MCZ S.p.A. - Via G.Oberdan 86, I - 33074 Vigonovo (PN) Italy.
07
EN 14785 - 2006
Art. 15a B-VG - VKF AEAI
Polar / Nova / Athos Power HYDRO
Potenci a nominal (agua - aire):
Potênci a nominal (água - ar):
Nominal heat output (water - air):
Brændværdi (vand - luft):
Emisión CO
al 13% de O2):
Emissão CO (13% de O2):
CO emission (at 13% O2)
CO emission (ved 13% O2):
Eficiencia:
Eficiencia:
Efficiency:
Virkningsgrad:
Temperadura humos:
Tempretura dos fumos:
Flue gas tem pe ra tur e :
Røggastemperatur:
Presión máxima de agua:
Pres sã o máxim a da águ a :
Permissible max. water pressure:
Max . va n d tr yk :
Asorbimiento electrico max:
Potênci a electrica absorbida:
Max. elec tr ical power supply :
Max. elektrisk effekt:
Tensión de funcionamiento:
Ten são electrica funcionamento:
Rated volta
e:
Netspænding:
Distancias de seguridad (retro):
Distancia de segurança (trasiera):
Sa fety clarence distance (back) :
Sikkerh edsafstand (bag):
Distancias de seguridad (laterales):
Distancia de segurança (lateral):
Sa fety clarence distance (side):
Sikkerh edsafstand (side):
Producto conforme a la instalación de tubos múltiples. Produto conforme para
instalação em condutas multiplas. Appliance suitable for installation in a shared flue.
Apparatet kan bruges i en røggassamleledning.
Utilizar sólo con combustibles adaptados. Utilizar somente combustivel adaquado. Use
only recommended fuels. Anvend kun anbefalede brændsler.
Leer y seguir las instrucciones! Leia atentamente e siga as instruções!
Leggere e seguir e le istruzioni! Read a nd f ollow the operating
instructions! Følg fabrikantens brugervejledning!
COD: 89009025 00
Max 23 ,7kW (16,2kW - 7,5kW)
Min 6,2 k W (3, 7k W - 2,5kW)
P max
P min
P max
P min
0,019%
0,055%
92,0%
93,0%
250 °C
2,5 bar
320 W
230 V - 50 Hz.
200 mm
500 mm
MCZ S.p.A. - Via G.Oberdan 86, I - 33074 Vigonovo (PN) Italy.
07
EN 14785 - 2006
Art. 15a B -V G - VKF AEA I
ATHOS HYDRO
Potencia nominal (agua - aire):
Potência nominal (água - ar):
Nominal heat output (water - air):
Brændværdi (vand - luft):
Emisión C O
Emissão CO (13% de O2):
CO emission (at 13% O2)
CO emission (ved 13% O2):
Eficiencia:
Eficiencia:
Efficiency:
Virkningsgrad:
Temperadura humos:
Tempretura dos fumos:
Flue gas temperature:
Røggastemperatur:
Presión máxima de agua:
Pressão máxima da água:
Permissible max. water pressure:
Max. vand tryk :
sorbimie nt o electrico max :
Potência electrica absorbida:
Max. electrical pow er supply:
Max. elektrisk effekt:
Tensión de funcionamiento:
Tensão electrica funcionamento:
Rated volta
Netspænding:
Distan cia s de segu r ida d (re tro):
Distancia de segur ança (trasier a):
Safety clarence distance (back):
Sikkerhedsafstand (bag):
Dis tan ci a s de segurid a d (l ate r al es ) :
Distancia de segur ança (lat eral):
Safety clarence distance (side):
Sikkerhedsafstand (side):
Producto c onfor m e a la ins talació n de tubos mú ltiples. Prod ut o conf orme pa r a
instalação em condutas multiplas. Appliance suitable for installation in a shared flue.
Appa rat et kan br uges i e n r øggassam leledning.
Utilizar sólo con combust ib les adaptados. Uti li za r somente combustivel adaqu ado . Use
only recommended fuels. Anvend kun anbefalede brændsler.
Leer y seguir las instrucciones! Leia atentamente e siga as instruções!
al 13% de O2):
e:
Leggere e seguire le istruzioni! Read and follow the operating
7.1. ELECTRICAL DIAGRAM OF POLAR-NOVA-ATHOS POWER Hydro WITH NO DOMESTIC HOT WATER KIT
62
7.2. ELECTRICAL DIAGRAM OF POLAR-NOVA-ATHOS POWER Hydro WITH DOMESTIC HOT WATER KIT....63
7.3. WIRING DIAGRAM for ATHOS Hydro without DOMESTIC HOT WATER KIT........................................64
Introduction Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
INTRODUCTION
Dear Customer,
We would like to thank you for selecting MCZ products, and particularly
for choosing one of the MCZ Pellet range.
