MHz
installed in a user provided panel or enclosure.
Rated for installation in a Pollution Degree 2 location per U.L. 5081989/Controlled Environment per CSA C22.2 No. 142-M1987. An
indoor, temperature controlled location (Control Room or Shop Floor)
where normally, only non-conductive pollution occurs; however,
temporary conductivity caused by condensation may be expected.
Location in environments more severe than those stated requires
supplementary protection
(1.27 mm), 5 -14 Hz: 0.5 g, 14 - 200 Hz.
to a hard surface, all sides, front and back.
Standard for Electrical and Electronic Test Measuring, Controlling and
Related Equipment; General Requirements and S82.03-1988 Safety
Standard for Electrical and Electronic Test, Measuring, Controlling and
Related Equipment; Electrical and Electronic Process Measurement
and Control Equipment.
FM Approved: Nonincendive for Class 1, Division 2, Groups A, B, C, &
D, Temperature Code T3C 160 ° C.
3
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
4
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
2 INSTALLATION
2.1 Inspection
A list of all items in the shipment is attached to the shipping container. Inspect the equipment upon arrival for
damage that may have occurred during shipment. All damage claims should be reported to the responsible
shipping agent before installation is attempted. If damage is such that faulty operation is likely to result, the
MicroMod Customer Service Department should be notified.
Inspect the packing material before discarding it as a precaution to prevent loosing mounting hardware or
special instructions that may have been included with the shipment. Normal care in the handling and
installation of this equipment will contribute toward its satisfactory performance.
2.2 Location
The 53SL5100 is supplied with an enclosure designed specifically for indoor mounting. The installation site
selected should be dry, well lighted, and vibration free. The ambient temperature should be stable and
maintained within the specified minimum and maximum temperature limits listed in the Section 1,
specifications of this Instruction Bulletin.
The instrument can be supplied for use with a 24 V dc supply or 120, 220 and 240 V ac line service.
Instrument power requirements are given on the instrument data tag.
2.3 Mounting
2.3.1 General
It is normally not necessary to open the instrument case during installation. If the instrument must be removed
from the case, refer to Section 5 for details. Incorrect procedures may damage the instrument.
The instrument can be flush panel mounted, either as a single unit or side by side. Appropriate mounting
hardware is supplied. Outline dimensions and panel cut-out requirements for case mounting are shown in
Figure 2-1.
The dimensions given for spacing between instruments were selected on the basis of 1/8" thick panel
strength. Panel strength must be considered when multiple case mounting is required. As the panel cut-out
becomes longer it may be necessary to install supporting members. Because the panel area between
instrument rows becomes weaker as the cut-out becomes longer to the point where the panel offers very little
support. It is recommended that the 9 inch minimum center line dimension between horizontally mounted
rows be increased as the number of units increases, or that the panel strip be stiffened.
The rear of the instrument case must be supported to prevent panel distortion. Mount an angle iron or similar
member along the bottom of the cases as indicated in Figure 2-2. If the panel is to be moved the instrument
cases must be tied down to prevent damage.
If multiple mounted instruments are installed in a panel that tilts back, it may be necessary to support the
instruments so the panel does not sag. The downward weight should be supported by additional panel
supports and/or by increasing panel thickness.
5
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
2.3.2 Mounting Procedure
For single and multiple case mounting the instruments are furnished with a trim collar (mounting frame).
Figure 2-2 illustrates the installation and use of the trim collar (mounting frame). Trim collars (mounting
frames) are available in various sizes and are supplied to conform with the particular panel cut-out.
NOTE: Mounting brackets and trim collars (mounting frames) are packaged separately. Check the
shipment carefully to prevent loss of mounting hardware.
To install single or multiple mounted instruments in a prepared panel cut-out, proceed as follows:
1. Remove the through-case shipping bolt.
2. Slip the trim collar (mounting frame) over the rear of the case and slide it forward to the front of the
case.
3. Slide the instrument case through the panel opening.
a. Single mounting case - support the weight of the case and attach the top and bottom
mounting brackets. Tighten the bracket screws.
b. Multiple mounted cases - spacer bars and self-adhesive pads must be used between the
cases, as shown in Figure 2-3. Start the installation from the right (when facing the panel),
installing the spacers as each case is added. Also, as each case is positioned in place, install
and tighten the top and bottom mounting brackets. Each case must be tight against the
previous case.
