
Willi-Memmert-Straße 90–96
Service hotline: +49 (0)9171 9792 911
Service fax: +49 (0)9171 9792 979
-mail: service@memmert.co
When contacting customer service, always quote the product serial number on the nameplate
lease contact our customer service before sending appliances for repair or before returnin
quipment, otherwise, we have to refuse acceptance of the shipment.
© 2

his manual describes the construction, function, transport and operation of the universal
vens UNxx/UFxx and the incubators INxx/IFxx. It is intended for use by trained personnel of
the owner who have the task of operatin
and/or maintaining the respective appliance.
f you are asked to work on the appliance, read this manual carefully before starting. Familiar-
ise yourself with the safety re
ulations. Only perform work that is described in this manual. If
there is somethin
you do not understand, or certain information is missing, ask your superior
r contact the manufacturer. Do not do anything without authorisation
he appliances are available in different configurations and sizes. If specific equipment fea-
tures or functions are available only for certain confi
urations, this is indicated at the relevant
points in t
functions described in this manual refer to the latest firmware version.
ue to individual configurations and sizes, illustrations in this manual may be slightly different
from the actual appearance. Function and operation are identical.
Other documents that have to be observed:
or operation of the appliance with MEMMERT AtmoCONTROL, observe the separate
or service and repair (see page 44), please refer to the separate service manual
is instruction manual belongs with the appliance and should always be stored where
on the appliance have access to it. It is the responsibility of the owner to
nsure that persons who are working or will work on the appliance are informed as to the
whereabouts of this instruction manual. We recommend that it is always stored in a protected
location close to the appliance. Make sure that the instruction manual is not dama
r humidity. If the appliance is sold on or transported and then set up again at a different
ocation, the operating instructions must go with it.
ou will find the current version of our operating manual as pdf file if you go to
e/service/downloads/bedienungsanleitung/

1.1 Terms and signs used..........................................................................................................
1.1.2 Signs used .........................................................................................................................
1.2 Product safety and dangers
................................................................................................
1.3 Requirements of the operating personnel
..........................................................................
.................................................................................................
1.6 Changes and alterations ......................................................................................................
1.7 Behaviour in case of malfunctions and irregularities ..........................................................
....................................................................
2. Construction and description 1
2.1 Construction ...................................................................................................................... 1
2.2 Function............................................................................................................................. 11
rial............................................................................................................................. 11
..........................................................................................................
...............................................................................................
2.5.1 Electrical connection ....................................................................................................... 1
...............................................................................................
2.6 Designation (nameplate) ................................................................................................... 1
2.8 Applied directives and standards ...................................................................................... 14
.................................................................................................
...............................................................................................................
..........................................................................................................
15
3. Delivery, transport and setting up 16
...................................................................................................................
..............................................................................................................................
Transport ............................................................................................................................ 17
.........................................................................................................................
3.4.1 Checking for completeness and transport damage
.......................................................
.4.2 Removing the transport protection ................................................................................17
.4.3 Disposing of packaging material .................................................................................... 17
3.5 Storage after delivery
........................................................................................................
..........................................................................................................................
.6.1 Prerequisites .................................................................................................................... 1
.6.2 Installation options .........................................................................................................1
.6.3 Tilt protection .................................................................................................................. 2
.6.4 Adjusting the doors (only for model sizes 450 and 750)...............................................
. Putting into operation 22
4.1 Connecting the appliance
.................................................................................................
.2 Switching on ......................................................................................................................

. Operation and control 23
5.1 Operating personnel.........................................................................................................
..............................................................................................................
.......................................................................................................
....................................................................................................
..............................................................................................................
5.4.5 Operation with digital backwards counter with target time setting, adjustable from 1
minute to 99 days (Timer)...............................................................................................
..................................................................................................
5.5.1 Electronic temperature monitoring ............................................................................... 2
5.5.2 Mechanical temperature monitoring: Temperature limiter (TB) .....................................
..........................................................................................................................
6. Malfunctions, warning and error messages 3
6.1 Warning messages of the temperature monitoring functio
1
6.2 Malfunctions, operatin
problems and appliance errors
4
7.2 Basic operation in menu mode usin
the example of language selection
.................................................................................................................................
...........................................................................................
..................................................................................................................................
7
7.3.3 Temperature monitorin
(Alarm Temp and Max Alarm)................................................37
9
7.3.5 Type of the slide-in unit (Grid or Shelf)
..........................................................................................................................
...................................................................................................................
7.5 Calibration .........................................................................................................................
. Maintenance and service 4
.............................................................................................................................
.1.1 Working chamber and metal surfaces
............................................................................
.2 Regular maintenance........................................................................................................44
9. Storage and disposal 4
.............................................................................................................................

n this manual and on the appliance itself, certain common terms and signs are used to warn
ers or to give you hints that are important in avoiding injury or damage.
bserve and follow these hints and regulations to avoid accidents and damage. These terms
signs are explained below.
is used whenever you or somebody else could be injured if you do not
bserve the accompanying safety regulation
is used for information that is important for avoiding damage
Warning signs (warning of a danger)
bserve the opera-
ting instruction
Prohibition signs (forbidding an action)
Regulation signs (stipulating an action)
Disconnect
mportant or useful additional informatio

he appliances described in this manual are technically sophisticated, manufactured usin
high-quality materials and subject to many hours of testing in the factory. They contain the
latest technolo
y and comply with recognised technical safety regulations. However, there are
risks involved, even when the appliances are used as intended. These are described below.
After removing covers, live parts may be exposed. You may receive
an electric shock if
ou touch these parts. Disconnect the mains plu
efore removing any covers. Only electrical technicians may work on
When loading the appliance with an unsuitable load, poisonous or
exp
osive vapours or gases may be produced. This could cause the
iance to explode, and persons could be severely injured or poi
soned. The appliance may only be loaded with materials/test objects
which do not
orm any toxic or explosive vapours when heated up
(see also Intended use on pa
If the door is open while the appliance is in operation, the appliance
@XNUDQGD@S@MCONRD@ÅQDG@Y@QC#NMNSKD@UDSGDCNNQNODM
durin
Depending on operation, the surfaces in the working chamber
and the chamber load ma
still be very hot after the appliance is
these surfaces can cause burns. Wear heat
esistant protective gloves or wait until the appliance cools down.
(MB@RDNE@OOKH@MBDRNE@BDQS@HMRHYDXNTB@MFDS@BBHCDMS@KK
ocked in, which is life-threatening. Do not climb into the appliance
Requirements of the operating personne
he appliance may only be operated and maintained by persons who are of legal age and
ave been instructed accordingly. Personnel who are to be trained, instructed or who are un-
oing general training may only work with the appliance under the continuous supervision
epairs may only be performed by qualified electricians. The regulations in the separate service
manua