We are convinced that as you use it, you will appreciate the quality of
the MCZ pellet line, which is the result of careful planning and
meticulous testing. Our aim is to combine technological complexity with
simplicity of use and, above all, with safety.
In order to get the best performance from your stove and to
enjoy to the fullest the warmth and the sense of well-being
which the flame will spread through the home, we recommend
that you read this booklet carefully before lighting the stove
for the first time.
Once you have learnt the basics, you will be able manage to best
advantage the various levels of power and the potential for presetting,
and you will also pick up a few little hints about cleaning and setting.
While thanking you again, may we remind you that the stove MUST NOT be used by children, and that they must always be kept at a safe
distance from it!
page
5
Revisions to the publication
In order to improve the product, to keep this publication up to date the
manufacturer reserves the right to make modifications without any
advance notice.
Any reproduction, even in part, of this manual without the consent of
the manufacturer is prohibited.
Care of the manual
•Take good care of this manual and keep it in a place which can
easily and quickly be reached.
•If this manual should be lost or destroyed, or if it is in poor
condition, ask for a copy from your retailer or directly from the
manufacturer, providing product identification data.
How to read the manual
•Information which is essential or that requires special attention is
shown in bold text.
“Italic text”
•
figures, or to ask the user to refer to other sections of the manual
for a more detailed explanation.
•NOTE: a NOTE provides the reader with additional information on
a specific topic.
is used to direct the user's attention to explanatory
Introduction Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
These symbols indicate specific messages included
in this booklet
ATTENTION:
This warning sign, used at various points in this booklet,
indicates that the message to which it refers should be
carefully read and understood, because failure to comply
with what these notices say can cause serious
damage to the stove and put the user's safety at risk.
INFORMATION:
This symbol is intended to highlight information important
for the proper functioning of the stove. Failure to comply
with what these notices say will compromise the use of the
stove and is likely to result in unsatisfactory operation.
OPERATING SEQUENCES:
Indicates a sequence of buttons to be pushed to access
menus or to make adjustments.
page
6
SEE MESSAGES:
This symbol instructs the user to see the messages shown
on the control display.
Introduction Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
1. WARNINGS AND GUARANTEE CONDITIONS
1.1. SAFETY INSTRUCTIONS
•Installation of the stove, making the electrical
and plumbing connections, checking its
operation, and maintenance are all tasks which
should be carried out ONLY by qualified and
authorised personnel.
•Install the stove in accordance with the
regulations in force in your local area, region and
country.
•For the correct use of the stove and of the electronic
apparatus connected to it, and to prevent accidents, the
instructions given in this booklet must always be
followed.
•In addition, adjustment and regulation must be carried
out by adults. Errors or incorrect settings can give rise
to hazardous conditions and/or bad running.
•Before beginning any operation, the user, or whoever is
preparing to operate on the stove, must have read and
understood the entire contents of this instruction
booklet.
•The stove is to be used only for its intended purpose.
Any other use is to be considered improper and
therefore hazardous.
•Do not use the stove for standing on or as any kind of
support.
•Do not put clothes to dry on the stove Any clothes
hangers and the like must be kept a suitable distance
from the stove. Danger of fire.
•All responsibility for improper use is taken entirely by
the user. Such use relieves MCZ of any civil or criminal
responsibility.
•Any kind of tampering or unauthorised substitution of
non-original spare parts can be hazardous for the safety
of the operator and relieves MCZ of any civil or criminal
responsibility.
•Most of the surfaces of the stove are extremely
hot (the door, the handle, the glass, smoke
discharge pipes etc.). Avoid coming into contact
with these parts, therefore, without adequate
protective clothing or suitable implements, such
as gloves with thermal protection or implements
which keep the hands cool.
•Carefully explain this hazard to elderly people, disabled
people and particularly to all children, keeping them
away from the stove while it is in operation.
•Under no circumstances should the stove be
operated with the door open or the glass broken.
•Do not touch the stove with wet hands, in view of the
fact that it is an electrical appliance. Always disconnect
the supply cable before doing anything to the unit.
•Before carrying out any cleaning or maintenance
page
7
Warnings and guarantee conciliations Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
operation, make sure in advance that the stove is
disconnected from the mains electricity supply, by
turning off the main switch located on the back of the
stove, or by unplugging the supply cable.
