◎ Risk of electrical shock and energy hazard, all failure should be examined by a qualified technician. Please do not remove the case from the
supply/charger or rack shelf unit by yourself.
◎ Please do not change any component on the unit or make any kind of modification on it.
◎ Please do not install the unit in places with high moisture, high ambient temperature or under direct sunlight.
◎ The input voltage range is 100- 240Vac (50/60Hz), please do not feed in voltage that is over or less than 10% of that range.
◎ The safety protection level of this unit is class I. The" Frame Ground"( ) on the rack shelf unit must be well connected to PE (Protective Earth).
1.Introduction
1.1 Introduction
The DRP-3200 is a rack mountable power supply that provides energy source for telecom equipments, monitoring systems, severs, etc, installing into a
19”rack shelf is required for operation.The DBR-3200 is a rack mountable charger, used to charge batteries, installing into a19” rack shelf is required
for operation.
1.2 Features Description
◎ 44 mm low profile, suitable for standard 1U rack applications
◎ UniversalAC input/Full range
◎ Built-in active PFC function, PF>0.98
◎ Protections: short circuit/overload/over voltage /over temperature
◎ Active current sharing up to00W ( units) in one 19" rackup to rackunits maximum) can be connected in parallel for- 00128428DRP 32;(shelfshelves
◎ Remote control forunit ofP/- 00eachDR DBU 32 。
◎ Built-in remote sense function for RD32P- 00
◎ Built-in battery temperature compensation function for DR32B- 00
◎ Output voltage programming
◎ Output current programming
◎ Hot Swap operation
◎ AC OK and DC OK signal outputs
◎ Forced air cooling by built-in DC fan with fan speed control function
◎ 5V/0.3Aand 12V/0.8Aauxiliary output
◎ Built-in ORing FETs。
◎ PMBus serial data transmission function
◎ 5 years warranty
1.3 Order Information
1.3.1 Explanation for Encoding
Single unit : DR P -3200-
1U Rack: DHP-1U -AshelfT
1.3.2 Marking
◎Please refer to the safety label on the top of the unit before(Figure 1-1~1- )use5
◎S/upply Charger unit model
DRP-3200-24
100-199VAC 18 .0A
INPUT:
200-240VAC 17. 7A
OUTPUT: +24V
+24V
Figure1-1 safety label of DRP-3200Figure1-2 safety label of DBR-3200
50/60Hz
50/60Hz
(For Input 100-199VAC)
66.5A
(For Input 200-240VAC)
133A
E183223
LEVEL5
24
Output Voltage
RP : Rack Power
BR : Battery Charger
T : Terminal Block
+V ADJ
+
Bauar
tgepruft
Sicherheit
egel gema
MADE IN
od
os
be
wac g
TAIWAN
www.
tuv.com
ID2000000000
DBR-3200-24
100-199VAC 18 .0A
INPUT:
200-240VAC 17. 7A
OUTPUT: +28.8V
+28.8V
(For Input 100-199VAC)
55A
(For Input 200-240VAC)
110A
E183223
LEVEL5
50/60Hz
50/60Hz
Bauar
tgepruft
Sicherheit
egel gema
od
os
be
wac g
www.
tuv.com
ID2000000000
MADE IN
TAIWAN
+V ADJ
+
1
Page 4
◎Rack Shelf :
DHP-1UT-A
Use only DRP-3200 or DBR-3200 series of identical model.
DRP-3200 series
48V MODEL, Max. 4 modules provide
100-199VAC
200-240VAC
100-199VAC
200-240VAC
17.7A OUTPUT : +48V
OUTPUT : +48V
17.4A
(For each module.)
18.0A OUTPUT : +24V
OUTPUT : +24V
17.7A
(For each module.)
Figure 1-3: Safety label of DHP-1U
INPUT:
INPUT:
50/60Hz
24V MODEL, Max. 4 modules provide
INPUT:
INPUT:
50/60Hz
WARNING :
Multiple power sources for configuration. Please disconnect
all power sources and refer to the user manual before any
service .
The rating listed above is advised for one single module.
Regarding the maximum output current when DHP-1U is fully
populated, please refer to the user manual.
◎Whole system :
DBR-3200 series
48V MODEL, Max. 4 modules provide
33.5A
67.0A
66.5A
133.0A
100-199VAC
200-240VAC
100-199VAC
200-240VAC
17.7A OUTPUT : +57 .6V
OUTPUT : +57.6V
17.4A
(For each module.)
18.0A OUTPUT : +28 .8V
OUTPUT : +28.8V
17.7A
(For each module.)
E183223
LEVEL5
INPUT:
INPUT:
50/60Hz
24V MODEL, Max. 4 modules provide
INPUT:
INPUT:
50/60Hz
27.5A
55.0A
55.5A
110.0A
Bauar
tgepruft
Sicherheit
egel gema
od
os
MADE IN
be
wac g
www.
tuv.com
ID2000000000
TAIWAN
DHP-12K1UT-X
Use only DRP-3200 series of identical model.
DRP-3200 series
,X=48, MODEL, Max. 4 D RP-3200 modules provide
100-199VAC
INPUT:
INPUT:
50/60Hz
,X=24, MODEL, Max. 4 D RP-3200 modules provide
INPUT:
INPUT:
50/60Hz
WARNING :
Multiple power sources for configuration. Please disconnect
all power sources and refer to the user manual before any
service .
The rating listed above is advised for one single module.
Regarding the maximum output current when DHP-1U is fully
populated, please refer to the user manual.
1.4 Main Specification
◎Supply/Charger unit
MODEL
OUTPUTVOLTAGE ADJ. RANGE
INPUT
PROTECTION
17.7A OUTPUT : +48V
200-240VAC
100-199VAC
200-240VAC
OUTPUT : +48V
17.4A
18.0A OUTPUT : +24V
OUTPUT : +24V
17.7A
Figure 1-4: Safety label of the whole DHP systemFigure 1-5: Safety label of the whole DHB system
DC VO LTAG E
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.4
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
Note.6
Note.5
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
DHB-12K1UT-X
Use only DBR-3200 series of identical model.
DBR-3200 series
,X=48, MODEL, Max. 4 D BR-3200 modules provide
100-199VAC
33.5A (For each module.)
(For each module.)
67.0A
(For each module.)
66.5A
(For each module.)
133.0A
E183223
LEVEL5
S/N
INPUT:
INPUT:
50/60Hz
,X=24, MODEL, Max. 4 D BR-3200 modules provide
INPUT:
INPUT:
50/60Hz
Bauar
tgepruft
Sicherheit
egel gema
od
os
MADE IN
be
wac g
www.
tuv.com
ID2000000000
TAIWAN
WARNING :
Multiple power sources for configuration. Please disconnect
all power sources and refer to the user manual before any
service .
