MicroMod Automation & Controls is dedicated to improving customer efficiency by providing the most cost-effective, application-specific
process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design
and implementation.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivaled service and support.
The quality, accuracy and performance of the Company's products result from over 100 years experience, combined with a continuous
program of innovative design and development to incorporate the latest technology.
Use of Instructions
Warning. An instruction that draws attention to the risk of
injury or death.
Note. Clarification of an instruction or additional information.
Caution. An instruction that draws attention to the risk of
the product, process or surroundings.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it
must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system
performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any
other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of MicroMod
Automation & Controls, Inc.
Licensing, Trademarks and Copyrights
MOD 30 and MOD 30ML are trademarks of MicroMod Automation & Controls, Inc.
MODBUS is a trademark of Modicon Inc.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
The relevant sections of these instructions must be read carefully before proceeding.
1. Warning Labels on containers and packages must be observed.
2. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the
information given or injury or death could result.
3. Normal safety procedures must be taken to avoid the possibility of an accident occurring when operating in conditions of high
pressure and/or temperature.
4. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling
procedures must be used.
5. When disposing of chemicals, ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual may be obtained from the Company address on the back
cover, together with servicing and spares information.
i Information. Further reference for more detailed information
or technical details.
5.4ERROR AND HARDWARE MALFUNCTION MESSAGES ................................................................................ 44
5.5RESETTING THE INSTRUMENT ................................................................................................................ 44
5.6PARTS LIST .......................................................................................................................................... 45
All software, including design, appearances, algorithms and source code is copyrighted by MicroMod
Automation & Controls, Inc. and is owned by MicroMod or its suppliers.
Page 5
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
1 INTRODUCTION
1.1 Product Overview
The 53IT5100B provides a suite of six operator displays to monitor process activity for up to four independent
process variables and also provides integration and totalization for each of the four process variables. The
displays are of three types: dynamic bar graph, digital readout, and alarm summary. There are three bar
graph displays, two digital readout displays, and one alarm summary display. These include:
Quad Bar Graph Display (Channels 1-4)
Two Dual Bar Graph Displays (Channels 1&2 and Channels 3&4)
Quad Process Digital Readout Display
Quad Totalizer Digital Readout Display
Alarm Summary Display.
The operator displays are paged forward or back, in the order given, by pressing the F2 (page forward) or the
F1 (page back) push button on the horizontal keypad of the instrument. The operator display suite is
illustrated in Figure 1-1 and the instrument horizontal keypad is identified in Figure 1-2.
Quad Bar Graph Display (Channels 1-4) - all four channels are arrayed across the display as bar graphs
with the digital readout and measured units of a selected bar graph in the lower quadrant of the display. A bar
graph digital readout with measured units is selected with the F3 push button, which moves a pointer to the
base of each bar graph in the display every time it is pressed. In the illustration, upper and lower alarm limits
appear with each 50 segment vertical axis. The measured units and alarm limits are selectable entries, as
well as the mode of alarm reporting (e.g., High/Low, High only, Low only, High/Hi-Hi, Low/Lo-Lo, or none).
Dual Bar Graph Display (Channels 1&2) - two channels are arrayed across the display as bar graphs with
the digital readout and measured units of each channel appearing beneath its bar graph. The channel tag
names appear in the upper quadrant of the display. Each 50 segment vertical axis has a numeric range and
alarm limits. The tag names, vertical axis numeric range (zero and span), measured units, alarm limits, and
alarm mode are all selectable entries.
Dual Bar Graph Display (Channels 3&4) - is identical to Dual Bar Graph Display (Channels 1&2) except it
displays process activity from channels 3 and 4.
Quad Process Digital Readout Display - is a process activity digital readout of all four channels
that is refreshed every second. The display is divided vertically into four quadrants, each one dedicated to a
channel. Each channel readout has a tag name, numeric value, and measured units field. The tag names and
measured units are identical to those selected for the bar graph displays.
Quad Totalizer Digital Readout Display - is an integrator accumulator digital readout of each of the four
channels that is refreshed every second. The display is divided vertically into four sections, each one
dedicated to a channel. Each channel totalizer has a tag name, accumulated value, and totalizer measured
units field. The tag names and measured units are selectable entries.
Alarm Summary Display - presents six alarm states relevant to the four input channels and two contact
inputs. The display has four partitions with the uppermost containing the display title. The word ALARM in the
title flashes should an alarm condition occur with any one of the channel inputs or if a contact input is
activated indicating an alarm. The specific channel or contact input in the alarm state is also differentiated
from the rest of the display coincident with the ALARM banner flashing in the title of the display. The four
channel inputs are listed together in the second partition, and partitions three and four are occupied by the
two contact inputs. All six tag names for this display are selectable entries. There are also selectable entries
that define how each contact input display message is differentiated from the others to indicate an alarm
state.
As shown in Figure 1-2, the 53IT5100 contains a graphical dot matrix display; horizontal and vertical keypads;
a MINI-DIN configuration port connector concealed behind the front panel pull-down door; terminals for signal
1
Page 6
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
input/output wiring and power wiring; and a compact instrument case that protects the instrument main
printed circuit board and internal power supply.
The display is a 96 X 48 gas discharge dot matrix, contrasted orange-on-black to enhance visibility and ease
of reading. The intensity is a range selectable entry from 0 to 7, with 0 being the brightest setting (see Table
4-10).
To the right of the display is the vertical keypad and directly beneath the display is the horizontal keypad.
Both keypads have functioning push buttons that are dependent on the instrument mode of operation which
can be either operator mode or engineering mode. Mode selection is made with the M
the horizontal keypad. Engineering mode is entered to make the necessary selections for the operator
displays and Datalink communications port; otherwise, the instrument is left in operator mode for process
applications. The vertical keypad is dedicated only to engineering mode functions and has no effect in
operator mode. Both keypads are described as follows:
Horizontal Keypad
ode push button on
Push Button Title Operator Mode Engineering Mode
F1
F2
F3
Title Engineering Mode
Ascending
Character umber, or symbol appears on
Select
Descending
Page back to previous display. Back to previous entry line function.
Page forward to next display. Pages the configure/display functions.
ter or display function. Moves Quad Bargraph pointer. Executes an en
Vertical Keypad
Displays one character at a time in ascending alphanumeric order; is
released when the desired character, n
the engineering mode data entry line.
Displays one character at a time in descending alphanumeric order; is
released when the desired character, n
the engineering mode data entry line.
data entry line each time this push button is pressed.
Shifts characters on engineering mode data entry line
position right each time this push button is pressed.
umber, or symbol appears on Charact
ering mode Shifts selected character one position left on the engine
one character
2
Page 7
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Quad Bar Graph (Chs. 1-4) Dual Bar Graph (Chs. 1&2) Dual Bar Graph (Chs. 3&4)
Quad Process Digital Readout Quad Totalizer Digital Readout Alarm Summary
Setup of the 53IT5100B can be done using the buttons on the horizontal and vertical keypads. It can also be
done via the MicroTools configuration software package, Directly beneath the horizontal keypad and
concealed behind the front panel pull-down door is the RS-232 Configuration Port which accept the
configuration cable that provides interface between the instrument and MicroTools running on a personal
computer. The configuration functions within MicroTools are limited to loaded functions of the 53IT5100B
indicator/totalizer described in this manual.
The internal power supply provides power to the main board and output power for transmitters (24-26 V dc,
80 mA total available output for instrument and transmitters).
A simplified input/output diagram of the Indicator/Totalizer is provided in the upper left corner of
Figure 1-2. As illustrated in the figure, the instrument can accept four Analog Inputs (ANI0-3) which are
digitized as operands for firmware interpretation and execution (totalization). Each ANI has a square root
extractor and can accept linear or squared signals of 0-20 mA, 0-5 V, 4-20 mA, or 1-5 V. Any one of the four
analog inputs can be selected as the Analog Output (ANO0).
There are two contact inputs (CCI0 and CCI1 ) that have a closed recognition level of 1 V dc and open
recognition level of 4-24 V dc. Each CCI indicates an alarm state, for example, a CCI can have a closed
recognition level when a secondary pump is activated to support the primary pump in maintaining a proper
tank level.
The totalizers provide a running total of each ANI input. The totalizers are incremented in ascending order
every 0.05 seconds, but all four totalizers are refreshed on the display every second. Each ANI value can be
independently adjusted by a scaling factor before being summed to the running total. The totalizer measured
units, therefore, can differ from the process activity measured units as determined by the scaling factor
entries for each channel. Also available as selectable totalizer entries are rollover and dropout values. The
rollover value specifies a maximum positive value that causes the totalizer accumulator to reset to zero when
the actual total reaches this value. An output pulse is strobed to a 1 for one scan each time the actual total
reaches the rollover value. The dropout value specifies a minimum input value required to increment the
running total.
All of the selectable entries for the Indicator/Totalizer are parameter entries to the database. The database is
subdivided into modules composed of datapoints that are accessed by the instruction code as the instrument
performs its functions. The database allows instrument functionality to be refined to specific process
applications, as display attributes can be altered, input signal characteristics can be defined, each totalizer
accumulated value can be flagged, and the instrument can be configured to properly match Datalink network
communications requirements. A datapoint location is represented as an alphanumeric address, such as
C103, which is the location to enter the value for the ANI0 upper alarm limit that is displayed on the Quad Bar
Graph or Dual Bar Graph (Channels 1&2) displays. Datapoints are specified parenthetically in the illustration
call-outs of Section 3 where the displays are described in detail. There are also illustrated procedures
provided in Section 3 that show how a datapoint is displayed and configured. Definitions for all of the
Indicator/Totalizer datapoints are provided in Section 4 and listed in alphanumeric order in Appendix C.
External alarm buzzers can be activated with the contact outputs (CCO0 and CCO1). Capability limits of each
CCO are 50 mA maximum current flow when closed and 30 V dc maximum tolerance voltage when open.
Flagged conditions, such as Totalizer 0 (ANI0) rollover pulse activation, can be specified as selectable entries
in the CCO module of the database. Specific details for CCO database selections are described in Table 4-6
of Section 4, and typical circuit layouts for the CCOs are described in Appendix A.
Datalink is another independent serial communications connection for the Indicator/Totalizer. It provides a
permanent connection to an RS-485 multi-drop network through which a host computer can access the
instrument. The Datalink connection is made at TB1 of the rear terminal board, screw lugs 19 through 22.