•The stove must be connected to an electrical system
which is equipped with an earth conductor, as set forth
in directives 73/23 EEC and 93/98 EEC.
•The system must be of adequate rated capacity for the
stated electrical power of the stove.
•Incorrect installation or faulty maintenance (not
conforming to the requirements set out in this booklet)
can cause harm to people, animals or property. In such
cases MCZ is relieved of any civil or criminal
responsibility.
1.2. OPERATING WARNINGS
•Shut the stove down in the event of a breakdown or
bad running.
• Pellets must not be fed manually into the burner.
• Accumulated unburnt pellets in the burner after
repeated failed ignitions must be removed
before lighting.
• Do not wash the inside of the stove with water.
• Do not wash the stove with water. The water could get
inside the unit and damage the electrical insulation and
cause electric shocks.
•Do not expose your body to hot air for extended
periods. Do not overheat the room you are in and
where the stove is installed. This could cause injuries
and health problems.
•Do not expose plants or animals directly to a current of
hot air. Both plants and animals could be harmed by it.
•Do not put anything in the hopper other than wood
pellets.
•Install the stove in a location which is suitable for for
fire protection, and equipped with all services such as
air and electricity supply and provision for discharging
combustion gases.
•If there is a fire in the flue pipe, extinguish the stove,
disconnect it from the power supply and never open
the door. Then contact the competent authorities.
•If the stove and the ceramic cladding are in storage, it
should be in a place that is free of damp, and they
should not be exposed to extremes of temperature.
•It is inadvisable to base the stove directly on the floor,
and if the floor is made of flammable material, it must
be suitably insulated.
•Do not light the stove with flammable materials if the
ignition system breaks down.
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
page
8
Warnings and guarantee conciliations Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
page
9
INFORMATION
•In case of any problems, get in touch with your dealer,
or qualified personnel authorised by MCZ. If repair is
necessary, insist on the use of original spare parts.
•Use only the fuel recommended by MCZ (for Italy pellets
with a diameter of 6 mm and for other European
countries with a diameter of 6-8 mm) and provided only
with an automatic supply system.
•Periodically check and clean the smoke outlet ducts
(connection to the flue pipe).
•Accumulated unburnt pellets in the burner after
repeated failed ignitions must be removed before
lighting.
• The pellet stove is not a cooking appliance.
• Always keep the cover of the fuel hopper closed.
• Keep this instruction manual carefully because it must
stay with the stove throughout its working life. If the
stove is sold or transferred to another user, always
make sure that the booklet goes with the product.
•If it gets lost, ask MCZ or your authorised dealer for
another copy.
1.3. GUARANTEE CONDITIONS
MCZ guarantees the stove, excluding the components
which are subject to normal wear, for a period of two
years from the date of purchase, as proved by a supporting
document which gives the name of the vendor and the date
on which the sale took place. The guarantee is conditional
on the guarantee certificate being filled in and returned
within 8 days, and requires that the product be installed
and tested by a specialised installer, according to the
detailed instructions given in the instruction booklet
supplied with the product.
The term 'guarantee' is to be understood to denote the
free-of-charge replacement or repair of parts recognised
to have been defective at the start by reason of
manufacturing defects.
1.3.1. Limitations
The above guarantee does not cover components relating to electrical
and electronic parts, or fans, on which the guarantee period is 1 year
from the purchase of the product, documented as specified above. The
guarantee does not cover parts subject to normal wear such as
gaskets, glass, and any parts with can be removed from the firebox.
The replacement parts will be guaranteed for the remainder of the
guarantee period starting from the date of purchase of the product.
1.3.2. Exceptions
Variations in colour in the painted or ceramic parts, and crackling of the
glaze on the ceramics, do not constitute grounds for a claim under the
guarantee, as they are natural characteristics of the material and of the
use of the product.
Warnings and guarantee conciliations Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 1
INSTALLATION AND USE MANUAL
The guarantee does not cover any parts which may be found to be
faulty as a result of negligence or carelessness in use, or of incorrect
maintenance, or of installation not complying with MCZ's specification
(see the relevant chapters in this user manual).
MCZ refuses to accept any responsibility for any damage which may be
caused, directly or indirectly, by persons, animals or things as a result
of the failure to observe all the prescriptions laid down in the
instruction booklet, especially those concerning warnings on the subject
of installation, use and maintenance of the appliance.
If the product does not perform correctly, contact your local retailer
and/or importer.
Damage caused by transport and/or handling is excluded from the
guarantee.