Responsibility of the owne
he owner of the appliance
is responsible for the flawless condition of the appliance and for its proper operation in
accordance with its intended use (see pa
is responsible for ensuring that persons who are to operate or service the appliance are
ualified to do this, have been instructed accordingly and are familiar with the operating
ust know about the applicable guidelines, requirements and operational safety regula-
ions, and train staff accordingly
is responsible for ensuring that unauthorised persons have no access to the appliance;
is responsible for ensuring that the maintenance plan is adhered to and that maintenance
work is carried out properly (see pa
as to ensure that the appliance and its surroundings are kept clean and tidy, for example
rough corresponding instructions and inspections
is responsible for ensuring that personal protective clothing is worn by operating person-
el, e.g. work clothes, safety shoes and protective gloves.
his appliance is exclusively intended for heating up non-explosive substances and objects.
ny other use is improper, and may result in hazards and damage.
he appliance is not explosion-proof (does not comply with the German workplace health &
afety regulation VBG 24). The appliance may only be loaded with materials and substances
which cannot form any toxic or explosive vapours at the set temperature and which cannot
he appliance may not be used for drying, vaporising and branding paints or similar materi
als the solvents of which could form an explosive mixture when combined with air. If there
is any doubt as to the composition of materials, they must not be loaded into the appliance.
otentially explosive gas-air mixtures must not form, neither in the working chamber nor in
the direct vicinity of the appliance.
Appliances IFxx/UFxx for use as medical device
or appliances IFxx and UFxx with extended overtemperature protection (option A6, recognis-
able due to standard DIN 12880-2007-Kl.:3.1 on the nameplate) subject to the 93/42/EEC
irective (Directive of the council on harmonisation of the laws of the member states relating
to medical devices), the intended use is defined as follows: The appliance’s intended use is the
warmin
of non-sterile cloths and covers
o unauthorised changes or alterations may be made to the appliance. No parts may be
added or inserted which have not been approved by the manufacturer.
Unauthorised modifications or chan
es result in the CE declaration of conformity losing its
ity and the appliance must no longer be operated.
he manufacturer is not liable for any damage, danger or injuries that result from unauthor
ised changes or alterations, or from non-observance of the regulations in this manual

ase of malfunctions and irregularitie
he appliance may only be used in a flawless condition. If you as the operator notice irregu-
larities, malfunctions or dama
e, immediately take the appliance out of service and inform
your super
ou can find information on correcting malfunctions from page 31.
witching off the appliance in an
ush the On/Off switch on the control panel
( Fi
. 1 ) and disconnect power plug. This
isconnects the appliance from the power
Depending on the operation
erformed , the surfaces in
e very hot after the appli
ance is switched off. Touch
ng these surfaces can cause

2. Construction and descriptio
ControlCOCKPIT with capacitive function
On/Off switch (see page 22)
Nameplate (covered, see page 12)
Door handle (see page 23)
Turn control with confirmation key

ppliances of the UNxx and
Nxx type series feature
natural circulation (convec
tion). For the UFxx and IFxx
type series, air is circu
hamber rear panel Fig. 3 ,
o. 1). It increases the air
flow and provides stron
n both the convection and
fan ventilated appliances,
upply air (2) is preheated
in a pre-heatin
lits in the side panel of the
workin
ated air is introduced into
ontrolled by the air flap
(4) on the rear
or the outer housing, MEMMERT deploys stainless steel (Mat.No. 1.4016 – ASTM 430) and
for the interior, stainless steel (Mat.No. 1.4301 – ASTM 304) is used, which stands out throu
h stability, optimal hygienic properties and corrosion-resistance towards many (but not
all!) chemical compounds (caution for example with chlorine compounds)
he chamber load for the appliance must be carefully checked for chemical compatibility with
the materials mentioned. A material resistance table can be requested from the manufacturer.
perating voltage and current consumption: See nameplat
rotection class I, i.e. operating insulation with PE conductor in accordance with EN 61010
rotection type IP 20 acc. to EN 60 529
nterference suppression acc. to EN 55011 class B
ppliance fuse: Fusible link 250 V/15 A quick-blow
he temperature controller is protected with a miniature fuse 100 mA (160 mA at 115 V)
Fig. 3 Function

his appliance is intended for operation on an electrical power system with a system imped-
anc
of a maximum of 0.292 ohm at the point of transfer (service line). The operator
must ensure that the appliance is operated only on an electrical power system that meets
these requirements. If necessary, you can ask your local ener
y supply company what the
bserve the country-specific regulations when connecting (e.g. in German
IN VDE 0100 with residual current circuit breaker).
.5.2 Communication interfac
he Ethernet interface is intended for appliances which meet the requirements of IEC 60950-1
Via Ethernet interface, the appliance can be
a network to read out protocol
s withAtmoCONTROL, the optional
appliance software. The Ethernet interface is
located on the rear of the appliance (Fi
or identification purposes, each appliance
onnected must have its own unique IP ad-
ress. Setting the IP address is described on
an optional USB to Ethernet converter,
e appliance can be directly connected to a
omputer / laptop (see Optional accessories
2.6 Designation ( nameplate)
The nameplate (Fig. 5) provides information about the appliance model, manufacturer and
technical data. It is attached to the front of the appliance, on the ri
ht side under the door
(see pa
e 10).
Typ: UN 260 F.-Nr.: 0109.0088
230 V
~
14.8 A 50/60 Hz 3400 W
DIN12880-Kl.3.1 Nenntemp.: 300 °C
1
2
3
4
5
6
10
8
9
7
Fig. 5 Nameplate (example)
Connection / power ratings