The rating listed above is advised for one single module.
Regarding the maximum output current when DHP-1U is fully
populated, please refer to the user manual.
200-240VAC
100-199VAC
200-240VAC
17.7A OUTPUT : +57. 6V
OUTPUT : +5 7.6V
17.4A
18.0A OUTPUT : +28. 8V
OUTPUT : +2 8.8V
17.7A
DRP-3200-24DRP-3200-48
24V48V
133A67A
0 ~ 133A0 ~ 67A
3192W3216W
300mVp-p
23.5 ~ 30V
480mVp-p
47.5 ~ 58.8V
±1.0%±1.0%
±0.5%
±0.5%
±0.5%
±0.5%
1500ms, 60ms/230VAC at full load
16ms / 230VAC at 75% load 9ms / 230VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
0.97/230VAC at full load
93.5%
94.5%
17A/230VAC
COLD START 55A/230VAC
<1.5mA / 230VAC
105 ~ 115% rated output power
Protection type : Constant current limiting, shut down O/P voltage 5 sec. after O/P voltage is down low, re-power on to recover
31.5 ~ 37.5V
63 ~ 75V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
27.5A
55.0A
55.0A
110.0A
E183223
LEVEL5
Bauar
tgepruft
Sicherheit
egel gema
od
os
MADE IN
be
wac g
www.
tuv.com
ID2000000000
TAIWAN
2
Page 5
MODEL
BOOST CHARGE VOLTAGE(Vboost)(default)
FLOAT CHARGE VOLTAGE(Vfloat)(default)
CONSTANT CURRENT(CC)(default)
OUTPUT
VOLTAGE ADJ. RANGE
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)
LEAKAGE CURRENT FROM
BATTERY
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
◎Rack system
MODEL
RECTIFIER
OUTPUT
INPUT
OUTPUT VOLTAGE
MAX. OUTPUT CURRENT
MAX. OUTPUT POWER
VOLTAGE RANGE
FREQUENCY RANGE
AC CURRENT (Typ.) per RECTIFIER
LEAKAGE CURRENT
OUTPUT VOLTAGE PROGRAMMABLE(PV)
CONSTANT CURRENT LEVEL
FUNCTION
ENVIRONMENT
REMOTE ON-OFF CONTROL
REMOTE SENSE
AUXILIARY POWER
ALARM SIGNAL
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
SAFETY &
EMC
(Note 8)
EMC IMMUNITY
(Typ.)
Note.4
per RECTIFIER
Note.7
PROGRAMMABLE(PC)
DBR-3200-24
28.8V
27.6V
110A
DBR-3200-48
57.6V
55.2V
55A
By built-in potentiometer, SVR
23.5 ~ 30V
330 ~ 1000Ah185500 ~Ah
Note.3
47.5 ~ 58.8V
<1.5mA
Note.4
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
0.97/230VAC at full load
93.5%94.5%
17A/230VAC
Note.4
COLD START 55A/230VAC
<1.5mA / 230VAC
31.5 ~ 37.5V63 ~ 75V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
DHP-12K1U -24DHP-12K1U -48
DRP-3200-24DRP-3200-48
24V
532A
12768W
Note.5
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
48V
268A
12864W
17A/230VAC
<1.5mA / 230VAC
Adjustment of output voltage is allowable to 50 ~ 125% of nominal output voltage. Please refer to the Function Manual.
Adjustment of constant current level is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual.
By electrical signal or dry contact ON:short OFF:open
Compensate voltage drop on the load wiring up to 0.5V
5V @ 0.3A, tolerance 10%, ripple 150mVp-p, 12V @ 0.8A, tolerance 10%, ripple 450mVp-p±±
Isolated TTL signal output for T-Alarm,AC-OK and DC-OK
-30 ~ +70℃℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel
operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to
normal ripple level once the output load is more than 5%.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Output of all the DRP-3200 modules are connected in parallel in the rack.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Because of component tolerance, there is a possibility that some of units connected in parallel will reach an overcurrent limit then overloading the other
units when operating at full load condition. If overload conditions happen in parallel usage, it is suggested that derate the total output current by 10%.
7. The equivalent leakage current of the system is determined by the quantity of populated rectifiers.
8. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm*mm metal plate with mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.210001300 For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
9. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
4.85Kg
; 3pcs/17.4Kg/1.8CUFT
MODEL
CHARGER
OUTPUT
BOOST CHARGE VOLTAGE(Vboost)(default)
FLOAT CHARGE VOLTAGE(Vfloat)(default)
CURRENT RANGE
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
AC CURRENT (Typ.) per CHARGER
LEAKAGE CURRENT
OUTPUT VOLTAGE PROGRAMMABLE(PV)
OUTPUT CURRENT
FUNCTION
REMOTE ON-OFF CONTROL
AUXILIARY POWER
ALARM SIGNAL
TEMPERATURE COMPENSATION
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY &
EMC
(Note 5)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
OTHERS
NOTE
DIMENSION
PACKING
DHB-12K1U -24DHB-12K1U -48
DBR-3200-24DBR-3200-48
28.8V
27.6V
0 ~ 440A
Note.2
90 ~ 264VAC 127 ~ 370VDC
57.6V
55.2V
0 ~ 220A
47 ~ 63Hz
17A/230VAC
per CHARGER
Note.4
<1.5mA / 230VAC
Adjustment of output voltage is allowable to 75 ~ 125% of nominal output voltage. Please refer to the Function Manual.
PROGRAMMABLE(PC)
Adjustment of output current is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual.
By electrical signal or dry contact ON: short OFF: open
Compliance to EN55032 (CISPR32) Conduction Class B, Radiation Class A; EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (E 50082-2),lev , criteria ANelHeavy industry
Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
5.5Kg; 3pcs/17.5Kg/2.11CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Derating may be needed under low input voltages. Please check the static characteristics for more details.
3. Output of all the DBR-3200 modules are connected in parallel in the rack.
4. The equivalent leakage current of the system is determined by the quantity of populated chargers.
5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm*mm metal plate with mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.210001300 For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
2.Mechanical Specification and Input/Output Terminals
2.1 Mechanism of Supply/Charger unit
41
12.5
5.8
CN1
11max.