NOTE: Spacers are not required on the outside of the right and left cases.
6
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
NOTES:
1. DIMENSIONS ARE IN INCHES. DIMENSIONS IN BRACKETS (
) ARE IN MILLIMIETERS.
2. DIMENSIONS GUARANTEED ON CERTIFIED PRINTS ONLY.
3. CASE MOUNTING HARDWARE SUPPLIED UNLESS
OTHERWISE SPECIFIED.
4. THIS DRAWING IS THIRD-ANGLE PROJECTION AS SHOWN
5. UNLESS OTHERWISE INDICATED ALL TOLERANCES ARE ±
1/16 (1.6)
PREPARATORY: The 53SL5100 can be configured for one to four analog inputs (ANI0-3), one analog output
(ANO0), two control contact inputs (CCI0 and 1), two control contact outputs (CCO0 and 1) and Datalink
network interconnectivity. Therefore, prior to making electrical connections, the particular instrument
configuration should be determined with all assigned inputs and outputs identified to assure proper signal
routing.
Provisions for electrical interconnections are located at the rear of the instrument case. Under ideal conditions
shielded cable may not be required. In noisy locations all system input, output and power wiring should be
enclosed in electrical conduit. System interconnection cables (except for power cables) should be fabricated
from 2-wire shielded signal cable. Signal transmission distance should not exceed the limit specified for the
particular transmitter (refer to applicable technical literature provided for the respective device). Polarity must
be observed when connecting the remote transmitters to the instrument.
The instrument has a vertically mounted terminal strip (TB1) for signal interconnections and a horizontally
mounted terminal strip (TB2) for power wiring. Both terminal strips are located at the rear terminal board of
the instrument case.
SNAP-OUT TERMINAL CONNECTORS
Both terminal strips, TB1 and TB2, have removable plug-in connectors. The upper connector for TB1 has
screw lugs 1 through 12 and the lower connector has screw lugs 13 through 22. All of the screw lugs are on a
single connector for TB2. To remove a signal connector, grasp it securely on both sides with the thumb and
forefinger, rock it gently from top to bottom (not side to side) and pull it straight out. To remove the power
connector, grasp the sides firmly with the thumb and forefinger, rock it gently from side to side and pull
straight out.
NOTE: The screw lugs on the back of the instrument are designed for 12 – 24 AWG wire. It is
important that the wire be stripped to expose 1/2 inch of conductor before installation.
WARNING! Instruments that are powered from an ac line service constitute a potential
electric shock hazard to the user. Make certain that these system ac power lines are
disconnected from the operating branch circuit before attempting electrical interconnections.
9
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
10
Figure 2-4. Controller Rear Power and Signal Terminal Boards
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Figure 2-5. Datalink Installation Diagram
11
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
2.4.1 Power Wiring
Refer to the instrument model number to verify the power input requirements:
53SL511…. – AC Power
53SL512…. – DC Power
2.4.1.1 DC Power
Reference Figure 2-4 and connect the remote 24 V dc power supply to the instrument as follows:
1.
Connect (+) input line, via remote SPST switch, to terminal L1.
2. Connect (-) input line to the system bus bar. The bus bar should be connected to a good earth ground
(#8 AWG wire is recommended). Individual wires should be run from the controller Power Common
(PC ) and Signal Common (SC ) terminals to the bus bar. The chassis should be grounded by
connecting terminal G to earth ground.
NOTE: Use of a common bus bar is recommended to minimize potential
voltage differences that may occur as the result of ground current loops, e.g.,
potential difference between separate signal grounds, power grounds, etc.
2.4.1.2 AC Power
Reference Figure 2-4 and connect the specified line service (110-120, 220-240 V ac, 50 or 60 Hz) to the
trument as follows:
ins
1. Connect the phase or hot line L, via a remote power disconnect switch or circuit breaker, to terminal
L1.
2. Connect the neutral line N to terminal L2 for 110-120 V ac. Connect the neutral line N to terminal L3
for 220-240 V ac.
3. Connect Power Common to a good earth ground (#12 AWG wire is recommended). The instrument
case should be grounded by connecting terminal G to earth ground at the source of supply
(green/green-yellow ground).
All supply connections include surge protection rated at 275 V ac normal mode.
NOTE: To minimize possible interference, ac power wiring should be routed away from signal
wiring.
