Micromod 53IT5100B User Manual

Page 1
Micro-DCI 4-Channel Indicator Totalizer 53IT5100B
Instruction Manual
Page 2
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
The Company
MicroMod Automation & Controls is dedicated to improving customer efficiency by providing the most cost-effective, application-specific process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design and implementation.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivaled service and support.
The quality, accuracy and performance of the Company's products result from over 100 years experience, combined with a continuous program of innovative design and development to incorporate the latest technology.
Use of Instructions
Warning. An instruction that draws attention to the risk of injury or death.
Note. Clarification of an instruction or additional information.
Caution. An instruction that draws attention to the risk of
the product, process or surroundings.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of MicroMod Automation & Controls, Inc.
Licensing, Trademarks and Copyrights
MOD 30 and MOD 30ML are trademarks of MicroMod Automation & Controls, Inc. MODBUS is a trademark of Modicon Inc.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
The relevant sections of these instructions must be read carefully before proceeding.
1. Warning Labels on containers and packages must be observed.
2. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the information given or injury or death could result.
3. Normal safety procedures must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressure and/or temperature.
4. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling procedures must be used.
5. When disposing of chemicals, ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual may be obtained from the Company address on the back cover, together with servicing and spares information.
i Information. Further reference for more detailed information or technical details.
Page 3
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
INTRODUCTION ......................................................................................................................................... 1
1
1.1 PRODUCT OVERVIEW .............................................................................................................................. 1
1.2 SPECIFICATIONS ..................................................................................................................................... 6
2 INSTALLATION........................................................................................................................................... 9
2.1 INSPECTION ............................................................................................................................................ 9
2.2 LOCATION............................................................................................................................................... 9
2.3 MOUNTING.............................................................................................................................................. 9
2.3.1 General.......................................................................................................................................... 9
2.3.2 Mounting Procedure .................................................................................................................... 10
2.4 POWER & SIGNAL WIRING ..................................................................................................................... 13
2.4.1 Power Wiring ............................................................................................................................... 16
2.4.2 Field Signal Wiring ...................................................................................................................... 16
2.4.3 Datalink Communication ............................................................................................................. 17
2.5 FACTORY SET CALIBRATION .................................................................................................................. 17
2.6 GROUNDING ......................................................................................................................................... 17
3 DISPLAYS AND PUSH BUTTONS........................................................................................................... 19
3.1 OPERATOR DISPLAYS............................................................................................................................ 19
3.2 ALARM OVERLAY .................................................................................................................................. 22
3.2.1 Front Panel Pushbuttons............................................................................................................. 24
3.3 ENGINEERING MODE OVERLAYS ............................................................................................................ 25
3.3.1 Responding to the Prompt: KEY? ............................................................................................... 25
3.3.2 Displaying a Datapoint ................................................................................................................ 27
3.3.3 Altering a Datapoint..................................................................................................................... 28
4 CONFIGURATION PARAMETERS .......................................................................................................... 29
4.1 DATAPOINT TYPES ................................................................................................................................29
4.2 FACTORY STANDARD CALIBRATION........................................................................................................ 29
4.3 CONFIGURING THE DATABASE MODULES................................................................................................ 29
5 MAINTENANCE ........................................................................................................................................ 43
5.1 SERVICE APPROACH ............................................................................................................................. 43
5.2 PARTS REPLACEMENT........................................................................................................................... 43
5.3 CALIBRATION ........................................................................................................................................ 44
5.4 ERROR AND HARDWARE MALFUNCTION MESSAGES ................................................................................ 44
5.5 RESETTING THE INSTRUMENT ................................................................................................................ 44
5.6 PARTS LIST .......................................................................................................................................... 45
APPENDIX A: DISCRETE CONTACT OUTPUT CCO’S ................................................................................ 49
APPENDIX B : COMMUNICATIONS............................................................................................................... 53
APPENDIX C: DATABASE.............................................................................................................................. 60
Page 4
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
IMPORTANT NOTICE
All software, including design, appearances, algorithms and source code is copyrighted by MicroMod Automation & Controls, Inc. and is owned by MicroMod or its suppliers.
Page 5
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

1 INTRODUCTION

1.1 Product Overview

The 53IT5100B provides a suite of six operator displays to monitor process activity for up to four independent process variables and also provides integration and totalization for each of the four process variables. The displays are of three types: dynamic bar graph, digital readout, and alarm summary. There are three bar graph displays, two digital readout displays, and one alarm summary display. These include:
Quad Bar Graph Display (Channels 1-4)
Two Dual Bar Graph Displays (Channels 1&2 and Channels 3&4)
Quad Process Digital Readout Display
Quad Totalizer Digital Readout Display
Alarm Summary Display.
The operator displays are paged forward or back, in the order given, by pressing the F2 (page forward) or the F1 (page back) push button on the horizontal keypad of the instrument. The operator display suite is
illustrated in Figure 1-1 and the instrument horizontal keypad is identified in Figure 1-2.
Quad Bar Graph Display (Channels 1-4) - all four channels are arrayed across the display as bar graphs with the digital readout and measured units of a selected bar graph in the lower quadrant of the display. A bar graph digital readout with measured units is selected with the F3 push button, which moves a pointer to the base of each bar graph in the display every time it is pressed. In the illustration, upper and lower alarm limits appear with each 50 segment vertical axis. The measured units and alarm limits are selectable entries, as well as the mode of alarm reporting (e.g., High/Low, High only, Low only, High/Hi-Hi, Low/Lo-Lo, or none).
Dual Bar Graph Display (Channels 1&2) - two channels are arrayed across the display as bar graphs with the digital readout and measured units of each channel appearing beneath its bar graph. The channel tag names appear in the upper quadrant of the display. Each 50 segment vertical axis has a numeric range and alarm limits. The tag names, vertical axis numeric range (zero and span), measured units, alarm limits, and alarm mode are all selectable entries.
Dual Bar Graph Display (Channels 3&4) - is identical to Dual Bar Graph Display (Channels 1&2) except it displays process activity from channels 3 and 4.
Quad Process Digital Readout Display - is a process activity digital readout of all four channels
that is refreshed every second. The display is divided vertically into four quadrants, each one dedicated to a channel. Each channel readout has a tag name, numeric value, and measured units field. The tag names and measured units are identical to those selected for the bar graph displays.
Quad Totalizer Digital Readout Display - is an integrator accumulator digital readout of each of the four channels that is refreshed every second. The display is divided vertically into four sections, each one dedicated to a channel. Each channel totalizer has a tag name, accumulated value, and totalizer measured units field. The tag names and measured units are selectable entries.
Alarm Summary Display - presents six alarm states relevant to the four input channels and two contact inputs. The display has four partitions with the uppermost containing the display title. The word ALARM in the title flashes should an alarm condition occur with any one of the channel inputs or if a contact input is activated indicating an alarm. The specific channel or contact input in the alarm state is also differentiated from the rest of the display coincident with the ALARM banner flashing in the title of the display. The four channel inputs are listed together in the second partition, and partitions three and four are occupied by the two contact inputs. All six tag names for this display are selectable entries. There are also selectable entries that define how each contact input display message is differentiated from the others to indicate an alarm state.
As shown in Figure 1-2, the 53IT5100 contains a graphical dot matrix display; horizontal and vertical keypads; a MINI-DIN configuration port connector concealed behind the front panel pull-down door; terminals for signal
1
Page 6
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
input/output wiring and power wiring; and a compact instrument case that protects the instrument main printed circuit board and internal power supply.
The display is a 96 X 48 gas discharge dot matrix, contrasted orange-on-black to enhance visibility and ease of reading. The intensity is a range selectable entry from 0 to 7, with 0 being the brightest setting (see Table 4-10).
To the right of the display is the vertical keypad and directly beneath the display is the horizontal keypad. Both keypads have functioning push buttons that are dependent on the instrument mode of operation which can be either operator mode or engineering mode. Mode selection is made with the M the horizontal keypad. Engineering mode is entered to make the necessary selections for the operator displays and Datalink communications port; otherwise, the instrument is left in operator mode for process applications. The vertical keypad is dedicated only to engineering mode functions and has no effect in operator mode. Both keypads are described as follows:
Horizontal Keypad
ode push button on
Push Button Title Operator Mode Engineering Mode
F1 F2 F3
Title Engineering Mode
Ascending Character umber, or symbol appears on Select Descending
Select
Shift Left
Shift Right
Mode Operator/Engineering mode select; Alarm reset.
er
Page back to previous display. Back to previous entry line function. Page forward to next display. Pages the configure/display functions.
ter or display function. Moves Quad Bargraph pointer. Executes an en
Vertical Keypad
Displays one character at a time in ascending alphanumeric order; is released when the desired character, n the engineering mode data entry line. Displays one character at a time in descending alphanumeric order; is released when the desired character, n the engineering mode data entry line.
data entry line each time this push button is pressed.
Shifts characters on engineering mode data entry line position right each time this push button is pressed.
umber, or symbol appears on Charact
ering mode Shifts selected character one position left on the engine
one character
2
Page 7
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Quad Bar Graph (Chs. 1-4) Dual Bar Graph (Chs. 1&2) Dual Bar Graph (Chs. 3&4)
Quad Process Digital Readout Quad Totalizer Digital Readout Alarm Summary
Figure 1-1. Indicator/Totalizer Operator Displays
3
Page 8
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
INPUT/OUTPUT DIAGRAM
4
Figure 1-2. Indicator/Totalizer Illustrated Overview
Page 9
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Setup of the 53IT5100B can be done using the buttons on the horizontal and vertical keypads. It can also be done via the MicroTools configuration software package, Directly beneath the horizontal keypad and concealed behind the front panel pull-down door is the RS-232 Configuration Port which accept the configuration cable that provides interface between the instrument and MicroTools running on a personal computer. The configuration functions within MicroTools are limited to loaded functions of the 53IT5100B indicator/totalizer described in this manual.
The internal power supply provides power to the main board and output power for transmitters (24-26 V dc, 80 mA total available output for instrument and transmitters).
A simplified input/output diagram of the Indicator/Totalizer is provided in the upper left corner of Figure 1-2. As illustrated in the figure, the instrument can accept four Analog Inputs (ANI0-3) which are digitized as operands for firmware interpretation and execution (totalization). Each ANI has a square root extractor and can accept linear or squared signals of 0-20 mA, 0-5 V, 4-20 mA, or 1-5 V. Any one of the four analog inputs can be selected as the Analog Output (ANO0).
There are two contact inputs (CCI0 and CCI1 ) that have a closed recognition level of 1 V dc and open recognition level of 4-24 V dc. Each CCI indicates an alarm state, for example, a CCI can have a closed recognition level when a secondary pump is activated to support the primary pump in maintaining a proper tank level.
The totalizers provide a running total of each ANI input. The totalizers are incremented in ascending order every 0.05 seconds, but all four totalizers are refreshed on the display every second. Each ANI value can be independently adjusted by a scaling factor before being summed to the running total. The totalizer measured units, therefore, can differ from the process activity measured units as determined by the scaling factor entries for each channel. Also available as selectable totalizer entries are rollover and dropout values. The rollover value specifies a maximum positive value that causes the totalizer accumulator to reset to zero when the actual total reaches this value. An output pulse is strobed to a 1 for one scan each time the actual total reaches the rollover value. The dropout value specifies a minimum input value required to increment the running total.
All of the selectable entries for the Indicator/Totalizer are parameter entries to the database. The database is subdivided into modules composed of datapoints that are accessed by the instruction code as the instrument performs its functions. The database allows instrument functionality to be refined to specific process applications, as display attributes can be altered, input signal characteristics can be defined, each totalizer accumulated value can be flagged, and the instrument can be configured to properly match Datalink network communications requirements. A datapoint location is represented as an alphanumeric address, such as C103, which is the location to enter the value for the ANI0 upper alarm limit that is displayed on the Quad Bar Graph or Dual Bar Graph (Channels 1&2) displays. Datapoints are specified parenthetically in the illustration call-outs of Section 3 where the displays are described in detail. There are also illustrated procedures provided in Section 3 that show how a datapoint is displayed and configured. Definitions for all of the Indicator/Totalizer datapoints are provided in Section 4 and listed in alphanumeric order in Appendix C.
External alarm buzzers can be activated with the contact outputs (CCO0 and CCO1). Capability limits of each CCO are 50 mA maximum current flow when closed and 30 V dc maximum tolerance voltage when open. Flagged conditions, such as Totalizer 0 (ANI0) rollover pulse activation, can be specified as selectable entries in the CCO module of the database. Specific details for CCO database selections are described in Table 4-6 of Section 4, and typical circuit layouts for the CCOs are described in Appendix A.
Datalink is another independent serial communications connection for the Indicator/Totalizer. It provides a permanent connection to an RS-485 multi-drop network through which a host computer can access the instrument. The Datalink connection is made at TB1 of the rear terminal board, screw lugs 19 through 22.
5
Page 10
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