Appliance size 30 55 75 110 160 260 450 750 1060
max. load per appliance [k
to +250 °C if your device is equipped with a

imensions (see table on page 13)
pplied directives and standard
irective 2004/108/EC amended (Directive of the council on harmonisation of the laws of
he member states on electromagnetic compatibility). Fulfilled standards:
IN EN 61326:2004-05, EN 61326:1997, EN 61326/A1:1998, EN 61326/A2:2001
irective 2006/95/EC amended (Directive of the council on harmonisation of the laws of
ember states relating to electrical equipment designed for use within certain voltage
limits). Standards complied with:
IN EN 61 010-1 (VDE 0411 Part 1)
IN EN 61 010-2-010 (VDE 0411 Part 2-010)
N 61 010-1:2001, EN 61 010-2-01
n used as a medical devic
irective 93/42/EEC (Directive of the Commission on the harmonisation of the legal regula-
ions of the member states on medical devices)
ou can download the EC declaration of conformity of the appliance online:
nglish: http://www.memmert.com/en/service/downloads/ce-statement/
German: http://www.memmert.com/de/service/downloads/e
-konformitaetserklaerung/

he appliance may only be used in enclosed rooms and under the following ambient
ient temperature
+5 C to +40
ax. 2,000 m above sea level
he appliance may not be used in areas where there is a risk of explosion. The ambient air
ust not contain any explosive dusts, gases, vapours or gas-air mixtures. The appliance is
eavy dust production or aggressive vapours in the vicinity of the appliance could lead to
imentation in the interior and, as a consequence, could result in short circuits or dam-
e to electrical parts. For this reason, sufficient measures to prevent large clouds of dust
r aggressive vapours from developing should be taken.
ne or two sliding steel grids (load capacity 30 kg each)
he operating instructions at han
tmoCONTROL software for reading out
USB to Ethernet converter (Fig. 7 ). Makes
it possi
e to connect the appliance's
etwork interface (see page 12) to the
USB port of a computer / laptop.
einforced, sliding steel grids with a load
apacity of 60 kg each (for appliance size

Delivery, transport and setting u
3. Delivery, transport an
Because of the heavy weight of the appliance, you could injure
ourself if you try to lift it. To B@QQX@OOKH@MBDRNESGDRHYDR@MC
@SKD@RSSVNODQRNMR
NQ@OOKH@MBDRNESGDRHYDR@MC
ENTQODNOKD@QDMDDCDC OOKH@MBDRK@QFDQSG@MSG@SL@XMNSAD
carried but must be transported with a manual pallet
30 55 75 110 160 260 450 750
Warning!
You may get your hands or
eet squashed when transport
ng and installing the appliance. Wear protective gloves and
afety boots. When grasping the bottom of the appliance,
rasp it only on the sides
he appliance could fall over and seriously injure you. Never
ilt the appliance and transport it in upright position and
(except for standard accessories such as
teel grids or shelves). Appliances with castors always have to

Delivery, transport and setting u
e appliance is packed in cardboard and is delivered on a wooden palette.
e appliance can be transported in three ways:
With aforklift truck; move the forks of the truck entirely under the pallet
n its own castors, in case of the corresponding configuration, for which the catch on the
front) castors must be released
o avoid damage, do not unpack the appliance until you reach the installation site.
emove the cardboard packaging by pulling it upwards or carefully cutting along an edge.
.4.1 Checking for completeness andtransport damag
heck the delivery note to ensure that the delivery is complete.
heck the appliance for damage.
f you notice deviations from the delivery note, damage or irregularities, do not put the appli-
ance into operation but inform the haula
e company and the manufacturer
emoving the transport protectio
emove the transport protection. It is located between the door hinge, door and frame and
has to be removed after openin
isposing of packaging materia
ispose of the packaging material (cardboard, wood, foil) in accordance with the applicable
isposal regulations for the respective material in your country.
f the appliance is first to be stored after delivery: Read the storage conditions from page

Delivery, transport and setting u
Due to its centre of gravity, the appliance can fall over to the front
and in
ure you or other people. Always attach the appliance to a wall
VHSGSGDSHKSOQNSDBSHNMRDDO@
D(ESGHRB@MMNSADCNMDCTD
to s
ace problems, do not operate the appliance and do not open
the door. Contact the Memmert service team (see pa
installation site must be flat and horizontal and must be able to reliably bear the weight
f the appliance (see Technical data on page 13). Do not place the appliance on a flamma-
epending on the model (see nameplate), a 230 V, 115 V or 400 V power connection must be
at the installation site.
he distance between the wall and the rear of the appliance must be at least 15 cm. The clear-
ance from the ceilin
must not be less than 20 cm and the side clearance from walls or nearby
appliances must not be less than 5 cm (Fi
. 8). Sufficient air circulation in the vicinity of the
app
iance must be guaranteed at all times.
or appliances with castors, these need to be positioned in forward direction at all times.
FP FP FP
FP
Fig. 8
inimum clearance from walls and ceiling

Delivery, transport and setting u
Setting up Comments Suitable for appliance size ...
30 55 75 110 160 260 450 750
two appliances
maximum; mount
ing material (feet)
provide
f delivery. Observe
the assembly instructions provided.

