◎ 4 Channels for shutter motors up to 600W, Manual control or 8 Channels for switching outputs for ohmic loads up to 2300W.
◎ Any supposable mixed form of switching outputs and shutter output possible.
KAA-8R Universal Actuator 8-fold, 230V AC, 16A.
◎ 4 Channels for shutter motors up to 600W, Manual control or 8 Channels for switching outputs for ohmic loads up to 3680W.
◎ Any supposable mixed form of switching outputs and shutter output possible.
1.2 Usage & possible applications
The universal actuator has its field of applications always if you ask flexibility. It can be parameterized as well as an adequate
switching actuator.
Further, there is the possibility of embedding the channel into automatic blocks and activate different scenes. At activation of the
automatic function, absolute position can be approached via 1 Bit object. This function is e.g. very suitable for the start-up of
sunblind positions, which are called via a brightness sensor. Additional weather alarms are parameterize able, which can call
determined functions at the universal actuator.
Additional a manual control of the shutter/blinds can be switched on or off.
Parameterized as switching actuator, the settings switching output and staircase are available. At the configuration switch, all
settings are available which are necessary for a comprehensive parameterization. As well On-/Off-delay, normally opened mode
or normally closed mode, cyclic sending, central function, logical functions as scene function are adjustable. Additional the reset
behavior and the blocking behavior can be set.
Via the staircase function an automatic switch off after a determined time can be adjusted.
1.3 Exemplary Circuit diagrams
1.3.1 Switching actuator
Parameterized as switching actuator, the actuator is connected in the following way:
Illustration 3: Exemplary circuit diagram as 8-fold switching actuator
1
Page 4
1.3.2 Mixed mode
Also arbitrary mixed modes are possible, e.g. in the following way:
Illustration 4: Exemplary circuit diagram as switching and shutter actuator
1.4 Structure & Handling
The universal actuator (KAA-8) contains of a programming button as well as a programming-LED, which shows a activated
programming button. The universal actuator works with 230V AC. Every channel of the MRDC device contains of a status-LEDs.
The status-LEDs show an active run-up or an active run-down command.
With the buttons left/right you can chose the channel and with the buttons up/down you can move the channel down or up.
The following illustration shows a 8-fold universal actuator:
Illustration 5: Overview hardware module (KAA-8R)
2
Page 5
1.5 Functions
The functionality is the same for all channels. Depending on the hardware module the device contains of up to eight channels.
At the first step, every channel can be selected as not active, Switch/Staircase/switch impulse, heating control with PWM
not active
The channel becomes no more functions allocated. There are no more opportunities to parameterize the channel.
Switch, Staircase, switch impulse, heating control with PWM
Every channel of the pair of channels can be selected individually as switch or staircase switch impulse…etc. at the next,
step.
If the channel is selected as switch, different switching actions can be parameterized.Additional actions, like logic functions
and scene functions, can be parameterized.
If the channel is selected as staircase, a staircase function, which causes an automatic cutout after an adjusted time, can be
parameterized. Additional settings for the adjustment of the staircase function are available. Like switch, staircase function,
you can find corresponding setting when selecting “switch impulse” or “heating control with PWM”. Please find detail
information in Later chapter.
1.5.1 Overview at general setting and functions
Parameter
Descriptions
not active
switching
General settings
Channel selection
staircase light
switch impulse
heating control with PWM
Startup Timeout
After the device is powered on, the delay
of relay closed/separated.
Manual Operation
Whether to allow manual operation of the
panel
Eco Mode,
Eco mode
switch LED's off after
send “operation” cyclic
Use to periodically report device status
(0=not active)
Chart 1: Overview general setting and functions
1.5.2 Overview functions at the switch/staircase mode/switch impulse/heating
Control with PWM
Group of functions
Group addresses
Functions
number of objects/connections=dynamic
(freely assignable of the user)
Reset behavior
behavior at bus power breakdown
behavior at bus power up
startup timeout
normally closed/ normally openedRelay mode
Switch functions
switching
central switching function
Time functions
on-delay
off-delay
Staircase light functions
time for staircase
pre-warning (with adjustable warning and
pre-warning time)
manual off
Extend time on/off
Forced control /priority functions
locking function
logic functions (AND/ OR)
3
Page 6
Group of functions
Scenes
State functions
Switch impulse functions
Functions
scene function for up to 8 scenes per channel
feedback function
Impulse time
locking function
Heating control with PWM
PWM function
Emergency mode
Chart 2: Overview functions for switch, staircase mode
1.6 Settings at the ETS-Software
Selection at the product database:
Manufacturer: MEANWELL Enterprises Co. Ltd
Product family: Output
Product type: Universal actuator
Product name: addicted to the used type, e.g.: KAA-8R universal actuator 8-fold, 16A
Order number: addicted to the used type, e.g.: KAA-8R
1.7 Starting up
After wiring, the allocation of the physical address and the parameterization of every channel follow:
(1) Connect the interface with the bus, e.g. MEANWELL USB interface KSI-01U
(2) Switching the power supply
(3) Set bus power up
(4) Press the programming button at the device(red programming LED lights)
(5) Loading of the physical address out of the ETS-Software by using the interface(red LED goes out, as well this process was
completed successful)
(6) Loading of the application, with requested parameterization
(7) If the device is enabled you can test the requested functions(also possible by using the ETS-Software)
4
Page 7
2.Communication Objects
2.1 Global communication objects
The central communication objects are standardly shown. They contain as well the communication objects, which are only valid
for corresponding functions.
