Technical data according to UL/cULus
General purpose amp rating pf= 0.7...0.8 -40° to 40 °C A 30 60 100 200
Max. operating voltage
pf= 0.4...0.5 Three phase 240 V HP/A 7.5/22.0 15/42.0 30/80.0 60/154.0
480 V HP/A 15/21.0 30/40.0 60/77.0 125/156.0
Single phase 120 V HP/A 2/24.0
Short circuit rating with fuse, 3 and 4-pole types
Min. electrical endurance pf= 0.75...0.8 operation cycles 6000 6000 6000 6000
Mechanical endurance operation 20 000 20 000 20 000 16 000
Terminal lug kits Integral Integral LUG100 LUG200
Wire range AWG #18-8 #14-4 #14-2/0 #4-300MCM
Torque
Technical data according to IEC 60947-3
Rated insulation voltage Pollution degree 3 V 1 000 1 000 1 000 1 000
Dielectric strength 50 Hz 1min. kV 10 10 10 10
Rated impulse withstand voltage kV 12 12
Rated thermal current in ambient 40 °C / In open air A/W 32/3.5 63/7.5 160/12 200/17
1)
max. fuse power dissipation
...with minimum cable cross section Cu mm
Rated operational current, AC-23A
Rated operational power, AC-23
Rated breaking capacity in category AC-23
Rated short-time withstand current, 1 s r.m.s. -value kA 1 2.5 5 8
Power loss / pole With rated current, without fuse W 2 4 9 8
Weight without accessories
Built-in terminal size Cu mm
Terminal bolt size (included) Metric thread diameter x length mm M6x20 M8x25
Fuse-links bolts tightening torque Nm 4 4
*) = Utilization category B
1) Ambient temperature 60°C: derating 20%
2) Mounting on "ceiling": derating 10%. Mounting on wall, horizontal fuses: derating 8%.
3) Some fuses limit these figures further. Starting current characteristics must be considered separately.
4) Approval pending
5) 30 lb.in with cable size #14-10, 35 lb.in with cable size #8-4
In enclosure2) A/W 32/3.5 63/7.5
3)
UL/CSA fuse size A 30 60 100 200
UL/CSA fuse type J/CC J J J
Wire tightening lb.in 17 30/35
Lug mounting lb.in N/A N/A 50 72
The kW-ratings are accurate for three-phase 1500 R.P.M. standard asynchronous motors.
3-pole switch fuses kg 0.7 1.3 1.5 2.6
4-pole switch fuses kg 0.9 1.6 1.8
600 V HP/A 20/22.0 50/52.0 75/77.0 150/144.0
240 V HP/A 3/17.0
up to 500 V A 32 63 160 200
690 V A 32 63 160 200
230 V kW 7.5 18.5 45 60
400 V kW 15 30 75 110
415 V kW 15 30 75 110
500 V kW 18.5 37 90 132
690 V kW 22 55 132 200
up to 500 V A 256 504 1280 1600
690 V A 256 504 1280 1600
VAC 600 600 600 600
VDC 250 250 250 250
kA 200 200 200 200
5)
120 275
160/10, 135/12
2
6 16 70 95
2
0.75...10 2.5...25
200/15
K
For the most current product performance data visit ep.mersen.com and use catalog search. K21