Mean Well DR-15-5, DR-15-12, DR-15-15, DR-15-24, DR-30-5 Installation Manual [ml]

...
Page 1
Installation Manual
AWG
18
16
14
12
Rated Current of Equipment (Amp)
6A
6-10A
13-16A
16-25A
Cross-section of Lead(mm2 )
0.75
1.00
1.5
2.5
NoteCurrent each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
TypeDR Family with Class IISeriesDR-15, DR-30, DR-60, DR-100
DR-15-5 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 5V 2.4A DR-15-12 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 12V 1.25A DR-15-15 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 15V 1A DR-15-24 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 24V 0.63A DR-30-5 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 5V 3A DR-30-12 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 12V 2A DR-30-15 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 15V 2A DR-30-24 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 24V 1.5A DR-60-5 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 5V 6.5A DR-60-12 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 12V 4.5A DR-60-15 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 15V 4A DR-60-24 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 24V 2.5A DR-100-12 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 12V 7.5A DR-100-15 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 15V 6.5A DR-100-24 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 24V 4.2A
Introduction
DR with class II is a double insulated DIN rail power supply series, meaning it is ungrounded. Like other Mean Wells DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
2The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top for DR-15, the input terminals on the right and output on the left for DR-30, DR-60, and DR-100. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
3Use stranded copper wire only, and recommended wires are shown as below.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure each contact is connected to wires to prevent too much current stress on a single contact.
Page 2
Installation Manual
3
1
2
4
Model
Fuse
Circuit breaker
C16
D16
DR-15
T2A/L250V
19
22
DR-30
F2A/L250V
7
15
DR-60
F3.15A/L250V
3
7
DR-100
F3.15A/L250V
3
6
"Click"
4Use wire that can withstand temperatures of at least 80°C such as UL1007. 5Recommended wire strapping length is 7mm/0.275inch.
6Recommended torque setting for terminals is 5 kgf-cm (4.4 Lb-in). 7Recommended screwdriver is 3mm, slotted type.
8Suggested fuse and maximum number of the DR class PSUs that can be connected to a circuit breaker at
230V are shown as below.
9Mounting Instruction
Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. Admissible DIN railTS35/7.5 or TS35/15 For rail fastening
aTilt the unit slightly rearwards. bFit the unit over top hat rail. cSlide it downward until it hits the stop. dPress against the bottom for locking. eShake the unit slightly to check the locking action.
10For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution !!
1Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do
2Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides
3Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 4Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
5Only install the unit in a pollution degree 2 environment (Note.1).6Please do not install the unit in places with high moisture or near the water.
7 The maximum operating temperatures is 50°C for DR-15 and DR-30 series and 40°C for DR-60 and DR-100 series,
8Output current and output wattage must not exceed the rated values on its specification.
not remove the case of the power supply by yourself!
together is not allowed.
please do not install the unit in places with high ambient temperature or near fire source.
Page 3
Installation Manual
China
MEAN WELL (GUANGZHOU) ENTERPRISES Co., LTD. 2F, A Building, Yuean lndustry Park, Huangcun,Dongpu Yown, Tianhe District, Gungzhou, China Post Code:510660 Tel: +86-20-2887-1200 Web: www.meanwell.com.cn
U.S.A.
MEAN WELL USA, INC. 44030 Fremont Blvd., Fremont, CA 94538, U.S.A. Tel: +1-510-683-8886 Web: www.meanwellusa.com
Europe
MEAN WELL EUROPE B.V. Langs de Werf 8, 1185XT Amstelveen, The Netherlands Tel: +31-20-758-6000 Web: www.meanwell.eu
9Disconnect system from supply voltage:
Before commencing any installation, maintenance or modification work: Disconnect your system from supply
voltage. Make sure that inadvertent connection in circuit will be impossible!
10For continued protection against risk of fire, replace only with same type and rating of fuse.
Pour ne pas compromettre la protection contre les risqué d’incendie, remplacer par un fusible de même type
et de memes caractéristiques nominales.
Note.1: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become
conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as
control cabinets.
Manufacturer MEAN WELL ENTERPRISES Co., LTD. No.28, Wuquan 3rd Rd., Wugu Dist., New Taipei City 24891, Taiwan Tel: +886-2-2299-6100 Web: www.meanwell.com
Branch Office
Page 4
Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products
Observing SJ/Z 11388-2009, General Guidelines of Environment-friendly Use Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment Friendly Use Period
Part Name
Hazardous Substances
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
chromium
(Cr6+)
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
PCB and its components
X O X O O
O
Metal structure parts
X O O O O
O
Plastic structure parts
O O O O O
O
Accessories
O O O O O
O
Cables X O O O O O
O: The concentration of the hazardous substances within the homogeneous material of that product is less than
the concentration limits set by GB/T 26572-2011.
X: The concentration of the hazardous substances within the homogeneous material of that product is over the
concentration limits set by GB/T 26572-2011; however, it follows the standard advised by 2011/65/EU.
Declaration of China RoHS Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China RoHS, an Administrative Measures for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products.
Environment Friendly Use Period Label
Names and Contents of Hazardous Substances Lists
Loading...