2.2 Default settings of the central communication objects
The following chart shows the default settings of the global communication objects:
Default settings
Nr.Object FunctionLengthPriorityCRWTU
1Manual Control1 itLowXBX
2Switch On/Off1 itLowXXB
31 BitLowXXXOperation
Chart 3: Default settings of the central communication objects
You can see the default values for the communication objects from the upper chart.According to requirements the priority of the
particular communication objects as well as the flags can be adjusted by the user. The flags allocates the function of the objects in the
programming thereby stands C for communication, R for Read, W for write, T for transmit and U for update.
2.3 Default settings of the communication objects for each functions
The following chart shows the default settings of the communication objects, if the pair of channels is selected as shutter/blinds:
3.Reference ETS-Parameter – Switch for different application
3.1 General setting
The following illustration shows the menu of General setting.
ParameterValueDescription
Startup Timeout2 ~ 60s
Manual Operation
Eco Mode,
switch LED' off after
send " peration" cyclicO
s
(0=not active)
After the device is powered on, the delay of relay closed/separated.
The manual operation allows the relay to be normally controlled during the delay
wait. If there is Object Communication, it will be recorded first and will not re-
spond. The delay ends and the corresponding action is executed.
active
disable
lockable over object
Whether to allow manual operation of the panel.
Lockable over object: means to enable or disable the Manual Operation via
Object.
not active
30S 1min 2min 5min
10min 20min 30min
Power saving mode. After the set time delay, turn off the LED on the panel.
40min 50min 60min
0 ~ 30000minUse to periodically report device status. It is independent Operation Object
6
Page 9
3.2 Channel selection
To operate the universal actuator as switching actuator, at first the each channel, e.g. Channel A, must be selected
as “switching”, “staircase light”,” Switch impulse”...etc. At the next step, for each channel can be selected if the
channel shall operate as switch for different application.
The following illustration shows the submenu channel selection:
Illustration 6: Channel selection
The following chart shows the available settings for the channel selection:
ETS-text
Channel A
not active
switching
staircase light
Dynamic range
[default value]
comment
Selection, if a pair of channels shall operate as switching
actuator or as shutter actuator.
Not active deactivates the pair of channels.
switch impulse
heating control with PWM
Channel A
Channel H
switching
staircase light
switch impulse
At the switching/staircase light/switch impulse
mode/heating control with PWM. Theses settings are
available.
heating control with PWM
Chart 6: Available settings channel selection for switch/staircase
Each channel can operate as switch.
At the chapter 4, the switching actuator mode is descripted. Each channel can be parameterized as well as switching output or
as its described function
7
Page 10
3.3 Identical parameter
The following parameters is available at channels selected as switch as at channels selected as switch.
3.3.1 Relay operating mode
The following illustration shows the setting options for this parameter:
illustration 7: Operating mode
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
comment
[default value]
I
Mode
normally opened
normally closed
Relaychanneloperating mode of the
When the channel output is in the Off state, the message information of ON is re-
ceived, and it takes a delayitch On.of n seconds to sw
On delay0-3000s
If the received message is also to switch on the output during the waiting period, it
will be ignored.