5
Page 10
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
1.2 Model Number Breakdown
53IT51 __ __ B 2 1 A A A
Base Instrument
Power Requirements
AC (120/240V)
DC (24V)
Functional Requirements
Standard
Standard with Factory Configuration
Design Level
Enclosure Type
DIN 72 x 144 mm bezel
Main Rear Terminal Requirement
Standard
Chassis
Standard
Safety Classification
General Purpose
Conformal Coating
Standard
6
Page 11
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
1.3 Specifications
Item Specification(s)
Power
Range (as specified in model number) 22 - 26 V dc
Power Consumption (ac/dc operation) 36 VA maximum
Internal Power Supply:
Available Power Output for Transmitters
Output Ripple 200 mV p-p maximum
Analog Input (ANI0-3) Signals (all analog in-puts are referenced to signal common)
Quantity 4 (ANI0, ANI1, ANI2, and ANI3)
Signal Range 0 -5 V dc or 1 -5 V dc (0 -20 mA and 4 -20 mA dc respectively).
Input Impedance 1 megohm minimum for voltage inputs; value of ranging resistor
Measurement Accuracy ± 0.1% of span
Contact Input CCI0/1 Signals (are referenced to power common)
Quantity 2 (CCI0 and CCI1)
Type discrete input
Permitted Contact Resistance 100 ohm maximum
Open/Close Contact Duration for open recognition: 0.05 seconds minimum
Contact Recognition Level Closed
Contact Recognition Level Open 4 V dc to 24 V dc
Analog Output (ANO0) Signal (is referenced to power common)
Quantity 1 (ANO0)
Signal Range 0 -20 mA dc (4 -20 mA dc typically)
Load Range 0 - 750 ohms
Accuracy ± 0.2% of span
Switch Output (CCO0, CCO1) Signals (are referenced to power common)
Quantity 2 (CCO0 and CCO1)
Type
Configuration solid state equivalent of a single pole single throw, normally
Voltage 30 V dc maximum
Current 50 mA dc maximum
Datalink Communication
Sampling and Update Attributes
Program Scan Rate 0.05 seconds
Analog Input Signal Sampling Rate 0.05 seconds
Contact Input Signal Sampling Rate 0.05 seconds
Display Update 0.10 seconds
Output Signal Update 0.05 seconds
108 - 132 V rms
216 - 264 V rms
50/60 Hz
25 V dc ± 1 V dc @ 80 mA maximum, short circuit protected.
NOTE: The rear terminal board has the appropriate resistors
for ANI0 and ANI1.
for current signals.
for closed recognition: 0.05 seconds minimum
1 V dc maximum
solid state switch output
open or normally closed contacts referenced to common.
RS485, four wire, asynchronous; baud rates 300 to 28,800
7
Page 12
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Item Specification(s)
Environmental Characteristics
Controlled Environment Enclosed temperature controlled location (Class A and B per ISA-S71.01
Ambient Temperature Limits 4 -52°C (40 - 125°F)
Relative Humidity Limits 10 - 90% maximum
Temperature Effects on Accuracy ± 0.28% per 28°C (50°F) change from reference temperature 25°C (77°F)
EMI Susceptibility SAMA PMC 33.1-1978: Class 3-abc: no effect at 30 V/m, at 27, 146, and
Enclosure Classification/Environment Panel Mounted Equipment: No enclosure rating. Designed to be installed
Shock 0.5g
Vibration SAMA PMC 31.1-1978; point-to-point constant displacement 0.05 in. (1.27
Drop and Topple SAMA PMC 31.1-1978; Tilt 30 degrees from horizontal and fall freely to a
Safety Classification General Purpose: Complies with ANSI/ISA S82.01-1988, Safety Standard
Physical Characteristics
Material of Construction:
1985)
pulses/s for 2.0 s
446 MHz
in a user provided panel or enclosure.
Rated for installation in a Pollution Degree 2 location per U.L. 5081989/Controlled Environment per CSA C22.2 No. 142-M1987. An indoor,
temperature controlled location (Control Room or Shop Floor) where
normally, only non-conductive pollution occurs; however, temporary
conductivity caused by condensation may be expected.
Location in environments more severe than those stated requires
supplementary protection
mm), 5 -14 Hz: 0.5 g, 14 - 200 Hz.
hard surface, all sides, front and back.
for Electrical and Electronic Test Measuring, Controlling and Related
Equipment; General Requirements and S82.03-1988 Safety Standard for
Electrical and Electronic Test, Measuring, Controlling and Related
Equipment; Electrical and Electronic Process Measurement and Control
Equipment.
FM Approved: Nonincendive for Class 1, Division 2, Groups A, B, C, & D,
Temperature Code T3C 160 ° C.
Dimensions 2.844W x 5.656H x 12.906L (inches) 73W x 144H x 329L (mm)
Flush Panel Mounting 0.125 inch - 1 inch thickness (3.2 mm - 25.4 mm)
Electrical Connections Screw type terminal block at rear of casework
Weight 5 lbs (2.3 kg)
Front Panel Display 96 x 48 dot addressable
Front Panel Push Buttons 10 membrane type switches
8
Page 13
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
2 INSTALLATION
2.1 Inspection
A list of all items in the shipment is attached to the shipping container. Inspect the equipment upon arrival for
damage that may have occurred during shipment. All damage claims should be reported to the responsible
shipping agent before installation is attempted. If damage is such that faulty operation is likely to result, the
MicroMod Customer Service Department should be notified.
Inspect the packing material before discarding it as a precaution to prevent loosing mounting hardware or
special instructions that may have been included with the shipment. Normal care in the handling and
installation of this equipment will contribute toward its satisfactory performance.
2.2 Location
The 53IT5100 is supplied with an enclosure designed specifically for indoor mounting. The installation site
selected should be dry, well lighted, and vibration free. The ambient temperature should be stable and
maintained within the specified minimum and maximum temperature limits listed in the Section 1,
specifications of this Instruction Bulletin.
The instrument can be supplied for use with a 24 V dc supply or 120, 220 and 240 V ac line service.
Instrument power requirements are given on the instrument data tag.
2.3 Mounting
2.3.1 General
It is normally not necessary to open the instrument case during installation. If the instrument must be removed
from the case, refer to Section 5 for details. Incorrect procedures may damage the instrument.
The instrument can be flush panel mounted, either as a single unit or side by side. Appropriate mounting
hardware is supplied. Outline dimensions and panel cut-out requirements for case mounting are shown in
Figure 2-1.
The dimensions given for spacing between instruments were selected on the basis of 1/8" thick panel
strength. Panel strength must be considered when multiple case mounting is required. As the panel cut-out
becomes longer it may be necessary to install supporting members. Because the panel area between
instrument rows becomes weaker as the cut-out becomes longer to the point where the panel offers very little
support. It is recommended that the 9 inch minimum center line dimension between horizontally mounted
rows be increased as the number of units increases, or that the panel strip be stiffened.
The rear of the instrument case must be supported to prevent panel distortion. Mount an angle iron or similar
member along the bottom of the cases as indicated in Figure 2-2. If the panel is to be moved the instrument
cases must be tied down to prevent damage.
If multiple mounted instruments are installed in a panel that tilts back, it may be necessary to support the
instruments so the panel does not sag. The downward weight should be supported by additional panel
supports and/or by increasing panel thickness.
9
Page 14
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
2.3.2 Mounting Procedure
For single and multiple case mounting the instruments are furnished with a trim collar (mounting frame).
Figure 2-2 illustrates the installation and use of the trim collar (mounting frame). Trim collars (mounting
frames) are available in various sizes and are supplied to conform with the particular panel cut-out.
NOTE: Mounting brackets and trim collars (mounting frames) are packaged separately. Check the
shipment carefully to prevent loss of mounting hardware.
To install single or multiple mounted instruments in a prepared panel cut-out, proceed as follows:
1. Remove the through-case shipping bolt.
2. Slip the trim collar (mounting frame) over the rear of the case and slide it forward to the front of the
case.
3. Slide the instrument case through the panel opening.
a. Single mounting case - support the weight of the case and attach the top and bottom
mounting brackets. Tighten the bracket screws.
b. Multiple mounted cases - spacer bars and self-adhesive pads must be used between the
cases, as shown in Figure 2-3. Start the installation from the right (when facing the panel),
installing the spacers as each case is added. Also, as each case is positioned in place, install
and tighten the top and bottom mounting brackets. Each case must be tight against the
previous case.
NOTE: Spacers are not required on the outside of the right and left cases.
10
Page 15
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
NOTES:
1. DIMENSIONS ARE IN INCHES. DIMENSIONS IN BRACKETS (
) ARE IN MILLIMIETERS.
2. DIMENSIONS GUARANTEED ON CERTIFIED PRINTS ONLY.
3. CASE MOUNTING HARDWARE SUPPLIED UNLESS
OTHERWISE SPECIFIED.
4. THIS DRAWING IS THIRD-ANGLE PROJECTION AS SHOWN
5. UNLESS OTHERWISE INDICATED ALL TOLERANCES ARE ±
1/16 (1.6)
PREPARATORY: The 53IT5100B can be configured for one to four analog inputs (ANI0-3), one analog
output (ANO0), two control contact inputs (CCI0 and 1), two control contact outputs (CCO0 and 1) and
Datalink network interconnectivity. Therefore, prior to making electrical connections, the particular instrument
configuration should be determined with all assigned inputs and outputs identified to assure proper signal
routing.
Provisions for electrical interconnections are located at the rear of the instrument case. Under ideal conditions
shielded cable may not be required. In noisy locations all system input, output and power wiring should be
enclosed in electrical conduit. System interconnection cables (except for power cables) should be fabricated
from 2-wire shielded signal cable. Signal transmission distance should not exceed the limit specified for the
particular transmitter (refer to applicable technical literature provided for the respective device). Polarity must
be observed when connecting the remote transmitters to the instrument.
The instrument has a vertically mounted terminal strip (TB1) for signal interconnections and a horizontally
mounted terminal strip (TB2) for power wiring. Both terminal strips are located at the rear terminal board of
the instrument case.
SNAP-OUT TERMINAL CONNECTORS
Both terminal strips, TB1 and TB2, have removable plug-in connectors. The upper connector for TB1 has
screw lugs 1 through 12 and the lower connector has screw lugs 13 through 22. All of the screw lugs are on a
single connector for TB2. To remove a signal connector, grasp it securely on both sides with the thumb and
forefinger, rock it gently from top to bottom (not side to side) and pull it straight out. To remove the power
connector, grasp the sides firmly with the thumb and forefinger, rock it gently from side to side and pull
straight out.
NOTE: The screw lugs on the back of the instrument are designed for 12 – 24 AWG wire. It is
important that the wire be stripped to expose 1/2 inch of conductor before installation.
WARNING! Instruments that are powered from an ac line service constitute a potential
electric shock hazard to the user. Make certain that these system ac power lines are
disconnected from the operating branch circuit before attempting electrical interconnections.
13
Page 18
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
14
Figure 2-4. Controller Rear Power and Signal Terminal Boards
Page 19
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 2-54. Datalink Installation Diagram
15
Page 20
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
2.4.1 Power Wiring
Refer to the instrument model number to verify the power input requirements:
53IT511nB21AAA – AC Power
53IT512nB21AAA – DC Power
2.4.1.1 DC Power
Reference Figure 2-4 and connect the remote 24 V dc power supply to the instrument as follows:
1.