Delivery, transport and setting u
with the tilt protection.
e tilt protection is included
s illustrated, fasten the
rill a hole, insert a plug

Delivery, transport and setting u
.6.4Adjusting the doors (only for model sizes 450 and 750
or model sizes 450 and 750, it is possible to adjust doors that warp due to the floor condi-
tions. In order to do so, every door has two adjuster screws at the top and at the bottom (Fi
.
9).
irst, adjust the door at the top and then, if further adjustment is necessary, at the bottom
. Tighten the screws again
f necessary, readjust.
Fig. 9 Door adjustment screws

he first time the appliance is operated, it must not be left unattended until it has reached
bserve the country-specific regulations when making connections (e.g. in Germany DIN
VDE 0100 with residual current circuit breaker). Observe the connection and power ratin
s (see nameplate and Technical data on page 13). Make sure to establish a safe PE
ay the power cable so that
it is always accessible and within reach so it can be disconnected quickly in the event of
it does not come into contact with any hot parts.
lug the provided power cable into the rear of the appli-
ance and connect it to a CEE 7/4 socket (Fi
e power cable is permanently installed. Connect the
to a 400 V CEE coupling (Fig. 11).
Switch on the appliance by pressing the On/Off switch
n the front of the appliance ( Fig. 12 ).
e starting process is shown by three animated white
. If the dots have another colour, an error has
fter the first start-up, the appliance display is set to
nglish by default. You can change the language as
escribed from page 35. However, to get a basic
verview of operating the appliance, you should read
he following chapter first.
Fig. 11 400 V CEE connectio
Fig. 12 Switch on appliance

he appliance may only be operated by persons who are of legal age and have been instruct-
accordingly. Personnel who are to be trained, instructed or who are undergoing general
may only work with the appliance under the continuous supervision of an experi-
o open the door, pull the door handle to the side (to the left or to the right, depending
n the door variation, see Fig. 13, A) and open the door completely.
o close the appliance, push the door closed and the door handle to the side (B).
A
B
Fig. 13 Opening and closing the door
If the door is open while the appliance is in operation, the appliance
@XNUDQGD@S@MCONRD@ÅQDG@Y@QC#NMNSKD@UDSGDCNNQNODM
(MB@RDNE@OOKH@MBDRNE@BDQS@HMRHYDXNTB@MFDS@BBHCDMS@KK
ocked in, which is life-threatening. Do not climb into the appliance

When loading the appliance with an unsuitable load, poisonous
r explosive vapours or gases may be produced. This could cause
he appliance to explode, and persons could be severely injured or
oisoned. The appliance may only be loaded with materials which do
ot form any toxic or explosive vapours when heated up and cannot
ignite (see also Intended use on page 8). I
o the composition of materials, they must not be loaded into the
the chamber load for chemical compatibility with the materials of the appliance
nsert the sliding steel grids or sliding shelves. The maximum number or grids / shelves and the
load capacity are specified in the technical data overview on pa
oaded too tightly, so that
roper air circulation in the
touching the side walls or
ight below the ceiling of the
n case of improper loadin
(chamber loaded too tightly),
t
e set temperature may
be exceeded or it may take
longer until it is reached.
To achieve the correct heatin
capacity, the type of slide-in unit used – Grid or Shelf –
must
e set in the menu under SETUP (see page 39).
.4 Operating the applianc
n manual operation, the desired parameters are entered at the ControlCOCKPIT on the front
f the appliance (Fig. 15 and Fig. 16 ). You can also make basic settings here (menu). Addition-
messages are displayed, e.g. if the temperature is exceeded.
g. 14 Correct placement of thechamber load

TIMER
End 14: 45
44h:44m
180.4°C
TEMP
Set 180
.4°C
20%
FLAP
FAN
%
0
FLAP
40%
53 412
TIMER
30m04h
End
13:30 23.11.
11 1267 8 9 10
Fig. 15 ControlCOCKPIT for UFxx/IFxx appliances in operating mode
180.0 °C
Set 180.9°C
TEMP
TIMER
End 14: 45
44h:44m
FLAP
FLAP
40%
12 5
TIMER
30m04h
End
13:30 23.11.
10 11 1267 8 9
Fig. 16 ControlCOCKPIT for UNxx/INxx appliances in operating mode
Activation key for temperature setpoint
Setpoint and actual temperature display
Activation key for fan speed setting
Switch to menu mode (see page 34)
Activation key digital backwards counter
with target time setting, adjustable from 1
Display digital backwards counter with
target time setting, adjustable from 1 min-
Air flap position display
Activation key for air flap position adjust-
Turn control for setpoint adjustment
Confirmation key (accepts setting made

n general, all settings are made according to the following pattern:
ctivate the desired parameter (e.g. tem-
erature). To do so, press the correspond-
ngactivation key on the left or right of
e respective display. The activated dis-
ay is lined in colour, the other displays
immed. The set value is hi
y turning the turn control to the left
r right, adjust the set value (e.g. to
ave the set value by pressing the confir-
isplay returns to normal and the
ins adjusting to the defined
dditional parameters (air flap position etc.) can be set accordingly.
f no new values are entered or confirmed for approx. 30 seconds, the appliance automati-
ally returns to the main menu and restores the former values.
f you want to cancel the setting procedure, press the
activation key on the left or ri
ht of the display that you
want to exit. The appliance restores the former values.
nly the settings that you have confirmed by pressing
he confirmation key before cancelling the setting
he appliance can be operated in different modes:
iance runs in permanent operation at the values set on the Con-
COCKPIT. Operation in this mode is described in chapter 5.4.4.
peration with digital backwards counter with target time setting, adjustable from 1 min-
te to 99 days (Timer): The appliance runs at the values set until the timer has elapsed.
peration in this mode is described in chapter 5.4.5 .
via remote control (see page 39)

n this operating mode, the appliance runs in permanent operation at the values set on the
s described in chapter 5.4.2, you can set the following parameters after pressing the cor-
activation key (in any sequence):
djustment range: model dependent (see nameplate and technical
eating operation is indicated by the
ou can select °C or °F as the temperature unit displayed (see
djustment range: 0 % (closed, recirculating operation) to 100 %
(completely opened, fresh air operation) in steps of 10%
FLAP
%40
(only for UFxx/IFxx appliances
djustment range: 0 to 100 % in steps of 10%
igital backwards counter with target time setting,
ustable from 1 minute to 99 days (Timer
n timer operation, you can adjust the time the appliance runs at the set value.
1.
ress the activation key to the left of
e timer display. The timer display is
TIMER
-
Ende
9:00 23.11.
--h- m
. Turn the turn control until the desired
uration is displayed – in this example 4
ours 30 minutes. The approximate end
ime is shown beneath, in a smaller font.
TIMER
End
0
13:30 23.11.
04 mh 3
Up to a duration of 23 hours 59 minutes, the time is displayed in hh:mm (hours:minutes)
ormat. For 24 hours and more, the format dd:hh (days:hours) is used. The maximum
uration adjustable is 99 days 00 hours.