1.2 Model Number Breakdown

53IT51 __ __ B 2 1 A A A
Base Instrument
Power Requirements AC (120/240V) DC (24V)
Functional Requirements Standard Standard with Factory Configuration
Design Level
Enclosure Type DIN 72 x 144 mm bezel
Main Rear Terminal Requirement Standard
Chassis Standard
Safety Classification General Purpose
Conformal Coating Standard
6
Page 11
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

1.3 Specifications

Item Specification(s)
Power
Range (as specified in model number) 22 - 26 V dc
Power Consumption (ac/dc operation) 36 VA maximum
Internal Power Supply: Available Power Output for Transmitters Output Ripple 200 mV p-p maximum
Analog Input (ANI0-3) Signals (all analog in-puts are referenced to signal common)
Quantity 4 (ANI0, ANI1, ANI2, and ANI3) Signal Range 0 -5 V dc or 1 -5 V dc (0 -20 mA and 4 -20 mA dc respectively).
Input Impedance 1 megohm minimum for voltage inputs; value of ranging resistor
Measurement Accuracy ± 0.1% of span
Contact Input CCI0/1 Signals (are referenced to power common)
Quantity 2 (CCI0 and CCI1) Type discrete input Permitted Contact Resistance 100 ohm maximum Open/Close Contact Duration for open recognition: 0.05 seconds minimum
Contact Recognition Level Closed Contact Recognition Level Open 4 V dc to 24 V dc
Analog Output (ANO0) Signal (is referenced to power common)
Quantity 1 (ANO0) Signal Range 0 -20 mA dc (4 -20 mA dc typically) Load Range 0 - 750 ohms Accuracy ± 0.2% of span
Switch Output (CCO0, CCO1) Signals (are referenced to power common)
Quantity 2 (CCO0 and CCO1) Type Configuration solid state equivalent of a single pole single throw, normally
Voltage 30 V dc maximum Current 50 mA dc maximum
Datalink Communication
Sampling and Update Attributes
Program Scan Rate 0.05 seconds Analog Input Signal Sampling Rate 0.05 seconds
Contact Input Signal Sampling Rate 0.05 seconds Display Update 0.10 seconds Output Signal Update 0.05 seconds
108 - 132 V rms 216 - 264 V rms 50/60 Hz
25 V dc ± 1 V dc @ 80 mA maximum, short circuit protected.
NOTE: The rear terminal board has the appropriate resistors for ANI0 and ANI1.
for current signals.
for closed recognition: 0.05 seconds minimum 1 V dc maximum
solid state switch output
open or normally closed contacts referenced to common.
RS485, four wire, asynchronous; baud rates 300 to 28,800
7
Page 12
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Item Specification(s)
Environmental Characteristics
Controlled Environment Enclosed temperature controlled location (Class A and B per ISA-S71.01
Ambient Temperature Limits 4 -52°C (40 - 125°F)
Relative Humidity Limits 10 - 90% maximum
Temperature Effects on Accuracy ± 0.28% per 28°C (50°F) change from reference temperature 25°C (77°F)
Transient Immunity (all circuits) ANSI C37.90a - 1974/IEEE Std 472-974: Ring Wave: 1.5 MHz, 3 kV, 60
EMI Susceptibility SAMA PMC 33.1-1978: Class 3-abc: no effect at 30 V/m, at 27, 146, and
Enclosure Classification/Environment Panel Mounted Equipment: No enclosure rating. Designed to be installed
Shock 0.5g Vibration SAMA PMC 31.1-1978; point-to-point constant displacement 0.05 in. (1.27
Drop and Topple SAMA PMC 31.1-1978; Tilt 30 degrees from horizontal and fall freely to a
Safety Classification General Purpose: Complies with ANSI/ISA S82.01-1988, Safety Standard
Physical Characteristics
Material of Construction:
1985)
pulses/s for 2.0 s
446 MHz
in a user provided panel or enclosure.
Rated for installation in a Pollution Degree 2 location per U.L. 508­1989/Controlled Environment per CSA C22.2 No. 142-M1987. An indoor, temperature controlled location (Control Room or Shop Floor) where normally, only non-conductive pollution occurs; however, temporary conductivity caused by condensation may be expected.
Location in environments more severe than those stated requires supplementary protection
mm), 5 -14 Hz: 0.5 g, 14 - 200 Hz.
hard surface, all sides, front and back.
for Electrical and Electronic Test Measuring, Controlling and Related Equipment; General Requirements and S82.03-1988 Safety Standard for Electrical and Electronic Test, Measuring, Controlling and Related Equipment; Electrical and Electronic Process Measurement and Control Equipment.
FM Approved: Nonincendive for Class 1, Division 2, Groups A, B, C, & D, Temperature Code T3C 160 ° C.
Case Steel, black enamel
Circuit Boards Glass epoxy
Bezel ULTEM 1000 (Polyethermide Resin) Flammability-UL94 5V
Dimensions 2.844W x 5.656H x 12.906L (inches) 73W x 144H x 329L (mm)
Flush Panel Mounting 0.125 inch - 1 inch thickness (3.2 mm - 25.4 mm)
Electrical Connections Screw type terminal block at rear of casework
Weight 5 lbs (2.3 kg)
Front Panel Display 96 x 48 dot addressable
Front Panel Push Buttons 10 membrane type switches
8
Page 13
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

2 INSTALLATION

2.1 Inspection

A list of all items in the shipment is attached to the shipping container. Inspect the equipment upon arrival for damage that may have occurred during shipment. All damage claims should be reported to the responsible shipping agent before installation is attempted. If damage is such that faulty operation is likely to result, the MicroMod Customer Service Department should be notified.
Inspect the packing material before discarding it as a precaution to prevent loosing mounting hardware or special instructions that may have been included with the shipment. Normal care in the handling and installation of this equipment will contribute toward its satisfactory performance.

2.2 Location

The 53IT5100 is supplied with an enclosure designed specifically for indoor mounting. The installation site selected should be dry, well lighted, and vibration free. The ambient temperature should be stable and maintained within the specified minimum and maximum temperature limits listed in the Section 1, specifications of this Instruction Bulletin.
The instrument can be supplied for use with a 24 V dc supply or 120, 220 and 240 V ac line service. Instrument power requirements are given on the instrument data tag.

2.3 Mounting

2.3.1 General

It is normally not necessary to open the instrument case during installation. If the instrument must be removed from the case, refer to Section 5 for details. Incorrect procedures may damage the instrument. The instrument can be flush panel mounted, either as a single unit or side by side. Appropriate mounting hardware is supplied. Outline dimensions and panel cut-out requirements for case mounting are shown in Figure 2-1.
The dimensions given for spacing between instruments were selected on the basis of 1/8" thick panel strength. Panel strength must be considered when multiple case mounting is required. As the panel cut-out becomes longer it may be necessary to install supporting members. Because the panel area between instrument rows becomes weaker as the cut-out becomes longer to the point where the panel offers very little support. It is recommended that the 9 inch minimum center line dimension between horizontally mounted rows be increased as the number of units increases, or that the panel strip be stiffened.
The rear of the instrument case must be supported to prevent panel distortion. Mount an angle iron or similar member along the bottom of the cases as indicated in Figure 2-2. If the panel is to be moved the instrument cases must be tied down to prevent damage.
If multiple mounted instruments are installed in a panel that tilts back, it may be necessary to support the instruments so the panel does not sag. The downward weight should be supported by additional panel supports and/or by increasing panel thickness.
9
Page 14
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

2.3.2 Mounting Procedure

For single and multiple case mounting the instruments are furnished with a trim collar (mounting frame). Figure 2-2 illustrates the installation and use of the trim collar (mounting frame). Trim collars (mounting frames) are available in various sizes and are supplied to conform with the particular panel cut-out.
NOTE: Mounting brackets and trim collars (mounting frames) are packaged separately. Check the shipment carefully to prevent loss of mounting hardware.
To install single or multiple mounted instruments in a prepared panel cut-out, proceed as follows:
1. Remove the through-case shipping bolt.
2. Slip the trim collar (mounting frame) over the rear of the case and slide it forward to the front of the
case.
3. Slide the instrument case through the panel opening.
a. Single mounting case - support the weight of the case and attach the top and bottom
mounting brackets. Tighten the bracket screws.
b. Multiple mounted cases - spacer bars and self-adhesive pads must be used between the
cases, as shown in Figure 2-3. Start the installation from the right (when facing the panel), installing the spacers as each case is added. Also, as each case is positioned in place, install and tighten the top and bottom mounting brackets. Each case must be tight against the previous case.
NOTE: Spacers are not required on the outside of the right and left cases.
10
Page 15
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
NOTES:
1. DIMENSIONS ARE IN INCHES. DIMENSIONS IN BRACKETS ( ) ARE IN MILLIMIETERS.
2. DIMENSIONS GUARANTEED ON CERTIFIED PRINTS ONLY.
3. CASE MOUNTING HARDWARE SUPPLIED UNLESS OTHERWISE SPECIFIED.
4. THIS DRAWING IS THIRD-ANGLE PROJECTION AS SHOWN
5. UNLESS OTHERWISE INDICATED ALL TOLERANCES ARE ± 1/16 (1.6)
Figure 2.1 Outline Dimensions & Panel Cut-out Requirements
11
Page 16
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 2-2. Single or Multiple Panel Mounting
Figure 2-3. Intercase Spacing
12
Page 17
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