For installation and use of the product, reference must be made
exclusively to the booklet supplied.
The guarantee will be invalidated in the event of damage caused by
tampering with the appliance, atmospheric agents, natural disasters,
electrical discharges, fire, defects in the electrical system, and lack of,
or incorrect, maintenance in terms of the manufacturer's instructions.
page
10
CLAIMS UNDER THE GUARANTEE
The request for action under the guarantee must be
addressed to the retailer, who will forward the claim
to MCZ's technical assistance service.
MCZ DECLARES THAT THE STOVE WHICH YOU HAVE
PURCHASED COMPLIES WITH EEC DIRECTIVE
89/336 AND 72/23 AND SUBSEQUENT
AMENDMENTS.
MCZ shall not be held liable if the stove or any other
accessory have been improperly used or modified
without authorisation.
For all replacement of parts, only original MCZ spare
parts must be used.
Warnings and guarantee conciliations Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2. THEORETICAL NOTIONS FOR INSTALLATION
2.1. PELLETS
Wood pellets are manufactured by hot-extruding compressed sawdust
which is produced during the working of natural dried wood. The
compactness of the material comes from the lignin which is contained
in the wood itself, and allows the production of pellets without the use
of glues or binders.
The market offers different types of pellet with characteristics which
vary depending on what mixture of woods is used. The diameter varies
between 6 mm and 8 mm, with a standard length in the range 5 mm to
30 mm. Good quality pellets have a density which varies between 550
3
to over 700 kg/m3, with a moisture content which varies from
kg/m
5% to 8% by weight.
With the aim of guaranteeing the stated rate of fuel
consumption per hour and ensuring optimum combustion, MCZ
has devised a patented method which allows the identification
and cataloguing of any type of pellet with a 6 mm and 8 mm
diameter, in terms of its specific gravity and particle size.
By using the special PelletBox® and following the procedure set out in
the paragraph on lighting the stove, the user can determine the correct
settings for configuring the stove.
Besides being an ecological fuel (exploiting timber residues to the
maximum and achieving cleaner combustion than is possible with fossil
fuels), pellets also have technical advantages. While good-quality
timber has a calorific power of 4.4 kW/kg (with 15% moisture, after
about 18 months' seasoning), the equivalent figure for pellets is 5.3
kW/kg.
To ensure good combustion, the pellets must be stored in an area that
is free of humidity and protected from dirt. The pellets are usually
supplied in 15 kg. sacks, so storing them is very convenient.
Good quality pellets ensure good combustion, thus lowering the
emission of harmful agents into the atmosphere.
The poorer the quality of the fuel, the more
frequently will intervention be necessary for cleaning
the internal parts, such as the grate and the
combustion chamber.
The pellets must be produced from pure wood which has not been
treated chemically.
The standards DIN 51731 and ONORM M 7135 certify a high-quality
pellet with the following characteristics:
9 Calorific power: 5.3 kW/kg
9 Density: 700 kg/m
9 Water content: max 8% of weight
9 Percentage of ashes: max 1% of weight
3
Figure 1 - Pellet fuel
Figure 2 - PelletBox®
Figure 3 - Sack of fuel, 15 kg
page
11
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
9 Diameter: 6 – 6.5mm
9 Length: max 30mm
9 Contents: 100% untreated wood, with no added bonding
substances (bark percentage 5% max)
9 Packaging: in sacks made from ecologically compatible or
biologically decomposing material
MCZ strongly recommends using certified fuel in its
stoves.
The use of fuel of inferior quality or not conforming
to the specification given above compromises the
running of your stove and can therefore lead to the
termination of the guarantee and of the
manufacturer's responsibility for the product.
MCZ pellet stoves run exclusively on pellets with a
diameter of 6 mm (only for Italy) and 6-8 mm
(European countries) with lengths that go from 5
mm to 30 mm.
page
12
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2.2. OPERATING AREA
For proper functioning and good temperature distribution, the stove
should be positioned in a location where it is able to take in the air
necessary for combustion of the pellets (about 40 m
available), as set forth in the standard governing the installation and in
accordance with local national standards.
The volume of the room must not be less than 30 m
The air must come in through permanent openings made in walls (in
proximity to the stove) which give onto the outside, with a minimum
cross-section area of 100 cm
2
.
These openings must be made in such a way that it is not possible for
them to be obstructed in any way.
Alternatively, the air can be taken from rooms adjacent to the one
which needs ventilating, as long as they are provided with an air intake
from the outside, and are not used as bedrooms or bathrooms, and
provided there is no fire risk such as there is for example in garages,
woodsheds, and storerooms, with strict compliance with the provisions
of current standards.
