85 100 Ultra Slim Step Shape~ W DIN Rail
Bauar
tgepruft
Sicherheit
egel gema
od
os
be
wac g
www.
tuv.com
(Blank type only)
UL508
UL62368 1-
■ Features
Ultra slim design with 70mm(4SU width)
Universal input 85 264VAC 277VAC operational ~ ( )
No load power consumption<0.3W
Isolation class Ⅱ
Pass LPS (Limited power source) for Blank type
DC output voltage adjustable
Protections : Short circuit / Overload Over voltage/
Cooling by free air convection (working temperature:-30~+70 C°)
DIN rail TS 35 7 5 or 15 mountable-/.
Over voltage category Ⅲ
LED indicator for power on
3 years warranty
ID 2000000000
EN61558
R33100
RoHS
TPTC004
AS/NZS60950-1
IEC62368-1
HDR-100 series
■ Applications
Household control system
Building automation
Industrial control system
Factory automation
Electro-mechanical apparatus
■ Description
HDR-100 is one economical ultra slim 100W DIN rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 70mm(4SU) in width, which allows space saving inside the
cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC
operational) and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.
HDR-100 is designed with plastic housing that it can effectively prevent user from electric hazards. With
working efficiency up to 90%, the entire series can operate at the ambient temperature between -30 ℃
and 70 under air convection. The complete protection functions and relevant certificates for home ℃
automations and industrial control apparatus UL508, UL62368-1, EN61558-2-16) make HDR-100 a (-,IEC62368 1
very competitive power supply solution for household and industrial applications.
■ Model Encoding
-12HDR - 100
Type
Blank
N
N
Performance difference
Output voltage
Rated wattage
Series name
Description
92W max, Pass LPS with a narrower output adjustable range
100W max, Non-LPS with a wider output adjustable range
Note
In stock
In stock
File Name:HDR- 0-SPEC10 2019-12-04

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note )
NOTE
VOLTAGE ADJ.
RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
OVERLOAD
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OPERATINGALTITUDE
OVER VOLTAGE CATEGORY
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
5
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 f & 47 f parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Harmonic current test at 90% load for HDR-100-xxN.
5.
The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC
directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
85 100 Ultra Slim Step Shape~ W DIN Rail
HDR-100-15N
6 5.A
0 ~ . A6 5
97 5.W
Note.2
Pass LPS
Non LPS
HDR-100-12
12V
7. A1
0 ~ 7. A1
85 2.W
120mVp-p
12 ~ 1 V3
12 8~ 1 V3.
±
2.0%
±
1.0%
±
1.0%
500ms, 0ms/230VAC 500ms, 0ms/115VAC at full load66
30ms/230VAC 12ms/115VAC at full load
85 ~ 2 VAC ( ) 120 ~ 3 VDC ( )64 277VAC operational 70 390VDC operational
47 ~ 63Hz
88%
HDR-100-12N
7. A5
0 ~ 7. A5
90W
HDR-100-15
15V
6. A13
0 ~ 6. A13
92W
120mVp-p
15 ~ 17V
13 8.5 ~ 1 V
±
1.0%
±
1.0%
±
1.0%
89%
3A/115VAC 1.6A/230VAC
COLD START 3 A/115VAC 0A/230VAC57
HDR-100 : 2 110 HDR-100-xxN : 5 15010 ~ % rated output power 10 ~ % rated output power;
H , recovers automatically after fault condition is removediccup mode when output voltage 50<%
Constant current limiting recovers automatically after fault condition is removed within 50% ~100% rated output voltage,
1 . ~ 1 . V4 2 6 2 18.8 ~ 22.5V 30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% -℃ R
±
0.03%/ (0 ~ 50 ) -℃℃R
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
2000 meters
According to E 61558, EN50178,EN60664-1, EN62477-1 altitude up to 2000Ⅲ;;N meters
UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, , BSMI CNS14336-1 aEAC TP TC 004 pproved; Design refer to TUV EN62368-1
4
I/P-O/P: KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH℃
Parameter
Conducted
Radiated
Harmonic Current (Note 5)
Voltage Flicker
EN55024, EN61000-6-2, EN61204-3
Parameter
ESD
Radiated Susceptibility
EFT/Burest
Surge
Conducted
Magnetic Field
Voltage Dips and interruptions
856 5K hrs min. MIL-HDBK-217F (25. ℃)
H non condensing
H non condensing
Standard
EN55032(CISPR32), CNS13438
EN55032(CISPR32), CNS13438
EN61000-3-2
EN61000-3-3
Standard
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
70*90* . mm (W*H*D)54 5
0.27Kg; 48pcs/14Kg/1.06CUFT
HDR-100 series
HDR-100-24
24V
3. A83
0 ~ 3. A83
9W2
150mVp-p
24 ~ 25.5V
21 6 9. ~ 2 V
±
1.0%
±
1.0%
±
1.0%
90% 9 %0
HDR-100-24N
4 2.A
0 ~ . A4 2
100 8.W
Test Level / Note
Class B
Class B
Class A
-------
Test Level /Note
Level 3, 8KV air; Level 2, 4KV contact, criteriaA
Level 3, criteriaA
Level 3, criteriaA
Level 4,2KV/L-N, criteriaA
Level 3, criteriaA
Level 4, criteriaA
>.95% dip 0 5 periods, 30% dip 25 periods,
95% interruptions 250 periods>
μμ
HDR-100-48
HDR-100-48N
48V
1.9 A2
0 ~ A1.92
92 2.W
2 1.A
0 ~ . A2 1
100 8. W
240mVp-p
48 ~ 48.7V
43 2 55 2..~V
±
1.0%
±
1.0%
±
1.0%
5 . ~ 6 . V6 5 4 8
File Name:HDR- 0-SPEC10 2019-12-04

Block Diagram
85 100 Ultra Slim Step Shape~ W DIN Rail
HDR-100 series
RECTIFIERS
FILTER
I/P
EMI
FILTER
Derating Curve VS Ambient Temperature
&
O.L.P.
POWER
SWITCHING
PWM
CONTROL
Output Derating VS Input Voltage
RECTIFIERS
&
FILTER
DETECTION
CIRCUIT
O.V.P.
+V
-V
100
80
60
50
40
LOAD (%)
20
-30 0 10 20 30 40 45 50 60 70 (VERTICAL)
AMBIENT TEMPERATURE ( )?
110VAC Input
230VAC Input
100
90
80
70
60
50
LOAD (%)
40
85 10095 120110 160140 200180 240220 277
115
INPUT VOLTAGE (VAC) 60Hz
(operational)
File Name:HDR- 0-SPEC10 2019-12-04

85 100 Ultra Slim Step Shape~ W DIN Rail
Mechanical Specification
(Unit: mm , tolerance ± 0.5mm)
HDR-100 series
58.4
12
70
3456
12
70
3456
5.54
90
35
6.3 65
45.15
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment
Pin No.
1
2
Assignment
AC/L
AC/N
Pin No.
3,4
5,6
Assignment
-V
+V
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
File Name:HDR- 0-SPEC10 2019-12-04