Note: The " n Delayerlapped with the " tartup Timeout" time inOS" time here is not ov
the " eneral Setting" above.G
When the channel output is in the On state, the message information of Off is re-
Off delay0-3000s
ceived, and it takes a delayitch to the Off output.of n seconds to sw
Note:" time here is not overThe " ff Delaylapped with the " tartup Timeout" timeO
S
in the " eneral Setting" above.G
Chart 7: Operating mode
The following diagram shows the behavior of the relay operating mode normally closed and normally opened. The input for
the channels is a KNX-telegram, which sends alternating 0-signals and 1-signals:
KNX telegram
101100
ON
Mode: “ normally opened”
OFF
ON
Mode: “ normally closed”
OFF
t
State
t
State
t
8
Page 11
3.3.2 Central function
The following illustration shows the setting options at the ETS-Software:
Illustration 8: Central function
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
[default value]
comment
Central function
Chart 8: Central function
not active
active
switches the central function
on/off for this channel
The central function can be switched on/off for every channel. For switching on this function, you have to choose the option
“active”. By calling the central communication object, all channels with an activated central function are switched on with
their current parameterization. So switch-on delays or staircase functions are still kept.
The following chart shows the associated communication object:
NumberName
2
Chart 9: Communication object central function
Central function1 Bitcentral switching of the channels
LengthUsage
3.3.3 Behavior at locking /unlocking
The following illustration shows the setting options at the ETS-Software:
Illustration 9: locking function
The following chart shows the dynamic range for this parameter:
ETS-text
Behavior at locking
Behavior at unlocking
Dynamic range
[default value]
On
Off
no change
On
Off
no change
comment
Behavior to a locking/unblocking process
Behavior to unlocking process
previous state, catch up on
Switching
previous state
Chart 10: Behavior at locking/unlocking
The locking function gets active, when the corresponding communication object becomes a logical 1 . By sending a
""
logical 0 , the locking function can be deactivated again.""
The parameter Behavior at locking defines an action for the output at activating the locking process.""
There are the setting on, off and no change available.
When the output channel is at the locking state, the manual button operation is invalid.
Note: Locking has the highest priority
The unlocking function gets active, when the corresponding communication object becomes a logical 0 . By sending a
""
logical 1 , the unlocking function can be deactivated again.""
The parameter Behavior at unlocking defines an action for the output at activating the unlocking. There are the setting""
on, off ,no change available, previous state, catch up on Switching and previous state.
Regarding the parameter previous state, catch up on Switching , If the actuator receives a message of type "Switch"
""
during locking, it will record it. After unlocking, the corresponding action will be executed on the output channel according
9
Page 12
The following chart shows the corresponding communication object:
Number Name
7
lock1 Bitlocks the channel
LengthUsage
Chart 11: Communication object locking function
The following diagram describes the blocking process. For the “Behavior at locking”, the action on was parameterized and
for the “Behavior at unlocking” the action off was parameterized:
KNX telegram
10101
t
State
ON
OFF
t
The KNX telegram shows which values are send to the locking object. By sending a logical “1”, the locking function is
activated and the channel is switched on. The locking function is deactivated again by sending a logical “0”. so the channel
is switched off.
3.3.4 Behavior at bus power up/down
The following illustration shows the setting options at the ETS-Software:
Illustration 10: Behavior at bus power up/down
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
comment
[default value]
Behavior at bus power up/Behavior
at bus power down
On
Off
no change
Adjustment, how the channel shall react
in case of a bus power breakdown/return
Chart 12: Behavior at bus power up/down
Every channel can occupy a certain state as well in case of a bus power breakdown as in case of a bus power return. The
channel can be switched off or on, but also stay in its current state by choosing the parameter “no change”.
To avoid problems in case of a bus power breakdown, you should adjust this parameter very conscientious. Because there
is no controlling possible as long as the bus power is down.
10
Page 13
3.4 Switching output
The following parameters, which are described at the headings 5.3.x, are only available at channels selected as switch.
3.4.1 Overview
By choosing a channel as switch, a sub menu, called ChannelA Switching, appears for this channel at the left drop down
menu.
Illustration 28: Switching output
11
Page 14
The chart shows the possible settings for switching outputs:
ETS-text
Mode
Dynamic range
[default value]
normally opened
normally closed
On-Delay
Off-Delay
Central function
0.... 0000 sec3
[]0=nodelay
0.... 0000 sec3
[]]0=no delay
not active
active
Send state
no send
at change
at change and lock
always at input of telegram
comment
Operation mode of the channel
Switch on delay of the channel in seconds
Switch off delay of the channel in seconds
Activates the central function for this channel
Set whether to send the telegram of "Status"
No send: do not send
At change: sent when the current output status changes
At change and lock: sent when the current state changes or during
the lock state
Note1: When the channel is locked, if the locking/unlocking behavior
Send state cyclic
(0=not active)
is set to no change, the locking/unlocking will not send the " tate"
because the status will not change; but if the switch telegram is sent
during the locking period, Upload the current actual "State" (although
the output status has not changed)
Note2: During the channel locking =>unlocking
if there is no change on output state , "State" is not uploaded; if there
is a state change, "State" needs to be uploaded.