Connect (+) input line, via remote SPST switch, to terminal L1.
2. Connect (-) input line to the system bus bar. The bus bar should be connected to a good earth
ground (#8 AWG wire is recommended). Individual wires should be run from the controller Power
Common (PC ) and Signal Common (SC ) terminals to the bus bar. The chassis should be grounded
by connecting terminal G to earth ground.
NOTE: Use of a common bus bar is recommended to minimize potential voltage differences that may
occur as the result of ground current loops, e.g., potential difference between separate signal grounds,
power grounds, etc.
2.4.1.2 AC Power
Reference Figure 2-4 and connect the specified line service (110-120, 220-240 V ac, 50 or 60 Hz) to the
trument as follows:
ins
1. Connect the phase or hot line L, via a remote power disconnect switch or circuit breaker, to terminal
L1.
2. Connect the neutral line N to terminal L2 for 110-120 V ac. Connect the neutral line N to terminal L3
for 220-240 V ac.
3. Connect Power Common to a good earth ground (#12 AWG wire is recommended). The instrument
case should be grounded by connecting terminal G to earth ground at the source of supply
(green/green-yellow ground).
All supply connections include surge protection rated at 275 V ac normal mode.
NOTE: To minimize possible interference, ac power wiring should be routed away from signal wiring.
2.4.2 Field Signal Wiring
2.4.2.1 Current/Voltage Input to AIN1 through AIN3
When the input signal is from a 4-20 mA current transmitter, a precision 250 ohms (+/-0.1%) resistor is
required. (The resistor tolerance is critical, as the resistor is used to accurately convert the current signal from
the transmitter, which is typically 4-20 mA, to a specified analog input voltage of 1 to 5 V dc). The back of the
rear terminal board has the appropriate resistors (R1 and R2, respectively) for ANI0 and ANI1. Resistor for
ANI2 and ANI3 are not supplied and must be installed as shown in the upper left corner of Figure 2-4. If the
input signal is already a voltage signal, its corresponding resistor should be removed.
2.4.2.2 Contact Input to CCI0 and CCI1
Separate contact input signals to CCI0 and CCI1 can be used for alarm inputs. One side of each
remote contact must be connected to power common as illustrated in Figure 2-4. Minimum opened
or closed recognition time for a remote contact must be 0.05 seconds.
2.4.2.3 Current Output from ANO0
A current output signal is available for re-transmission of one of the input signals ANI0 through
ANI3. Observe the proper polarity when connecting the output to another instrument.
2.4.2.4 Contact Outputs CCO0 and CCO1
Discrete contact outputs CCO0 and CCO1 are identified in Figure 2-4. Each discrete output is a
solid state switch with a rating of 30 V dc, 50 mA maximum. A CCO is referenced to power common.
When this contact is connected to an inductive load, an external arc suppression network is required
for contact protection.
16
Page 21
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
2.4.3 Datalink Communication
Datalink is an interrogator/responder serial interface capable of supporting 32 instruments on a single
network. It uses an RS485 physical interface. The Datalink wiring diagram for this instrument
is provided as Figure 2-5. Complete coverage of the Datalink is provided in the SUPERVISOR-PC
Instruction Bulletin 53SU5000.
2.5 Factory Set Calibration
Each unit contains individual factory set entries that calibrate the four analog inputs (ANI0 through ANI3) and
analog output (ANO0). There is a calibration sheet supplied with each instrument that should be retained for
future reference when the installation is completed. Reference Section 5.3 for additional information.
2.6 Grounding
Installations are expected to have access to an independent, high quality, noise-free point of earth reference.
The system should be connected by a dedicated, low resistance (less than one ohm) lead wire directly to the
installation’s point of earth reference. This ground reference is referred to as the Instrumentation Ground. If
an instrumentation ground reference does not exist in the installation, an earth ground electrode should be
established with an independent grounding rod or ground grid mesh.
17
Page 22
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
18
Page 23
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3 DISPLAYS AND PUSH BUTTONS
This section provides illustrations with item call-outs of the six operator displays, alarm overlays, and
engineering mode overlays. Where applicable, datapoints are identified parenthetically with the display item
call-outs. The datapoints are defined in Section 4. The front panel push button definitions are repeated in this
section from Section 1, because they are used in the engineering mode display overlay examples to enter a
key password, display a datapoint, and alter a datapoint.
3.1 Operator Displays
The Quad Bar Graph (Chs. 1-4), Dual Bar Graph (Chs. 1&2), Dual Bar Graph (Chs. 3&4), Quad Process
Digital Readout, Quad Totalizer Digital Readout, and Alarm Summary operator displays are illustrated in
Figures 3-1 through 3-6 respectively.
Alarm Index 0-3 and Alarm Dead Band 0-3 must alsobe configured:
ANI0 Alarm Index (B335) ANI0 Dead Band (C105)
ANI1 Alarm Index (B340) ANI1 Dead Band (C141)
ANI2 Alarm Index (B345) ANI2 Dead Band (C177)
ANI3 Alarm Index (B350) ANI3 Dead Band (C213)
Figure 3-1. Quad Bar Graph (Channels 1-4)
19
Page 24
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 3-2. Dual Bar Graph (Channels 1 & 2)
20
Figure 3-3. Dual Bar Graph (Channels 3 & 4)
Page 25
53IT5100B Indicator/Totalizer
Figure 3-4. Quad Process Digital Readout
INSTRUCTION MANUAL
Figure 3-5. Quad Totalizer Digital Readout
21
Page 26
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3.2 Alarm Overlay
Figure 3-6. Alarm Summary
Any one of the six operator displays can have the upper quadrant of the display overlaid with an ALARM
indicator. An alarm indication warns of variation changes that exceed tolerance limits; the process may
require immediate attention. In the five illustrations of Figure 3-7, the process variable exceeded Alarm Limit 1
for ANI1. The five illustrations show how the alarm state would manifest itself on each operator display. The
alarm display for Dual Bar Graph (Chs. 3&4) is not illustrated, as the alarm banner appears in the identical
manner as shown in the illustration for Dual Bar Graph (Chs. 1&2).
In the Quad Bar Graph (Chs. 1-4) illustration of Figure 3-7, the alarm banner blinks from normal to reverse
video alternately with the ANI-1 graph scale (second from left). The ANI-1 graph scale does not appear in
reverse video, but disappears and reappears on the display. In the Dual Bar Graph (Chs. 1&2) illustration of
Figure 3-7, the alarm banner blinks from normal to reverse video alternately with the ANI-1 graph scale (on
the right of the display). The ANI-1 graph scale does not appear in reverse video, but disappears and
reappears on the display. The alarm banner in the Dual Bar Graph (Chs. 3&4) operator display (not shown)
would alternately blink from normal to reverse video; however, graph scales for channels 3 and 4 would be
unaffected.
In the Quad Process Digital Readout illustration of Figure 3-7, the alarm banner blinks from normal to reverse
video.
In the Quad Totalizer Digital Readout illustration of Figure 3-7, the alarm banner blinks from normal to reverse
video.
In the Alarm Summary illustration of Figure 3-7, the alarm banner and ANI-1 tag name blink from normal to
reverse video independent of one another.
The alarm banner blinking is stopped by pressing the Mode () push button on the horizontal keypad; the
alarm banner remains on the display, but does not blink, until the process variable returns to a value within
the alarm limit (passed dead band).
22
Page 27
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 3-7. Alarm Overlays on the Operator Displays
23
Page 28
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3.2.1 Front Panel Pushbuttons
The front panel push buttons are repeated here from Section 1 because they are used in the engineering
mode display overlay examples to enter a key password, display a datapoint, and alter a datapoint.
To the right of the display is the vertical keypad and directly beneath the display is the horizontal keypad.
Both keypads have functioning push buttons that are dependent on the instrument mode of operation which
can be either operator mode or engineering mode. Mode selection is made with the Mode () push button
on the horizontal keypad. Engineering mode is entered to make the necessary selections for the operator
displays and to configure the Datalink port; otherwise, the instrument is left in operator mode for process
applications. The vertical keypad is dedicated only to engineering mode functions and has no effect in
operator mode. Both keypads are described as follows:
Horizontal Keypad
Push Button Title Operator Mode Engineering Mode
F1
F2
F3
Title Engineering Mode
Ascending
Character
Select
Descending
Character
Select
Page back to previous display. Back to previous entry line function.
Page forward to next display. Pages the configure/display functions.
Moves Quad Bargraph pointer. Executes enter or display function.
Vertical Keypad
Displays one character at a time in ascending alphanumeric order; is released
when the desired character, number, or symbol appears on the engineering
mode data entry line.
Displays one character at a time in descending alphanumeric order; is released
when the desired character, number, or symbol appears on the engineering
mode data entry line.
Shifts selected character one position left on the engineering mode data entry
line each time this push button is pressed.
Shifts characters on engineering mode data entry line one character position
right each time this push button is pressed.
24
Page 29
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3.3 Engineering Mode Overlays
The engineering mode overlays are used to make the necessary parameter entry selections for the operator
displays and to configure the Datalink communications port. The entries are made to addressed datapoints
via the overlay single edit line at the bottom of the display. It should be noted that engineering mode has a 20
second timeout if it is accessed and its functions (e.g., configure or display) are not used.
3.3.1 Responding to the Prompt: KEY?
When the password prompt KEY? appears, it indicates a password was set in the MicroTools software. The
password can not be set via the front panel push buttons.
A password key is a maximum of 10 numeric characters (numbers 0-9 only). It does not impede display
functions in engineering mode but must be unlocked to perform configuration functions. A password key is
NOT SET FOR NEW INSTRUMENTS from the factory; therefore, if it is set, it must have been done locally.
The password must first be obtained from the originator before the procedure in Table 3-1 can be used to
access the engineering mode configuration function capabilities.
Table 3-1. Entering a Key Password
Step Press
Once
1
Shift
Result
Press to
Locate
Target
Char.
Result
Puts instrument in engineering mode.
2
3
F3
4
If DISPLAY appears instead of CONFIGURE, press 2.
Displays password query: KEY?
2
Puts first password number on entry line: KEY? .2.
5
.2Δ
6
7 Repeat step 6 until all of the password characters are entered.
.22Δ
2
2
8
F3
NOTE: Δ indicates Space
Shifts 2 and puts second password number on entry
line: KEY? .22.
Shifts 22 and puts third password number on entry
line: KEY? .222.
Enters the password key and displays the entry line:
POINT . The engineering mode configuration
function is now accessible for use.