It is not permissible to install the stove in bedrooms,
bathrooms or showers, or in a room where another
heating appliance is installed (fireplace, stove etc.)
which does not have its own independent air intake.
Locating the stove in a room with an explosive
atmosphere is prohibited.
The floor of the room where the stove is to be
installed must be strong enough to support its
weight.
If the walls are not flammable, position the stove with a clearance to
the rear of at least 10 cm.
In the case of walls made of flammable material, maintain a minimum
clearance to the rear of 20 cm, a clearance to the sides of 50 cm, and a
clearance to the front of 150 cm. If the room contains objects which
are believed to be particularly delicate, such as curtains, sofas and
other furniture, their distance from the stove should be considerably
increased.
If the flooring is made of wood, provide a floor
protection surface in compliance with current
national standards.
3
/h must be
3
.
page
13
Figure 4 - Example of installation with Polar stove
Figure 5 - Example of installation with Polar stove
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2.3. PRECAUTIONS
IMPORTANT!
Installation and assembly of the stove must be
carried out by qualified personnel.
The stove must be installed in a suitable position to allow the normal
operations of opening and ordinary maintenance.
The site must be:
• capable of providing the environmental conditions for operation
• equipped with power supply 230V 50 Hz (EN73-23)
• capable of taking an adequate system for smoke discharge
• provided with external ventilation
• provided with an earth connection complying with CEI 64-8
The stove must be connected to a flue pipe or an internal or
external vertical duct conforming to current standards UNI
7129 - 7131 9615.
The stove must be positioned in such a way that the electrical
plug is accessible.
IMPORTANT!
The stove must be connected to a flue pipe or a
vertical duct which can discharge the fumes at the
highest point of the building.
The fumes are however derived from the combustion
of wood products, and if they come into contact with
or close to walls, they can make dirty marks.
Also take care because the fumes are very hot but
almost invisible, and can cause burns on contact.
The holes for the passage of the smoke pipe and for
the intake of air from outside should be made before
positioning the stove unit.
page
14
2.4. CONNECTION TO THE EXTERNAL AIR INTAKE
It is essential that at least as much air must be able to flow into the
room where the stove is installed as is required for proper combustion
in the appliance and for the ventilation of the room. This can be
effected by means of permanent openings in the walls of the room to
be ventilated, which give onto the outside, or by single or collective
ventilation conduits.
For this purpose, on the external wall near the stove, a hole must be
made with a minimum free cross-section of 100 cm². (equivalent to a
round hole of 12 cm diameter or a square hole 10x10 cm), protected by
a grille on the inside and the outside.
The air intake must also:
• communicate directly with the room where the stove is installed
• be protected by a grille, metal mesh or suitable guard, as long as
this does not reduce the cross-section below the minimum.
•be positioned in such a way as to be impossible to obstruct
It is not compulsory to connect the air inlet of the
stove directly with the exterior, but an air flow must
be guaranteed of at least 50 m³/h. Refer to current
standards.
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Figure 6 – Air intake grille
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2.5. CONNECTION OF SMOKE DISCHARGE PIPE
page
15
When making the hole for the passage of the smoke discharge pipe, it
is necessary to take into account the possible presence of flammable
materials. If the hole will be going through a wall made of wood or any
other material which is sensitive to heat, the INSTALLER MUST first
of all use the special wall union (diam. 13cm minimum) and properly
insulate the pipe of the stove that passes through it, using adequate
insulation materials (thickness 1.3 - 5cm with minimum thermal
conductivity of 0.07 W/m°K).
The same is true if the stove pipe must run through vertical or
horizontal stretches passing in proximity (min. 20cm) to the heatsensitive wall.
As an alternative we recommend the use of insulated pipe, which can
also be used on the outside to avoid condensation.
The combustion chamber works in low pressure. The smoke duct for
the discharge of fumes will also be under low pressure when connected
to an efficient flue pipe as directed.
Pipes and unions with suitable gaskets must always
be used, to guarantee a hermetic seal.
All sections of the smoke duct must be inspectable and
removable to enable periodic internal cleaning. Tee
connectors with inspection caps should be used.
Position the stove bearing in mind all the instructions and
considerations above.
IMPORTANT!
All 90 degree changes of direction in the flue pipe
must be fitted with suitable tee connectors to allow
the possibility of inspection (see the pellet stove
accessory list).
It is absolutely prohibited to fit a grille on the end of
the smoke discharge pipe, because it could lead to
poor operation of the stove.