29.7
SVR
47.3
107
53.5
18.6
62.4
3.6
10max.325
Air flow
direction
Figure 2-1
LED Status Indicator
4
Page 7
2.2 Mechanism of Whole Rack System
5-M4 L=4
400
11.65
20.7
26
ADDRESSADDRESS
SWITCHSWITCH
2
26
1
25
CN1
SWCSWD
2
125
D
B
C
N
L
FGNLFGNL
A
FGNLFG
SWASWB
4-M8 L=16
440
10 910 910 910 9
SVRSVRSVRSVR
2
4
13
8
1
1
8
42
13
8
1
CN2
1
8
JK1
5-M4 L=4
11.65
20.7
306
11.65
24
7.65
306
20.7
22
10 max.
45
Air flow
direction
Module BModule CModule D
Module A
11.65
24
20.7
22
7.65
7
44
10.2
StatusStatusStatusStatus
29.5
7.4
466.2
482.6
5
Page 8
※ LED Status Indicators & Corresponding Signal at Function Pins
For power supply system
LED
Green
Red Flashing()
Red
Description
The power supply functions normally
The LED will flash with red light when internal temperature reaches
60 ; under this condition, the unit still operates normally without entering℃
OT . (In the meantime, an alarm signal will be sent out through the PMBusP
/interface.)CANBus
The LED will present a constant red light when the abnormal status (OTP,
OLP, fan fail and charging timeout) arises.
For charger system
LED
Green
Orange
Red (Flashing)
Red
Description
Float(stage 3)
Charging (stage 1 or stage 2)
The LED will flash with red light when internal temperature reaches
60 ; under this condition, the unit still operates normally without entering℃
OTP. In the meantime, an alarm signal will be sent out through the PMBus(
interface.)
The LED will present a constant red light when the abnormal status (OTP, OLP,
fan fail and charging timeout) arises.
※ Connector Pin No. Assignment (CN1)
26
1
Pin No.Function
Description
High (4.5 ~ 5.5V) : When the input voltage is 87Vrms .≧
1,5,9,13,17AC-OK
Low (-0.1 ~ 0.5V) : When the input voltage is 75Vrms.≦
The maximum sourcing current is 10mAand only for output. (Note.2)
For power supply system
High (4.5 ~ 5.5V) : When the Vout 80% 5%.≦±
Low (-0.1 ~ 0.5V) : When Vout 80% 5%.≧±
2,6,10,14,18
DC-OK
The maximum sourcing current is 10mAand only for output. (Note.2)
For charger system
High (4.5 ~ 5.5V) : When the Vout 16V/32V.≦
Low (~ 0.5V) : When Vout 16V/32V.The maximum sourcing current is 10mAand only for output. (Note.2)-0.1≧±1V
DC OK is associated with battery low protection.
3,7,11,15,19
Remote
ON-OFF
The unit can turn the output ON/OFF by electrical signal or dry contact between Remote ON-OFF and +5V-AUX. (Note.2)
Short (4.5 ~ 5.5V) : Power ON ; Open (0 ~ 0.5V) : Power OFF ; The maximum input voltage is 5.5V.
High (4.5 ~ 5.5V) : When the internal temperature exceeds the limit of temperature alarm, or when fan fails.
4,8,12,16,20
T-ALARM
Low (-0.1 ~ 0.5V) : When the internal temperature is normal, and when fan works normally.
The maximum sourcing current is 10mAand only for output(Note.2)
21+5V-AUX
22
GND-AUX
23
+12V-AUX
24-V(Signal)
25
26
Note.1: Non-isolated signal,
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX (pin 22).
The maximum load current is 0.3A.This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Auxiliary voltage output, 10.8~13.2V, referenced to GND-AUX (pin 22).
The maximum load current is 0.8A.This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Negative output voltage. For local sense use only; It can't be connected directly to the load.
PC
Connection for output current programming. The current can be trimmed within its defined range. (Note.1)
PV
Connection for output voltage programming. The voltage can be trimmed within its defined range. (Note.1)
referenced to [-V(signal)].
Note.2: Isolated signal, referenced to GND-AUX.
※ Connector Pin No.Assignment (CN2)
422
LED Status Indicator
Figurefront panel2-3 DRP/DBR-3200
±1V
Note3 Wiring cable of CN2 varies in rack shelf with DRP 3200DBR 3200 please follow the discription below to select the:--,or
correct cable for wiring, DO NOT make it misplaced!
1253
For power supply system
1
2
3
+V(Signal)
4
-V(Signal)
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be
+S
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be
-S
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Positive output voltage. For local sense use only, can't be connected directly to the load.
Negative output voltage. For local sense use only, can't be connected directly to the load.
◎ The RED wiring cable goes with the DRP-3200, used to compensate voltage drop on the load wiring.
6
Page 9
◎ For charger system
1RTH+
2RTH-
3,4NC
Temperature sense associated with the temperature compensation function.
Not use.
◎ The Black wiring cable goes with the DBR-3200, used for battery temperature compensation.
Note.1: Non-isolated signal, referenced to [-V(signal)].
Note.2: Isolated signal, referenced to GND-AUX.
Function
DA,DB
3
4
5
6
7
8GND-AUX
(signal)
-V
CONTROL
NC
SDA
CANH
SCL
CANL
Description
Differential digital signal for parallel control. (Note.1)
Negative output voltage signal.
It is for local sense and certain function reference; it cannot be connected directly to the load.
Remote ON-OFF control pin used in the PMBus interface. (Note.2)
Retain for future use.
For PMBus model: Serial Data used in the PMBus interface. (Note.2)
For CANBus model: Data line used in CANBus interface. (Note.2)
For PMBus model: Serial Clock used in the PMBus interface. (Note.2)
For CANBus model: Data line used in CANBus interface. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
3.Functions
3.1 Input Voltage Range
◎.The input voltage rang isorAC90~264V DC127~370V
◎ To insure proper operation,AC input should be within the pre-specified range. Awrong input will cause the supply/operating improperly,charger units
losing PFC function or even damaging the units.in worst case scenario
◎ The efficiency will be lower and theto a predetermined safe value if the units are applied with a loweroutput current will be automatically limited
input voltage. Please refer to 4.2 Derating for more information.
3.2 Inrush Current Limiting
◎.Built-in inrush current limiting circuit
◎ If adding an external switch (relay/circuit break) at the input side is required, choose switches that are able to withstand inrush current of the units.
◎ Since the inrush limiting circuit mainly consists of a thermistor and a relay, inrush current will be much higher than the specified value if input
thermistor is not allowed sufficient time to cool down.After turning off the supplys/chargers, a 10 second cool down period is recommended before
turning them on again.
◎ Built-in active power factor correction (PFC) function, power factor (PF) will be 0.98 or better when the input voltage is in a range of 90 -230Vac
and operated at full load condition. PF will be less than 0.98 if the output is not at full load or the input voltage is higher than 230Vac.