Note3: During the channel unlocking=>locking, if
if there is no change on output state, "State" is not uploaded; if there
is a state change, "State" needs to be uploaded.
Always at input of telegram: As long as the message of the
"Switch" type is received, it will be sent regardless of the output sta-
tus, even if it is in the locking state.
0~30000sSet whether to send "State" telegram periodically.
Additional inverted state
not active
active
If the Additional inverted state is activated, the "Inverted State" mes-
sage is sent.
This activation will add an "Inverted State" Object that coexists with
S
Behavior at locking
Off
On
no change
the "State" Object.
Not active, "Inverted State" Object does not appear.
Action for activating the locking process.
Note: Locking has the highest priority
12
Page 15
ETS-text
Behavior at unlocking
Priority/Forced control
Behavior after bus power
up
Behavior after bus power
down
Logic function
Dynamic range
[default value]
Off
On
no change
previous state, catch up on
switching
previous state
not active
2 Bit force control
1 Bit Priority on
1 Bit Priority off
Release time
for forced control
:
(0=not active)
Behavior after forced control:
0-600min
Off
On
no change
previous state, catch up on
switching
previous state
no change
off
on
no change
off
on
not active
active
comment
Action for deactivating the unlocking process
Priority control
Not active: not active
2 bit force control: 00/01 No Control, "10"-priority, Off; "11"priority, On
1 bit Priority On: "1" - enabled; "0" - released
1 bit Priority Off: "1" - enabled; "0" - released
0: indicates that the forced control is always valid unless an
Object message is received to release the command;
1-600min: Forced control maintains the setting range of time.
When time is up, the forced control is automatically released.
Previous state, catch up on Switching: If the actuator receives "Switch" type telegram during the forced control, it will
record it. After forced control remove, the corresponding action
will be performed on the output channel according to the
latest set of "Switch" type telegram values received previous .ly
Previous state:After the forced control ends, the relay outp
channel will restore the state value before the forced control.
Action for a bus power return.
If the actuator receives "Switch" type telegram during waiting the
power up. After the bus power up, the value of the Switch type telegram is used and the bus power up setting is ignored.
Action for a bus power breakdown
Whether the logic function is enabled or not
ut
Scenes
not active
active
Threshold switch
not active
active
Operation hours
counter
Chart 38: Switching output
not active
active
3.4.2 On/Off delay
The following illustration shows the setting options at the ETS-Software:
Whether the scene function is enabled or not
Whether the threshold control function is enabled or not
Whether the operation time statistics function is enabled or not
13
Page 16
The on-delay causes a delayed switch of the channel. At sending an on-signal to the channel, first the adjusted on delay time
expires and afterwards the channel will be switched on.
The off delay works on the same principle. At sending an off-signal, first the adjusted off delay time expires and afterwards the
channel will be switched off.
Both functions work as well alone as combined. By adjusting “0 seconds” for a delay the function is switched off.
The following diagram describes the combination of on and off delay:
KNX telegram
1010
t
State
ON
OFF
t ont ont offt off
t
3.4.3 Logic function
The following illustration shows the setting options at the ETS-Software:
Illustration 30: Logic function
The logic function can be activated with one or two objects. The objects are the inputs of the logic block. Furthermore you can
choose between an AND-function and an OR-function.
When you have activated the logic function, the logic block has to be satisfied before switching the channel. As long as the
logic function is not satisfied, the channel does not react to any signal.
14
Page 17
The chart shows the possible settings for Logic function:
ETS-textDynamic range
[default value]
with Switch object and one Logic
Logictionfunc
Logicionsoperat
object
with Switch object and two Logic
objects
OR
AND
XOR
gate opened with Logic object=0
gate opened with Logic object=1
Comment
With Switch object and one Logic object:
The calculated result of the switch object and logic1 object
as the executing value of the output channel.
With Switch object and two Logic object:
The calculated result of the switch object and logic1,logic2 object as the execut-
ing value of the output channel.
Note: The Switch object mentioned here is not limited to the "Switch On/Off"
Object. It is also included for the Switch brought by Object such as "Scene" and
"Threshold switch".