25
Page 30
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
26
Figure 3-8. Engineering Mode Key Password Prompts
Page 31
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3.3.2 Displaying a Datapoint
The following procedure illustrates how to display the contents of datapoint C175, which is ANI2 Alarm Limit
1. Figure 3-9 contains supporting illustrations for the display procedure described in Table 3-2. (Notice in
these illustrations that ANI-2 Alarm Limit 1 is set at 80.)
Table 3-2. Procedure to Display a Datapoint
Step Press
Once
1
2
Shift
Result
Press to
Locate
If DISPLAY does not appear, press F2.
Target
Char.
Result
Puts instrument in engineering mode.
.CΔ
.C1Δ
.C17Δ
3
4
5
6
7
8 F3
9
F3
NOTE: Δ indicates Space
C
1
7
5
Displays entry line: POINT
Puts C on entry line: POINT .C.
Shifts C and puts 1 on entry line:
POINT .C1.
Shifts C1 and puts 7 on entry line:
POINT .C17.
Shifts C17 and puts 5 on entry line:
POINT .C175.
Enters address to display datapoint contents.
The address with the contents are displayed as
follows: C175 80.0000
Returns instrument to operator mode.
Figure 3-9. Displaying a Datapoint
27
Page 32
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
3.3.3 Altering a Datapoint
The procedure in Table 3-3 illustrates how to alter the contents of datapoint
C175, which is ANI2 Alarm Limit 1, from 80 to 90. Figure 3-10 is provided to
show the maximum input character length for the engineering mode edit line.
The edit line can accept ten characters. The full ten character field is used
primarily for the A type datapoint text strings (tag names). Reference Table
4-1 in Section 4 for information about the datapoint types. Note that in Figure
3-10, the PO is residual from the prompt POINT and that the character field
string starts with 1 and ends with 0 (underlined in the figure) to illustrate 10
characters.
Table 3-3. Procedure to Alter a Datapoint
Step Press
Once
1
2
3 F3 Displays entry line: POINT
4
5
6
7
8 F3
9
Hold
10
11
12 F3
13
NOTE:
Shift
Result
Puts instrument in engineering mode.
.CΔ
.C1Δ
.C17Δ
locator
.9Δ
Δ indicates Space
•
Press to
Locate
If CONFIGURE does not appear, press F2.
Target
Char.
C Puts C on entry line: POINT .C.
1
7
5
9
0
Result
Shifts C and puts 1 on entry line:
POINT .C1.
Shifts C1 and puts 7 on entry line:
POINT .C17.
Shifts C17 and puts 5 on entry line:
POINT .C175.
Enters address to display datapoint contents.
The address with the contents are displayed as
follows: C175 80.0000
C175 contents shifted right; only the locator
point remains on the entry line: C175 .
Puts 9 on entry line: C175 .9.
Shifts 9 and puts 0 on entry line:
C175 .90.
Enters the value 90 in datapoint C175.
Returns instrument to operator mode.
Figure 3-10. Entry Line
Ten Character Field
28
Page 33
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
4 CONFIGURATION PARAMETERS
The configuration parameters provide the latitude to define the instrument’s personality attributes, so that
while still functioning within its designed specifications, it can perform application requirements with greater
refinement. Typical configuration parameters are the instrument’s indicator zero point and span, the display
tag names, engineering units of the displayed process value, and alarm limits, etc. IT IS NOT NECESSARY TO DEFINE ALL OF THE CONFIGURATION PARAMETERS, as commonly used preset values may not
have to be altered and certain parameter selections eliminate others.
Although all resident in a memory database as datapoints, the configuration parameters are clustered into
modular groups that may have specific hardware identities (e.g., the ANI, ANO, CCI, and CCO circuits
illustrated in Figures 4-1 through 4-4), or may represent software controlled functions that are not specific to
any one hardware element.
4.1 Datapoint Types
A parameter can be any one of five data types. Each data type represents a specific data format:
integers, alphanumeric text strings, etc. A database module containing multiple parameters can
have a mix of data types. The data types are defined in Table 4-1 as follows:
Table 4-1. Datapoint Types
Type Byte
Size
L 1 Bit Represents a single binary bit that can have the value of 0 or 1.
B 1 Represents a positive integer with values from 0 to 255.
C 3 Represents a real analog (floating point) value that has a resolution of one part in
H 5 Represents a high precision analog (floating point) value that has a resolution of
A 10 Represents a text string that can be 10 characters long.
4.2 Factory Standard Calibration
The instrument is shipped from the factory configured with all parameters set to the default values. The
default values are listed in the parameter tables under the heading Default. The gray-tone shading in a
default cell of a parameter indicates the contents of the datapoint are left unchanged after the database is
returned to the default condition using the procedure described in Section 5.5. Examples of datapoints
unaltered by default are the Calibrate Zero and Calibrate Span parameters which are factory set.
4.3 Configuring the Database Modules
The datapoints in the database modules must be changed to reflect required alterations in the factory
standard configuration or when the instrument is re-configured. There are generally four datapoint parameter
types contained in the eight database modules. The parameter types affect Datalink communications, display
indications, input-output signals, and alarm conditions. The eight database modules are described in Table 4-
2. Although it is not an absolute criterion, it is assumed the modules will be configured in the table Item order;
however, if the instrument is to be connected to a Datalink network, item 7, Communication Module, should
be configured first. By configuring the Communication Module first, the instrument can function on the
Datalink and the remaining datapoint values can be entered via the Datalink interrogator (master). Reference
the applicable instruction bulletin (e.g., IB 53HC3300, IB53WS5000, or IB 53SU5000) for the procedure.
Table 4-2 is also a pointer to the descriptions of the database modules; the descriptions are presented
as Tables 4-3 through 4-10. (The gray tone shading in the default cell of a datapoint indicates the datapoint
contents are left unchanged after default. See Section 5.5 for the default procedure.)
Format
32,768 (15 bits) and a dynamic range of ± 10
one part in 2 billion (31 bits) and a dynamic range of ± 10
38 .
38 .
29
Page 34
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-2. Database Modules
Item Title Purpose See
Table
1 Analog Input Module This module is used to configure the voltage input
characteristics (e.g., input voltage range) and how the input
signal is interpreted (linear or square root representation).
2
Analog Output Module
3 Contact Input Module This module allows the action of the CCIs to be reversed
4 Contact Output
Module
5 Alarm Module The primary purpose of this module is to set the instrument’s
6 Totalizer Module The totalizers provide the sum of each analog input (ANI0-3).
7 Communication
Module
8 System Module This module is used to set the instrument tag name and the
The primary purpose of this module is to set the 0 - 20 mA
output signal relative to the displayed percent output.
(normally a closed contact = 1, but can be change to = 0).
This module allows the action of a CCOs to be reversed
(normally a closed contact = 1, but can be changed to = 0).
Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead
Band.
This module is used to set input scaling factors, rollover and
dropout values, and to define display tags for each totalizer.
This module is used to configure the Datalink port
parameters (e.g., baud rate, parity selection, etc.).
4-10
display brightness.
4-3
4-4
4-5
4-6
4-7
4-8
4-9
30
Page 35
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-3. Analog Input (ANI) Module
Purpose: This module is used to configure input voltage characteristics (e.g., input voltage range), and how the
input signals are interpreted (linear or square root representation).
TitleSymbolANIDatapointDefaultAttribute
Analog
Input
(Display
Only)
Engineering
Span
Engineering
Zero
Digital Filter
Index
0 - 5 V Input
Square
Root
Signal
Calibrate
Zero
Calibrate
Span
Tag Name
Engineering
Units
ANI0
ANI1
ANI2
ANI3
SPAN0
SPAN1
SPAN2
SPAN3
ZERO0
ZERO1
ZERO2
ZERO3
DFILT0
DFILT1
DFILT2
DFILT3
NOBIAS0
NOBIAS1
NOBIAS2
NOBIAS3
SQRT0
SQRT1
SQRT2
SQRT3
CIZ0
CIZ1
CIZ2
CIZ3
CIS0
CIS1
CIS2
CIS3
AITAG0
AITAG1
AITAG2
AITAG3
AIEU0
AIEU1
AIEU2
AIEU3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
ANI0
ANI1
ANI2
ANI3
H000
H001
H002
H003
C256
C257
C258
C259
C276
C277
C278
C279
B269
B270
B271
B272
L416
L417
L418
L419
L440
L441
L442
L443
B263
B264
B265
B266
C296
C297
C298
C299
A224
A225
A226
A227
A298
A299
A300
A301
0
0
0
0
100
100
100
100
0
0
0
0
3
3
3
3
0
0
0
0
0
0
0
0
ANI-0
ANI-1
ANI-2
ANI-3
PERCENT
(ALL)
This is the value in engineering units of the
measured input after all signal conditioning
has been applied.
This determines the upper range the analog
input represents in engineering units. The
upper range value equals Engineering Zero
plus Engineering Span.
This is the lower range value.
This controls a first order filter that is applied
to the input signal. The time constant is
entered as an index value as follows:
0 -No Smoothing (no effect)
1 -0.05 s
2 - 0.1 s
3 - 0.3 s
4 - 0.7 s
5 - 1.5 s
Setting this parameter to 1 indicates the input
range is from 0 -5 volts (0 -20 mA). 0
indicates the input range is from 1 -5 volts (4 20 mA).
When a 0, it indicates the analog input signal
should be interpreted linearly.
When 1, it indicates the analog input signal
should be interpreted as a square root
representation of the value. When square root is
selected, input signals less than 1% (10% input
range) forces the input to its zero value.
This is the calibration zero adjustment. This
parameter is factory set and should not need adjustment under normal operation.
See Section 5.3 for adjustment.
This is the calibration span adjustment. This
parameter is factory set and should not need adjustment under normal operation.
See Section 5.3 for adjustment.
an assignable 10 character name for the analog
input (ANI-0, ANI-1, ANI-2, ANI-3).
assignable for units of measure the ANI
represents (e.g., GPM for gallons/minute).
6 - 3.1 s
7 - 6.3 s
8 -12.7 s
9 -25.5 s
10 -51.1 s
11 - 102 s
12 - 205 s
13 - 410 s
14 - 819 s
15 -1638 s
31
Page 36
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 4-1. ANI0-3 Figure 4-2. ANO0
NOTE: These figures are graphical representations of the signal conditioning that occurs on the
instrument main board. They are provided for reference purposes only.
32
Page 37
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-4. Analog Output (ANO) Module
Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the
displayed percent and to select the analog input signal (ANI0-3) that is to be routed to the analog
output (ANO0).
Title Symbol ANO0
Datapoint
Analog Output
(Display Only)
Analog Output
Source
0 -20 mA
Output
Calibrate Zero COZ0 B267
Calibrate
Span
Tag Name AOTAG0 A244 ANO0 The assignable 10 character name for ANO0.
ANO0 C000 0 The value in this datapoint represents the
OZBASE0 L472 0
COS0 C300
B100 0 This parameter determines which analog input
Default Attribute
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).
