Meanwell HDR Installation Manual

Page 1
Installation Manual
TypeHDR DIN rail power supplySeriesHDR-15, HDR-30, HDR-60, HDR-100, HDR-150
HDR-15-5 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 5V 2.4A HDR-15-12 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 12V 1.25A HDR-15-15 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 15V 1.0A HDR-15-24 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 24V 0.63A HDR-15-48 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 48V 0.32A HDR-30-5 INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 5V 3.0A HDR-30-12 INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 12V 2.0A HDR-30-15 INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 15V 2.0A HDR-30-24 INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 24V 1.5A HDR-30-48 INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 48V 0.75A HDR-60-5 INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 5V 6.5A HDR-60-12 INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 12V 4.5A HDR-60-15 INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 15V 4.0A HDR-60-24 INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 24V 2.5A HDR-60-48 INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 48V 1.25A HDR-100-12 INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 12V 7.1A HDR-100-15 INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 15V 6.13A HDR-100-24 INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 24V 3.83A HDR-100-48 INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 48V 1.92A HDR-100-12N INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 12V 7.5A HDR-100-15N INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 15V 6.5A HDR-100-24N INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 24V 4.2A HDR-100-48N INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 48V 2.1A HDR-150-12 INPUT: 100-120VAC 3.0A 50/60Hz OUTPUT: 12V 10.2A
INPUT: 200-240VAC 1.8A 50/60Hz OUTPUT: 12V 11.3A
HDR-150-15 INPUT: 100-120VAC 3.0A 50/60Hz OUTPUT: 15V 8.55A
INPUT: 200-240VAC 1.8A 50/60Hz OUTPUT: 15V 9.5A
HDR-150-24 INPUT: 100-120VAC 3.0A 50/60Hz OUTPUT: 24V 5.31A
INPUT: 200-240VAC 1.8A 50/60Hz OUTPUT: 24V 6.25A
HDR-150-48 INPUT: 100-120VAC 3.0A 50/60Hz OUTPUT: 48V 2.72A
INPUT: 200-240VAC 1.8A 50/60Hz OUTPUT: 48V 3.2A
Introduction
HDR is a DIN rail power supply series with ultra slim appearance and full range AC input (100-240Vac). The series conforms to EN6100-3-2, the norm the European Union regulates for harmonic current. With plastic housing, it can effectively prevent user from electric hazards. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the
unit in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
Page 2
Installation Manual
2The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
3Use copper wire only, and recommended wires are shown as below.
AWG 18 16 14
Rated Current of Equipment
(Amp)
7 10 15
Cross-section of Lead(mm2 ) 0.8 1.3 2.1
NoteCurrent each wire carries should be de-rated to 80% of the current suggested
above when using 4-6 wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure each contact is connected to wires to prevent too much current stress on a single contact.
4Use wires that can withstand temperatures of at least 80°C, such as UL1007. 5Recommended wire strapping length is 6mm (0.236”). 6Recommended screwdriver is 3mm, slotted type. 7The recommended torque setting for terminals is shown as below.
Model I/P O/P HDR-15 5 kgf-cm (4.4 Lb-in) 5 kgf-cm (4.4 Lb-in) HDR-30 3.4 kgf-cm (3.0 Lb-in) 5 kgf-cm (4.4 Lb-in) HDR-60 3.4 kgf-cm (3.0 Lb-in) 5 kgf-cm (4.4 Lb-in)
HDR-100 3.4 kgf-cm (3.0 Lb-in) 5 kgf-cm (4.4 Lb-in) HDR-150 5.8 kgf-cm (5.0 Lb-in) 5.8 kgf-cm (5.0 Lb-in)
8Suggested fuse and maximum number of the HDR that can be connected to a circuit breaker at 230V are shown
as below.
Model Fuse
HDR-15 HDR-30 HDR-60
HDR-100 HDR-150
T2A/L250V T3.15A/H250V T3.15A/H250V
T3.15A/H250V
F5A/H250V
Circuit breaker C16 D16
32 51 12 24
7 14 7 8 7 8
Page 3
Installation Manual
9Mounting Instruction
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. Admissible DIN railTS35/7.5 or TS35/15 For rail fastening
aTilt the unit slightly rearwards. bFit the unit over top hat rail. cSlide it downward until it hits the stop. dPress against the bottom for locking. eShake the unit slightly to check the locking action.
1
2
3
4
"Click"
10For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution !!
“CAUTIONFOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITION”
ATTENTION: A UTILISER DANS UN ENVIRONNEMENT CONTROLE. REFEREZ VOUS AU MANUEL POUR LES CONDITIONS D’ENVIRONNEMENT.
1Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do
not remove the case of the power supply by yourself!
2Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides
together is not allowed.
3Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 4Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids. 5Only install the unit in a pollution degree 2 environment (Note.1).6Please do not install the unit in places with high moisture or near the water. 7The maximum operating temperature is 50°C for the HDR-15/30; 45°C for the HDR-60/100/150, 40°C for the
HDR-100N, please do not install the unit in places with high ambient temperature or near fire source.
8Output current and output wattage must not exceed the rated value on its specification. 9Disconnect system from supply voltage:
Before commencing any installation, maintenance or modification work: Disconnect your system from supply voltage. Make sure that inadvertent connection in circuit will be impossible!
Note.1: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become
conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as
control cabinets.
Page 4
Installation Manual
Manufacturer MEAN WELL ENTERPRISES Co., LTD. No.28, Wuquan 3rd Rd., Wugu Dist., New Taipei City 24891, Taiwan Tel: +886-2-2299-6100 Web: www.meanwell.com
Branch Office
China
MEAN WELL (GUANGZHOU) ENTERPRISES Co., LTD. 2F, A Building, Yuean lndustry Park, Huangcun,Dongpu Yown, Tianhe District, Gungzhou, China Post Code:510660 Tel: +86-20-2887-1200 Web: www.meanwell.com.cn
U.S.A.
MEAN WELL USA, INC. 44030 Fremont Blvd., Fremont, CA 94538, U.S.A. Tel: +1-510-683-8886 Web: www.meanwellusa.com
Europe
MEAN WELL EUROPE B.V. Langs de Werf 8, 1185XT Amstelveen, The Netherlands Tel: +31-20-758-6000 Web: www.meanwell.eu
Page 5
Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products
Observing SJ/Z 11388-2009, General Guidelines of Environment-friendly Use Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment Friendly Use Period
Part Name
Hazardous Substances
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
chromium
(Cr6+)
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
PCB and its components
X O X O O
O
Metal structure parts
X O O O O
O
Plastic structure parts
O O O O O
O
Accessories
O O O O O
O
Cables X O O O O O
O: The concentration of the hazardous substances within the homogeneous material of that product is less than
the concentration limits set by GB/T 26572-2011.
X: The concentration of the hazardous substances within the homogeneous material of that product is over the