OR: At least one input is active (=1)
AND:All inputs are active (=1)
XOR:Only one input is active (=1)
gate opened with Logic object=0:The output can be switched via the switch-
ing object if all logic objects have the value 0
gate opened with Logic object=1:The output can be switched via the switch-
ing object if all logic objects have the value 1
Invert inputs
(with Switch object
and one Logic
object)
Invert inputs:
(with Switch object
and two Logic
object)
Invert output
Set objects value
after bus power up
no invert
invert object Switching
invert Logic1object
invert object Switching & Logicject1ob
no invert
invert object Switching
invert Logic object1
invert Logic object2
invert object Switching & Logic object1
invert object Switching & Logic object2
invert Logic object1 & Logic object2
invert object Switching &Logic object1
& Logic object2
no invert
invert
not active
active
Whether to invert the input of the objects such as switch, logic1, etc.
(in the case of one logic Object)
Note: Invert object Switching is not onlyitch On/Off" Object.limited to the "Sw
It also works on " witch" brought byjects such as "Scene" and "ThresholdSOb
switch".
Whether to invert the input of the objects such as switch, logic1, logic2, etc.
(in the case of two Logic Objects)
Whether to invert the calculated results of the output
It is used to set the initial values of three objects: switch, Logic1, and logic2
after the actuator is powered on.
If the setting is not activated, the default value of the three objects is "0",
and the Logic operation is not executed after power-on.
operation is executed and output after
If the setting is activated, a Logic
power-on.
15
Page 18
The following chart shows the relevant communication objects:
NumberName
12Logic 11 BitLogic object 1, is the rst input for the logic
13Logic 21 BitLogic object 2, is the second input for the logic
Chart 39: Communication objects logic
According to the chosen logic operation only one or both objects have to become a 1-signal. The following chart shows the
both logic operations with two objects:
AND-Connection
Logic 1Logic 2Channel
switchable?
LengthUsage
block
block
OR-Connection
Logic 1Logic 2Channel
switchable?
00
01
10
11 Yes11 Yes
Chart 40: Logic operations
No
No
No
00
01 Yes
10 Yes
No
3.4.4 Scene function
When functions of different groups (e.g. light, heating ) shall be changed simultaneously with only one keystroke, it is practical
to use the scene function. By calling a scene, you can switch the lights to a specific value, drive the shutter to an absolute
position, switch the heating to the day mode and switch the power supply of the sockets on. The telegrams of these functions
can have as well different formats as different values with different meaning (e.g. “0” for switch the lights off and open the
shutters). If there were no scene function, you would have to send a single telegram for every actuator to get the same
function.
The scene function of the switch actuator enables you to connect the channels of the switch actuator to a scene control. For
that, you have to assign the value to the appropriated space (scene A..H). It is possible to program up to 8 scenes per switching
output. When you activate the scene function at the switching output, a new sub menu for the scenes appears at the left drop
down menu. There are settings to activate single scenes, set values and scene numbers and switch the memory function on/off
at this sub menu.
Scenes are activated by receiving their scene numbers at the communication object for the scenes. If the memory function of
the scenes is activated, the current value of the channel will be saved at the called scene number.
The communication objects of the scenes have always the length of 1 byte.
The following illustration shows the setting options at the ETS-Software for activating the scene function:
Illustration 31: Scene function
The following chart shows the relevant communication object:
NumberName
11
Scene
LengthUsage
1 ByteCall of the scene
Chart 41: Communication object scene
For calling a certain scene, you have to send the value for the scene to the communication object. The value of the scene
number is always one number less than the adjusted scene number. For calling scene 1, you have to send a “0”. “o the scene
numbers have the numbers from 1 to 64, but the values for the scenes only from 0 to 63.
If you want to call scenes by a binary input or another KNX device, you have to set the same number at the calling device as at
the receiving device. The calling device, e.g. a binary input, sends automatically the right value for calling the scene.
There are up to 8 storage options for scenes at every channel.
16
Page 19
These 8 storage options can get any of the possible 64 scene numbers.
Illustration 32: Sub function scene
The chart shows the possible settings for scenes, which are identical for all channels. The settings are available at the sub
menu for the scenes:
ETS-textDynamic range
[default value]
not active
Learn scene
active
not active
Scene A
active
Scene number : 1-64
Behavior of scene :
off / on / lock / unlock
-----
Comment
not active :The Learn scene function is not enabled
Object Value corresponds to DPT17.001 scene number.
active : Enable the Learn scene feature. Object Value corresponds to DPT
18.001 scene control.