ress the confirmation key.
isplay now shows the remaining time in
a large font and the approximate end time in
a smaller font beneath.
TIMER
30m04h
End
13:30 23.11.
ow, as described under 5.4.
set the individual values for temperature, air flap position
tc. which you want the appliance to operate at. The set values can be changed at any
ime while the timer elapses. The changes are effective immediately.
n Setup, you can choose if the timer should run setpoint-dependent or not. This deter-
ines whether the timer should not start until a tolerance band around the set tempera-
ure is reached or whether it should start right after activation (see page 39). If the timer
uns setpoint-dependent, this is indicated by the
symbol in the timer display.
When the timer has elapsed, the display shows 00h:00m. All functions (heatin
etc.) are switched off. If a fan had been active, it will
keep on runnin
for a short safety period. In addition, an acoustic
alarm sounds, which can be turned off by pressin
eactivate the timer, open the timer display by pressing the
ey again and then turning the turn contro
until --:-- is displayed. Confirm with the confirma-
tion
ey.
5.5 Temperature monitorin
he appliance is equipped with a double overtemperature protection (mechanical/electronic)
in accor
ance with DIN 12 880. This serves to avoid damage to the chamber load and/or ap-
liance in case of a malfunction
Electronic temperature monitoring
TWB) (TWB only if equipped with a second tem-
erature sensor, option A6)
echanical temperature limiter (TB
TIMER
00m00h
End
13:30 23.11.
TIMER
--m--h
End
9:00 23.11.

lectronic temperature monitorin
he monitoring temperature of the electronic temperature monitoring is measured via the
t100 temperature sensor in the interior of the chamber. The type of temperature monitoring
(TWW/TWB) and the monitorin
temperature are set in menu mode in the Setup display (see
pa
e 38). The setting made applies to all operating modes.
f the manually set monitoring temperature is exceeded, temperature monitoring takes over
temperature control and be
ins to regulate the monitoring temperature (TWW, Fig. 17) or
witches off the heating (TWB, Fig. 18).
he two types of temperature monitoring are only available for appliances equipped with
a second temperature sensor (option A6). For appliances with only one temperature
ensor, only TWW is available
t
°C
Setting Max Alarm
Set temperature
Controller error
Emergency operation
Fig. 17 Schematic diagram of how the TWW temperature monitoring system wor
t
°C
heating switched off by TWB
Setting Max Alarm
Set temperature
Controller error
Schematic diagram of how the TWB temperature monitoring works (only if equipped
with a second temperature sensor, option A6)

echanical temperature monitoring: Temperature limiter (TB
he appliance is equipped with a mechanical temperature limiter (TB) of protection class 1 in
ccordance with DIN 12 880.
f the electronic monitoring unit should fail during operation and the factory-set maximum
emperature is exceeded by approx. 20 °C, the temperature limiter, as the final protective
easure, switches off the heating permanently.
temperature monitoring has been
ered, this is indicated by the
emperature display: the actual tempera-
ture is highlighted in red and a warning
is shown (Fig. 19 ). The type
temperature monitoring triggered is
shown beneath the tem
echanical and TWW or TWB for
lectronic temperature monitoring. The
arm is additionally signalled by an
intermittent acoustic signal, which can
e turned off by pressing the confirma-
ion key. Information on what to do in
his case are provided in the chapter
alfunctions, warning and error
essages from page 31.
epending on the operation performed , the surfaces in the working
hamber and the chamber load may still be very hot after the appli
ance is switched off. Touching these surfaces can cause burns. Wear
eat-resistant protective gloves or wait until the appliance cools
wn.
1. Switch off active appliance functions
turn back the set values).
. Switch off the appliance (Fig. 20 ).
TIMER
End 14: 45
44h:44m
180.4°C
TEMP
Set 185
.0°C
20%
FLAP
LÜFTER
%
0
KLAPPE
40%
TIMER
30m04h
Ende
13:30 23.11.
23.2°C
TEMP
Set 180
.0°C
TEMP
TB Set 190.0 °C
195.4°C
180.4°C
TEMP
Set 185
.0°C
23.2°C
TEMP
Set 180
.0°C
TEMP
TB Set 190.0 °C
195.4°C
Fig. 19
emperature monitoring triggere
. 20 Switch off appliance

Malfunctions, warning and error messages
. Malfunctions, warning and
fter removing covers, live parts may be exposed. You may receive
n electric shock if you touch these parts. Malfunctions requirin
VNQJHMRHCDSGD@OOKH@MBDL@XNMKXADQDBSHÅDCAXDKDBSQHBH@MR.A
serve the separate service manual for this
o not try to rectify appliance errors yourself but contact the MEMMERT customer service
department
see page 2) or an authorised service point.
n case of enquiries, please always specify the model and appliance number from the name-
arning messages of the temperature monitoring functio
Description Cause Action See
erature alarm and
"TWW" are displaye
TEMP
TWW Set 190.0 °C
195.4°C
ncrease the difference between
the monitoring and setpoint
temperature – by either in-
reasing the max value of the
or decreasing the set-
point temperature.
f the alarm continues: Contact
erature alarm and
"TWB" are displayed
TEMP
TWB Set 190.0 °C
195.4°C
erature
limiter (TWB) permanently switched
eactivate the alarm by pressing
ncrease the difference between
the monitoring and setpoint
temperature – by either in-
reasing the max value of the
f the alarm continues: Contact
he mechanical
temperature limiter (TB) permanently switched
ff heating.
Switch off the appliance and
leave to cool down. Contact
ustomer service and have the
rror rectified (e.g. by replacing

alfunctions, warning and error message
perating problems and appliance errors
Error description Cause of errors Rectifying errors See
xternal power supply
was interrupte
ndividual or all displays
When switching on
the appliance, the start