3.5 Output Voltage/Current Adjustment
3.5.1 Adjustment of single unit
Output voltage can be trimmed by adjusting SVR (which can be found under the small circular hole, located on the top of the unit). Please utilize
an insulated cross-head screwdriver to make an adjustment.
7
Page 10
Iout
V
0.4 14.7 5
20
100
External voltage (VDC)
OUTPUT CURRENT (%)
Non-Linear
110
Iout
V
0.44.7
20
100
External voltage (VDC)
OUTPUT CURRENT (%)
Non-Linear
51
3.5.2 Voltage adjustment of whole rack system by an external 0 -5 Vdc source (Output Voltage Programming)
+V
-S
CN2 +S
-V
DHP-1U System
LOAD
PC
CN1 -V Signal
EXTERNAL
VOLTAGE
25
24
1
2
(1) Connect output of the external DC source to PV(PIN 26) and –V(PIN 24) on CN1, as shown in Figure3-1.
(2) Relationship between the output voltage and the external DCis shown in Figure3-2.source
(3) When increase the output to a higher voltage level, please reduce the load current accordingly. Output wattage of each unit should not
exceed the rated value under any circumstances.
26
PV
-V
0~5V
24
Figure 3-1 Connection of external DC voltage source
DBR-3200-24DRP-3200-24
DBR-3200-48DRP-3200-48
OUTPUT VOLTAGE(V)
30306060
24244848
18123624
OUTPUT VOLTAGE(V)
0000
Non-LinearNon-Linear
110.40.4
External voltage (DC)External voltage (DC)
Figure 3-2
3.5 3Output Current Programming. Output current adjustment ()
※ Constant current level (DRP-3200)/output current (DBR-3200) can be adjusted within a range of 20-100% of the rated current via an external DC
source, the wiring is show as below.
Connection between +S & +V, -S & -V on CN1 is required (DRP-3200system)
Relationship between the output current and the external DC source is shown as below.
VV
554.74.7
◎ DRP-3200 System◎SystemDBR-3200
Note The DRP-3200 will trigger OLP to shut down itself if the output stays on constant current level condition for more than 5 seconds.:
8
Page 11
3.6 Fan Speed Control
◎ Built-in fan speed control circuit, fan speed changesepending on internal temperature.automatically d
3.7 Short Circuit Protection & Over Current Protection
◎ ODRP 3200nly for-.
◎ The protection activates when the output is short-circuited or the output current exceeds 110%±5% of the rated output current. Re-power on to recover
when the short-circuit/overload condition is removed.
3.8 Over Voltage Protection (OVP)
◎ Built-in over voltage protection circuit for every single units.
OVP triggering points vary in different output models. Please refer to the specification sheet for detailed information.◎
◎ Once OVPis triggered, leave the units off for 10 seconds before recycling AC again.
3.9 Over Temperature Protection (OTP) and Alarm
◎ Built-in 2 sets of thermal detection circuit, once the internal temperature exceeds a threshold value, the unit will shut down automatically (the fans wills
still be operating to cool down the unit). Please switch off theAC input, remove all possible causes and then leave the units cooling down to normala
working temperature (approximate 10 minutes –1 hour) before repower on again.
◎℃When the internal temperature reaches 60 , trigger point of a thermal alarm, the red LED on the front panel will flash and there will be an alarm signal
sent out through the PMBus/interface (refer to 3.19). Even so, the units still operate normally.CANBus
◎ When the internal temperature is within a normal value, there will be a "LOW" signal (-0.1 -0.5V) sent out through T-ALARM on CN1; there will be a "HIGH"
signal (4.5 -5.5V) sent out throughT-ALARM on CN1 when internal temperature exceeds a certain value. (referenced to GND-AUX).
◎ Maximum output current: 10mA.
3.10 AC OK signal
◎ Built-in AC input voltage detection circuit.
When AC input voltagerms, the output voltage can start working normally and there will be a “” signal ( . - .5V) sent outAC-OK n≧87VHIGH4 5 5o◎through
CN1. (GND-AUX).referenced to
When AC input voltagerms, The output voltage shuts off and the red LED on the fron panel will light up. In the mean time, there will be a ””≦75VLOW◎
signal (- . - .5V) sent outAC-O. (-).0 1 0K on CN1 referenced to GND AUXthrough
Maximum output current10mA.◎
3.11 DC OK signal
◎.Built-in DC output voltage detection circuit
◎ When DC output voltage is within a normal value, there is a “LOW” (-0. -0.5V) signal sent outDC-OK. (-).1on CN1 referenced to GND AUXthrough
◎-When DC output voltage is out of normal range, there is a “HIGH” (4.5-5.5V) signal sent out. (-).DC OK on CN1 referenced to GND AUXthrough
◎ Maximum output current 10mA.
3.12 Fan-lock Protection &Alarm Signals
◎ Built-in fan-lock protection circuit, the output will shut off when the DC fans stop operating (fan-lock or broken wires). In the meantime, there will
be a “HIGH” signal sent out through T-ALARM, referenced to GND AUX. Please remove the unit from your system and send back to our localdistributor or MEAN WELL for repair.
Maximum output current 10mA.
◎
3.13 Remote Control
◎ Built-in remotecontrol circuit, refer to Figure 3-3 for control methods of single unit or whole rack system.ON/OFF
◎ Please be aware that “ON/OFF” and “+ V-AUX” n CN1 should be linked together to allow the units operate normally; If, there will be no5okept open
output voltage.
◎ Maximum input voltage 5.5V.
ON/OFF ACN1CN1 ON/OFF A
ON/OFF BON/OFF B
DHP-1U SystemDHP-1U System
ON/OFF C
ON/OFF DON/OFF D
+5V-AUX+5V-AUX
33
77
11
15
2121
ON/OFF C
11
15
Between CN1 ON/OFF
and +5V-AUX
SW Open
SW Short
Whole rack system ON/OFFSingle unit ON/OFF
Figure 3-3 Connection of Remote Control
3.14 Remote Sense
◎ ODRP 3200nly for-.
◎.Built-in remote sense circuit that is able to compensate voltage drop up to 0.5V
When using this function, the sensing wires should either be twisted or shielded to prevent external noise interference (refer to Figure 3-4).◎
Voltage drop across the output wires must be limited to less than 0.5V.Also wires with adequate current rating should be used between◎+V,-V and the
loads. Please firmly connect the output wires to prevent them from loosing, or the power supply may be out of order.
The +S and –S have to be connected to the +V(signal) and –V(signal), respectively, as shown in Figure 3-5, which is Local Sense, in order to get the◎
correct output voltage if Remote Sense is not used. Otherwise, the output voltage will increase to a extremely high level which may trigger OVP.