Whether to enable the setting of scene A
Note about the behavior of scene:
Behavior of scene = unlock,When the corresponding Scene number is received, the channel is at lock state (locked by the lock object), then the Scene
Object can release the lock state of the channel.
17
Page 20
ETS-textDynamic range
[default value]
Comment
Scene H
active
Scene number : 1-64
Behavior of scene :
not active
off / on / lock / unlock
3.4.5 Threshold switch
The following illustration shows the setting options at the ETS-Software:
The chart shows all possible settings peration hours counter function:o
ETS-textDynamic range
1 Byte percent value(0-100%)
1 Byte value(0-255)
Whether to enable the setting of scene H.
Supports up to 8 scene settings at every channel.
Comment
[default value]
Value setting
Behavior of Channel at
lower deviation
Behavior of Channel at
exceedance
2 Byte value(0-65500)
2 Byte temperature value(-100-250℃)
2 Byte brightness value(0-100000Lux)
not active
off
on
Lower threshold< :
0-100%
0-255
0-65500
-100~250℃
0-100000 Lux
not active
off
on
Threshold setting, 5 types of threshold
Behavior of Channel at lower threshold
Threshold setting: five threshold ranges correspond to the
above five threshold types
Threshold comparison: compare to the value sent by the
"Threshold switch" Object.
If the value sent by the "Threshold switch" Object is less than
the threshold, the action set by "Behavior of Channel at lower
deviation" is executed.
Behavior of Channel at higher threshold
18
Page 21
ETS-textDynamic range
[default value]
Comment
Upper threshold> :
0-100%
0-255
0-65500
-100~250℃
0-100000 Lux
3.4.6 Operation hours counter function
The following illustration shows the setting options at the ETS-Software:
Threshold setting: five threshold ranges correspond to the
above five threshold types
Threshold comparison: compare to the value sent by the
"Threshold switch" Object.
If the value sent by the "Threshold switch" Object is less than
the threshold, the action set by "Behavior of Channel at ex-
ceedance" is executed.
The chart shows all possible settings Operation hours counter function:
ETS-textDynamic range
[default value]
Type of operation hours
counter
operation hours counter
reverse counter to the service
Comment
There are 2 type of operation hours counter
operation hours counter :The operation hours counter counts up the
operation hours when the relay is closed.
Note: After the output channel is set to the ON state, the counting opera-
tion time is started. When the output channel is turned OFF, the timing is
paused, but the timing is not cleared. After the OFF state, although the
timer is paused, the count value is still reported at regular intervals,
which is equivalent to the same timer value for each report.。
reverse counter to the service
from the adjusted service interval to zero when the relay is closed and
reports a service message at zero.
Note: During countdown, the countdown starts after the output channel
is turned ON. When the output channel is turned OFF, the countdown is
suspended. When the countdown reaches zero, a service telegram is
generated. Please refer to the Database Object Description table.
:The reverse counter to service counts
19
Page 22
ETS-textDynamic range
Select data type
[default value]
4Byte value in s(DPT13.100)
2Byte value in h(DPT7.007)
Comment
Set the data type of the uploaded telegram
operation hours counter
reverse counter to the
service
Send status of operation hours every
(0=not active): 0 -10000 h
Send operation hours small cyclic:
not active 10min 20min 30min
Send status of Service hours every
(0=not active) : 0-10000h
Send service status at intervals:
0-60000h
Upload " peration hours counter" counting value regularly ino
" ours" time unitsh
Upload operation hours counting value r
Upload the count down the remaining time value of "reverse counter to
the service "regularly in " ours" time units
Start value of Countdown
h
egularly in smaller time units
3.5 Staircase
The following parameters, which are described at the headings 4.5.x, are only available at channels selected as staircase.
3.5.1 Overview
By choosing a channel as staircase, a sub menu, called Channel A Staircase, appears for this channel at the left drop down menu.
The sub menu is shown at the following illustration:
Illustration 34: Staircase
20
Page 23
The chart shows all possible settings for staircase outputs:
ETS-textDynamic range
[default value]
Comment
Output mode
normally closed
Operation mode of the channel
The Switch Object can controls the On/Off of the Channel and has no stair-
normally open
Additional switching
not active
case time limit.
object
active
Time of staircase light1-30000sDuration of the switching process
Prewarning
not active
Light on-off
prewarning object
Light on/off and prewarning
object
Prewarning mode setting before the stair light is turned off
Note: If set to """prewarning objectLight on/off and prewarning object
"prewarning object" will send Value=1 after " ime of staircase light "ends. AfterT
the Prewarning is over, the "prewarning object" will send Value=0. Declare the
end of a complete staircase light action.