2.4.2 Field Signal Wiring
2.4.2.1 Current/Voltage Input to AIN0 and AIN1
When the input signal is from a 4-20 mA current transmitter, a precision 250 ohms (+/-0.1%) resistor is
required. (The resistor tolerance is critical, as the resistor is used to accurately convert the current signal from
the transmitter, which is typically 4-20 mA, to a specified analog input voltage of 1 to 5 V dc). The back of the
rear terminal board has the appropriate resistors (R1 and R2, respectively) for ANI0 and ANI1.
2.4.2.2 Contact Input to CCI0
Separate contact input signals to CCI0 and CCI1 can be used for alarm inputs. One side of each
remote contact must be connected to power common as illustrated in Figure 2-4. Minimum opened
or closed recognition time for a remote contact must be 0.05 seconds.
2.4.2.3 Current Output from ANO0
A current output signal is available for re-transmission of one of the input signals ANI0 through
ANI3. Observe the proper polarity when connecting the output to another instrument.
2.4.2.4 Contact Output CCO0
Discrete contact output CCO0 is identified in Figure 2-4. Each discrete output is a solid state switch with a
rating of 30 V dc, 50 mA maximum. A CCO is referenced to power common. When this contact is connected
to an inductive load, an external arc suppression network is required for contact protection.
12
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
2.4.3 Datalink Communication
Datalink is an interrogator/responder serial interface capable of supporting 32 instruments on a single
network. It uses an RS485 physical interface. The Datalink wiring diagram for this instrument is provided as
Figure 2-5. Complete coverage of the Datalink is provided in Instruction Bulletin 53SU5000.
2.5 Factory Set Calibration
Each unit contains individual factory set entries that calibrate the four analog inputs (ANI0 through ANI3) and
analog output (ANO0). There is a calibration sheet supplied with each instrument that should be retained for
future reference when the installation is completed. Reference Section 5.3 for additional information.
2.6 Grounding
Installations are expected to have access to an independent, high quality, noise-free point of earth reference.
The system should be connected by a dedicated, low resistance (less than one ohm) lead wire directly to the
installation’s point of earth reference. This ground reference is referred to as the Instrumentation Ground. If
an instrumentation ground reference does not exist in the installation, an earth ground electrode should be
established with an independent grounding rod or ground grid mesh.
13
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
14
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
3 FRONT PANEL
The front panel of the instrument contains the display and all push buttons used to change display
presentations and parameters. The front panel has a gas discharge 96 X 48 dot matrix display, a six
pushbutton vertical keypad, and a four pushbutton horizontal keypad. It also has a configuration port DIN
plug, which is concealed behind the identification tag pull-down door. To open this door, press on the lower
front edge. Front panel display information is presented as bar graphs with associated alphanumerics or as
alphanumeric only. (See Figure 3-1.)
Figure 3-1. Front Panel
3.1 Display
The bar graph display is a visual indication of the process events monitored and subsequently altered either
by the instrument or other device. This instrument provides three unique bar graph displays and one
alphanumeric parameter display. Bar graph response dynamics as well as the alphanumerics on all of the
display types are selected when the instrument is configured.
There are four configurable operating modes, called control strategies (CS1-4). The control strategies are:
CS1, Single Loop PID Controller
CS2, Analog Backup Controller
CS3, Ratio Controller
CS4, Automatic/Manual Station
Two of the control strategies, CS1 and CS2, have identical bar graph presentations; that is why there are
three, rather than four, unique bar graph types. Each control strategy (CS1 - CS4) also has a pushbutton
selectable parameter display. Although the contents of the parameter display are selectable configuration
items, the display format is identical for each of the four control strategies.
Any display type can have a portion of its contents overlaid with an ALARM indicator. If the instrument is
manually set to engineering mode, the display can be overlaid with the CONFIGURATION or DISPLAY data
entry line. Alarm indicators warn of variation changes that exceed tolerance limits; the process may require
immediate attention. The engineering mode (EMODE) overlay provides a single entry line for data display and
alteration.
15
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
The three bar graph display types for CS1-4 and the parameter display, with appropriate call outs, are
illustrated in Figure 3-2 through Figure 3-5. Figure 3-6 and Figure 3-7 illustrate displays with alarm and
configuration overlays.
