ƤUniversal AC input / Full range
ƤUL508 listed
ƤInstalled on DIN rail TS35 / 7.5 or 15
ƤProtections: Short circuit / Overload /
Over voltage / Over temp.
ƤFixed switching frequency at 50KHz
ƤApprovals: UL / CUL / TUV / CB / CE
ƤLED indicator for power on
ƤCooling by free air convection
Ƥ100% full load burn-in test
Ƥ3 years warranty
AC input voltage range
AC inrush current
DC adjustment range
Overload protection
Over voltage protection
Setup, rise, hold up time
Withstand voltage
Working temperature
Safety standards
EMC standards
Connection
Packing
85~264VAC; 120~370VDC
Cold start, 20A at 11 5VAC, 40A at 230VAC
12V: 12~14V, 24V: 24~28V, 48V: 48~53V
105%~150% constant current limiting,
auto-recovery
121%~142% rated output voltage
1000ms, 60ms, 60ms at full load and 230VAC
I/P-O/P:3KVAC, I/P-FG:1.5KVAC, 1minute
-10~60OC (refer to output de rating curve)
UL508, TUV EN60950-1 approved
EN55022 class B, EN61000-3-2,3,
EN61000-6-2, EN61000-4-2,3,4,5,6,8,11,
ENV50204
I/P: 3 poles, O/P : 4 poles screw DIN terminal
0.6kg ; 20pcs / 13.0kg / 1.1CUFT
75W Single Output DIN Rail Power75W Single Output DIN Rail Power
55.5 x 1 2 5.2x 10 0 m mCASE : 9 2 3
. . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stock No. Model No. Output Tol. R&N Effi.
10531
10532
10533
DR-75-12
DR-75-24
DR-75-48
12V, 0~6.3A
24V, 0~3.2A
48V, 0~1.6A
²2%
²1%
²1%
100mV
150mV
240mV
76%
80%
81%