FOR CONNECTION TO THE FLUE PIPE, NOT MORE
THAN 2-3 METRES OF HORIZONTAL PIPE MUST BE
USED AND NOT MORE THAN THREE 90° CURVES
MUST BE USED
NOT ADVISABLE TO EXCEED A LENGTH OF 6 LINEAR
METRES OF PIPE Ø 80 mm.
Smoke outlet
Air intake
Figure 7 – Back of POLAR/NOVA stove
Ispection cover
2 - 3 mt. MAX
.
t
m
4
n
e
h
t
r
e
t
a
e
r
g
t
h
g
i
e
H
t
m
2
5
,
1
n
i
M
3-5 %
Ispection cover
THE DIRECT DISCHARGE OF THE
COMBUSTION PRODUCTS MUST BE
Figure 8 – Example of installation of POLAR/NOVA stove
PROVIDED ON THE ROOF, AND THE SMOKE
DUCT MUST SATISFY THE SPECIFICATIONS
PROVIDED FOR BY CURRENT LAWS AND
STANDARDS ON THE SUBJECT (UNI 10683)
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2.6. CONNECTION TO THE FLUE PIPE
page
16
The flue pipe must have internal dimensions not larger than 20 x 20
cm, or diameter 20 cm. In the event of larger dimensions, or of the flue
pipe being in poor condition (for example cracks, poor insulation, etc.),
it is advisable to fit a stainless steel pipe of suitable diameter inside the
flue pipe throughout its length, right up to the top.
Figure 9
Check with suitable instruments that there is a minimum draught of 10 Pa.
At the bottom of the flue pipe, provide an inspection cap to allow
periodic checking and cleaning, which must be done annually.
Make a gas-tight connection to the flue pipe, using pipes and
connectors as recommended by us.
You must ensure that a windproof cowl is fitted which complies with
current standards.
This type of connection ensures the evacuation of the
fumes even in the event of a temporary power
outage.
2.7. CONNECTION TO AN EXTERNAL FLUE WITH
INSULATED OR DOUBLE-WALL PIPE
The external fluepipe must have internal dimensions of minimum 10x10
cm or 10 cm diameter, and maximum 20x20 cm or 20 cm diameter.
Check with suitable instruments that there is a minimum draught of 10 Pa.
Figure 10
The only type of pipe which is permissible is insulated (double-walled)
stainless steel, smooth on the inside, fixed to the wall. Flexible stainless
steel pipe must not be used.
At the bottom of the flue pipe, provide an inspection cap to allow
periodic checking and cleaning, which must be done annually.
Make a gas-tight connection to the flue pipe, using pipes and
connectors as recommended by us.
You must ensure that a windproof cowl should be fitted which complies
with the standards in force.
This type of connection ensures the evacuation of the
fumes even in the event of a temporary power cut.
0,5 mt.
Figure 9
0,5 mt.
Figure 10
0, 5 mt.
Windproof
Comignolo
cowl
antivento
Flue pipe
Canna fumaria
Inspection
cover
Ispezione
Condotto
Insulated
esterno
external pipe
isolato
Inspection
Ispezione
cover
Comignolo
Windproof
antivento
cowl
2.8. CONNECTION TO FLUE PIPE OR SMOKE DUCT
2 - 3 mt. MAX
For proper operation, the connection between the stove and the flue
3-5 %
pipe or smoke duct must have a slope of not more than 3%. The length
of the horizontal segment must not exceed 2/3 m. and the vertical
distance between one tee connector and another (change of direction)
must not be less than 1.5m.
Check with suitable instruments that there is a minimum draught of 10 Pa.
Figure 11
At the bottom of the flue pipe, provide an inspection cap to allow
Minimo 1,5 - 2 mt.
periodic checking and cleaning, which must be done annually.
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Canna fumaria
Flue pipe
Ispezione
Inspection
cover
Figure 11
PELLET STOVES Chapter 2
y
INSTALLATION AND USE MANUAL
Make a gas-tight connection to the flue pipe, using pipes and
connectors as recommended by us.
You must ensure that a windproof cowl is fitted which complies with
current standards.
This type of connection ensures the evacuation of the
fumes even in the event of a temporary power cut.