Figure 3-2. CS1, Single Loop PID Controller or CS2, Analog Backup Controller
16
Figure 3-3. CS-3, Ratio Controller
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Figure 3-4. CS4, Automatic/Manual Station
Figure 3-5. CS1 - CS4 Parameter Display
17
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Figure 3-6. Alarm Overlay
18
Figure 3-7. Configure Overlay
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
3.2 Front Panel Pushbuttons
The front panel pushbuttons are used to vary the display presentation, to select instrument operator or
engineering modes, and to select local or remote setpoint levels. In engineering mode, (EMODE) they are
also used to display and/or alter database parameters which are presented as single line datapoints in the
configuration overlay.
Pushbutton operator mode functions differ slightly with each control strategy implemented; however, the
engineering mode pushbutton functions are identical for all four control strategies. General pushbutton
functions are illustrated in Figure 3-8 below and defined in Table 3-1 on the facing page. The summary table
in Figure 3-8 shows the functional differences of the push buttons by control strategy. These differences are
included as part of the push button descriptions provided in each individual control strategy section of the
book.
Figure 3-8. Front Panel Pushbuttons
19
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Pushbutton Title Operator Mode Engineering Mode
Used to select between Remote setpoint control
and Local setpoint control. When in Remote, an
R appears in the lower right of the display. When
in Local, anLappears in the lower right of the
display.
The setpoint indicator increases (rises) when this
pushbutton is pressed and held. Release the
pushbutton when the desired setpoint level is
reached. This pushbutton is for Local operation
only.
The setpoint indicator decreases (falls) when this
push button is pressed and held. Release the
pushbutton when the desired setpoint level is
reached. This pushbutton is for Local operation
only.
This pushbutton is the Auto/ Manual mode
toggle. When toggled to Auto, an A appears
before the R or L (for Remote or Local), in the
lower middle right of the display. When toggled to
Manual, an M appears before the R or L (for
Remote or Local), in the lower right of the
display. Auto indicates the process is under
instrument control. Manual indicates the process
is controlled by the instrument panel pushbuttons
(e.g., output increase and decrease.
The output indicator decreases when this
pushbutton is pressed and held. Release the
pushbutton when the desired output level is
reached. This pushbutton is for Manual operation
only.
The output indicator increases when this
pushbutton is pressed and held. Release the
push button when the desired output level is
reached. This push button is for Manual
operation only.
These two push buttons have similar functions,
but work in reverse of one another. They are the
bar graph - Param display toggles. The two
display types interchange and alternately appear
each time either one of these two pushbuttons is
pressed.
Not used
This pushbutton clears the flashing ALARM message, but the alarm indication remains until the
process variable is restored within tolerable limits past dead band. It is also used to toggle between
Operator and Engineering modes. If no ALARM message is present, pressing this pushbutton will
toggle the instrument between Operator mode and Engineering mode.
Not used
For configure or a display function, the character
set displays one character at a time in ascending
alphanumeric order when this pushbutton is
pressed and held. Release the push button when
the desired character, number, or symbol
appears.
For configure or a display function, the character
set displays one character at a time in descending
alphanumeric order when this pushbutton is
pressed and held. Release the pushbutton when
the desired character, number, or symbol
appears.
Not used
For configure or display functions, the cursor shifts
one position to the left each time this button is
pressed. When pressed and held, characters
continue to shift left one position at a time.
Maximum character length is 10 characters (9
character shifts).
For configure or display functions, the cursor shifts
one position to the right each time this button is
pressed. When pressed and held, characters
continue to shift right one position at a time.
Maximum character length is 10 characters (9
character shifts).
Pushbutton F2 is used to select the configure or
display functions in EMODE. Pressing F2 in
EMODE alternately selects one function or the
other.
In the configuration function, pressing this
pushbutton causes the addressed datapoint to be
altered with the character string that was entered
with the EMODE Cursor Control and Character
Select pushbuttons. In display function, pressing
this pushbutton causes the addressed datapoint to
display its contents.
F1, F2
F3
Remote/
Local
Select
Setpoint
Increase
(EMODE
Character
Select)
Setpoint
Decrease
(EMODE
Character
Select)
Auto/Manual
Select
Output
Decrease
(EMODE
Cursor
Control)
Output
Increase
(EMODE
Cursor
Control)
Page Forward
and Page
Back
(EMODE
ENTER key)
Mode
Select/Alarm
Reset
20
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
3.3 Displaying a Datapoint
The following procedure illustrates how to enter Engineering Mode (EMODE) and use the display function to
access the contents of datapoint A001 (A1). The displayed contents will be PERCENT. Figure 3-9 and Figure
3-10 are supporting illustrations for the display procedure which is described in Table 3-2. It should be noted
that EMODE has a 20 second timeout if it is accessed and its functions (e.g., configure or display) are not
used.