Output
OFF
ON
9
Page 12
DHP-1U
CN2
+V
1
+S
-S
2
-V
Twisted wires
FigureConnection of3-4Remote Sense
+V
LOAD
-V
DHP-1U
CN2
+V
+S
-S
-V
3
1
2
4
FigureConnection of3-5Local Sense
3.15 Hot Swap Operation
◎ Built-in "Oring MOSFET", the units can be installed/removed without tu ning power off.r
Insert units: Grasp the handle and push into the rack shelf through the rail.◎
Figure 3-6 Illustration of how to insert theinto a rackDRP/DBR-3200
◎ Pull out units: Press the clip shown in Figure 3-7 and pull it out.
"Click"
Figure 3-7 Illustration of how to remove thefrom a rackDRP/DBR-3200
Caution: Please use adequate force to insert theinto the rack. Slamming units into the rack can damage the connectors bothDRP/DBR-3200helfs
on the rear of the units and inside the rack.
3.16 Parallel Operation
3.16.1 Operation of Single Rack Shelf
◎ Pshelfarallel operation in a single rackis only suitable for the identical units (with the same model and the same output voltage/current).
Each rack shelf ( HP-1U ) has built-in parallel connection/wiring. OnceP orunits insert in the rack shelf thenDhave DRDBRedheset◎
.front end unit are operated in parallel
.Please refer to 3.13 & 3.14 for the connection/wiring of other functions◎
10
Page 13
3.16.2 Operation ofrack shelves in parallel (- 00 system)twoDRP 32
◎ Parallel operation is only suitable for the identical units (with the same model and the same output voltage/current). Up to rack shelves2
and the maximum supply units that can be connected in parallel is .8
Because of component tolerance, there is a possibility that some of the units connected in parallel will reach an overcurrent limiting then◎
overloading the other units when operating at full load condition. It is suggested that reduce the total output current by 10%.
For example:P- 00-24x connected in parallel (in rack shelves), the total output current should betoA x unit x 0.9DR 3282reduced 1338
=9 . A.57 6
Difference of output voltage among parallel units should be less than 0.2V.◎
Corack shelf units in parallel beforeing to the load. Do not connect rack shelf units to the load separately. Refer to Figure 3-8nfigureconnect◎
Control singles of DA, DB and V should also be connected in parallel. (Refer to Figure 3.8).–◎
Use twisted wires for the wiring of +S and S, the twisted wires should not touch the load wires to avoid interference. Refer to Figure 3-8.–◎
A too long cable length might be with a higher amount of noise that affects rack units proper operation in parallel. To reduce the noise,'◎
installing termination resistors, an accessory, to the unused JK1 is recommended.
JK1
DA
DB
-V
+5V-AUX
ON / OFF-A
ON / OFF-B
ON / OFF-C
ON / OFF-D
JK1
DADA
DBDB
-V
+5V-AUX
ON / OFF-A
ON / OFF-B
ON / OFF-C
ON / OFF-D
DHP-1U#1
CN1
}
DHP-1U#2
CN1
}
+V -V
+V
CN2
+S
-S
-V
+V
LOAD
-V
Twisted wires
Figure 3-8 Configuration ofrack shelf units in paralleltwo
◎ Under operation of more than one rack shelf in parallel, value of Ripple & Noise may be larger than that stated in the specification at light load or
. It will return to normal level once the loads draw more current than 10% of the total rating.no load condition
3.17 Series Operation
◎ Higher output voltage can be acquired by connecting rack shelves in series.
The rack shelves ( HP-1U ) connected in series should have the identical units. Please refer to Figure3-9 for wiringD◎
configuration.
Total output current should not exceed currents that can be produced in each rack shelf.◎
Difference of rise time in each unit may lead to steps/stairs like turn on.◎
The totalof output voltage in series should be less than 60Vdc [the requirement of SELV (Safety Extra Low Voltage) of].ratingIEC62368-1◎
It is suggested that add external diodes (*) on the output, shown in Figure 3-9, to prevent reverse voltage. Rating of these diodes should be◎
higher than the total amount of output voltage and current.
DHP-1U#1
ON/OFF
ON/OFF
A
3
DHP-1U#2
ON/OFF
ON/OFF
A
3
ON/OFF
B
7
B
7
ON/OFF
C
1111151521
ON/OFF
ON/OFF
C
DD+5V-AUX
+5V-AUX
21
+V
+S
+V
+S
22
23
-S
-V
22
23
-S
-V
(*)
+V
LOAD
-V
(*)
Figure 3-9 Configuration of rack shelf units in series
11
Page 14
3.18 Auxiliary Output
◎ Built-in 5V/0.3Aand 12V/0.8Aauxiliary output.
3.19P- 00 PMBus Communication InterfaceDR 32
◎ DRP-3200 is compliant with PMBus Rev.1.1, the maximum communication speed is 100KHz and it has the capability of identifying up to16
addressed units.
PMBusinformationscommunication interface is able to provide the current operating status andas follow :◎
1 Output voltage current and internal temperature..,
2 Alarm and status..
.3 Manufacturers and model data.
3.19.1 RD32AddressingP- 00 PMBus
◎ EachP- 00 unit should have their unique and own device address to communicate over the PMbus. 7-bit address setting pins areDR 32
used to assign a device address for a-unit, as shown in the description below.DRP 3200
MSB
1
00A3A2A1A0
LSB
◎ A0-A3 allow users to designate the address for each DRP-3200 unit; these four bits are defined through a 4-pole DIP switch on the rear panel
of the rack shelf. There are up to 16 different addresses are available to be assigned. When DIP switch in the “ON” position means logic “0”;
when it is in the “OFF” position, meaning logic “1”, for example, position 3 in “OFF”, the corresponding bit, A2, is set to logic “1”. Please refer to
Table 3-1 for the detailed setup advice.
1 2 3 4
ON
Device addressDevice address
A0A0
A1A1
A2A2
Module
No.
0
1
2
3
4
5
6
7
DIP switch positionDIP switch position
11
22
ONON
ON
OFF
OFF
OFF
OFF
ONON
OFFOFF
ON
OFFOFF
OFFOFF
ONON
ON
OFFOFF
ONON
OFFOFF
OFFOFF
ON
OFFOFF
OFFOFF
A3A3
Module
No.