2.4 Power & Signal Wiring

PREPARATORY: The 53IT5100B can be configured for one to four analog inputs (ANI0-3), one analog
output (ANO0), two control contact inputs (CCI0 and 1), two control contact outputs (CCO0 and 1) and Datalink network interconnectivity. Therefore, prior to making electrical connections, the particular instrument configuration should be determined with all assigned inputs and outputs identified to assure proper signal routing.
Provisions for electrical interconnections are located at the rear of the instrument case. Under ideal conditions shielded cable may not be required. In noisy locations all system input, output and power wiring should be enclosed in electrical conduit. System interconnection cables (except for power cables) should be fabricated from 2-wire shielded signal cable. Signal transmission distance should not exceed the limit specified for the particular transmitter (refer to applicable technical literature provided for the respective device). Polarity must be observed when connecting the remote transmitters to the instrument.
The instrument has a vertically mounted terminal strip (TB1) for signal interconnections and a horizontally mounted terminal strip (TB2) for power wiring. Both terminal strips are located at the rear terminal board of the instrument case.
SNAP-OUT TERMINAL CONNECTORS
Both terminal strips, TB1 and TB2, have removable plug-in connectors. The upper connector for TB1 has screw lugs 1 through 12 and the lower connector has screw lugs 13 through 22. All of the screw lugs are on a single connector for TB2. To remove a signal connector, grasp it securely on both sides with the thumb and forefinger, rock it gently from top to bottom (not side to side) and pull it straight out. To remove the power connector, grasp the sides firmly with the thumb and forefinger, rock it gently from side to side and pull straight out.
NOTE: The screw lugs on the back of the instrument are designed for 12 – 24 AWG wire. It is important that the wire be stripped to expose 1/2 inch of conductor before installation.
WARNING! Instruments that are powered from an ac line service constitute a potential electric shock hazard to the user. Make certain that these system ac power lines are disconnected from the operating branch circuit before attempting electrical interconnections.
13
Page 18
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
14
Figure 2-4. Controller Rear Power and Signal Terminal Boards
Page 19
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 2-54. Datalink Installation Diagram
15
Page 20
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

2.4.1 Power Wiring

Refer to the instrument model number to verify the power input requirements:
53IT511nB21AAA – AC Power 53IT512nB21AAA – DC Power
2.4.1.1 DC Power
Reference Figure 2-4 and connect the remote 24 V dc power supply to the instrument as follows:
1.
Connect (+) input line, via remote SPST switch, to terminal L1.
2. Connect (-) input line to the system bus bar. The bus bar should be connected to a good earth ground (#8 AWG wire is recommended). Individual wires should be run from the controller Power Common (PC ) and Signal Common (SC ) terminals to the bus bar. The chassis should be grounded by connecting terminal G to earth ground.
NOTE: Use of a common bus bar is recommended to minimize potential voltage differences that may occur as the result of ground current loops, e.g., potential difference between separate signal grounds, power grounds, etc.
2.4.1.2 AC Power
Reference Figure 2-4 and connect the specified line service (110-120, 220-240 V ac, 50 or 60 Hz) to the
trument as follows:
ins
1. Connect the phase or hot line L, via a remote power disconnect switch or circuit breaker, to terminal L1.
2. Connect the neutral line N to terminal L2 for 110-120 V ac. Connect the neutral line N to terminal L3 for 220-240 V ac.
3. Connect Power Common to a good earth ground (#12 AWG wire is recommended). The instrument case should be grounded by connecting terminal G to earth ground at the source of supply (green/green-yellow ground).
All supply connections include surge protection rated at 275 V ac normal mode.
NOTE: To minimize possible interference, ac power wiring should be routed away from signal wiring.

2.4.2 Field Signal Wiring

2.4.2.1 Current/Voltage Input to AIN1 through AIN3
When the input signal is from a 4-20 mA current transmitter, a precision 250 ohms (+/-0.1%) resistor is required. (The resistor tolerance is critical, as the resistor is used to accurately convert the current signal from the transmitter, which is typically 4-20 mA, to a specified analog input voltage of 1 to 5 V dc). The back of the rear terminal board has the appropriate resistors (R1 and R2, respectively) for ANI0 and ANI1. Resistor for ANI2 and ANI3 are not supplied and must be installed as shown in the upper left corner of Figure 2-4. If the input signal is already a voltage signal, its corresponding resistor should be removed.
2.4.2.2 Contact Input to CCI0 and CCI1
Separate contact input signals to CCI0 and CCI1 can be used for alarm inputs. One side of each remote contact must be connected to power common as illustrated in Figure 2-4. Minimum opened or closed recognition time for a remote contact must be 0.05 seconds.
2.4.2.3 Current Output from ANO0
A current output signal is available for re-transmission of one of the input signals ANI0 through ANI3. Observe the proper polarity when connecting the output to another instrument.
2.4.2.4 Contact Outputs CCO0 and CCO1
Discrete contact outputs CCO0 and CCO1 are identified in Figure 2-4. Each discrete output is a solid state switch with a rating of 30 V dc, 50 mA maximum. A CCO is referenced to power common. When this contact is connected to an inductive load, an external arc suppression network is required for contact protection.
16
Page 21
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

2.4.3 Datalink Communication

Datalink is an interrogator/responder serial interface capable of supporting 32 instruments on a single network. It uses an RS485 physical interface. The Datalink wiring diagram for this instrument is provided as Figure 2-5. Complete coverage of the Datalink is provided in the SUPERVISOR-PC Instruction Bulletin 53SU5000.

2.5 Factory Set Calibration

Each unit contains individual factory set entries that calibrate the four analog inputs (ANI0 through ANI3) and analog output (ANO0). There is a calibration sheet supplied with each instrument that should be retained for future reference when the installation is completed. Reference Section 5.3 for additional information.

2.6 Grounding

Installations are expected to have access to an independent, high quality, noise-free point of earth reference. The system should be connected by a dedicated, low resistance (less than one ohm) lead wire directly to the installation’s point of earth reference. This ground reference is referred to as the Instrumentation Ground. If an instrumentation ground reference does not exist in the installation, an earth ground electrode should be established with an independent grounding rod or ground grid mesh.
17
Page 22
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
18
Page 23
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3 DISPLAYS AND PUSH BUTTONS

This section provides illustrations with item call-outs of the six operator displays, alarm overlays, and engineering mode overlays. Where applicable, datapoints are identified parenthetically with the display item call-outs. The datapoints are defined in Section 4. The front panel push button definitions are repeated in this section from Section 1, because they are used in the engineering mode display overlay examples to enter a key password, display a datapoint, and alter a datapoint.

3.1 Operator Displays

The Quad Bar Graph (Chs. 1-4), Dual Bar Graph (Chs. 1&2), Dual Bar Graph (Chs. 3&4), Quad Process Digital Readout, Quad Totalizer Digital Readout, and Alarm Summary operator displays are illustrated in Figures 3-1 through 3-6 respectively.
Alarm Index 0-3 and Alarm Dead Band 0-3 must alsobe configured: ANI0 Alarm Index (B335) ANI0 Dead Band (C105) ANI1 Alarm Index (B340) ANI1 Dead Band (C141) ANI2 Alarm Index (B345) ANI2 Dead Band (C177) ANI3 Alarm Index (B350) ANI3 Dead Band (C213)
Figure 3-1. Quad Bar Graph (Channels 1-4)
19
Page 24
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 3-2. Dual Bar Graph (Channels 1 & 2)
20
Figure 3-3. Dual Bar Graph (Channels 3 & 4)
Page 25
53IT5100B Indicator/Totalizer
Figure 3-4. Quad Process Digital Readout
INSTRUCTION MANUAL
Figure 3-5. Quad Totalizer Digital Readout
21
Page 26
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3.2 Alarm Overlay

Figure 3-6. Alarm Summary
Any one of the six operator displays can have the upper quadrant of the display overlaid with an ALARM indicator. An alarm indication warns of variation changes that exceed tolerance limits; the process may require immediate attention. In the five illustrations of Figure 3-7, the process variable exceeded Alarm Limit 1 for ANI1. The five illustrations show how the alarm state would manifest itself on each operator display. The alarm display for Dual Bar Graph (Chs. 3&4) is not illustrated, as the alarm banner appears in the identical manner as shown in the illustration for Dual Bar Graph (Chs. 1&2).
In the Quad Bar Graph (Chs. 1-4) illustration of Figure 3-7, the alarm banner blinks from normal to reverse video alternately with the ANI-1 graph scale (second from left). The ANI-1 graph scale does not appear in reverse video, but disappears and reappears on the display. In the Dual Bar Graph (Chs. 1&2) illustration of Figure 3-7, the alarm banner blinks from normal to reverse video alternately with the ANI-1 graph scale (on the right of the display). The ANI-1 graph scale does not appear in reverse video, but disappears and reappears on the display. The alarm banner in the Dual Bar Graph (Chs. 3&4) operator display (not shown) would alternately blink from normal to reverse video; however, graph scales for channels 3 and 4 would be unaffected.
In the Quad Process Digital Readout illustration of Figure 3-7, the alarm banner blinks from normal to reverse video.
In the Quad Totalizer Digital Readout illustration of Figure 3-7, the alarm banner blinks from normal to reverse video.
In the Alarm Summary illustration of Figure 3-7, the alarm banner and ANI-1 tag name blink from normal to reverse video independent of one another.
The alarm banner blinking is stopped by pressing the Mode () push button on the horizontal keypad; the alarm banner remains on the display, but does not blink, until the process variable returns to a value within the alarm limit (passed dead band).
22
Page 27
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 3-7. Alarm Overlays on the Operator Displays
23
Page 28
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3.2.1 Front Panel Pushbuttons

The front panel push buttons are repeated here from Section 1 because they are used in the engineering mode display overlay examples to enter a key password, display a datapoint, and alter a datapoint.
To the right of the display is the vertical keypad and directly beneath the display is the horizontal keypad. Both keypads have functioning push buttons that are dependent on the instrument mode of operation which can be either operator mode or engineering mode. Mode selection is made with the Mode () push button on the horizontal keypad. Engineering mode is entered to make the necessary selections for the operator displays and to configure the Datalink port; otherwise, the instrument is left in operator mode for process applications. The vertical keypad is dedicated only to engineering mode functions and has no effect in operator mode. Both keypads are described as follows:
Horizontal Keypad
Push Button Title Operator Mode Engineering Mode
F1 F2 F3
Title Engineering Mode
Ascending Character Select Descending Character Select
Shift Left
Shift Right
Mode Operator/Engineering mode select; Alarm reset.
Page back to previous display. Back to previous entry line function. Page forward to next display. Pages the configure/display functions. Moves Quad Bargraph pointer. Executes enter or display function.
Vertical Keypad
Displays one character at a time in ascending alphanumeric order; is released when the desired character, number, or symbol appears on the engineering mode data entry line. Displays one character at a time in descending alphanumeric order; is released when the desired character, number, or symbol appears on the engineering mode data entry line.
Shifts selected character one position left on the engineering mode data entry line each time this push button is pressed.
Shifts characters on engineering mode data entry line one character position right each time this push button is pressed.
24
Page 29
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3.3 Engineering Mode Overlays

The engineering mode overlays are used to make the necessary parameter entry selections for the operator displays and to configure the Datalink communications port. The entries are made to addressed datapoints via the overlay single edit line at the bottom of the display. It should be noted that engineering mode has a 20 second timeout if it is accessed and its functions (e.g., configure or display) are not used.