Table 3-2. Procedures to Display a Datapoint
Step Press
Once
1
MODE
2
3
F3
4
Shift
Result
Press to
Locate
If CONFIGURE appears instead of DISPLAY, press F2.
Target
Char.
A
Result
Puts instrument in engineering mode.
Displays entry line: POINT .
Puts A on entry line: POINT .A.
5
6
7
NOTE:
F3
MODE
Δ = space.
.AΔ
1
Shifts A and puts 1 on entry line: POINT .A1.
Enters address to display datapoint contents.
The address and the contents are displayed as
follows: A1 PERCENT.
Returns instrument to operator mode.
Figure 3-9. POINT.A1 Figure 3-10. A1 PERCENT
21
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
3.4 Altering a Datapoint
The following procedure illustrates how to enter EMODE and use the configuration function to alter the
contents of datapoint B000 (B0) with a 97. Entering a 97 in B00 invokes the display test which strobes the
display matrix dots on and off at 5 second intervals (approximate). When off, a perimeter of dots still remains
lit. Figures 3-11 and 3-12 are display test illustrations that support the procedure provided in Table 3-3. It
should be noted that EMODE has a 20 second timeout if it is accessed and its functions (e.g., configure or
display) are not used.
Table 3-3. Procedures to Display a Datapoint
Step Press
Once
1
MODE
2
3
F3
4
Shift
Result
Press to
Locate
If CONFIGURE appears instead of DISPLAY, press F2.
Target
Char.
B
Result
Puts instrument in engineering mode.
Displays entry line: POINT .
(If the prompt KEY? appears, see Table 3-5.)
Puts B on entry line: POINT .B.
5
6
7
8
9
F3
Hold
.BΔ
0
Shifts B and puts 0 on entry line: POINT .B0.
.B0Δ
0
Shifts B0 and puts 0 on entry line: POINT .B00.
.
locator
9
Displays contents of B00 (0).
B00 contents shifted right; only locator point
remains on the entry line: B00 .
Puts 9 on entry line: B00 .9.
10
11
12
13
NOTE:
22
F3
MODE
Δ = space.
.9Δ
To stop test, change B00 contents from 97 to 00 (Instrument Suspend State).
Defaulting the database sets all non-instrument-specific datapoint parameters to predetermined values, then
suspends the instrument which is indicated by the logo presented on the display. When instrument operation
is suspended, instrument algorithmic control ceases.
The procedure to default the database is presented in Table 3-4 and the display logo is illustrated in Figure 3-
13. Entering a 98 in datapoint B00 defaults the database. If it is desired to suspend instrument operation
without defaulting the database, enter a 00 in lieu of a 98 into B00. The defaulted database values are
provided in the configuration tables of Section 4 and the database tables in Appendix C, Database, under the
column headed Default. Those parameter values that are left unaltered when the database is defaulted are
identified with gray-tone shading in the Default column of the tables. It should be noted that EMODE has a 20
second timeout if it is accessed and its functions (e.g., configure or display) are not used.
Figure 3-13. Display Logo
23
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Table 3-4. Defaulting the Database
Step Press
Once
1
MODE
2
3
F3
4
Shift
Result
Press to
Locate
If DISPLAY appears instead of CONFIGURE press F2.
Target
Char.
B
5
6
7
8
9
F3
Hold
.BΔ
0
.B0Δ
0
.
locator
9
Result
Puts instrument in engineering mode.
Displays entry line: POINT .
(If the prompt KEY? appears, see Table 3-5.)
Puts B on entry line: POINT .B.
Shifts B and puts 0 on entry line: POINT .B0.
Shifts B0 and puts 0 on entry line: POINT .B00.
Displays contents of B00 (0).
B00 contents shifted right; only locator point
remains on the entry line: B00 .
Puts 9 on entry line: B00 .9.
10
11
12
NOTE:
F3
MODE
Δ = space.
.9Δ
8
Shifts 9 and puts 7 on entry line: B00 .98.
Enters 97 in B00 to default the database.
Returns instrument to operator mode.
24
Loading...
+ 85 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.