Malfunctions, warning and error message
Depending on the operation performed, the surfaces in the interior
and the chamber load ma
still be very hot after power loss. Ad
ditionally, depending on the duration of the power loss, the appli
ance might heat up again after power supply has been restored (see
elow). Touching these surfaces can cause burns. Wear heat-resistant
QNSDBSHUDFKNUDRNQV@HSTMSHKSGD@OOKH@MBDBNNKRCNVMÅQRS
n case of a power failure, the appliance operates as follows:
In manual mo
fter power supply has been restored, operation is continued with the parameters set. The
time and the duration of the power failure is documented in the
n case of an interruption of the power supply of less than 60 minutes, the current timer is
ontinued from the point at which it was interrupted. For interruptions of the power supply
lon
er than this, all appliance functions (heating, fan etc.) are switched off and the air flap is
e previous values are restored.

n menu mode, you can make basic settings as well as adjust appliance parameters
efore changing menu settings, read the description of the respective functions on the fol-
owing pages to avoid possible damage to the appliance and/or chamber load.
enter menu mode, press the MENU key.
exit the menu mode at any time, press the MENU key
ain. The appliance then returns to manual mode. Only
hanges accepted by pressing the confirmation key are
ress the MENU key to change between the displays in menu mode:
SETUP
SIGNALTÖNE
CALIB
LANGUAGE
TIME
12 34 5
6789 1011
Fig. 21
Language selection activation key
Language selection display
Date and time setting activation key
Setup activation key (basic appliance sett
Setup display (basic appliance settings)
Adjustment activation key
Turn control for adjustment
Confirmation key (accepts setting made

Basic operation in menu mode using the example of
n general, all settings in menu mode are done just like in manual mode: Activate the re-
pective display, use the turn control for setting and press the confirmation key to accept
e. A more detailed description is provided in the following, using the example of
1. Activate the desired parameter (in this
xample the language). To do so, press
e corresponding activation key on the
ht of the respective display. The
activate
ENGLISH
DEUTSCH
ESPANOL
FRANCAIS
f you want to exit or cancel your settings,
again press the activation key which you
ave used to activate the display. The
a
iance returns to the menu overview.
nly the settings that you have con-
irmed by pressing the confirmation key
before cancelling the setting procedure
are accepted.
SETUP
SIGNALTÖNE
CALIB
LANGUAGE
TIME
ON
. With the turn control, select the desired
ew setting, e.g. Español (Spanish).
ave the setting by pressing the confir-
SPRACHE
ENGLISH
DEUTSCH
ESPANOL
FRANCAIS
. To return to the menu overview, press the
activate another menu function by pressin
e corresponding activation key o
eturn to manual mode by pressing the
Balance
Einheit
IP Adresse
Alarm Tem
Unit
IP address
Subnet mas
Alarm temp
Timer mode
Slide-in unit
SPRACHE
ENGLISH
DEUTSCH
ESPANOL
FRANCAIS

ll other settings can be made accordingly. The settings possible are described in the follow-
f no new values are entered or confirmed for approx. 30 seconds, the appliance automati-
ally returns to the main menu and restores the former values.
7.
ETUP display, you can set the followin
of the appliance's Ethernet interface (for connection to
Unit of the temperature display (°C or °F, see page 37)
he type of temperature monitoring (TWW or TWB, Alarm Tem
nly if equipped with
a second temperature sensor, option A6) and the tri
er temperature of the monitoring
ow the digital backwards counter with target time setting works
he type of the slide-in unit (Grid or Shelf, see page 39)
emote control (see page 39)
f the SETUP menu contains more entries than can be
isplayed, this is indicated by the display “1/2”. This
eans that there is a second „page“ of entries.
isplay the hidden entries, use the turn control
o scroll beyond the lowest entry. The page display
f you want to operate one ore more appliances in a network, each appliance must have its
wn unique IP address for identification. By default, each appliance is delivered with the IP
address 192.168.1
.
LAN 1: 192.168.1.233
192.168.1.216
LAN 2: 192.168.1.215
LAN 3: 192.168.1.241
Editor
Programmname
Simulation Protokoll
-
+-+
INP 250 Test 01
180
.0°C
i
HPP 250 Labor
i
37
.0°C
44
.4%rh
151
STAND BY
Programm negnulletsniEllokotorPtäreG efliHnekcurD
AtmoCONTROL
Fig. 22 Operation of several appliances in a network (schematic example)
Unit
IP adress 255.145.136.
Subnet mask 255.255.0. 0
°C F
1/2

SETUP
Balance
Einheit
IP Adresse
+30%
192.168. 10 0. 100
Alarm Temp
°C F
TWW TWB
Timer Mode
Setup
Unit
IP address 192.168.1 00 .100
Subnet mask 255.255.0. 0
Alarm temp
°C F
TWW TWB
Timer mode
Slide-in unit
Grid Shelf
. Accept the selection by pressing the con-
irmation key. The first three digits of the
P address are automatically selected.
Unit
IP address 192.168.100 .100
Subnet mask 255.255. 0. 0
Alarm temp
°C F
TWW TWB
Timer mode
. With the turn control, set the new num-
Unit
IP address 255.168.100 .100
Subnet mask 255.255. 0. 0
Alarm temp
°C F
TWW TWB
Timer mode
. Accept the selection by pressing the con-
irmation key. The next three digits of the
P address are automatically selected. Set-
these is done with the turn control
accor
to the description above.
Unit
IP address 255.168.100.100
Subnet mask 255.255. 0. 0
Alarm temp
°C F
TWW TWB
Timer mode
5. After setting the last three digits, accept
he new IP address by pressing the con-
irmation key. The selection returns to the
e subnet mask is set accordingly
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0. 0
Alarm temp
°C F
TWW TWB
Timer mode
ere, you can choose whether the temperature is displayed in °C
.3.3 Temperature monitoring (Alarm Temp and Max
ere, the type of monitoring function that should be activated (TWW or TWB, description
, as well as the temperature at which the auto-
matic temperature monitorin
he selection option TWW/TWB is only available for appliances with a second temperature
he monitoring temperature must be set sufficiently high above the maximum set tem-
erature. We recommend 5 to 10 K difference for UNxx/UFxx and 1 to 3 K difference for
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0. 0
Alarm temp
°C °F
TWW TWB
Timer mode