3.3.1 Responding to the Prompt: KEY?

When the password prompt KEY? appears, it indicates a password was set in the MicroTools software. The password can not be set via the front panel push buttons.
A password key is a maximum of 10 numeric characters (numbers 0-9 only). It does not impede display functions in engineering mode but must be unlocked to perform configuration functions. A password key is NOT SET FOR NEW INSTRUMENTS from the factory; therefore, if it is set, it must have been done locally. The password must first be obtained from the originator before the procedure in Table 3-1 can be used to access the engineering mode configuration function capabilities.
Table 3-1. Entering a Key Password
Step Press
Once
1
Shift
Result
Press to
Locate
Target
Char.
Result
Puts instrument in engineering mode.
2
3
F3
4
If DISPLAY appears instead of CONFIGURE, press 2.
Displays password query: KEY?
2
Puts first password number on entry line: KEY? .2.
5
.2Δ
6
7 Repeat step 6 until all of the password characters are entered.
.22Δ
2
2
8
F3
NOTE: Δ indicates Space
Shifts 2 and puts second password number on entry line: KEY? .22.
Shifts 22 and puts third password number on entry line: KEY? .222.
Enters the password key and displays the entry line: POINT . The engineering mode configuration function is now accessible for use.
25
Page 30
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
26
Figure 3-8. Engineering Mode Key Password Prompts
Page 31
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3.3.2 Displaying a Datapoint

The following procedure illustrates how to display the contents of datapoint C175, which is ANI2 Alarm Limit
1. Figure 3-9 contains supporting illustrations for the display procedure described in Table 3-2. (Notice in
these illustrations that ANI-2 Alarm Limit 1 is set at 80.)
Table 3-2. Procedure to Display a Datapoint
Step Press
Once
1
2
Shift
Result
Press to
Locate
If DISPLAY does not appear, press F2.
Target
Char.
Result
Puts instrument in engineering mode.
.CΔ
.C1Δ
.C17Δ
3
4
5
6
7
8 F3
9
F3
NOTE: Δ indicates Space
C
1
7
5
Displays entry line: POINT
Puts C on entry line: POINT .C.
Shifts C and puts 1 on entry line: POINT .C1.
Shifts C1 and puts 7 on entry line:
POINT .C17.
Shifts C17 and puts 5 on entry line: POINT .C175.
Enters address to display datapoint contents. The address with the contents are displayed as follows: C175 80.0000
Returns instrument to operator mode.
Figure 3-9. Displaying a Datapoint
27
Page 32
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

3.3.3 Altering a Datapoint

The procedure in Table 3-3 illustrates how to alter the contents of datapoint C175, which is ANI2 Alarm Limit 1, from 80 to 90. Figure 3-10 is provided to show the maximum input character length for the engineering mode edit line. The edit line can accept ten characters. The full ten character field is used primarily for the A type datapoint text strings (tag names). Reference Table 4-1 in Section 4 for information about the datapoint types. Note that in Figure 3-10, the PO is residual from the prompt POINT and that the character field string starts with 1 and ends with 0 (underlined in the figure) to illustrate 10 characters.
Table 3-3. Procedure to Alter a Datapoint
Step Press
Once
1
2
3 F3 Displays entry line: POINT
4
5
6
7
8 F3
9
Hold
10
11
12 F3
13
NOTE:
Shift Result
Puts instrument in engineering mode.
.CΔ
.C1Δ
.C17Δ
locator
.9Δ
Δ indicates Space
Press to Locate
If CONFIGURE does not appear, press F2.
 
Target Char.
C Puts C on entry line: POINT .C.
1
7
5
9
0
Result
Shifts C and puts 1 on entry line: POINT .C1.
Shifts C1 and puts 7 on entry line: POINT .C17.
Shifts C17 and puts 5 on entry line: POINT .C175.
Enters address to display datapoint contents. The address with the contents are displayed as follows: C175 80.0000
C175 contents shifted right; only the locator point remains on the entry line: C175 .
Puts 9 on entry line: C175 .9.
Shifts 9 and puts 0 on entry line: C175 .90.
Enters the value 90 in datapoint C175.
Returns instrument to operator mode.
Figure 3-10. Entry Line
Ten Character Field
28
Page 33
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

4 CONFIGURATION PARAMETERS

The configuration parameters provide the latitude to define the instrument’s personality attributes, so that while still functioning within its designed specifications, it can perform application requirements with greater refinement. Typical configuration parameters are the instrument’s indicator zero point and span, the display tag names, engineering units of the displayed process value, and alarm limits, etc. IT IS NOT NECESSARY TO DEFINE ALL OF THE CONFIGURATION PARAMETERS, as commonly used preset values may not have to be altered and certain parameter selections eliminate others.
Although all resident in a memory database as datapoints, the configuration parameters are clustered into modular groups that may have specific hardware identities (e.g., the ANI, ANO, CCI, and CCO circuits illustrated in Figures 4-1 through 4-4), or may represent software controlled functions that are not specific to any one hardware element.

4.1 Datapoint Types

A parameter can be any one of five data types. Each data type represents a specific data format: integers, alphanumeric text strings, etc. A database module containing multiple parameters can have a mix of data types. The data types are defined in Table 4-1 as follows:
Table 4-1. Datapoint Types
Type Byte
Size
L 1 Bit Represents a single binary bit that can have the value of 0 or 1. B 1 Represents a positive integer with values from 0 to 255.
C 3 Represents a real analog (floating point) value that has a resolution of one part in
H 5 Represents a high precision analog (floating point) value that has a resolution of
A 10 Represents a text string that can be 10 characters long.

4.2 Factory Standard Calibration

The instrument is shipped from the factory configured with all parameters set to the default values. The default values are listed in the parameter tables under the heading Default. The gray-tone shading in a default cell of a parameter indicates the contents of the datapoint are left unchanged after the database is returned to the default condition using the procedure described in Section 5.5. Examples of datapoints unaltered by default are the Calibrate Zero and Calibrate Span parameters which are factory set.