This parameter will be shown when Prewarning is set to the Light on-off and
Light on-off
Prewarning duration :0 - 30000s
Light on/off and prewarning mode. When stair light operating time is end, it
enters a short time to turn off the light. This parameter corresponds to: Light-
Off time.
This parameter will be shown when Prewarning is set to the Light on-off and
or
Manual switching off
Extend time staircase
light
Time factor for object
"Staircase light with
time"
Light on-off
Prewarning time : 0 - 30000s
not active
active
no extend time
restart time
add time
1s
10s
1min
Light on/off and prewarning mode.
After the above Light-Off time is over, Light-On will be restarted. This parame-
ter corresponds to: Light-On time. After the Light-On operating time is over,
Output is OFF and the entire process ends.
Activation of the manual turn off of the staircase
During the stair light operating time, the stair light is triggered again, the pro-
cessing mode for time.
No extend time: no longer expands the time, it is equivalent to ignore the new
trigger.
Restart time: restart counting time
Add time: superimpose the remaining Light Onstair light ontime to the new
time.
The time value sent byith time", the time unitthe Object "Staircase light w
corresponding to it. For example, if Object Value=10 and Time factor is set to
"0s" it means that the lighting ti me of Staircase light is 10*10=100s.
Central function
notactiveactive
Set whether this channel is responsive to central function's unified control
21
Page 24
ETS-textDynamic range
[default value]
Comment
Set whether to send the telegram of "Status"
Send state
Send state cyclic
(0=not active)
Behavior at locking
Behavior at unlocking
Priority/Forced control
no send
at change
at change and lock
always at input of telegram
0~30000sSet whether to send "Status" telegram periodically.
Additional inverted state:
no send:
at change:Sent when the current output status changes
at change and lock:Sent when the current state changes or during lock
For related explanations, refer to the previous Switch mode.
If the Additional inverted state is activated, the message "inverted state" is
not active
sent.
active
off
on
Action for activating the blocking process.
no change
off
start time of staircase light
Action for deactivating the blocking process
not active
2 bit force control:00/01 No Control,
2 Bit force control
"10"priority ,Off;"1 "-priority1,On
1Bit priority On
1 bit Priority On :"1"enabled ;"0"removed
1Bit priority Off
1 bit Priority Off :"1"enabled ;"0"removed
For related explanations, refer to the previous Switch mode.
Release time
for forced control
(0=not active):0-600min
Behavior after forced control:
off
Start time of Staircase Light
0: indicates that the forced control is always valid unless an Object message
is received to release the command;
1-600min: Forced control maintains the setting range of time. When the time
is end, the forced control is automatically removed.
For related explanations, refer to the previous Switch mode.
OFF:Output channel is set to OFF state
Start time of Staircase Light:After the forced control is over, the output
channel will execute a complete Staircase Light process.
22
Page 25
ETS-textDynamic range
[default value]
Comment
bus power up, the actuator will execute the corresponding action type on the
relay output channel Off:Output channel is set to OFF state
Behavior after
bus power up
Behavior after
bus power down
Scenes
off
start time of staircase light
state before bus power down
off
on
no change
not active
active
start time of staircase light: Start stair light output
state before bus power down:Restore the state before power down. If the
staircase light output=ON state before power failure, the complete output ow
of the staircase light will be executed afterer-on; if the staircase light out-pow
put=OFF state before power failure, the action will not be performed after
power-on, only report it. State.
If bus power down is detected, the actuator will perform the corresponding
action on the relay output.
Whether to activate the scene function.
The scene function settings of Staircase Light are the same as those of Switch
mode.
The difference is:
"On"、"Off" in Behavior of Scene
"On" means to start the Staircase Light"processff"means to turn off theO
Staircase Light output (Manual switching off is required to be Active)
3.5.2 Staircase time
The following illustration shows the setting options at the ETS-Software:
Illustration 35: Staircase time
The staircase function is activated by choosing a channel as staircase. This function enables an automatic turn off of the
channel after an adjusted time, called “time for staircase”. The time for staircase can be parameterized freely. By sending an
“on-signal” at the communication object, the channel is switched on and the time runs out. After the time is ran out, the channel is
switched off automatically. There are a lot of further functions to adjust the staircase function. These functions are described at
the following segments.