33
44
10
11
12
13
14
15
8
9
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ONON
ON
ONON
ON
ONON
ON
ONON
ON
ON
ON
ON
Table 3-1
12
Page 15
3.19.2 PMBus Command List
◎ The command list of theP- 00 is shown in Table 3- . It is compliant with the standard protocol of PMBus Rev. 1.1. For more detailedDR 322
information, please refer to PMBus official website http://pmbus.org/specs.html).(
Command
Code
01h
02h
19h
20h
21h
22h2
46h
47h
79h
7Ah
7Bh
7Ch
7Dh
7Eh
80h
81h
88h
8Bh
8Ch
8Dh2
90h
91h
98h
99h
9Ah
9Bh
9Ch
9Dh
9Eh
Command
Name
OPERATION
ON_OFF_CONFIG
CAPABILITY
VOUT_MODE
VOUT_COMMAND
Transaction
Type
R/W Byte
Read Byte
Read Byte
R Byte
R Word
VOUT_TRIMR/W Word
IOUT_OC_FAULT_LIMITR/W Word
IOUT_OC_FAULT_RESPONSE
STATUS_WORD
STATUS_VOUT
STATUS_IOUT
STATUS_INPUT
STATUS_TEMPERATURE
STATUS_CML
STATUS_MFR_SPECIFIC
STATUS_FANS_1_2
READ_VIN
READ_VOUT
READ_IOUT
READ_TEMPERATURE_1
READ_FAN_SPEED_1
READ_FAN_SPEED_2
PMBUS_REVISION
MFR_ID
MFR_MODEL
MFR_REVISION
MFR_LOCATION
MFR_DATE
MFR_SERIAL
R Byte
R Word
R Byte
R Byte
R Byte
R Byte
R Byte
R Byte
R Byte
R Word
R Word
R Word
R Word
R Word
R Word
R Byte
Block Read
Block Read
Block Read
Block R/W
Block R/W
Block R/W
# of data
Bytes
1
1
1
1
2
2
1
2
1
1
1
1
1
1
1
2
2
2
2
2
1
12
12
6
3
6
12
Description
Remote ON/OFF control
ON/OFF function configuration
Capabilities of a PMBus device
Define data format for output voltage
(format: Linear, N= -9)
Output voltage setting value
(format: Linear, N= -9)
Output voltage trimmed value
(format: Linear, N= -9)
Output overcurrent setting value
(format: Linear, N= -2)
Define protection and response when an
output overcurrent fault occurred
Summary status reporting
Output voltage status reporting
Output current status reporting
AC input voltage status reporting
Temperature status reporting
Communication, logic,
Memory status reporting
Manufacture specific status reporting
Fan1 and 2 status reporting
AC input voltage reading value
(format: Linear, N=-1)
Output voltage reading value
(format: Linear, N= -9)
Output current reading value
(format: Linear, N= -2)
Temperature 1 reading value
(format: Linear, N= -3)
Fan speed 1 reading value
(format: Linear, N= 5)
Fan speed 2 reading value
(format: Linear, N= 5)
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
1.READ_IOUT will display ZERO amp when output current is less than values in the table below.
Minimum readable current
Model
24V
48V
5.3A 1A±
2.7A 1A±
Table 3-5
2.When using PMBus to adjust output voltage, VOUT_COMMAND only can be used to display the rated voltage of the unit and cannot be.written
It is VOUT_TRIM that. TakingP- 00-as an example, to get a 2V output, pleasevalue ofsets the rating of trimmed voltageDR 32 241set
VOUT_TRIM to - V.Adjustable voltage range for each model is shown as below.12
Model
24V
48V
Adjustable voltage
12 ~ 30V
24 ~ 60V
Table 3-6
3.20 DBR-3200 PMBus Communication Interface
◎ DBR 32- 00 is compliant with PMBus Rev.1.1, the maximum communication speed is 100KHz and it has the capability of identifying up to 8
addressed units.
PMBus communication interface is able to provide the current operating status and data as the following:◎
1.Output voltage, current and internal temperature.
Alarm and status.2.
3 Manufaturers and model data..
.4. ead/write o charge curve settingsRn
14
Page 17
3.20.1 PMBus DeviceAddresing and Charge Mode Selection
Each DBR 3200 unit should have their unique and own device address to communicate over the PMbus 7 bit address setting pins are used-.to assign a device address for a DBR 3200 unit as shown in the below description-,.
MSB
1
000A2A1A0
LSB
A0-A2 allow users to designate the address for each DBR-3200 unit; these three bits are defined through a 4-pole DIP switch on the rear
panel of the rack shelf. There are up to 8 different addresses are available to be assigned. Please refer to Table 3-7(left) for the detailed
setup advice.
1 2 3 4
ON
* The charging operation can be determined by the setup over D0, position 4 on the DIP switch. When D0 is “ON”, DBR-3200 follows a built charging curve
to charge the batteries; when D0 is “OFF”, the charging operation is completely defined by the control over PMBus, PV/PC or SVR. Please refer to Table 3-7
(right).
Module
No.
0
1
2
3
4
5
6
7
Device address
A0
A13A2
DIP switch position
1
2
ON
ON
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
DIP switch position 4
ON
ON
ON
ON
OFF
OFF
OFF
OFF
D0
Function describe
ONCharging curve
OFFPMBu s or V PC or SVR controlP/
Table 3-7
3.20.2 Charge Curve
When it is opted for charging curve, D0 set to ON, charging curve function is enabled with additional PMBus commands.
There are 4 built-in charging curves, “default” curve, one pre-defined curve for “gel battery”, one pre-defined curve for
“flooded battery” and one pre-defined curve for “AGM battery”. Each curve can be selected by Command B4h
CURVE_CONFIG. Please refer to Table 3-8. In addition users are able to customize their own charge curves which will be,,
stored to “default” after modification CV can be set by Command B1h CURVE CV FV can be set by Command B2h._;
CURVE FV Charge current level of stage1 can be set by Command B0h CURVE CC Taper current level from stage2 to_;_;
stage3 can be set by Command B3h CURVE TC Please refer to the following PMBus Command List in 3.20.4 for detailed_.
◎ Suitable for lead-acid batteries (flooded, Gel andAGM) and
Li-ion batteries (lithium iron and lithium manganese).
Constant Current
(CURVE_CC)
stage 1stage 2stage 3
Constant Voltage
(CURVE_CV)
Orange
Charger fail if charging time
exceed charging timeout
Float
(CURVE_FV)
Green
boost
V
V
float
100% CC
10% CC
MODEL
Note:
When using this charger unit, please configured the system with
recommended battery capacity by specification defined. Should battery
capacity in use be much smaller so that user needs to set a low current
for charging, under such condition it might cause higher current ripple.
Description
Default, programmable
Pre-defined gel battery
24V
Pre-defined flooded battery
Pre-defined AGM battery
Default, programmable
Pre-defined gel battery
48V
Pre-defined flooded battery
Pre-defined AGM battery
Table 3-8
Figure 3-10
NOTE: 1.The updated charging parameters are saved into EEPROM. The updated charging curve takes effect after DBR-3200 is restarted.