Unit
IP address 255.145.136.225
Subnet mask 255.255. 0.0
Alarm temp
°C F
TWW TWB
Timer mode
. Accept the selection by pressing the con-
irmation key. The adjustment options are
automatica
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0.0
Alarm temp
°C F
TWW TWB
Timer mode
. With the turn control, select the desired
etting – in this example TWB.
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0.0
Alarm temp
°C F
TWW TWB
Timer mode
ave the setting by pressing the confir-
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0.0
Alarm temp
°C F
TWW TWB
Timer mode
SETUP
Max Alarm
190 °C
2/2
. Accept the selection by pressing the
onfirmation key. The current settings are
SETUP
Max Alarm
190 °C
2/2
7. With the turn control, select the desired
ew trigger temperature - in this example
SETUP
Max Alarm
160 °C
2/2
ave the setting by pressing the confir-
ation key. The electronic temperature
onitoring system will now be triggered
en the actual temperature reaches 160
SETUP
Max Alarm
160 °C
2/2

ere, you can choose whether the digital backwards counter with
et time setting (see page 27, timer) should run setpoint-
ependent or not – this determines whether the timer should
t start until a tolerance band of ±3 K around the set
temperature is reached (Fi
. 23, B) or whether it should start
ri
ht after activation (A).
t
Timer
t
Timer
A
B
°C/°F
t
6 K
Fig. 23 Timer Mo
A Timer independent of setpoint: Timer starts right after activation
B Timer setpoint-dependent: Timer does not start until tolerance band is reached
f the temperature tolerance band is exceeded in setpoint-dependent operation, the timer will
e interrupted and only be resumed when the setpoint temperature has been reached again.
.3.5 Type of the slide-in unit (Grid or Shelf)
ere, you have to set the type of the slide-in unit (grid or shelf)
sed. The selection Shelf enables you to adjust the control
functi
n to the different air flow characteristics in the interior
optional sliding shelves instead of the grids that are
part of the standard delivery.
liance should be controlled via remote control and if
o, in which mode. These settings are available:
When the appliance is in remote control mode, the
symbol appears in the temperature display. In the
be controlled at the ControlC
ontrol has been switched off (setting Off) or set to Read
n order to use the remote control function, program-
ing skills and special libraries are required.
Unit
IP address 255.145.136.225
Subnet mask 255.255. 0. 0
Alarm temp
°C F
TWW TWB
Timer mode
Unit
IP adress 255.145.136.225
Subnet mask 255.255. 0. 0
°C °F
Timer mode
Alarm temp
TWW TWB
Slide-in unit
Grid Shelf
Balance
Remote Control Off
Gateway 192.168.5 .1
+30 %
2/2
23.2°C
TEMP
Set 180
.0°C

is used to connect two networks
with different protocols.
he gateway is set the same way as the IP address (see
display, you can set date and time, time zone and daylight saving time.
lways set the time zone (and summer time yes/no) before you set the date and time.
void changing the set time after that since this can lead to gaps or overlapping when
ecording measured values. If you still need to change the time, you should not run a
rogramme immediately before or after doing so
ctivate the time setting. To do so, press
he activation key on the right side of
me display. The display is enlar
ed
and the first adjustment option (
Dat
.
Date and time
Time
Time zone
Daylight savings
12.05 .2012
12:00
GMT 01:00
Date
urn the turn control until T
.
Time
Daylight savings
12.05.2012
12:00
GMT 01:00
Date
Time zone
. Accept the selection by pressing the
onfirmation key.
Time
Daylight savings
12.05.2012
12:00
GMT
Date
Time zone
01:00
t the time zone of the installation site
with the turn control, e.
rance, Spain or Great Britain, 01:00 for
Germany. Accept t
Time
Daylight savings
12.05.2012
12:00
GMT
Date
Time zone
00:00
5. With the turn control, select the Dayli
Time
12.05.2012
12:00
GMT 00:00
Date
Time zone
Daylight savings
Balance
Remote Control Off
Gateway 192.168.5 .1
+30 %
2/2

. Accept the selection by pressing the
onfirmation key. The adjustment options
are hi
Time
12.05.2012
12:00
GMT 00:00
Date
Time zone
Daylight savings
7.
et daylight savings to off () or on
with the turn control – in this case
n (). Save the setting by pressing the
Time
12.05.2012
12:00
GMT 00:00
Date
Time zone
Daylight savings
aylight saving time and standard time are not changed automatically. For this reason,
lease keep in mind to adjust them at the beginning of each period.
ow, set date (day, month year) and time
hours, minutes) in the same way. Accept
he selection by pressing the confirma-
Time
Time zone
Daylight savings
..2012
12:00
GMT 00:00
Date 27 05