The following chart shows the relevant communication object:
NumberName
18
Chart 45: Communication object staircase
Staircase1 BitCalling of the staircase function
LengthUsage
23
Page 26
3.5.3 Scenes (Staircase Light)
ETS-textDynamic range
[default value]
Comment
Learn scene
Scene A
-----
Scene H
not active
active
not active
active
Scene number : 1-64
Behavior of scene :
off / on / lock / unlock
not active
active
not active:
active
Whether to enable the setting of scene A
Note about the behavior of scene:
Behavior of scene = unlock,When the corresponding Scene number is received, the
channel is at lock state (locked by the lock object), then the Scene Object can release the
lock state of the channel.
Note: When Behavior of scene = ON, the function is to trigger the Staircase light to start.
When the Behavior of scene = OFF, you need to set "Manual switching off" to Active to
close the Staircase light process.
Whether to enable the setting of scene H.
Supports up to 8 scene settings at every channel.
The Learn scene function is not enabled
:
Enable the Learn scene feature.
Value corto DPT 18.Objectresponds001 scene control.
.Object Value corresponds to DPT17.001 scene number
Scene number : 1-64
Behavior of scene :
off / on / lock / unlock
3.6 Switch impulse
The following illustration shows the setting options at the ETS-Software:
24
Page 27
There are some functions to adjust the Switch impulse function. These functions are described at the following segments.
ETS-textDynamic range
Comment
[default value]
Normally open:relay contact is normally open. Impulse is relay con-
Output mode
Impulse time
Repeat impulse signal once
normally open
normally closed
300ms 400ms 500ms
750ms 1s 1.5s 2s 3s
5s 7.5s 10s 15s 20s
25s 30s
not active
active
Time to the next impulse:
0.5s 0.75s 1s 1.5s
2s 3s 5s 7.5s 10s
tact closure
Normally closed:relay contact is normally closed. Impulse is relay
contact open
Impulse pulse width, it means the time of the relay contacts are closed
(or separated)
If the output mode set as normally open, this time is the relay contact
closure time.
If the output mode set as normally closed,contactthis time is the relay
separation time.
Set whether to activate the function of repeat impulse signal output
once.
After the current Impulse output ends, the interval of the next Impulse
which is repeated
15s 20s 25s 30s
Set the action of the output channel to enter the "locking" state
Off: The output channel turns OFF. If impulse is being output, it will be
off
Behavior at locking
interrupted;
no change
no change: the output channel is locked in the current output state
off
Set the action when the output channel returns to the "unlocking" state.
Behavior at unlocking
Off: the output channel becomes OFF;
switch impulse
switch impulse : output channel executes an impulse output process
3.7 Heating Control with PWM
The following illustration shows the setting options at the ETS-Software:
25
Page 28
There are several functions to adjust the Heating Control with PWM function. These functions are described at the following segments.
ETS-textDynamic range
[default value]
not energized closed
Valve type
not energized opened
PWM cycle0-255min
not active
Emergency mode
10min 20min 30min
monitoring time
1h 2h 3h 4h
Comment
not energized closed:corresponding to Output On for relay contact
not energized opened:corresponds to Output On for relay contact separation
Set the cycle of the PWM. The value of the Object "Control Value" is as the
PWM duty cycle and it the time of output On.
For example: When set cycle=10min and Object " ontrol Value"=75%,TheC
Output On time is 7.5min, Switch Off is 2.5min
Monitoring time setting for emergency mode. In normal conditions, the Object
"Control Value" needs to send to the actuator periodically. When the system
fails to receive the Object "Control Value" periodically, the "Emergency mode"
can play a protective function.
When "Emergency mode" is active, the setting value here is the monitoring
time. If the Object "Control Value" is not received beyond the monitoring time,
it will automatically enter "Emergency mode". At this time, the duty cycle value
of the PWM output is determined by the following one.
control value for emergency
mode:0%-100%
Note: If the setting value of "Emergency mode monitoring time" is larger than
the setting value of "PWM cycle", the actuator will not send "State Emergency
Mode" Object.
For example: PWM cycle=9min, Emergency mode monitoring time=10min.
The duty cycle value of the PWM output after entering "Emergency mode".
For example: PWM cycle=10min, where is set 20%, after entering " mergencyE
mode", the duty ratio of PWM output is 10*20%=2min.
26
Page 29
No.28, Wuquan 3rd Rd., Wugu Dist., New Taipei City 248, Taiwan
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.