(ANI0-3) is routed to the analog output (ANO0).
The routing index values are as follows: 0 =
ANI0 →ANO0, 1 = ANI1 →ANO0 2 = ANI2
→ANO0, 3 = ANI3 →ANO0
When a 0, the percentage output generates a 4
-20 mA signal. When set to 1 , the percentage
output generates a 0 -20 mA signal.
These parameters are factory set and should not need adjustment under normal operation.
See Section 5.3 for adjustment.
Figure 4-3. CCI0/1 Figure 4-4. CCO0/1
NOTE: These figures are graphical representations of the signal conditioning that occurs on the
instrument main board. They are provided for reference purposes only.
33
Page 38
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-5. Contact Input Module (CCI)
Purpose: This module allows the action of the CCIs to be reversed (normally a closed contact = 1, but can be
changed to = 0).
Datapoin
Title Symbol CCI
Contact
Input
(Display
Only)
CCI0
CCI1
CCI0
CCI1
t Default Attribute
L000
L001
0
0
When open, a 4 -24 V dc input signal = 0 when IINV =
0.
When open, a 4 -24 V dc input signal = 1 when IINV =
1.
When closed, a < 1 V dc input signal = 1 when IINV = 0.
When closed, a < 1 V dc input signal = 0 when IINV = 1.
Contact
Input
Invert
Display
Message
Tag
Name
Display
Mode
Alarm
Enable
Contact Input = 0 1 0 1
Display Mode
Display Mode
= 0
= 1
IINV0
IINV1
CCI0
CITAG0
CITAG1
SMA
SMB
SAA
SAB
CCI0
CCI1
CCI1
CCI0
CCI1
CCI0
CCI1
CCI0
CCI1
10 character
message.
No message blinking and no Alarm Banner blinking.
Frst half (5
characters) of 10
character
message
sequence.
No message blinking and no Alarm Banner blinking.
L264
L265
A055
A056
A262
A263
L352
L353
L368
L369
Alarm Enable = 0Alarm Enable = 1
10 character
message in
reverse video.
Second half (5
characters) of
10 character
message
sequence.
0 0 As shown above, it reverses the action of the CCI
datapoint.
ALARM A
ALARM B
CCI-0
CCI-1
0 0
0 0
The messages for CCI0 and CCI1, respectively, on the
Alarm Summary display.
It is an assignable 10 character name for the contact
control input.
Display Mode, Alarm Enable, and Contact Input interact
to alter the two five character segments of the Display
Messages (A055 and A056) as shown in the table that
follows:
10 character
message.
First half (5
characters) of
10 character
message
sequence.
10 character message blinking in
reverse video with Alarm Banner
also blinking. (After pressing
Mode push button, 10 character
message appears in reverse
video.)
Second half (5 characters) of 10
character message blinking with
Alarm Banner blinking. (After
pressing Mode push button, 5
character message remains, but
stops blinking.)
34
Page 39
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-6. Contact Output Module (CCO)
Purpose: This module allows the action of the CCOs to be reversed (normally a closed contact =
1, but can be changed to = 0) and is used to select the signal or condition that activates the CCO.
Title SymbolCCOData-point DefaultAttribute
Contact
Output
(Display
Only)
Contact
Output
Invert
Control
Contact
Output
Source
Tag
Name
CCO0
CCO1
OINV0
OINV1
COTAG0
COTAG1
CCO0
CCO1
CCO0
CCO1
CCO0
CCO1
CCO0
CCO1
L024
L025
L288
L289
B101
B102
A280
A281
0
0
0
0
110
134
CCO-0
CCO-1
If CCO = 0 and OINV = 0, then it is open.
If CCO = 0 and OINV = 1, then it is closed.
If CCO = 1 and OINV = 0, then it is closed.
If CCO = 1 and OINV = 1, then it is open.
As shown above, it reverses the action of the
CCO datapoint.
This parameter selects the signal or condition
that activates the CCO. The routing index
values
are as follows:
110 Channel 0 Alarm A (PA10).
111 Channel 0 Alarm B (PA20).
134 Channel 1 Alarm A (PA11).
135 Channel 1 Alarm B (PA21).
158 Channel 2 Alarm A (PA12).
159 Channel 2 Alarm B (PA22).
182 Channel 3 Alarm A (PA13).
183 Channel 3 Alarm B (PA23).
0 Contact Input 0 (CCI0).
1 Contact Input 1 (CCI1).
224 Totalizer 0 Rollover Pulse (TMP0).
225 Totalizer 1 Rollover Pulse (TMP1).
226 Totalizer 2 Rollover Pulse (TMP2).
227 Totalizer 3 Rollover Pulse (TMP3).
65 Horn - latches the OR function of all
alarms (8 process alarm bits and 2 contact
input alarms).
99 Non-latched OR function of all alarms (8
process alarm bits and 2 contact input
alarms). It is cleared when the last alarmgoes
away.
An assignable 10 character name for the
contact control output.
35
Page 40
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-7. Alarm Module
Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm
Limits 1 & 2, and Alarm Dead Band.
Title SymbolCCOData-point DefaultAttribute
This parameter defines the Alarm Active (PA1 &
PA2) interpretation of the two Alarm Limits (PL1
& PL2). It is entered into the datapoint as an
index value (0-5 ) as follows (n = 0-3 and
correlates with ALRM0 through ALRM3):
0 PA1n: high when PV> PL1n
PA2n: low when PV< PL2n
1 None
2 PA1n: high when PV> PL1n
PA2n: not affected
3 PA1n: not affected
PA2n: low when PV< PL1n
4 PA1n: high when PV> PL1n
PA2n: hi-hi when PV> PL2n
5 PA1n: low when PV< PL1n
PA2n: lo-lo when PV< PL2n
Examples are provided as follows:
Alarm
Index
AIX0
AIX1
AIX2
AIX3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
B335
B340
B345
B350
1
1
1
1
Alarm Examples:
B335 PV PL1
(C103)
0 >60 60 high Alarm Llimit 1 is set for 60: PV > 60 = high Alarm.
0 <40 40 low Alarm Limit 2 is set for 40: PV < 40 = low Alarm.
2 >60 60 high Alarm Limit 1 is set for 60: PV > 60 = high Alarm.
2 <40 40 N/A Alarm Limit 2 is set for 40: PV < 40 = no alarm.
3 >60 60 N/A Alarm Limit 1 is set for 60: PV > 60 = no alarm.
3 <40 40 Low
4 >60 60 high Alarm Limit 1 is set for 60: PV > 60 = high Alarm.
4 <70 70 hi-hi Alarm Limit 2 is set for 70: PV > 70 = hi-hi Alarm.
5 >40 40 low Alarm Limit 1 is set for 40: PV < 40 = low Alarm.
5 <30 30 low-lowAlarm Limit 2 is set for 30: PV < 30 = lo-lo Alarm.
PL2 (C104)AlarmNotes
low Alarm Limit 2 is set for 40: PV < 40 = low
Alarm.
36
Page 41
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-7. Alarm Module (continued)
Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm
Limits 1 & 2, and Alarm Dead Band.
Title SymbolCCOData-point DefaultAttribute
Alarm A
(Display
Only)
Alarm B
(Display
Only)
Alarm
Limit 1
Alarm
Limit 2
Alarm
Dead
Band
PA10
PA11
PA12
PA13
PA20
PA21
PA22
PA23
PL10
PL11
PL12
PL13
PL20
PL21
PL22
PL22
ADB0
ADB1
ADB2
ADB3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
L110
L134
L158
L182
L111
L135
L159
L183
C103
C139
C175
C211
C104
C140
C176
C212
C105
C141
C177
C213
0
0
0
0
0
0
0
0
100
100
100
100
0
0
0
0
2
2
2
2
When active, it indicates one of the four PA1
conditions (PA10-PA13) specified in its
respective
Alarm Index (AIX0-AIX3) has an alarm indication
as determined by the index value (0-5) that was
entered for the Alarm Index.
When active, it indicates one of the four PA2
conditions (PA20-PA23) specified in its
respective
Alarm Index (AIX0-AIX3) has an alarm indication
as determined by the index value (0-5) that was
entered for the Alarm Index.
These parameters are the points in engineering
units at which the alarms are triggered.
This parameter sets the activation/deactivation
gap for the alarm. This value in engineering units
defines an area of hysteresis at the alarm point.
37
Page 42
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-8. Totalizer Module
Purpose: The totalizers provide a running total of each analog input (ANI0-3). This module is
used to set input scaling factors, rollover and dropout values, and to define display tags for each
totalizer.
Title SymbolTMDatapoint Default Attribute
Tag
Name
Eng.
Units
Scale
Factor
TMTAG0
TMTAG1
TMTAG2
TMTAG3
TMEU0
TMEU1
TMEU2
TMEU3
TMF0
TMF1
TMF2
TMF3
TM0
TM1
TM2
TM3
TM0
TM1
TM2
TM3
TM0
TM1
TM2
TM3
A092
A094
A096
A098
A093
A095
A097
A099
C318
C320
C322
C324
TOTAL-0
TOTAL-1
TOTAL-2
TOTAL-3
UNITS
UNITS
UNITS
UNITS
16666
16666
16666
16666
These are assignable 10 character names that
appear on the totalizer display.
These are assignable 10 character names that
appear on the totalizer display as the engineering
units of measure.
The value of the input is multiplied by this
parameter prior to being summed to the running
total. The parameter is used for both scaling and
time interval integration. For example, if ANI0 is in
M gallons/day, in order to totalize in K gallons the
scale factor (SF) would be:
SF = [Units Conversion] X [Time Base Conversion]
SF = [1000 K gal / M gal] X [(1 day/24 hrs) X (1
hr/60 mins) X (1 min/60 sec) X (1 sec/sample)] =
1000/86400 = 0.01157
NOTE: The time between totalizer updates is
one second.
The default value of 16666 uses the scale factor
for time interval integration. Due to the internal
timing of the instrument, a scale factor of 16666 will
cause the rollover total to occur once every minute.
Rollover
Value
Dropout
Value
Reset
38
TMM0
TMM1
TMM2
TMM3
TMD0
TMD1
TMD2
TMD3
TMR0
TMR1
TMR2
TMR3
TM0
TM1
TM2
TM3
TM0
TM1
TM2
TM3
TM0
TM1
TM2
TM3
H048
H049
H050
H051
C319
C321
C323
C325
L232
L233
L234
L235
1000000
1000000
1000000
1000000
0
0
0
0
0
0
0
0
Specifies the maximum value of the totalizer.
When the total reaches this value it is reset to
0.0; however totalizing continues. This value
must be a positive number.
When the input value is less than this value, no
change in the total occurs.
This parameter acts like a momentary switch.