4.3 Configuring the Database Modules

The datapoints in the database modules must be changed to reflect required alterations in the factory standard configuration or when the instrument is re-configured. There are generally four datapoint parameter types contained in the eight database modules. The parameter types affect Datalink communications, display indications, input-output signals, and alarm conditions. The eight database modules are described in Table 4-
2. Although it is not an absolute criterion, it is assumed the modules will be configured in the table Item order;
however, if the instrument is to be connected to a Datalink network, item 7, Communication Module, should be configured first. By configuring the Communication Module first, the instrument can function on the Datalink and the remaining datapoint values can be entered via the Datalink interrogator (master). Reference the applicable instruction bulletin (e.g., IB 53HC3300, IB53WS5000, or IB 53SU5000) for the procedure.
Table 4-2 is also a pointer to the descriptions of the database modules; the descriptions are presented as Tables 4-3 through 4-10. (The gray tone shading in the default cell of a datapoint indicates the datapoint contents are left unchanged after default. See Section 5.5 for the default procedure.)
Format
32,768 (15 bits) and a dynamic range of ± 10
one part in 2 billion (31 bits) and a dynamic range of ± 10
38 .
38 .
29
Page 34
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-2. Database Modules
Item Title Purpose See
Table
1 Analog Input Module This module is used to configure the voltage input
characteristics (e.g., input voltage range) and how the input signal is interpreted (linear or square root representation).
2
Analog Output Module
3 Contact Input Module This module allows the action of the CCIs to be reversed
4 Contact Output
Module
5 Alarm Module The primary purpose of this module is to set the instrument’s
6 Totalizer Module The totalizers provide the sum of each analog input (ANI0-3).
7 Communication
Module
8 System Module This module is used to set the instrument tag name and the
The primary purpose of this module is to set the 0 - 20 mA output signal relative to the displayed percent output.
(normally a closed contact = 1, but can be change to = 0). This module allows the action of a CCOs to be reversed (normally a closed contact = 1, but can be changed to = 0).
Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead Band.
This module is used to set input scaling factors, rollover and dropout values, and to define display tags for each totalizer. This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection, etc.).
4-10
display brightness.
4-3
4-4
4-5
4-6
4-7
4-8
4-9
30
Page 35
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-3. Analog Input (ANI) Module
Purpose: This module is used to configure input voltage characteristics (e.g., input voltage range), and how the input signals are interpreted (linear or square root representation).
Title Symbol ANI Datapoint Default Attribute
Analog Input (Display Only)
Engineering Span
Engineering Zero
Digital Filter Index
0 - 5 V Input
Square Root Signal
Calibrate Zero
Calibrate Span
Tag Name
Engineering Units
ANI0 ANI1 ANI2 ANI3
SPAN0 SPAN1 SPAN2 SPAN3
ZERO0 ZERO1 ZERO2 ZERO3
DFILT0 DFILT1 DFILT2 DFILT3
NOBIAS0 NOBIAS1 NOBIAS2 NOBIAS3
SQRT0 SQRT1 SQRT2 SQRT3
CIZ0 CIZ1 CIZ2 CIZ3
CIS0 CIS1 CIS2 CIS3
AITAG0 AITAG1 AITAG2 AITAG3
AIEU0 AIEU1 AIEU2 AIEU3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
ANI0 ANI1 ANI2 ANI3
H000 H001 H002 H003
C256 C257 C258 C259
C276 C277 C278 C279
B269 B270 B271 B272
L416 L417 L418 L419
L440 L441 L442 L443
B263 B264 B265 B266
C296 C297 C298 C299
A224 A225 A226 A227
A298 A299 A300 A301
0 0 0 0
100 100 100 100
0 0 0 0
3 3 3 3
0 0 0 0
0 0 0 0
ANI-0 ANI-1 ANI-2 ANI-3
PERCENT
(ALL)
This is the value in engineering units of the measured input after all signal conditioning has been applied.
This determines the upper range the analog input represents in engineering units. The upper range value equals Engineering Zero plus Engineering Span.
This is the lower range value.
This controls a first order filter that is applied to the input signal. The time constant is entered as an index value as follows:
0 -No Smoothing (no effect)
1 -0.05 s
2 - 0.1 s 3 - 0.3 s 4 - 0.7 s 5 - 1.5 s
Setting this parameter to 1 indicates the input range is from 0 -5 volts (0 -20 mA). 0 indicates the input range is from 1 -5 volts (4 ­20 mA).
When a 0, it indicates the analog input signal should be interpreted linearly. When 1, it indicates the analog input signal should be interpreted as a square root representation of the value. When square root is selected, input signals less than 1% (10% input range) forces the input to its zero value.
This is the calibration zero adjustment. This parameter is factory set and should not need adjustment under normal operation. See Section 5.3 for adjustment. This is the calibration span adjustment. This parameter is factory set and should not need adjustment under normal operation.
See Section 5.3 for adjustment.
an assignable 10 character name for the analog input (ANI-0, ANI-1, ANI-2, ANI-3).
assignable for units of measure the ANI represents (e.g., GPM for gallons/minute).
6 - 3.1 s
7 - 6.3 s 8 -12.7 s 9 -25.5 s
10 -51.1 s
11 - 102 s 12 - 205 s 13 - 410 s 14 - 819 s
15 -1638 s
31
Page 36
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 4-1. ANI0-3 Figure 4-2. ANO0
NOTE: These figures are graphical representations of the signal conditioning that occurs on the instrument main board. They are provided for reference purposes only.
32
Page 37
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-4. Analog Output (ANO) Module
Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the displayed percent and to select the analog input signal (ANI0-3) that is to be routed to the analog output (ANO0).
Title Symbol ANO0
Datapoint
Analog Output (Display Only)
Analog Output Source
0 -20 mA Output
Calibrate Zero COZ0 B267
Calibrate Span
Tag Name AOTAG0 A244 ANO0 The assignable 10 character name for ANO0.
ANO0 C000 0 The value in this datapoint represents the
OZBASE0 L472 0
COS0 C300
B100 0 This parameter determines which analog input
Default Attribute
percent of output to be generated by hardware (e.g., 100% output = 20 mA).
(ANI0-3) is routed to the analog output (ANO0). The routing index values are as follows: 0 = ANI0 ANO0, 1 = ANI1 ANO0 2 = ANI2 ANO0, 3 = ANI3 ANO0
When a 0, the percentage output generates a 4
-20 mA signal. When set to 1 , the percentage output generates a 0 -20 mA signal.
These parameters are factory set and should not need adjustment under normal operation. See Section 5.3 for adjustment.
Figure 4-3. CCI0/1 Figure 4-4. CCO0/1
NOTE: These figures are graphical representations of the signal conditioning that occurs on the instrument main board. They are provided for reference purposes only.
33
Page 38
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-5. Contact Input Module (CCI)
Purpose: This module allows the action of the CCIs to be reversed (normally a closed contact = 1, but can be changed to = 0).
Datapoin
Title Symbol CCI
Contact Input (Display Only)
CCI0 CCI1
CCI0 CCI1
t Default Attribute
L000 L001
0 0
When open, a 4 -24 V dc input signal = 0 when IINV =
0. When open, a 4 -24 V dc input signal = 1 when IINV =
1. When closed, a < 1 V dc input signal = 1 when IINV = 0. When closed, a < 1 V dc input signal = 0 when IINV = 1.
Contact Input Invert Display Message Tag Name Display Mode Alarm Enable
Contact Input = 0 1 0 1
Display Mode
Display Mode
= 0
= 1
IINV0 IINV1
CCI0
CITAG0 CITAG1
SMA SMB
SAA SAB
CCI0 CCI1
CCI1 CCI0 CCI1 CCI0 CCI1 CCI0 CCI1
10 character message.
No message blinking and no Alarm Banner blinking.
Frst half (5 characters) of 10 character message sequence.
No message blinking and no Alarm Banner blinking.
L264 L265
A055 A056 A262 A263 L352 L353 L368 L369
Alarm Enable = 0 Alarm Enable = 1
10 character message in reverse video.
Second half (5 characters) of 10 character message sequence.
0 0 As shown above, it reverses the action of the CCI
datapoint.
ALARM A ALARM B
CCI-0 CCI-1
0 0
0 0
The messages for CCI0 and CCI1, respectively, on the Alarm Summary display. It is an assignable 10 character name for the contact control input. Display Mode, Alarm Enable, and Contact Input interact to alter the two five character segments of the Display Messages (A055 and A056) as shown in the table that follows:
10 character message.
First half (5 characters) of 10 character message sequence.
10 character message blinking in reverse video with Alarm Banner also blinking. (After pressing Mode push button, 10 character message appears in reverse video.) Second half (5 characters) of 10 character message blinking with Alarm Banner blinking. (After pressing Mode push button, 5 character message remains, but stops blinking.)
34
Page 39
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-6. Contact Output Module (CCO)
Purpose: This module allows the action of the CCOs to be reversed (normally a closed contact = 1, but can be changed to = 0) and is used to select the signal or condition that activates the CCO.
Title Symbol CCO Data-point Default Attribute
Contact Output (Display Only)
Contact Output Invert
Control Contact Output Source
Tag Name
CCO0 CCO1
OINV0 OINV1
COTAG0 COTAG1
CCO0 CCO1
CCO0 CCO1
CCO0 CCO1
CCO0 CCO1
L024 L025
L288 L289
B101 B102
A280 A281
0 0
0 0
110 134
CCO-0 CCO-1
If CCO = 0 and OINV = 0, then it is open. If CCO = 0 and OINV = 1, then it is closed. If CCO = 1 and OINV = 0, then it is closed. If CCO = 1 and OINV = 1, then it is open.
As shown above, it reverses the action of the CCO datapoint.
This parameter selects the signal or condition that activates the CCO. The routing index values are as follows:
110 Channel 0 Alarm A (PA10). 111 Channel 0 Alarm B (PA20). 134 Channel 1 Alarm A (PA11). 135 Channel 1 Alarm B (PA21). 158 Channel 2 Alarm A (PA12). 159 Channel 2 Alarm B (PA22). 182 Channel 3 Alarm A (PA13). 183 Channel 3 Alarm B (PA23). 0 Contact Input 0 (CCI0). 1 Contact Input 1 (CCI1). 224 Totalizer 0 Rollover Pulse (TMP0). 225 Totalizer 1 Rollover Pulse (TMP1). 226 Totalizer 2 Rollover Pulse (TMP2). 227 Totalizer 3 Rollover Pulse (TMP3). 65 Horn - latches the OR function of all
alarms (8 process alarm bits and 2 contact input alarms). 99 Non-latched OR function of all alarms (8 process alarm bits and 2 contact input alarms). It is cleared when the last alarm goes away.
An assignable 10 character name for the contact control output.
35
Page 40
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-7. Alarm Module
Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead Band.
Title Symbol CCO Data-point Default Attribute
This parameter defines the Alarm Active (PA1 & PA2) interpretation of the two Alarm Limits (PL1 & PL2). It is entered into the datapoint as an index value (0-5 ) as follows (n = 0-3 and correlates with ALRM0 through ALRM3): 0 PA1n: high when PV> PL1n PA2n: low when PV< PL2n
1 None 2 PA1n: high when PV> PL1n
PA2n: not affected 3 PA1n: not affected PA2n: low when PV< PL1n 4 PA1n: high when PV> PL1n PA2n: hi-hi when PV> PL2n 5 PA1n: low when PV< PL1n PA2n: lo-lo when PV< PL2n Examples are provided as follows:
Alarm Index
AIX0 AIX1 AIX2 AIX3
ALRM 0 ALRM 1 ALRM 2
ALRM
3
B335 B340 B345 B350
1 1 1 1
Alarm Examples:
B335 PV PL1
(C103)
0 >60 60 high Alarm Llimit 1 is set for 60: PV > 60 = high Alarm.
0 <40 40 low Alarm Limit 2 is set for 40: PV < 40 = low Alarm.
2 >60 60 high Alarm Limit 1 is set for 60: PV > 60 = high Alarm.
2 <40 40 N/A Alarm Limit 2 is set for 40: PV < 40 = no alarm.
3 >60 60 N/A Alarm Limit 1 is set for 60: PV > 60 = no alarm.
3 <40 40 Low
4 >60 60 high Alarm Limit 1 is set for 60: PV > 60 = high Alarm.
4 <70 70 hi-hi Alarm Limit 2 is set for 70: PV > 70 = hi-hi Alarm.
5 >40 40 low Alarm Limit 1 is set for 40: PV < 40 = low Alarm.
5 <30 30 low-low Alarm Limit 2 is set for 30: PV < 30 = lo-lo Alarm.
PL2 (C104) Alarm Notes
low Alarm Limit 2 is set for 40: PV < 40 = low Alarm.
36
Page 41
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-7. Alarm Module (continued)
Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead Band.
Title Symbol CCO Data-point Default Attribute Alarm A
(Display Only)
Alarm B (Display Only)
Alarm Limit 1
Alarm Limit 2
Alarm Dead Band
PA10 PA11 PA12 PA13
PA20 PA21 PA22 PA23
PL10 PL11 PL12 PL13
PL20 PL21 PL22 PL22
ADB0 ADB1 ADB2 ADB3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
ALRM
0
ALRM
1
ALRM
2
ALRM
3
L110 L134 L158 L182
L111 L135 L159 L183
C103 C139 C175 C211
C104 C140 C176 C212
C105 C141 C177 C213
0 0 0 0
0 0 0 0
100 100 100 100
0 0 0 0
2 2 2 2
When active, it indicates one of the four PA1 conditions (PA10-PA13) specified in its respective Alarm Index (AIX0-AIX3) has an alarm indication as determined by the index value (0-5) that was entered for the Alarm Index.
When active, it indicates one of the four PA2 conditions (PA20-PA23) specified in its respective Alarm Index (AIX0-AIX3) has an alarm indication as determined by the index value (0-5) that was entered for the Alarm Index.
These parameters are the points in engineering units at which the alarms are triggered.
This parameter sets the activation/deactivation gap for the alarm. This value in engineering units defines an area of hysteresis at the alarm point.
37
Page 42
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-8. Totalizer Module
Purpose: The totalizers provide a running total of each analog input (ANI0-3). This module is used to set input scaling factors, rollover and dropout values, and to define display tags for each totalizer.
Title Symbol TM Datapoint Default Attribute
Tag Name
Eng. Units
Scale Factor
TMTAG0 TMTAG1 TMTAG2 TMTAG3
TMEU0 TMEU1 TMEU2 TMEU3
TMF0 TMF1 TMF2 TMF3
TM0 TM1 TM2 TM3
TM0 TM1 TM2 TM3
TM0 TM1 TM2 TM3
A092 A094 A096 A098
A093 A095 A097 A099
C318 C320 C322 C324
TOTAL-0 TOTAL-1 TOTAL-2 TOTAL-3
UNITS UNITS UNITS UNITS
16666 16666 16666 16666
These are assignable 10 character names that appear on the totalizer display.
These are assignable 10 character names that appear on the totalizer display as the engineering units of measure.
The value of the input is multiplied by this parameter prior to being summed to the running total. The parameter is used for both scaling and time interval integration. For example, if ANI0 is in M gallons/day, in order to totalize in K gallons the scale factor (SF) would be: SF = [Units Conversion] X [Time Base Conversion] SF = [1000 K gal / M gal] X [(1 day/24 hrs) X (1 hr/60 mins) X (1 min/60 sec) X (1 sec/sample)] = 1000/86400 = 0.01157 NOTE: The time between totalizer updates is one second. The default value of 16666 uses the scale factor for time interval integration. Due to the internal timing of the instrument, a scale factor of 16666 will cause the rollover total to occur once every minute.
Rollover Value
Dropout Value
Reset
38
TMM0 TMM1 TMM2 TMM3
TMD0 TMD1 TMD2 TMD3
TMR0 TMR1 TMR2 TMR3
TM0 TM1 TM2 TM3
TM0 TM1 TM2 TM3
TM0 TM1 TM2 TM3
H048 H049 H050 H051
C319 C321 C323 C325
L232 L233 L234 L235
1000000 1000000 1000000 1000000
0 0 0 0
0 0 0 0
Specifies the maximum value of the totalizer. When the total reaches this value it is reset to
0.0; however totalizing continues. This value must be a positive number.
When the input value is less than this value, no change in the total occurs.
This parameter acts like a momentary switch. When this parameter is set to 1 the total is forced to 0.0 and then this parameter is reset to 0.
Page 43
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-8. Totalizer Module (continued)
Purpose: The totalizers provide a running total of each analog input (ANI0-3). This module is used to set input scaling factors, rollover and dropout values, and to define display tags for each totalizer.
Title Symbol TM Datapoint Default Attribute
Actual Total (Display Only)
Output Pulse
TO0 TO1 TO2 TO3
TMP0 TMP1 TMP2 TMP3
TM0 TM1 TM2 TM3
TM0 TM1 TM2 TM3
H032 H033 H034 H035
L224 L225 L226 L227
0 0 0 0
0 0 0 0
This parameter indicates the integer value of the total accumulation.
This value is pulsed to a 1 for one scan each time the actual total reaches the rollover value.
39
Page 44
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-9. Communication Module
Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection, etc.).
Title Symbol Datapoint Default Attribute
It identifies the address of this instrument on the Instrument Address
Baud Rate BR B002 253
No Parity CP L256 0
No Byte Stuffing
Datalink Disable
IA B001 0
CB L258 0
DLD L257 0
Datalink network. Each unit connected to the Datalink
network must have its own unique address. Valid
addresses are from 0 -31.
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments connected to
the same Datalink network. Datapoint values and their
corresponding baud rates are as follows:
Value Baud Rate Value Baud Rate
255 28800 9 28800 254 14400 8 14400 N/A N/A 7 19200 253 9600 6 9600 250 4800 5 4800 244 2400 4 2400 232 1200 3 1200 208 600 2 600 160 300 1 300 N/A N/A 0 110
This datapoint indicates if parity generation and
checking should be turned on or off. It is set to 0 for
even parity serial byte protocol. It is set to 1 for no parity
protocol.
When set to a 1, this datapoint disables the standard
communication protocol feature which inserts a 00
(NUL) byte after every 7EH (SOH) that is not the
beginning of a message. (This permits user written
communications software to determine the number of
bytes to expect in a response message.) It must be set
to 0 when using the Micro-DCI communications
software or equipment.
When set to 0 , it permits full Datalink communication
capabilities. When set to 1, it disables Datalink
communication capabilities.
40
Page 45
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table 4-10. System Module
Purpose: This module is used to set the instrument tag name and the display brightness.
System
Title Symbol
Module
Datapoint
Default Attribute
Display Brightness Index
Model Number Low (Display Only)
Model Number High (Display Only)
Unit Tag Name TAG A008 53IT5100
BRIGHT B012 4
A190 Factory Set
A191 Factory Set
This parameter controls the display screen intensity. A value of 0 is the brightest and a value of 7 is the dimmest intensity. Normal viewing setting is 4.
It contains the first ten characters of the model number.
It contains the last ten characters of the model number.
It is an assignable 10 character name for the system module (53IT5100).
41
Page 46
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
42
Page 47
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