2.When charging curve is enabled, the following commands will be invalid while other PMBus commands are effective: Command 01h
OPERATION (regarding Remote ON-OFF function), Command 22h VOUT_TRIM (regarding Output voltage programming function) and
Command 46h IOUT_OC_FAULT_LIMIT (regarding Output current programming function).
V
28.8
28.4
57.6
56.8
boost
28
29
56
58
V
27.6
27.2
26.8
55.2
54.4
53.6
float
27
54
CC (default)
110A
55A
15
Page 18
3.20.3 PMBUS, PV/PC or SVR Functions
Users are able to fully control and design the entire charging behavior, without the charging curve, by one of the following means- PMBus
command, PV/PC function or SVR adjustment, please refer to the previous chapter. The operating priority is, PMBus > PV/PC > SVR.
NOTE: When operating in this mode, PMBus commands B0h/B1h…B8h can be set but there will be no response whereas other PMBus
commands and functions work normally.
3.20.4 PMBus Command List
◎ The command list of the- 00 is shown inTable 3- . It is compliant with the standard protocol of PMBus Rev. 1.1. For more detailedDBR 329
information, please refer to PMBus official website http://pmbus.org/specs.html).(
Table 3-9
Command
Code
01h
02h
19h
20h
21h
22h2
46h
47h
79h
7Ah
7Bh
7Ch
7Dh
7Eh1
80h
81h
88h
8Bh
8Ch
8Dh2
90h
91h
98h
99h
9Ah
9Bh
9Ch
9Dh
9Eh
Command
Name
OPERATION
ON_OFF_CONFIG
CAPABILITY
VOUT_MODE
VOUT_COMMAND
Transaction
Type
R/W Byte
Read Byte
Read Byte
R Byte
R Word
VOUT_TRIMR/W Word
IOUT_OC_FAULT_LIMITR/W Word
IOUT_OC_FAULT_RESPONSE
STATUS_WORD
STATUS_VOUT
STATUS_IOUT
STATUS_INPUT
STATUS_TEMPERATURE
R Byte
R Word
R Byte
R Byte
R Byte
R Byte
STATUS_CMLR Byte
STATUS_MFR_SPECIFIC
STATUS_FANS_1_2
READ_VIN
READ_VOUT
READ_IOUT
READ_TEMPERATURE_1
READ_FAN_SPEED_1
READ_FAN_SPEED_2
PMBUS_REVISION
MFR_ID
MFR_MODEL
MFR_REVISION
MFR_LOCATION
MFR_DATE
MFR_SERIAL
R Byte
R Byte
R Word
R Word
R Word
R Word
R Word
R Word
R Byte
Block Read
Block Read
Block Read
Block R/W
Block R/W
Block R/W
# of data
Bytes
1
1
1
1
2
2
1
2
1
1
1
1
1
1
2
2
2
2
2
1
12
12
6
3
6
12
Description
Remote ON/OFF control
ON/OFF function configuration
Capabilities of a PMBus device
Define data format for output voltage
(format: Linear, N= -9)
Output voltage setting value
(format: Linear, N= -9)
Output voltage trimmed value
(format: Linear, N= -9)
Output overcurrent setting value
(format: Linear, N= -2)
Define protection and response when an
output overcurrent fault occurred
Summary status reporting
Output voltage status reporting
Output current status reporting
AC input voltage status reporting
Temperature status reporting
Communication, logic,
Memory status reporting
Manufacture specific status reporting
Fan1 and 2 status reporting
AC input voltage reading value
(format: Linear, N=-1)
Output voltage reading value
(format: Linear, N= -9)
Output current reading value
(format: Linear, N= -2)
Temperature 1 reading value
(format: Linear, N= -3)
Fan speed 1 reading value
(format: Linear, N= 5)
Fan speed 2 reading value
(format: Linear, N= 5)
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
Manufacturer's name
Manufacturer's model name
Firmware revision
Manufacturer's factory location
Manufacture date. (format: YYMMDD)
Product serial number
16
Page 19
Command
Code
B0h
B1h
B2h
B3h
B4h
B5h
B6h
B7h
B8h
Command
Name
CURVE_CC
CURVE_CV
CURVE_FV
CURVE_TC
CURVE_CONFIG
CURVE_CC_TIMEOUT
CURVE_CV_TIMEOUT
CURVE_FLOAT_TIMEOUT
CHG_STATUS
Valid when charging according to charge curve(Do=ON)
Note:
◎:Definition of Command B4h CURVE_CONFIG
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
High byte-----FVTOECVTOECCTOE
Transaction
Type
R/W Word
R/W Word
R/W Word
R/W Word
R/W Word
R/W Word
R/W Word
R/W Word
READ Word
# of data
Bytes
2
2
2
2
2
2
2
2
2
Description
Constant current setting value of charging curve
(format: Linear, N= -2)
Constant voltage setting value of charging curve
(format: Linear, N= -9)
Constant voltage setting value of charging curve
(format: Linear, N= -9)
Taper current setting value of charging curve
(format: Linear, N= -2)
Configuration setting of charging curve
CC stage timeout setting value of charging curve
(format: Linear, N= 0)
CV stage timeout setting value of charging curve
(format: Linear, N= 0)
Floating timeout setting value of charging curve
(format: Linear, N= 0)
Charger's status reporting
Low byte-STGS--TCSCUVS
Low byte
Bit 1-0 CUVS:Charge Curve electingS
00=Customized Charge Curve (default)
01 Gel Battery=
10 Flooded Battery=
11 AGM Battery=
Bit 1 CCM:Constant Current Mode Status
0=the charger NOT in constant current mode
1=the charger in constant current mode
Bit 2 CVM:Constant Voltage Mode Status
0=the charger NOT in constant voltage mode
1=the charger in constant voltage mode
Bit 3 FVM:Float Mode Status
0=the charger NOT in float mode
1=the charger in float mode
High byte
Bit 0 EEPER: EEPROM CPEharge arameter rror
=0 charge parameter correct
1=charge parameter error
Bit 2 NTCER: Temperature Compensation tatusS
0=NO short-circuit in the circuitry of temperature compensation
1=the circuitry of temperature compensation has short-circuited
Bit 3 BTNC: BDattery etection
0=battery detected
1=NO battery detected
Bit 5 CCTOF:Time ut lag f onstant urrent odeOF OCCM
0=NO time out in constant current mode
1=constant current mode timed out
:Bit 6 CVTOF Time ut lag f onstant oltage odeOF OCVM
0=NO time out in constant voltage mode
1=constant voltage mode timed out
:Bit 7 FV TOF Time ut lag f loat odeOF OF M
0=NO time out in float mode
1=float mode timed out
Note:
EEPER When EEPROM Charge Parameter Error occurs, the charger stops charging the battery and the LED indicator turns:
red. The charger needs to re-power on to re-start charging the battery.