he appliances are temperature calibrated and adjusted at the factory. In case readjustment
hould be necessary later on – for example due to influence of the chamber load – the ap-
pliance can be calibrated customer-specifically usin
three calibration temperatures of your
emperature calibration at low temperature
2 Temperature calibration at medium temperatur
al3 Temperature calibration at high temperatur
uarantee perfect control, we recommend to calibrate the appliance once a year.
or temperature adjustment, you will need a calibrated reference measuring device.
CAL 1
+0,5 K
CAL 3
-0,8 K
CAL 2
+2,6 K
180°C
40°C
120°C
0°C
factory calibration
Fig. 24 Schematic example of temperature adjustment
xample: Temperature deviation at 120 °C should be corrected.
ctivate the adjustment setting. To do so,
ress the activation key on the right side
ALIB display. The display is en-
lar
ed and the first calibration tempera-
ure – in this case 40 °C – automatically
.
Cal1
°C -0,2
K
Cal2 100.0 °C +0,1K
Cal3 180.0 °C -0,2K
JUSTIEREN
Temperatur
letzte Justierung 12.10.2012 12:00
40.0
CK0,2-
CK0,1+
CK0,2-
Calibration
Temperature
Last updated 12.10.2012 12:00:00
Cal1
Cal2
Cal3
100.0
180.0
40.0
ress the confirmation key repeatedly,
ntil the calibration temperature Cal2 is
.
CK0,2-
CK0,1+
CK0,2-
Temperature
Cal1
Cal2
Cal3
180.0
40.0
100.0

. With the turn control, set the calibration
emperature Cal2 to 120 °C.
CK0,2-
CK0,1+
CK0,2-
Temperature
Cal1
Cal2
Cal3
180.0
40.0
120.0
ave the setting by pressing the confir-
ation key. The corresponding calibra
ion value is automatically highlighted
CK0,2-
CK
CK
0,2-
Temperature
Cal1
Cal2
Cal3
180.0
40.0
120.0 0,1+
5.
et the calibration value to 0.0 K and ac-
ept the setting by pressing the confirma-
CK0,2-
CK
CK
0,2-
Temperature
Cal1
Cal2
Cal3
180.0
40.0
120.0 0,0
sition the sensor of a calibrated refer-
nce instrument centrally in the appli-
ose the door and, in manual mode
adjust the set temperature to 120 °C.
. Wait until the appliance reaches the set
emperature and displays 120 °C. The
eference instrument for example displays
120.0°C
TEMP
Set 120
.0°C
n the SETUP, adjust the calibration value
al2 to +2.6 K (actual value measured
inus setpoint temperature) and save the
etting by pressing the confirmation key.
CK0,2-
CK
CK
0,2-
Temperature
Cal1
Cal2
Cal3
180.0
40.0
120.0 2,6+
10. After the calibration procedure, the
emperature measured by the reference
instrument s
120.0°C
TEMP
Set 120
.0°C
120.0 °C
al3, a temperature above. The minimum difference between the Cal values is 20 K for univer-
al ovens UNxx/UFxx and 10 K for incubators INxx/IFxx
f all calibration values are set to 0.0 K, the factory calibration settings are restored.

8. Maintenance and servic
er due to electric shock. Before doing any maintenance
work, pull out the mains plu
(MB@RDNE@OOKH@MBDRNE@BDQS@HMRHYDXNTB@MFDS@BBHCDMS@KK
ocked in, which is life-threatening. Do not climb into the appliance
Danger of cuts due to sharp edges. Always wear gloves when wor
ing in the chamber interior
orking chamber and metal surface
egular cleaning of the easy-to-clean working chamber prevents build up of material remains
that could impair the appearance and functionality of the stainless steel workin
he metal surfaces of the appliance can be cleaned with normal stainless steel cleaning
ents. Make sure that no rusty objects come into contact with the working chamber or with
the stainless steel housin
. Rust deposits can lead to an infection of the stainless steel. If rust
pots should appear on the surface of the working chamber due to impurities, the affected
area must be immediately cleaned and polished.
o not clean the ControlCOCKPIT and other plastic parts of the appliance with caustic or
vent-based cleaning agents.
Glass surfaces can be cleaned with a commercially available glass cleaner
nce a year, grease the moving parts of the doors (hinges and lock) with thin silicone grease
uarantee perfect control, we recommend to calibrate the appliance once a year (see page
fter removing covers, live parts may be exposed. You may
eceive an electric shock if you touch these parts. Disconnect
before removing any covers. Any work inside
SGD@OOKH@MBDL@XNMKXADODQENQLDCAXPT@KHÅDCDKDBSQH
epairs and service work are described in a separate service manual.

he appliance may only be stored under the following conditions:
in a dry and enclosed, dust-free room
isconnected from the power supply
is product is subject to the Directive 2002/96/EC on Waste
lectrical and Electronic Equipment (WEEE) of the European Parliament
and of the Council. This appliance has been brou
2005 in countries which have already integrated this
irective into their national laws. It may not be disposed of in normal
ousehold waste. For disposal, please contact your dealer or the
manufacturer. Any appliances that are infected, infectious or contami
nated with materials hazardous to health are excluded from return.
ease also observe all other regulations applicable in this context.
efore disposing of the appliance, please render the door locking
mechanism unusable, for example, to prevent playin
locked inside the appliance.
here is a lithium battery in the ControlCOCKPIT of the appliance.
emove it and dispose of it in accordance with the regulations in your
Fig. 25 Removing the lithium batter
he appliance may not be left at public or communal recycling or collection points.

asic device settings 34
asic settings 34
eclaration of conformity 1
elivery 16, 17,
igital backwards counter
lectronic temperature moni-
nding operation 30
rror description 32
rror messages
an speed 27
ehlermeldung 32
oading the appliance 24
og memory
aintenance 44
alfunctions
aterial 11
echanical temperature
perating 23
perating modes 26
perating personnel 7,
wer failure 33
roduct safety 7
utting into operation 22
e after delivery 17
Switchin

Memmert GmbH + Co. KG
Willi-Memmert-Straße 90-96 | D-91186 Büchenbach
Tel. +49 9122 925-0 | Fax +49 9122 14585
E-Mail: sales@memmert.com
facebook.com/memmert.family
Die Experten-Plattform: www.atmosafe.net
Universal ovens
Incubators
D33363 | Date 06/2016
englisch