5 MAINTENANCE

NOTE: The factory set calibration constants for ANI0-3 and ANO0 are applicable only for the main printed circuit board supplied in the particular instrument. This data is recorded on a calibration sheet supplied with the instrument. The data should be retained to facilitate easy field recalibration in the event one or more of the constants is inadvertently changed.

5.1 Service Approach

This instrument is a microprocessor based device; all mathematical computations, data manipulation, and sequencing operations are software controlled. After the instrument has been configured, normal operations are controlled via the front panel push buttons. Because the instrument does not have internal circuitry that requires field adjustment, diagnostic testing and preventive maintenance are not required.
Generally, when a process malfunction occurs, it usually manifests itself as an instrument problem even though it might be a defective process variable monitoring device, remote transmitter, or interconnecting wires. These associated remote devices should be checked before attempting instrument troubleshooting and repair.
Due to the complexity of microprocessor based instruments, attempting fault finding analysis to integrated circuits (ICs) on the main printed circuit board (PCB) is not recommended. The ICs are static sensitive and can be damaged if not properly handled. Also, when test probes are connected, even a momentary short across several IC pins with a probe tip can damage the IC. Therefore, only trained technicians familiar with CMOS technology and microprocessor functionality should be permitted to service the equipment.

5.2 Parts Replacement

WARNING: ALWAYS REMOVE POWER BEFORE ATTEMPTING TO INSTALL, DISASSEMBLE, OR SERVICE ANY OF THE EQUIPMENT. FAILURE TO REMOVE POWER MAY RESULT IN SERIOUS PERSONAL INJURY AND/OR EQUIPMENT DAMAGE.
Access to internal instrument parts is achieved by removing the front display panel. The front display panel can be removed by inserting a small screwdriver into the notch at the top center of the display and twisting the screwdriver to depress the retaining latch. The upper sides of the display are held and pulled forward as the latch is depressed. The cable at the rear of the front display panel is disconnected from its socket. The other cable end connects to the main printed circuit board. Replacing the display unit requires reconnecting the display end of the cable to the new front display panel, inserting the extended portion of the display panel into the instrument cabinet and latching it in place with a screwdriver.
After the front display panel is removed, the main printed circuit board can be accessed. The main printed circuit board also has the power supply as well as the microprocessor circuitry. To remove the main PCB, use its front edge board ejector to pull it free from the rear terminal board slot and carefully slide it from the case. Disconnect the front display panel flat ribbon cable from the main PCB. The replacement main PCB can now be installed by connecting the front display panel ribbon cable, sliding the PCB into the instrument case, seating it into the rear terminal board slot, and installing the front display panel.
NOTE: Power Supply Fuses
AC Power: 1A, 250 V, Fast Blow Schurter Type 034.3930 DC Power: 3A, 250 V, Slow Blow BEL Type 5TT3
For additional information, contact MicroMod Automation.
43
Page 48
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
NOTE: When communicating with MicroMod for replacement of the main PCB, reference the unit’s serial number to ensure the correct replacement assembly is supplied. The necessary ordering information is provided on the instrument data tag and on the manufacturing specification sheet supplied with that particular controller.
In the event of a hardware malfunction, a replacement PCB can be quickly substituted for the defective assembly to minimize downtime. Contact MicroMod for instructions before returning equipment. The defective PCB should be carefully packaged and returned, shipping charges prepaid, to the Repair Dept. of MicroMod Automation. Do not wrap PCBs in plastic, as it can cause static damage. It is suggested that the defective PCB be returned in the special bag in which the replacement module was supplied.

5.3 Calibration

The instrument’s analog inputs (ANI0-3) and output (ANO0) are extremely stable. They normally do not require recalibration. If it becomes necessary to recalibrate the instrument, due to the inadvertent change of the stored calibration values, then this can be accomplished by altering their respective datapoints. The calibration span and zero datapoint locations are as follows:
ANI0 ANI1 ANI2 ANI3 ANO0
Calibrate Zero B263 B264 B265 B266 B267 Calibrate Span C296 C297 C298 C299 C300

5.4 Error and Hardware Malfunction Messages

Entire Display Flashes - The watchdog timer has timed out.
CPU RAM FAILURE - IC U1 is bad.
ROM CHKS FAILURE - IC U3 is bad.

5.5 Resetting the Instrument

The instrument can be reset either by cycling the power, or by carefully pressing the reset button by inserting a thin wire, such as a paper clip, through the small hole in the upper left corner of the front bezel. (See Figure 1-2 for the location of the reset hole.) When the instrument restarts, it immediately checks to determine if any of the horizontal keypad push buttons are held pressed.
If the 1 push button is held pressed during instrument reset, the instrument enters a factory test
mode. The test mode can be exited by resetting the instrument again using the thin wire with no push
buttons pressed.
If the 2 push button is held pressed during instrument reset, the instrument database is set to the
defaulted values.
44
Page 49
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL

5.6 Parts List

The parts list is provided in Table 5-1 and the parts breakdown is illustrated in Figure 5-1. Note that these boards are for the 53IT5000B, not the 53IT5000A. Contact MicroMod for more information on spare parts availability for the 53IT5000 Design Level A.
Table 5-1. Parts List
Key Part Number Description
1 612B395U02 Case 2 686B803U06 Main Printed Circuit Board 3 685B736U01 Power Supply - 120/220/240 V ac, 50/60 Hz 3 685B736U02 Power Supply -24 V dc 4 698B179U03 Front Display 5 686B598U02 Rear Terminal Board
6 614C157U01 Cable - Display to Main PCB 355J093U01 Trim Collar for Single Case Contact Factory Trim Collar and Spacer for two or more cases 614B762U02 Kit of Three Plates for 3 X 6 Instrument Panel Cutout
45
Page 50
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
46
Figure 5-1. Illustrated Parts Breakdown
Page 51
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure 5-3. Communication ITB Pin Assignments
47
Page 52
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
48
Page 53
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Appendix A: Discrete Contact Output CCO’s
The discrete output CCOs are not mechanical contact closures but NPN Transistors that are analogous to single pole, single throw switches with one terminal connected to power common. This circuit type layout is commonly called an Open Collector Output. (See Figure A-1.)
Capability limits of each CCO are as follows:
50 mA maximum current flow when closed.  30 V dc maximum tolerance voltage when open.
A CCO will operate any external device that can be made to switch if it does not require more than 50 mA of current to the (+) terminal.
Typical uses for a CCO are to actuate a small relay, activate an external alarm buzzer, provide Contact Input (CCI) to another instrument, or provide output to an annunciator panel.
A CCO circuit is equivalent to an unpowered switch. If the 24 V dc supply of the instrument is not already fully loaded (see note), it can be used as a source of power for a CCO; otherwise, a separate, external dc supply must be used. In the upper circuit illustration of Figure A-2, the +24 V is obtained from screw lugs 1 or 4 of TB1 located on the instrument rear terminal board. (See Figure 2-4.)
NOTE: Power source - 80 mA maximum.
In Figure A-1, the switch is closed when the output logic bit (L24 for CCO0, L25 for CCO1) is set to 1, provided that its respective invert bit (L288 for CCO0, L289 for CCO1) is 0. The relay in Figure A-2 is energized when the output bit is set to 1 if the invert bit is 0. If the invert bit is set to 1, the output bit will cause the relay to de-energize when it is set to 1.
Figure A-2 also shows how a dc electromechanical relay is operated using an internal or external power source. There are many dc relays available with a coil resistance of 430 ohms or more. (Note: with the 24 V dc supply, a 430 ohm coil resistance will pass 50 mA of current.) Figure A-3 shows how several CCOs can be arranged in parallel using one power source so that any one CCO can actuate a single relay.
Figure A-4 shows a CCO used to control a solid state relay (see note). The resistor is added to the circuit from the power source to limit the current flow, and also to establish the voltage across the relay when the CCO switch is open.
NOTE: Several manufacturers are Crydom Division, International Rectifier and OPTO 22.
In Figure A-5, the CCO of one instrument is applied directly to the CCI of another instrument.
When the CCO closes, the CCI circuit of the second instrument is complete. An appropriate resistance is required in the second instrument, as it provides the power for its CCI operation.
49
Page 54
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Figure A-1. CCO Circuit and its Equivalent
50
Figure A-2. Circuits for Operating DC Relays
Page 55
53IT5100B Indicator/Totalizer
Figure A-3. Operating CCOs in Parallel
INSTRUCTION MANUAL
Figure A-4. CCO with Solid State Relay
Figure A-5. CCO Operating CCI Directly
51
Page 56
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
52
Page 57
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Appendix B : Communications
Two digital communication channels are provided with this instrument:
RS-232 serial configuration port, accessed via a 5 pin mini-DIN connector located under the pull-
down door on the front panel (see Figure 1-2). It is used to configure instrument parameters for selected operational characteristics. The parameters are configured with Micro-Tools software running on a customer supplied PC.
RS-422/485 serial interface used to connect the instrument to a Datalink multi-drop network. Interface
connection to the Datalink network is via the rear terminal board (TB1) of the instrument, pins 19 through 22, as shown in Section 2.
Information in this section applies to both the configuration port and the Datalink interface
The configuration port data rate is 9600 baud, with 8 data bits, and no parity.
The Datalink interface requires four conductors: a transmit pair and a receive pair. The voltage levels of each conductor pair conform to the EIA RS-422/485 standard. In accordance with this standard, the overall Datalink network distance is limited to 4000 feet when #24 AWG twisted pair wire is used to interconnect the nodes. Adapters are available to convert RS-422/485 to RS-232 or 20 mA current loops.
In a Datalink network, the instruments communicate as Responders to host queries. The host or PC functions as the Interrogator and acts as the central control point for the Datalink network. A maximum of 32 addressable instruments can be connected to a Datalink network.
53
Page 58
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table B-1. Communication Module
Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection, etc.).
Title Datapoint Setup Default Attribute
It identifies the address of this instrument on the Instrument Address
Baud Rate B02
No Parity L256
No Byte Stuffing
Datalink Disable
NOTE : S = Select a value from the Attribute column. Use all other datapoint values as shown.
B01
L258
L257
S
S
0
0
0
0
253
0
0
0
Datalink network. Each unit connected to the Datalink
network must have its own unique address. Valid
addresses are from 0 -31.
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments connected to
the same Datalink network. Datapoint values and their
corresponding baud rates are as follows:
Value Baud Rate Value Baud Rate
255 28800 9 28800 254 14400 8 14400 N/A N/A 7 19200 253 9600 6 9600 250 4800 5 4800 244 2400 4 2400 232 1200 3 1200 208 600 2 600 160 300 1 300 N/A N/A 0 110
This datapoint indicates if parity generation and
checking should be turned on or off. It is set to 0 for
even parity serial byte protocol. It is set to 1 for no parity
protocol.
When set to a 1, this datapoint disables the standard
communication protocol feature which inserts a 00
(NUL) byte after every 7EH (SOH) that is not the
beginning of a message. (This permits user written
communications software to determine the number of
bytes to expect in a response message.) It must be set
to 0 when using the Micro-DCI communications
software or equipment.
When set to 0 , it permits full Datalink communication
capabilities. When set to 1, it disables Datalink
communication capabilities.
54
Page 59
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Protocol
The Datalink protocol requires the host to initiate all transactions. There are two basic categories for all of the Datalink message types: Interrogate - used to read data from an addressed instrument, and Change used to alter a value in an addressed instrument. The addressed instrument decodes the message and provides an appropriate response. The protocol definitions for the Datalink message types are provided in Table B-2.
Table B-2. Message Field Definitions
Symbol Title Definition SOH Start of Header This character, 7E, denotes the beginning of a message.
The address of the instrument responding to the transaction. It must
I.A. Instrument Address
CMD Command
NUM Number LO-ADD Lower Address Bits The least significant 8 bits of a 16 bit instrument address. HI-ADD Higher Address Bits The most significant 8 bits of a 16 bit instrument address. DATA An 8 bit data byte. XXXX Represents a variable number of data bytes.
MASK
STATE
Longitudinal Redundancy
LRC
Character
Message Types
The types of messages that are sent between the host and the Datalink network instrument are formatted as follows:
be within a range of 00-1F (00-31 decimal). Is the operation to be performed or a description of the message that
follows the Command-I.A. byte. The Command-I.A. byte has two fields: the Command field (3 bits), and the I.A. field (5 bits). There are five commands, listed as follows: Interrogate Change Change Bits Acknowledge Response The commands are covered in Section B.1.3, Message Types.
The number of data bytes transferred or requested. The NUM must be in a range of 00-32.
An 8 bit byte where each bit, called a flag, is dedicated to an event that is permitted or prohibited, depending on the flag setting. If the flag is set to 0, the event is permitted. If the flag is set to 1, the event is prohibited.
Represents the bit settings of a particular byte: which bits are set to 1, and which bits are set to 0.
Is a character written at the end of the message that represents the byte content of the message and is checked to ensure data was not lost in transmission. It is the sum of all bytes Modulo 256 of the message not including the SOH character or its own bit settings (LRC).
HOST TO INSTRUMENT:
1. INTERROGATE - This message requests up to 20H consecutively stored bytes, beginning at the specified memory address location of the addressed instrument.
01111110 E0H + I.A. NUM LO ADD HI ADD LRC
2. CHANGE - This message sends up to 20H bytes of new data to the addressed instrument.
01111110 A0H + I.A. NUM LO ADD HI ADD Data 1 XXXXXXXXX Data N LRC
3. CHANGE BITS - This message alters only the specified bits in the specified bytes in the addressed instrument. (NUM = 2n)
01111110 C0H + I.A. NUM LO ADD HI ADD Mask 1 State 1 XXXX Mask N State N LRC
55
Page 60
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
4. ACKNOWLEDGE - This message signals the addressed instrument that its last echoed change message was received correctly; the instrument performs the change requested.
01111110 80H + I.A.
INSTRUMENT TO HOST:
1. RESPONSE - This message furnishes the data requested by the INTERROGATE command of the Host. It is also used to echo back the previous CHANGE message of the Host.
01111110 20H + I.A. NUM LO ADD HI ADD Data 1 XXXXX Data N LRC
Communication Transaction Examples
Transaction A Example - Host requests 9 bytes of data beginning at hexadecimal memory address 1000H
from the instrument at Datalink address 03.
1. Host sends INTERROGATE message.
01111110 11100011 00001001 00000000 00010000 11111100
SOH
2. Instrument sends RESPONSE message.
01111110 00100011 00001001 00000000
SOH
Transaction B Example - Host or SUPERVISOR-PC sends two bytes of new data, to be loaded into the instrument at Datalink address 03 beginning at hexadecimal memory address 1000H.
1. Host sends CHANGE message.
01111110 10100011 00000010 00000000
SOH
2. Instrument sends RESPONSE message.
01111110 00100011 00000010 00000000
Command
+ I.A.
Command
+ I.A.
Command
+ I.A.
NUM LO ADD HI ADD LRC
00010000 XXXXX XXXXX XXXXX LRC
NUM LO ADD HI ADD Data 1 ................. Data 9
00010000 0000100
0
NUM LO ADD HI ADD Data 1 Data 2 LRC
00010000 00001000 00001100
00001100
1100100
1
0100100
1
SOH
3. Host sends ACKNOWLEDGE message.
01111110 10000011
SOH Command
56
Command
+ I.A.
NUM LO ADD HI ADD Data 1 Data 2 LRC
Page 61
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
+ I.A.
4. Instrument performs the change requested at end of the current program scan.
57
Page 62
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Calculating Data Addresses