2.9. OPERATING PROBLEMS CAUSED BY DRAUGHT
DEFECTS IN THE FLUE
Of all the weather and geographical conditions which affect the
operation of a flue pipe (rain, fog, snow, altitude a.s.l., exposure to
sunlight, direction of facing), the wind is unquestionably the most
decisive. In fact, along with thermal depression caused by the
difference in temperature inside and outside of the chimney, there is
another type of depression or over-pressure: dynamic pressure caused
by the wind. An updraft always increases depression and hence
draught. A crosswind increases depression provided the cowl has been
installed properly. A downdraft always decreases depression, at times
inverting it.
Least favourable points
WIND
High-pressure
Besides the direction and force of the wind, the position of the flue and
the cowl with respect to the roof of the building and the surrounding
landscape is important.
The wind also influences the operation of the chimney indirectly by
creating high-pressure and low-pressure zones, not only outside the
building but inside as well. In rooms directly exposed to the wind (2),
an indoor high-pressure area can be created which can augment the
draught in stoves and fireplaces, but it can be counteracted by the
external high pressure if the cowl is situated on the side exposed to the
wind (1). On the other hand, in the rooms on the opposite side from
the direction of the wind (3), a dynamic depression can be created
which competes with the natural thermal depression developed by the
chimney, but this can be compensated for (sometimes) by locating the
flue on the opposite side from the direction of the wind (4).
IMPORTANT!
The operation of the pellet stove is noticeabl
sensitive to the conformation and position of the flue
which is adopted.
Hazardous conditions can only be overcome by
suitable setting-up of the stove carried out by
qualified MCZ personnel.
Most favourable position
Low-pressure zone
page
E.g. Downdraft at 45° of 8m/sec.
Overpressure of 17 Pa
E.g. Crosswind 2: 8 m/sec:
Depression of 30Pa
Downdraft
WIND
1
2 3
1-2 = High-pressure zones
3-4 = Low-pressure zones
17
4
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
2.10. PLUMBING CONNECTION
IMPORTANT!
The connection of the stove to the plumbing system
must be carried out ONLY
who are capable of carrying out installation properly,
in compliance with current standards in the country
of installation.
If installation of the stove will involve interaction
with another, pre-existing system complete with
heating equipment (gas boiler, methane boiler, fuel
oil boiler, etc.), it is even more advisable to call in
qualified personnel, who subsequently will be
responsible for conformity of the system with current
applicable law.
MCZ will not be held responsible for damage to
persons or things in the event of failed or incorrect
operation if the aforementioned warnings are not
complied with.
For connection of the plumbing system to the stove, the user should
refer to chapter 3, INSTALLATION AND ASSEMBLY; specifically,
paragraph 3.4, CONNECTION TO PLUMBING SYSTEM
by specialized personnel
page
18
Theoretical notions for installation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
page
19
3. INSTALLATION AND ASSEMBLY
3.1. DRAWINGS and TECHNICAL CHARACTERISTICS
3.1.1. Dimensions of POLAR-NOVA in HYDRO version with no kit for the
production of domestic hot water
Ø80
Ø48
281
334
192
275
3.1.2. Dimensions of POLAR-NOVA in HYDRO version with kit for the production
of domestic hot water
Ø80
Ø48
281
334
192
275
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
page
20
3.1.3. Dimensions of ATHOS POWER in HYDRO version with no kit for the
production of domestic hot water
281
198
364
330
578
1120
643
3.1.4. Dimensions of ATHOS POWER in HYDRO version with kit for the
production of domestic hot water
1120
281
198
364
330
643
578
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
3.1.5. ATHOS HYDRO Dimensions
Ø48
281
Ø80
350
198
364
3.1.6. TECHNICAL CHARACTERISTICS
page
21
1120
643
578
Technical specificationsAthos Hydro
Overall thermal power Max. 14.0 kW (12040 kcal/h) / 10.4 kW (8944 kcal/h)
Overall thermal power Min. 4.0 kW (3440 kcal/h) / 1.4 kW (1204 kcal/h)
Yield at maximum 91 %
Yield at minimum 94 %
Temperature of exhaust smoke at maximum 190°C
Temperature of exhaust smoke at minimum 90°C
CO at 13%O
at minimum and maximum 0.045 — 0.017%
²
CO2 at minimum and maximum 3.4% – 5.9%
Mass of smoke at minimum and maximum 8.3 – 16,7 g/sec
Minimum draught at maximum power 0.10 mbar – 10 Pa
Minimum draught at minimum power 0.05 mbar – 5 Pa
Hopper capacity 52 litres
Fuel pellet type Pellet diameter 6-8 mm. Length range 5-30 mm
Pellet consumption per hour Min ~ 0.8 kg/h * Max. ~ 3 kg/h *
Operating time between re-fuelling At min~ 43 h * At max. ~ 12 h *
Heatable volume m3 301/40 – 344/35 – 401/30 **
Combustion air inlet External diameter 50 mm.