When this parameter is set to 1 the total is forced
to 0.0 and then this parameter is reset to 0.
Page 43
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-8. Totalizer Module (continued)
Purpose: The totalizers provide a running total of each analog input (ANI0-3). This module is
used to set input scaling factors, rollover and dropout values, and to define display tags for each
totalizer.
Title SymbolTMDatapoint Default Attribute
Actual
Total
(Display
Only)
Output
Pulse
TO0
TO1
TO2
TO3
TMP0
TMP1
TMP2
TMP3
TM0
TM1
TM2
TM3
TM0
TM1
TM2
TM3
H032
H033
H034
H035
L224
L225
L226
L227
0
0
0
0
0
0
0
0
This parameter indicates the integer value of the
total accumulation.
This value is pulsed to a 1 for one scan each
time the actual total reaches the rollover value.
39
Page 44
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-9. Communication Module
Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity
selection, etc.).
Title SymbolDatapoint Default Attribute
It identifies the address of this instrument on the
Instrument
Address
Baud Rate BR B002 253
No Parity CP L256 0
No Byte
Stuffing
Datalink
Disable
IA B001 0
CB L258 0
DLD L257 0
Datalink network. Each unit connected to the Datalink
network must have its own unique address. Valid
addresses are from 0 -31.
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments connected to
the same Datalink network. Datapoint values and their
checking should be turned on or off. It is set to 0 for
even parity serial byte protocol. It is set to 1 for no parity
protocol.
When set to a 1, this datapoint disables the standard
communication protocol feature which inserts a 00
(NUL) byte after every 7EH (SOH) that is not the
beginning of a message. (This permits user written
communications software to determine the number of
bytes to expect in a response message.) It must be set
to 0 when using the Micro-DCI communications
software or equipment.
When set to 0 , it permits full Datalink communication
capabilities. When set to 1, it disables Datalink
communication capabilities.
40
Page 45
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-10. System Module
Purpose: This module is used to set the instrument tag name and the display brightness.
System
Title Symbol
Module
Datapoint
Default Attribute
Display
Brightness
Index
Model Number
Low (Display
Only)
Model Number
High (Display
Only)
Unit Tag Name TAG A008 53IT5100
BRIGHT B012 4
A190 Factory Set
A191 Factory Set
This parameter controls the display screen
intensity. A value of 0 is the brightest and a
value of 7 is the dimmest intensity. Normal
viewing setting is 4.
It contains the first ten characters of the model
number.
It contains the last ten characters of the model
number.
It is an assignable 10 character name for the
system module (53IT5100).
41
Page 46
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
42
Page 47
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
5 MAINTENANCE
NOTE: The factory set calibration constants for ANI0-3 and ANO0 are applicable only for the main
printed circuit board supplied in the particular instrument. This data is recorded on a calibration sheet
supplied with the instrument. The data should be retained to facilitate easy field recalibration in the event
one or more of the constants is inadvertently changed.
5.1 Service Approach
This instrument is a microprocessor based device; all mathematical computations, data manipulation, and
sequencing operations are software controlled. After the instrument has been configured, normal operations
are controlled via the front panel push buttons. Because the instrument does not have internal circuitry that
requires field adjustment, diagnostic testing and preventive maintenance are not required.
Generally, when a process malfunction occurs, it usually manifests itself as an instrument problem even
though it might be a defective process variable monitoring device, remote transmitter, or interconnecting
wires. These associated remote devices should be checked before attempting instrument troubleshooting and
repair.
Due to the complexity of microprocessor based instruments, attempting fault finding analysis to integrated
circuits (ICs) on the main printed circuit board (PCB) is not recommended. The ICs are static sensitive and
can be damaged if not properly handled. Also, when test probes are connected, even a momentary short
across several IC pins with a probe tip can damage the IC. Therefore, only trained technicians familiar with
CMOS technology and microprocessor functionality should be permitted to service the equipment.
5.2 Parts Replacement
WARNING: ALWAYS REMOVE POWER BEFORE ATTEMPTING TO INSTALL, DISASSEMBLE,
OR SERVICE ANY OF THE EQUIPMENT. FAILURE TO REMOVE POWER MAY RESULT IN
SERIOUS PERSONAL INJURY AND/OR EQUIPMENT DAMAGE.
Access to internal instrument parts is achieved by removing the front display panel. The front display panel
can be removed by inserting a small screwdriver into the notch at the top center of the display and twisting
the screwdriver to depress the retaining latch. The upper sides of the display are held and pulled forward as
the latch is depressed. The cable at the rear of the front display panel is disconnected from its socket. The
other cable end connects to the main printed circuit board. Replacing the display unit requires reconnecting
the display end of the cable to the new front display panel, inserting the extended portion of the display panel
into the instrument cabinet and latching it in place with a screwdriver.
After the front display panel is removed, the main printed circuit board can be accessed. The main printed
circuit board also has the power supply as well as the microprocessor circuitry. To remove the main PCB, use
its front edge board ejector to pull it free from the rear terminal board slot and carefully slide it from the case.
Disconnect the front display panel flat ribbon cable from the main PCB. The replacement main PCB can now
be installed by connecting the front display panel ribbon cable, sliding the PCB into the instrument case,
seating it into the rear terminal board slot, and installing the front display panel.
NOTE: Power Supply Fuses
AC Power: 1A, 250 V, Fast Blow Schurter Type 034.3930
DC Power: 3A, 250 V, Slow Blow BEL Type 5TT3
For additional information, contact MicroMod Automation.
43
Page 48
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
NOTE: When communicating with MicroMod for replacement of the main PCB, reference the
unit’s serial number to ensure the correct replacement assembly is supplied. The necessary ordering
information is provided on the instrument data tag and on the manufacturing specification sheet
supplied with that particular controller.
In the event of a hardware malfunction, a replacement PCB can be quickly substituted for the defective
assembly to minimize downtime. Contact MicroMod for instructions before returning equipment.
The defective PCB should be carefully packaged and returned, shipping charges prepaid, to the Repair Dept.
of MicroMod Automation. Do not wrap PCBs in plastic, as it can cause static damage. It is suggested that
the defective PCB be returned in the special bag in which the replacement module was supplied.
5.3 Calibration
The instrument’s analog inputs (ANI0-3) and output (ANO0) are extremely stable. They normally do not
require recalibration. If it becomes necessary to recalibrate the instrument, due to the inadvertent change of
the stored calibration values, then this can be accomplished by altering their respective datapoints. The
calibration span and
zero datapoint locations are as follows:
Entire Display Flashes - The watchdog timer has timed out.
CPU RAM FAILURE - IC U1 is bad.
ROM CHKS FAILURE - IC U3 is bad.
5.5 Resetting the Instrument
The instrument can be reset either by cycling the power, or by carefully pressing the reset button by inserting
a thin wire, such as a paper clip, through the small hole in the upper left corner of the front bezel. (See Figure
1-2 for the location of the reset hole.) When the instrument restarts, it immediately checks to determine if any
of the horizontal keypad push buttons are held pressed.
If the 1 push button is held pressed during instrument reset, the instrument enters a factory test
mode. The test mode can be exited by resetting the instrument again using the thin wire with no push
buttons pressed.
If the 2 push button is held pressed during instrument reset, the instrument database is set to the
defaulted values.
44
Page 49
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
5.6 Parts List
The parts list is provided in Table 5-1 and the parts breakdown is illustrated in Figure 5-1.
Note that these boards are for the 53IT5000B, not the 53IT5000A. Contact MicroMod for more information on
spare parts availability for the 53IT5000 Design Level A.
Table 5-1. Parts List
Key Part Number Description
1 612B395U02 Case
2 686B803U06 Main Printed Circuit Board
3 685B736U01 Power Supply - 120/220/240 V ac, 50/60 Hz
3 685B736U02 Power Supply -24 V dc
4 698B179U03 Front Display
5 686B598U02 Rear Terminal Board
6 614C157U01 Cable - Display to Main PCB
355J093U01 Trim Collar for Single Case
Contact Factory Trim Collar and Spacer for two or more cases
614B762U02 Kit of Three Plates for 3 X 6 Instrument Panel Cutout
45
Page 50
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
46
Figure 5-1. Illustrated Parts Breakdown
Page 51
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 5-3. Communication ITB Pin Assignments
47
Page 52
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
48
Page 53
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Appendix A: Discrete Contact Output CCO’s
The discrete output CCOs are not mechanical contact closures but NPN Transistors that are analogous to
single pole, single throw switches with one terminal connected to power common. This circuit type layout is
commonly called an Open Collector Output. (See Figure A-1.)
Capability limits of each CCO are as follows:
50 mA maximum current flow when closed.
30 V dc maximum tolerance voltage when open.
A CCO will operate any external device that can be made to switch if it does not require more than 50 mA of
current to the (+) terminal.
Typical uses for a CCO are to actuate a small relay, activate an external alarm buzzer, provide
Contact Input (CCI) to another instrument, or provide output to an annunciator panel.
A CCO circuit is equivalent to an unpowered switch. If the 24 V dc supply of the instrument is not already fully
loaded (see note), it can be used as a source of power for a CCO; otherwise, a separate, external dc supply
must be used. In the upper circuit illustration of Figure A-2, the +24 V is obtained from screw lugs 1 or 4 of
TB1 located on the instrument rear terminal board. (See Figure 2-4.)
NOTE: Power source - 80 mA maximum.
In Figure A-1, the switch is closed when the output logic bit (L24 for CCO0, L25 for CCO1) is set to 1,
provided that its respective invert bit (L288 for CCO0, L289 for CCO1) is 0. The relay in Figure A-2 is
energized when the output bit is set to 1 if the invert bit is 0. If the invert bit is set to 1, the output bit will cause
the relay to de-energize when it is set to 1.
Figure A-2 also shows how a dc electromechanical relay is operated using an internal or external power
source. There are many dc relays available with a coil resistance of 430 ohms or more. (Note: with the 24 V
dc supply, a 430 ohm coil resistance will pass 50 mA of current.) Figure A-3 shows how several CCOs can be
arranged in parallel using one power source so that any one CCO can actuate a single relay.
Figure A-4 shows a CCO used to control a solid state relay (see note). The resistor is added to the circuit
from the power source to limit the current flow, and also to establish the voltage across the relay when the
CCO switch is open.
NOTE: Several manufacturers are Crydom Division, International Rectifier and OPTO 22.
In Figure A-5, the CCO of one instrument is applied directly to the CCI of another instrument.
When the CCO closes, the CCI circuit of the second instrument is complete. An appropriate resistance is
required in the second instrument, as it provides the power for its CCI operation.