NTCER When Temperature Compensation Short occurs, the charger output will shut down and the LED indicator will turn red.:
The charger will automatically restart after the Temperature Compensation Short condition is removed.
BTNC When there is no battery detected, the charger stops charging the battery and the LED indicator turns red.The charger:
needs to re-power on to re-start charging the battery.
CCTOF When timeout arises in the Constant Current stage, the charger stops charging the battery and the LED indicator:
CVTOF When timeout arises in the Constant Voltage stage, the charger stops charging the battery and the LED indicator:
FVTOF When timeout arises in the Float stage, the charger stops charging the battery and the LED indicator turns green.:
turns red. The charger needs to re-power on to re-start charging the battery.
turns red. The charger needs to re-power on to re-start charging the battery.
This charging flow is finished; the charger needs to re-power on to start charging a different battery.
18
Page 21
3.20.5 PMBus Data Range and Tolerance
◎ Display parameters
PMBus commandRangeToleranceMode
READ_VIN
READ_VOUT
READ_IOUT
(Note. 1)
READ_TEMPERATURE_1
READ_FAN_SPEED_1
READ_FAN_SPEED_2
Control parameter
◎
PMBus commandAdjustablerangeToleranceDefaultModel
OPERATION
VOUT_COMMAND
(Note. 2)
VOUT_TRIM
(Note. 2)
CURVE_CV
(Note. 3)
CURVE_FV
(Note. 3)
IOUT_OC_FAULT_LIMIT
CURVE_CC
CURVE_TC
ALL
24V
48V
24V
48V
ALL
ALL
ALL
ALL
24V24V24V
48V48V48V
24V
48V
24V
48V
24V
48V
24V
48V
24V
48V
80 ~ 264V
0 ~ 30V
0 ~ 60V
0 ~ 160A
0 ~ 80A
-40 ~ 100℃
0 ~ 25000RPM
0 ~ 25000RPM
Tabel 3-10
00h(OFF) / 80h(ON)
-6 ~ 6V
-12 ~ 12V
18 ~ 30V
36 ~ 60V
18 ~ VBST
36 ~ VBST
22 ~ 110A
11 ~ 55A
5.5A ~ 33A
3A ~ 16.5A
±10V
±0.36V
±0.48V
±5.32A
±2.68A
±℃5
±2000RPM
±2000RPM
N/A
N/A
N/A
±0.36V
±0.48V
±0.36V
±0.48V
±0.36V
±0.48V
±5.32A
±2.68A
±5.32A
±2.68A
80h(ON)
0V
0V
28.8V
57.6V
27.6V
55.2V
110A
55A
11A
5.5A
CURVE_CC_TIMEOUT
CURVE_CV_TIMEOUT
CURVE_FLOAT_TIMEOUT
ALL
Tabel 3-11
60 ~ 64800 Minute
±5 Minute
600 Minute
Note:
1.READ_IOUT will display ZERO amp when output current is less than values in the table below.
Minimum readable currentModel
24V5.3A 1A±
48V2.7A 1A±
Tabel 3-12
19
Page 22
2.
When using PMBus to adjust output voltage, VOUT_COMMAND only can be used to display the rated voltage of the unit and
cannot beIt is VOUT_TRIM that provide voltage trimming function. Taking- 00-as an example, to get aDBR 3224written.s
18set6V output, pleasevalue of VOUT_TRIM to - V.Adjustable voltage range for each model is shown as below.
Adjustable voltage rangeModel
24V18 ~ 30V
48V36 ~ 60V
Tabel 3-13
3.The value of CURVE_FV should be set less or equal to CURVE_CV,If CURVE_FV is greater than CURVE_CV, it will be saved as
CURVE_FV = CURVE_CV in EEPROM.
◎ Please refer to our specifications about PV/PC or SVR function.
3.21 CANBus Communication Interface
◎ For further CANBus information, Please contact MEAN WELL for detail.
4.Notes on Operation
4.1 Installation Method
◎ Mount the HP-1U in a 19 inch rack cabinet before operating.D
Insert 1 4 pieces of DRP DBR 3200 with the same output voltage and current into the DHP 1U refer to Figure4 1~/-()-(-)◎
This is a unit with forced air cooling, please keep fans and ventilation holes free from any obstructions. It is suggested that there◎
should be no barriers within 10cm of the ventilation holes.
Connect AC source to the AC inlets (A, B, C, D) respectively.◎
FigureSystem assembly diagram4-1 DHP
◎ Suggested wire selection for input/out wirings, e.g.- 00DRP 32
Input/ OutputModuleCurrent
115VAC
230VAC
+24VDC
+48VDC
1 unit
1 unit
1 unit
2 unit
3 unit
4 unit
1 unit
2 unit
3 unit
4 unit
9Arms
17Arms
133Adc
266Adc
399Adc
532Adc
67Adc
134Adc
201Adc
268Adc
Minimum Cross-section of copper wire
14AWG UL1015
12AWG UL1015
16AWG UL1015
12AWG UL1015
10AWG UL1015
Other commonly used wires
30mm
100mm
200mm
250mm
22mm
30mm
60mm
100mm
30mm
50mm
60mm
80mm
100mm
125mm
150mm
200mm
250mm
325mm
Module BModule CModule D
Module A
StatusStatusStatusStatus
Maximum Current
12A
22A
2
2
2
2
2
2
2
2
139A
298A
469A
556A
115A
139A
217A
298A
8A
22A
35A
2
2
2
2
2
2
2
2
2
2
139A
190A
217A
257A
298A
344A
395A
469A
556A
665A
Table 4-1 Suggested wire selection for input/output wirings
20
Page 23
4.2 De-rating
◎ WhenP- 00/- 00 units are operating at a lowerAC input voltage, these units will de-rate their output current automatically to protectDR 32 DBR 32
themselves, shown as Figure 4-2.
100
80
230VAC
Input only
60
50
40
LOAD (%)
20
-30-250-101530406070
(HORIZONTAL)
100
50
LOAD (%)
90100115180264
AMBIENT TEMPERATURE ( )℃
Figure 4-2 Output de-rating curves
4.3 Warranty
◎
A fiveisyear global warranty provided under normal operation. Please do not change ny component or modify the unit bya
yourself or MEANWELL may reserve the right not to provide the complete warranty service.
INPUT VOLTAGE (VAC) 60Hz
21
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.