If communications software must be generated to accommodate unique Datalink applications requirements, then the instrument memory address scheme must be known for proper data bit (e.g., L data type) and data byte (e.g., B, C, H, and A data types) memory location determination.
NOTE: Numbers used in this section that are expressed in hexadecimal notation (base 16) are identified with an H after the number.
This memory address scheme applies only if a 6 is in memory address location 8002H. Memoryaddress location 8002H must be read and if it contains a 6, then the address scheme that is described in Table B-3 should be applied for this instrument.
Table B-3. Instrument Memory Address Scheme
Data
Type
B 200H 1 Represents a positive integer with
Base
Memory
Address
Byte
Size
Data Format Address Calculation Algorithm
values from 0 to 255.
Address = B Base + (B Number) = 200H + (B Number) Address example: B012 location = 200H + 12D = 200H + CH = 20CH
L 500H 1 Bit A single binary bit with a logical
value of 0 or 1. L datapoints are packed 8 to a byte.
C 600H 3 Represents floating point values that
have a resolution of one part in 32,768 (15 bits) and a dynamic range of ± 1038 . The first two bytes represent a 2’s complement notation in fractional form (2-n ) whose absolute value is between 0.5 and
0.9999. The third byte is the power of 2 in 2’s complement notation. Floating point example: 64H 00H 07H = 100D (Decimal) 64H = 0110 0100, fractional binary weights left to right are 0 = 2’s complement positive, 1 = 2-1 = 1/2 = 0.5, 1 = 2-2 = 1/4 = 0.25, 0=0, 0=0, 1 = 2-5 = 1/32 = 0.03125, 0=0, and 0=0. 64H =
0.5+0.25+0.03125 = 0.78125.07H = 128D. 128D X 0.78125D = 100.
Address = L Base + (L Number/8) = 500H + (L Number/8) Remainder = bit position in byte
Address example: L014 location = 500H + 14/8 = 501H, bit 6 (remainder).
Address = C Base + (3 X C Number) = 600H + (3 X C Number)
Address example: C011 location 600H + (3 X 11) = 600H + 33D = 600H + 21H = 621H.
58
Page 63
53IT5100B Indicator/Totalizer
Table B-3. Instrument Memory Address Scheme (continued)
Data
Type
H F00H 5 Represents high precision floating
A (F)* 1400H 10 (A)
Base
Memory
Address
Byte
Size
5 (F)*
Data Format Address Calculation Algorithm
point values that have a resolution of one part in 2 billion (31 bits) and a dynamic range of ± 1038 . The first four bytes represent a 2’s complement notation in fractional form (2-n) whose absolute value is between 0.5 and 0.9999. The fifth byte is the power of 2 in 2’s complement notation. Floating point example: 9CH 00H 00H 00H 07H =
-100. The 2’s complement notation bit in the 9 = 1 (1001) indicating a negative number; therefore, 9C must be re-complemented . 9C = 1001 1100, change 1’s to 0’s and 0’s to 1’s = 0110 0011 and add 1= 0110 0100 (64H). Fractional binary weights left to right for 0110 0100 are 0 = 2’s complement positive, 1 = 2-1 = 1/2 = 0.5, 1 = 2-2 = 1/4 =
0.25, 0=0, 0=0, 1= 2-5= 1/32 =
0.03125, 0=0, 0=0. 64H = 0.5 +
0.25 + 0.03125 = 0.78125. 07H=128D, 128D X 0.78125D =
100. A negative sign is assigned (-
100) because the original 2’s complement binary bit in the 9 (1001) of 9C was set indicating a negative number. The A data format represents text strings that are 10 characters long. The F data format represents text strings that are 5 characters long.
Address = H Base + (5 X H Number) = F00H + (5 X H Number)
Address example: H001 location F00H + (5 X 1) = F00H + 5D = F00H + 5H = F05H.
Address = A Base + (10 X Number) = 1400H + (10 X Number) (for both A and F data types)
Address example: A015 location 1400H + (10 X 15) = 1400H + 150D = 1400H + 96H 1496H.
INSTRUCTION MANUAL
59
Page 64
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Appendix C: Database
The database contains five datapoint types. Each datapoint type represents a specific data format: whole integers, alphanumeric text strings, etc. The datapoint types are defined in Table C-1 and the database is listed in alphanumeric order in Table C-2. The gray-tone shading in the Symbol cell of a datapoint indicates the datapoint does not have an assigned symbol.
Table C-1. Datapoint Types
Type Qty
L 40 1 Bit Represents a single binary bit that can have the value of 0 or 1.
B 19 1 Represents a positive integer with values from 0 to 255.
Byte
Size
Format
C 34 3
H 12 5
A 26 10 Represents a text string that can be 10 characters long.
Represents a real analog (floating point) value that has a resolution of one part in 32,768 (15 bits) and a dynamic range of ± 1038 .
Represents a high precision analog (floating point) value that has a resolution of one part in 2 billion (31 bits) and a dynamic range of ± 10
38
60
Page 65
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database
Datapoint Title Symbol Default
A008 Unit Tag Name TAG 53IT5100 4-10 System A055 CCI0 Display Message ALARM A 4-5 CCI A056 CCI1 Display Message ALARM B 4-5 CCI A092 Totalizer 0 Tag Name TMTAG0 TOTAL-0 4-8 Totalizer A093 Totalizer 0 Engineering Units TMEU0 UNITS 4-8 Totalizer A094 Totalizer 1 Tag Name TMTAG1 TOTAL-1 4-8 Totalizer A095 Totalizer 1 Engineering Units TMEU1 UNITS 4-8 Totalizer A096 Totalizer 2 Tag Name TMTAG2 TOTAL-2 4-8 Totalizer A097 Totalizer 2 Engineering Units TMEU2 UNITS 4-8 Totalizer A098 Totalizer 3 Tag Name TMTAG3 TOTAL-3 4-8 Totalizer A099 Totalizer 3 Engineering Units TMEU3 UNITS 4-8 Totalizer A190 Model Number Low (Display Only) (factory set) 4-10 System A191 Model Number High (Display Only) 4-10 System A224 ANI0 Tag Name AITAG0 ANI-0 4-3 ANI A225 ANI1 Tag Name AITAG1 ANI-1 4-3 ANI A226 ANI2 Tag Name AITAG2 ANI-2 4-3 ANI A227 ANI3 Tag Name AITAG3 ANI-3 4-3 ANI A244 ANO0 Tag Name AOTAG0 ANO0 4-4 ANO A262 CCI0 Tag Name CITAG0 CCI-0 4-5 CCI A263 CCI1 Tag Name CITAG1 CCI-1 4-5 CCI A280 CCO0 Tag Name COTAG0 CCO-0 4-6 CCO A281 CCO1 Tag Name COTAG1 CCO-1 4-6 CCO A298 ANI0 Engineering Units AIEU0 PERCENT 4-3 ANI A299 ANI1 Engineering Units AIEU1 PERCENT 4-3 ANI A300 ANI2 Engineering Units AIEU2 PERCENT 4-3 ANI A301 ANI3 Engineering Units AIEU3 PERCENT 4-3 ANI B001 Instrument Address (Datalink) AI 0 4-9 COMM B002 Baud Rate BR 253 4-9 COMM B012 Display Brightness Index BRIGHT 4 4-10 System B100 Analog Output Source 0 4-4 ANO B101 Control Contact 0 Output Source 110 4-6 CCO B102 Control Contact 1 Output Source 134 4-6 CCO B263 ANI0 Calibrate Zero CIZ0 Factory Set 4-3 ANI B264 ANI1 Calibrate Zero CIZ1 Factory Set 4-3 ANI B265 ANI2 Calibrate Zero CIZ2 Factory Set 4-3 ANI B266 ANI3 Calibrate Zero CIZ3 Factory Set 4-3 ANI B267 ANO0 Calibrate Zero COZ0 Factory Set 4-10 ANO B269 ANI0 Digital Filter Index DFILT0 3 4-3 ANI B270 ANI1 Digital Filter Index DFILT1 3 4-3 ANI B271 ANI2 Digital Filter Index DFILT2 3 4-3 ANI B272 ANI3 Digital Filter Index DFILT3 3 4-3 ANI B335 ALRM0 Alarm Index (ANI0) AIX0 1 4-7 Alarm
Section 4
Table
Module
61
Page 66
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
Datapoint Title Symbol Default
B340 ALRM1 Alarm Index (ANI1) AIX1 1 4-7 Alarm B345 ALRM2 Alarm Index (ANI2) AIX2 1 4-7 Alarm B350 ALRM3 Alarm Index (ANI3) AIX3 1 4-7 Alarm C000 ANO0 Analog Output (Display Only) ANO0 0 4-4 ANO C103 ALRM0 Alarm Limit 1 (ANI0) PL10 100 4-7 Alarm C104 ALRM0 Alarm Limit 2 (ANI0) PL20 0 4-7 Alarm C105 ALRM0 Alarm Dead Band (ANI0) ADB0 2 4-7 Alarm C139 ALRM1 Alarm Limit 1 (ANI1) PL11 100 4-7 Alarm C140 ALRM1 Alarm Limit 2 (ANI1) PL21 0 4-7 Alarm C141 ALRM1 Alarm Dead Band (ANI1) ADB1 2 4-7 Alarm C175 ALRM2 Alarm Limit 1 (ANI2) PL12 100 4-7 Alarm C176 ALRM2 Alarm Limit 2 (ANI2) PL22 0 4-7 Alarm C177 ALRM2 Alarm Dead Band (ANI2) ADB2 2 4-7 Alarm C211 ALRM3 Alarm Limit 1 (ANI3) PL13 100 4-7 Alarm C212 ALRM3 Alarm Limit 2 (ANI3) PL23 0 4-7 Alarm C213 ALRM3 Alarm Dead Band (ANI3) ADB3s 2 4-7 Alarm C256 ANI0 Engineering Span SPAN0 100 4-3 ANI C257 ANI1 Engineering Span SPAN1 100 4-3 ANI C258 ANI2 Engineering Span SPAN2 100 4-3 ANI C259 ANI3 Engineering Span SPAN3 100 4-3 ANI C276 ANI0 Zero ZERO0 0 4-3 ANI C277 ANI1 Zero ZERO1 0 4-3 ANI C278 ANI2 Zero ZERO2 0 4-3 ANI C279 ANI3 Zero ZERO3 0 4-3 ANI C296 ANI0 Calibrate Span CIS0 Factory Set 4-3 ANI C297 ANI1 Calibrate Span CIS1 Factory Set 4-3 ANI C298 ANI2 Calibrate Span CIS2 Factory Set 4-3 ANI C299 ANI3 Calibrate Span CIS3 Factory Set 4-3 ANI C300 ANO0 Calibrate Span COS0 Factory Set 4-4 ANO C318 Totalizer 0 Scale Factor TMF0 16666 4-8 Totalizer C319 Totalizer 0 Dropout Value TMD0 0 4-8 Totalizer C320 Totalizer 1 Scale Factor TMF1 16666 4-8 Totalizer C321 Totalizer 1 Dropout Value TMD1 0 4-8 Totalizer C322 Totalizer 2 Scale Factor TMF2 16666 4-8 Totalizer C323 Totalizer 2 Dropout Value TMD2 0 4-8 Totalizer C324 Totalizer 3 Scale Factor TMF3 16666 4-8 Totalizer C325 Totalizer 3 Dropout Value TMD3 0 4-8 Totalizer H000 ANI0 Analog Input (Display Only) ANI0 0 4-3 ANI H001 ANI1 Analog Input (Display Only) ANI1 0 4-3 ANI H002 ANI2 Analog Input (Display Only) ANI2 0 4-3 ANI H003 ANI3 Analog Input (Display Only) ANI3 0 4-3 ANI H032 Totalizer 0 Actual Total (Display Only) TO0 0 4-8 Totalizer
Section 4
Table
Module
62
Page 67
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
Datapoint Title Symbol Default
H033 Totalizer 1 Actual Total (Display Only) TO1 0 4-8 Totalizer H034 Totalizer 2 Actual Total (Display Only) TO2 0 4-8 Totalizer H035 Totalizer 3 Actual Total (Display Only) TO3 0 4-8 Totalizer H048 Totalizer 0 Rollover Value TMM0 1000000 4-8 Totalizer H049 Totalizer 1 Rollover Value TMM1 1000000 4-8 Totalizer H050 Totalizer 2 Rollover Value TMM2 1000000 4-8 Totalizer H051 Totalizer 3 Rollover Value TMM3 1000000 4-8 Totalizer L000 CCI0 Contact Input CCI0 0 4-5 CCI L001 CCI1 Contact Input CCI1 0 4-5 CCI L024 CCO0 Contact Output (Display Only) CCO0 0 4-6 CCO L025 CCO1 Contact Output (Display Only) CCO1 0 4-6 CCO L110 ALRM0 Alarm A (ANI0) (Display Only) PA10 0 4-7 Alarm L111 ALRM0 Alarm B (ANI0) (Display Only) PA20 0 4-7 Alarm L134 ALRM1 Alarm A (ANI1) (Display Only) PA11 0 4-7 Alarm L135 ALRM1 Alarm B (ANI1) (Display Only) PA21 0 4-7 Alarm L158 ALRM2 Alarm A (ANI2) (Display Only) PA12 0 4-7 Alarm L159 ALRM2 Alarm B (ANI2) (Display Only) PA22 0 4-7 Alarm L182 ALRM3 Alarm A (ANI3) (Display Only) PA13 0 4-7 Alarm L183 ALRM3 Alarm B (ANI3) (Display Only) PA23 0 4-7 Alarm L224 Totalizer 0 Output Pulse TMP0 0 4-8 Totalizer L225 Totalizer 1 Output Pulse TMP1 0 4-8 Totalizer L226 Totalizer 2 Output Pulse TMP2 0 4-8 Totalizer L227 Totalizer 3 Output Pulse TMP3 0 4-8 Totalizer L232 Totalizer 0 Reset TMR0 0 4-8 Totalizer L233 Totalizer 1 Reset TMR1 0 4-8 Totalizer L234 Totalizer 2 Reset TMR2 0 4-8 Totalizer L235 Totalizer 3 Reset TMR3 0 4-8 Totalizer L256 No Parity CP 0 4-9 COMM L257 Datalink Disable DLD 0 4-9 COMM L258 No Byte Stuffing CB 0 4-9 COMM L264 CCI0 Contact Input Invert IINV0 0 4-5 CCI L265 CCI1 Contact Input Invert IINV1 0 4-5 CCI L288 CCO0 Contact Output Invert OINV0 0 4-6 CCO L289 CCO1 Contact Output Invert OINV1 0 4-6 CCO L352 CCI0 Display Mode SMA 0 4-5 CCI L353 CCI1 Display Mode SMB 0 4-5 CCI L368 CCI0 Alarm Enable SAA 0 4-5 CCI L369 CCI1 Alarm Enable SAB 0 4-5 CCI L416 ANI0 0-5 V Input NOBIAS0 0 4-3 ANI L417 ANI1 0-5 V Input NOBIAS1 0 4-3 ANI L418 ANI2 0-5 V Input NOBIAS2 0 4-3 ANI L419 ANI3 0-5 V Input NOBIAS3 0 4-3 ANI
Section 4
Table
Module
63
Page 68
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
Table C-2. Database (continued)
Datapoint Title Symbol Default
L440 ANI0 Square Root Signal SQRT0 0 4-3 ANI L441 ANI1 Square Root Signal SQRT1 0 4-3 ANI L442 ANI2 Square Root Signal SQRT2 0 4-3 ANI L443 ANI3 Square Root Signal SQRT3 0 4-3 ANI L472 ANO0 0-20 mA Output OZBASE0 0 4-4 ANO
Section 4
Table
Module
64
Page 69
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
65
Page 70
53IT5100B Indicator/Totalizer
INSTRUCTION MANUAL
66
Page 71
The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice, or to make engineering refinements that may not be reflected in this bulletin. MicroMod Automation & Controls, Inc. assumes no responsibility for errors that may appear in this manual. © 2004 MicroMod Automation & Controls, Inc. Printed in USA
PN24479 Issue 1, 8/2013
MicroMod Automation & Controls, Inc.
75 Town Centre Drive
Rochester, NY USA 14623
Tel. 585-321 9200 Fax 585-321 9291
www.micromod.com
Loading...