49
Page 54
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure A-1. CCO Circuit and its Equivalent
50
Figure A-2. Circuits for Operating DC Relays
Page 55
53IT5100B Indicator/Totalizer
Figure A-3. Operating CCOs in Parallel
INSTRUCTION MANUAL
Figure A-4. CCO with Solid State Relay
Figure A-5. CCO Operating CCI Directly
51
Page 56
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
52
Page 57
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Appendix B : Communications
Two digital communication channels are provided with this instrument:
RS-232 serial configuration port, accessed via a 5 pin mini-DIN connector located under the pull-
down door on the front panel (see Figure 1-2). It is used to configure instrument parameters for
selected operational characteristics. The parameters are configured with Micro-Tools software
running on a customer supplied PC.
RS-422/485 serial interface used to connect the instrument to a Datalink multi-drop network. Interface
connection to the Datalink network is via the rear terminal board (TB1) of the instrument, pins 19
through 22, as shown in Section 2.
Information in this section applies to both the configuration port and the Datalink interface
The configuration port data rate is 9600 baud, with 8 data bits, and no parity.
The Datalink interface requires four conductors: a transmit pair and a receive pair. The voltage levels of each
conductor pair conform to the EIA RS-422/485 standard. In accordance with this standard, the overall
Datalink network distance is limited to 4000 feet when #24 AWG twisted pair wire is used to interconnect the
nodes. Adapters are available to convert RS-422/485 to RS-232 or 20 mA current loops.
In a Datalink network, the instruments communicate as Responders to host queries. The host or PC functions
as the Interrogator and acts as the central control point for the Datalink network. A maximum of 32
addressable instruments can be connected to a Datalink network.
53
Page 58
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table B-1. Communication Module
Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection,
etc.).
Title DatapointSetupDefault Attribute
It identifies the address of this instrument on the
Instrument
Address
Baud Rate B02
No Parity L256
No Byte
Stuffing
Datalink
Disable
NOTE : S = Select a value from the Attribute column. Use all other datapoint values as shown.
B01
L258
L257
S
S
0
0
0
0
253
0
0
0
Datalink network. Each unit connected to the Datalink
network must have its own unique address. Valid
addresses are from 0 -31.
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments connected to
the same Datalink network. Datapoint values and their
checking should be turned on or off. It is set to 0 for
even parity serial byte protocol. It is set to 1 for no parity
protocol.
When set to a 1, this datapoint disables the standard
communication protocol feature which inserts a 00
(NUL) byte after every 7EH (SOH) that is not the
beginning of a message. (This permits user written
communications software to determine the number of
bytes to expect in a response message.) It must be set
to 0 when using the Micro-DCI communications
software or equipment.
When set to 0 , it permits full Datalink communication
capabilities. When set to 1, it disables Datalink
communication capabilities.
54
Page 59
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Protocol
The Datalink protocol requires the host to initiate all transactions. There are two basic categories for all of the
Datalink message types: Interrogate - used to read data from an addressed instrument, and Change used to
alter a value in an addressed instrument. The addressed instrument decodes the message and provides an
appropriate response. The protocol definitions for the Datalink message types are provided in Table B-2.
Table B-2. Message Field Definitions
SymbolTitleDefinition
SOH Start of Header This character, 7E, denotes the beginning of a message.
The address of the instrument responding to the transaction. It must
I.A. Instrument Address
CMD Command
NUM Number
LO-ADD Lower Address Bits The least significant 8 bits of a 16 bit instrument address.
HI-ADD Higher Address Bits The most significant 8 bits of a 16 bit instrument address.
DATA An 8 bit data byte.
XXXX Represents a variable number of data bytes.
MASK
STATE
Longitudinal
Redundancy
LRC
Character
Message Types
The types of messages that are sent between the host and the Datalink network instrument are formatted as
follows:
be within a range of 00-1F (00-31 decimal).
Is the operation to be performed or a description of the message that
follows the Command-I.A. byte. The Command-I.A. byte has two
fields: the Command field (3 bits), and the I.A. field (5 bits). There
are five commands, listed as follows: Interrogate Change Change
Bits Acknowledge Response The commands are covered in Section
B.1.3, Message Types.
The number of data bytes transferred or requested. The NUM must
be in a range of 00-32.
An 8 bit byte where each bit, called a flag, is dedicated to an event
that is permitted or prohibited, depending on the flag setting. If the
flag is set to 0, the event is permitted. If the flag is set to 1, the event
is prohibited.
Represents the bit settings of a particular byte: which bits are set to
1, and which bits are set to 0.
Is a character written at the end of the message that represents the
byte content of the message and is checked to ensure data was not
lost in transmission. It is the sum of all bytes Modulo 256 of the
message not including the SOH character or its own bit settings
(LRC).
HOST TO INSTRUMENT:
1. INTERROGATE - This message requests up to 20H consecutively stored bytes, beginning at the
specified memory address location of the addressed instrument.
01111110 E0H + I.A. NUM LO ADD HI ADD LRC
2. CHANGE - This message sends up to 20H bytes of new data to the addressed instrument.
01111110 A0H + I.A. NUM LO ADD HI ADD Data 1 XXXXXXXXX Data N LRC
3. CHANGE BITS - This message alters only the specified bits in the specified bytes in the addressed
instrument. (NUM = 2n)
01111110 C0H + I.A. NUM LO ADD HI ADD Mask 1 State 1 XXXX Mask N State N LRC
55
Page 60
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
4. ACKNOWLEDGE - This message signals the addressed instrument that its last echoed change
message was received correctly; the instrument performs the change requested.
01111110 80H + I.A.
INSTRUMENT TO HOST:
1. RESPONSE - This message furnishes the data requested by the INTERROGATE command of the
Host. It is also used to echo back the previous CHANGE message of the Host.
01111110 20H + I.A. NUM LO ADD HI ADD Data 1 XXXXX Data N LRC
Communication Transaction Examples
Transaction A Example - Host requests 9 bytes of data beginning at hexadecimal memory address 1000H
Transaction B Example - Host or SUPERVISOR-PC sends two bytes of new data, to be loaded into the
instrument at Datalink address 03 beginning at hexadecimal memory address 1000H.
1. Host sends CHANGE message.
01111110 10100011 00000010 00000000
SOH
2. Instrument sends RESPONSE message.
01111110 00100011 00000010 00000000
Command
+ I.A.
Command
+ I.A.
Command
+ I.A.
NUM LO ADD HI ADD LRC
00010000 XXXXX XXXXX XXXXX LRC
NUM LO ADD HI ADD Data 1 ................. Data 9
00010000 0000100
0
NUM LO ADD HI ADD Data 1 Data 2 LRC
00010000 00001000 00001100
00001100
1100100
1
0100100
1
SOH
3. Host sends ACKNOWLEDGE message.
01111110 10000011
SOH Command
56
Command
+ I.A.
NUM LO ADD HI ADD Data 1 Data 2 LRC
Page 61
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
+ I.A.
4. Instrument performs the change requested at end of the current program scan.
57
Page 62
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Calculating Data Addresses
If communications software must be generated to accommodate unique Datalink applications requirements,
then the instrument memory address scheme must be known for proper data bit (e.g., L data type) and data
byte (e.g., B, C, H, and A data types) memory location determination.
NOTE: Numbers used in this section that are expressed in hexadecimal notation (base 16) are
identified with an H after the number.
This memory address scheme applies only if a 6 is in memory address location 8002H. Memoryaddress
location 8002H must be read and if it contains a 6, then the address scheme that is described in Table B-3
should be applied for this instrument.
value of 0 or 1. L datapoints are
packed 8 to a byte.
C 600H 3 Represents floating point values that
have a resolution of one part in
32,768 (15 bits) and a dynamic
range of ± 1038 . The first two bytes
represent a 2’s complement notation
in fractional form (2-n ) whose
absolute value is between 0.5 and
0.9999. The third byte is the power
of 2 in 2’s complement notation.
Floating point example: 64H 00H
07H = 100D (Decimal) 64H = 0110
0100, fractional binary weights left to
right are 0 = 2’s complement
positive, 1 = 2-1 = 1/2 = 0.5, 1 = 2-2
= 1/4 = 0.25, 0=0, 0=0, 1 = 2-5 =
1/32 = 0.03125, 0=0, and 0=0. 64H =
0.5+0.25+0.03125 = 0.78125.07H =
128D. 128D X 0.78125D = 100.
Address = L Base + (L Number/8)
= 500H + (L Number/8)
Remainder = bit position in byte
point values that have a resolution
of one part in 2 billion (31 bits) and
a dynamic range of ± 1038 . The
first four bytes represent a 2’s
complement notation in fractional
form (2-n) whose absolute value is
between 0.5 and 0.9999. The fifth
byte is the power of 2 in 2’s
complement notation. Floating point
example: 9CH 00H 00H 00H 07H =
-100. The 2’s complement notation
bit in the 9 = 1 (1001) indicating a
negative number; therefore, 9C
must be re-complemented . 9C =
1001 1100, change 1’s to 0’s and
0’s to 1’s = 0110 0011 and add 1=
0110 0100 (64H). Fractional binary
weights left to right for 0110 0100
are 0 = 2’s complement positive, 1
= 2-1 = 1/2 = 0.5, 1 = 2-2 = 1/4 =
0.25, 0=0, 0=0, 1= 2-5= 1/32 =
0.03125, 0=0, 0=0. 64H = 0.5 +
0.25 + 0.03125 = 0.78125.
07H=128D, 128D X 0.78125D =
100. A negative sign is assigned (-
100) because the original 2’s
complement binary bit in the 9
(1001) of 9C was set indicating a
negative number.
The A data format represents text
strings that are 10 characters long.
The F data format represents text
strings that are 5 characters long.
Address = H Base + (5 X H Number) =
F00H + (5 X H Number)
The database contains five datapoint types. Each datapoint type represents a specific data format: whole
integers, alphanumeric text strings, etc. The datapoint types are defined in Table C-1 and the database is
listed in alphanumeric order in Table C-2. The gray-tone shading in the Symbol cell of a datapoint indicates
the datapoint does not have an assigned symbol.
Table C-1. Datapoint Types
TypeQty
L 40 1 Bit Represents a single binary bit that can have the value of 0 or 1.
B 19 1 Represents a positive integer with values from 0 to 255.
Byte
Size
Format
C 34 3
H 12 5
A 26 10 Represents a text string that can be 10 characters long.
Represents a real analog (floating point) value that has a resolution of one part in
32,768 (15 bits) and a dynamic range of ± 1038 .
Represents a high precision analog (floating point) value that has a resolution of
one part in 2 billion (31 bits) and a dynamic range of ± 10
38
60
Page 65
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database
DatapointTitleSymbolDefault
A008 Unit Tag Name TAG 53IT5100 4-10 System
A055 CCI0 Display Message ALARM A 4-5 CCI
A056 CCI1 Display Message ALARM B 4-5 CCI
A092 Totalizer 0 Tag Name TMTAG0 TOTAL-0 4-8 Totalizer
A093 Totalizer 0 Engineering Units TMEU0 UNITS 4-8 Totalizer
A094 Totalizer 1 Tag Name TMTAG1 TOTAL-1 4-8 Totalizer
A095 Totalizer 1 Engineering Units TMEU1 UNITS 4-8 Totalizer
A096 Totalizer 2 Tag Name TMTAG2 TOTAL-2 4-8 Totalizer
A097 Totalizer 2 Engineering Units TMEU2 UNITS 4-8 Totalizer
A098 Totalizer 3 Tag Name TMTAG3 TOTAL-3 4-8 Totalizer
A099 Totalizer 3 Engineering Units TMEU3 UNITS 4-8 Totalizer
A190 Model Number Low (Display Only) (factory set) 4-10 System
A191 Model Number High (Display Only) 4-10 System
A224 ANI0 Tag Name AITAG0 ANI-0 4-3 ANI
A225 ANI1 Tag Name AITAG1 ANI-1 4-3 ANI
A226 ANI2 Tag Name AITAG2 ANI-2 4-3 ANI
A227 ANI3 Tag Name AITAG3 ANI-3 4-3 ANI
A244 ANO0 Tag Name AOTAG0 ANO0 4-4 ANO
A262 CCI0 Tag Name CITAG0 CCI-0 4-5 CCI
A263 CCI1 Tag Name CITAG1 CCI-1 4-5 CCI
A280 CCO0 Tag Name COTAG0 CCO-0 4-6 CCO
A281 CCO1 Tag Name COTAG1 CCO-1 4-6 CCO
A298 ANI0 Engineering Units AIEU0 PERCENT 4-3 ANI
A299 ANI1 Engineering Units AIEU1 PERCENT 4-3 ANI
A300 ANI2 Engineering Units AIEU2 PERCENT 4-3 ANI
A301 ANI3 Engineering Units AIEU3 PERCENT 4-3 ANI
B001 Instrument Address (Datalink) AI 0 4-9 COMM
B002 Baud Rate BR 253 4-9 COMM
B012 Display Brightness Index BRIGHT 4 4-10 System
B100 Analog Output Source 0 4-4 ANO
B101 Control Contact 0 Output Source 110 4-6 CCO
B102 Control Contact 1 Output Source 134 4-6 CCO
B263 ANI0 Calibrate Zero CIZ0 Factory Set 4-3 ANI
B264 ANI1 Calibrate Zero CIZ1 Factory Set 4-3 ANI
B265 ANI2 Calibrate Zero CIZ2 Factory Set 4-3 ANI
B266 ANI3 Calibrate Zero CIZ3 Factory Set 4-3 ANI
B267 ANO0 Calibrate Zero COZ0 Factory Set 4-10 ANO
B269 ANI0 Digital Filter Index DFILT0 3 4-3 ANI
B270 ANI1 Digital Filter Index DFILT1 3 4-3 ANI
B271 ANI2 Digital Filter Index DFILT2 3 4-3 ANI
B272 ANI3 Digital Filter Index DFILT3 3 4-3 ANI
B335 ALRM0 Alarm Index (ANI0) AIX0 1 4-7 Alarm
Section 4
Table
Module
61
Page 66
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
DatapointTitleSymbolDefault
B340 ALRM1 Alarm Index (ANI1) AIX1 1 4-7 Alarm
B345 ALRM2 Alarm Index (ANI2) AIX2 1 4-7 Alarm
B350 ALRM3 Alarm Index (ANI3) AIX3 1 4-7 Alarm
C000 ANO0 Analog Output (Display Only) ANO0 0 4-4 ANO
C103 ALRM0 Alarm Limit 1 (ANI0) PL10 100 4-7 Alarm
C104 ALRM0 Alarm Limit 2 (ANI0) PL20 0 4-7 Alarm
C105 ALRM0 Alarm Dead Band (ANI0) ADB0 2 4-7 Alarm
C139 ALRM1 Alarm Limit 1 (ANI1) PL11 100 4-7 Alarm
C140 ALRM1 Alarm Limit 2 (ANI1) PL21 0 4-7 Alarm
C141 ALRM1 Alarm Dead Band (ANI1) ADB1 2 4-7 Alarm
C175 ALRM2 Alarm Limit 1 (ANI2) PL12 100 4-7 Alarm
C176 ALRM2 Alarm Limit 2 (ANI2) PL22 0 4-7 Alarm
C177 ALRM2 Alarm Dead Band (ANI2) ADB2 2 4-7 Alarm
C211 ALRM3 Alarm Limit 1 (ANI3) PL13 100 4-7 Alarm
C212 ALRM3 Alarm Limit 2 (ANI3) PL23 0 4-7 Alarm
C213 ALRM3 Alarm Dead Band (ANI3) ADB3s 2 4-7 Alarm
C256 ANI0 Engineering Span SPAN0 100 4-3 ANI
C257 ANI1 Engineering Span SPAN1 100 4-3 ANI
C258 ANI2 Engineering Span SPAN2 100 4-3 ANI
C259 ANI3 Engineering Span SPAN3 100 4-3 ANI
C276 ANI0 Zero ZERO0 0 4-3 ANI
C277 ANI1 Zero ZERO1 0 4-3 ANI
C278 ANI2 Zero ZERO2 0 4-3 ANI
C279 ANI3 Zero ZERO3 0 4-3 ANI
C296 ANI0 Calibrate Span CIS0 Factory Set 4-3 ANI
C297 ANI1 Calibrate Span CIS1 Factory Set 4-3 ANI
C298 ANI2 Calibrate Span CIS2 Factory Set 4-3 ANI
C299 ANI3 Calibrate Span CIS3 Factory Set 4-3 ANI
C300 ANO0 Calibrate Span COS0 Factory Set 4-4 ANO
C318 Totalizer 0 Scale Factor TMF0 16666 4-8 Totalizer
C319 Totalizer 0 Dropout Value TMD0 0 4-8 Totalizer
C320 Totalizer 1 Scale Factor TMF1 16666 4-8 Totalizer
C321 Totalizer 1 Dropout Value TMD1 0 4-8 Totalizer
C322 Totalizer 2 Scale Factor TMF2 16666 4-8 Totalizer
C323 Totalizer 2 Dropout Value TMD2 0 4-8 Totalizer
C324 Totalizer 3 Scale Factor TMF3 16666 4-8 Totalizer
C325 Totalizer 3 Dropout Value TMD3 0 4-8 Totalizer
H000 ANI0 Analog Input (Display Only) ANI0 0 4-3 ANI
H001 ANI1 Analog Input (Display Only) ANI1 0 4-3 ANI
H002 ANI2 Analog Input (Display Only) ANI2 0 4-3 ANI
H003 ANI3 Analog Input (Display Only) ANI3 0 4-3 ANI
H032 Totalizer 0 Actual Total (Display Only) TO0 0 4-8 Totalizer
Section 4
Table
Module
62
Page 67
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
DatapointTitleSymbolDefault
H033 Totalizer 1 Actual Total (Display Only) TO1 0 4-8 Totalizer
H034 Totalizer 2 Actual Total (Display Only) TO2 0 4-8 Totalizer
H035 Totalizer 3 Actual Total (Display Only) TO3 0 4-8 Totalizer
H048 Totalizer 0 Rollover Value TMM0 1000000 4-8 Totalizer
H049 Totalizer 1 Rollover Value TMM1 1000000 4-8 Totalizer
H050 Totalizer 2 Rollover Value TMM2 1000000 4-8 Totalizer
H051 Totalizer 3 Rollover Value TMM3 1000000 4-8 Totalizer
L000 CCI0 Contact Input CCI0 0 4-5 CCI
L001 CCI1 Contact Input CCI1 0 4-5 CCI
L024 CCO0 Contact Output (Display Only) CCO0 0 4-6 CCO
L025 CCO1 Contact Output (Display Only) CCO1 0 4-6 CCO
L110 ALRM0 Alarm A (ANI0) (Display Only) PA10 0 4-7 Alarm
L111 ALRM0 Alarm B (ANI0) (Display Only) PA20 0 4-7 Alarm
L134 ALRM1 Alarm A (ANI1) (Display Only) PA11 0 4-7 Alarm
L135 ALRM1 Alarm B (ANI1) (Display Only) PA21 0 4-7 Alarm
L158 ALRM2 Alarm A (ANI2) (Display Only) PA12 0 4-7 Alarm
L159 ALRM2 Alarm B (ANI2) (Display Only) PA22 0 4-7 Alarm
L182 ALRM3 Alarm A (ANI3) (Display Only) PA13 0 4-7 Alarm
L183 ALRM3 Alarm B (ANI3) (Display Only) PA23 0 4-7 Alarm
L224 Totalizer 0 Output Pulse TMP0 0 4-8 Totalizer
L225 Totalizer 1 Output Pulse TMP1 0 4-8 Totalizer
L226 Totalizer 2 Output Pulse TMP2 0 4-8 Totalizer
L227 Totalizer 3 Output Pulse TMP3 0 4-8 Totalizer
L232 Totalizer 0 Reset TMR0 0 4-8 Totalizer
L233 Totalizer 1 Reset TMR1 0 4-8 Totalizer
L234 Totalizer 2 Reset TMR2 0 4-8 Totalizer
L235 Totalizer 3 Reset TMR3 0 4-8 Totalizer
L256 No Parity CP 0 4-9 COMM
L257 Datalink Disable DLD 0 4-9 COMM
L258 No Byte Stuffing CB 0 4-9 COMM
L264 CCI0 Contact Input Invert IINV0 0 4-5 CCI
L265 CCI1 Contact Input Invert IINV1 0 4-5 CCI
L288 CCO0 Contact Output Invert OINV0 0 4-6 CCO
L289 CCO1 Contact Output Invert OINV1 0 4-6 CCO
L352 CCI0 Display Mode SMA 0 4-5 CCI
L353 CCI1 Display Mode SMB 0 4-5 CCI
L368 CCI0 Alarm Enable SAA 0 4-5 CCI
L369 CCI1 Alarm Enable SAB 0 4-5 CCI
L416 ANI0 0-5 V Input NOBIAS0 0 4-3 ANI
L417 ANI1 0-5 V Input NOBIAS1 0 4-3 ANI
L418 ANI2 0-5 V Input NOBIAS2 0 4-3 ANI
L419 ANI3 0-5 V Input NOBIAS3 0 4-3 ANI
Section 4
Table
Module
63
Page 68
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
DatapointTitleSymbolDefault
L440 ANI0 Square Root Signal SQRT0 04-3 ANI
L441 ANI1 Square Root Signal SQRT1 04-3 ANI
L442 ANI2 Square Root Signal SQRT2 04-3 ANI
L443 ANI3 Square Root Signal SQRT3 04-3 ANI
L472 ANO0 0-20 mA Output OZBASE0 04-4 ANO