Smoke outlet External diameter 80 mm.
Maximum absorbed electrical power Max 300 W – Med 120 W
Power supply frequency and voltage 230 Volts / 50 Hz
Net weight 200 kg
Weight with packaging 210 kg
*Data that may vary depending on the type of pellets used.
**Heatable volume based on demand of cal/h for m
Appliance suitable for installation in a shared flue.
3
40-35-30 (respectively 40-35-30 Kcal/h for m3)
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
Technical characteristics Polar Nova Athos Power Hydro
Overall thermal power (total/water) Max. 23.7 kw (20382 kcal/h) / 16.2 kw / 7.5 kw
Overall thermal power (total/water) Min. 6.2 kw (5332 kcal/h) / 3.7 kw / 2.5 kw
Yield at maximum 92 %
Yield at minimum 93 %
Temperature of exhaust smoke at maximum 250°C
Temperature of exhaust smoke at minimum 100°C
page
22
CO at 13%O
at minimum and maximum 0.055 — 0.018%
²
CO2 at minimum and maximum 5.5% – 11.9%
Mass of smoke at minimum and maximum 7.3 – 13 g/sec
Minimum draught at maximum power 0,10 mbar – 10 Pa
Minimum draught at minimum power 0,05 mbar – 5 Pa
Hopper capacity 52 lt
Fuel pellet type Pellet diameter 6-8 mm. Length range 5-30 mm
Pellet consumption per hour Min ~ 1 kg/h * Max. ~ 5 kg/h *
Operating time between re-fuelling At min~ 33 h * At max. ~ 7 h *
Heatable volume m3 510/40 – 582/35 – 679/30 **
Combustion air inlet Ø 50 mm.
Smoke outlet Ø 80 mm.
Maximum absorbed electrical power Max 320 W – Med 120 W
Power supply frequency and voltage 230 Volt / 50 Hz
Net weight 200 Kg.
Weight with packaging 210 Kg.
*Data that may vary depending on the type of pellets used.
**Heatable volume based on demand of cal/h for m
Appliance suitable for installation in a shared flue.
3
40-35-30 (respectively 40-35-30 Kcal/h for m3)
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
3.2. PREPARATION AND UNPACKING
Polar and Nova stoves are delivered in two packages:
9 The first contains the stove unit (
9 The second contains the ceramic cladding. (
The Athos stove is delivered only with the packaging in fig. 1.
Open the packaging, take off the bands, remove the stove unit from
the pallet and position it in the chosen location, taking care that its
position complies with the above instructions.
The main stove unit must always be moved in an upright position and a
trolley must always be used. Take particular care to see that the door
and its glass are protected from mechanical impact which could
damage them.
Moving the product must always be done with care.
If possible, unpack the stove in the area where it is going to be
installed.
The materials which make up the packaging are not toxic or harmful,
so no special procedures for disposal by required.
Their storage, disposal or possible recycling are therefore the
responsibility of the final user, in compliance with current legislation on
the subject.
Do not store the stove unit or its cladding without their packaging.
If the stove needs to be connected to a discharge pipe which goes
through the rear wall (to connect up with the flue), take the greatest
care to make sure that the joint is not stressed.
If the smoke outlet of the stove is forced or used
improperly to lift it or position it, the operation of the
stove can be damaged irreparably.
Figure 1
)
Figure2
)
page
23
Figure 1 – Example of stove packaging
Figure 2 - Example of packing for
ceramics
Use the four adjustable feet (J) to get the stove correctly levelled so
that the smoke outlet (S) is lined up with the connecting pipe (H).
Adjustment ranges from a minimum of 12 mm to a maximum of 23
mm.
1. Turn the foot clockwise to
lower the stove
2. Turn the foot counter-
clockwise to raise the stove
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Bottom
view
Foot J
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
3.3. INSTALLATION OF CERAMIC CLADDING FOR
POLAR AND NOVA
3.3.1. Installation of upper panel
Remove the two pre-installed nuts in the upper part of the frame. Take
the upper panel, open the hinge and install it, using the two screws
welded onto the frame, which you freed when you removed the nuts.
Check the alignment of the panel and tighten the nuts
Figure 3
3.3.2. Installation of lower panel
page
24
Remove the two pre-installed nuts in the lower part of the frame
alongside the ash compartment door. Take the lower panel, open the
hinge and install it, using the two screws welded onto the frame, which
you freed when you removed the nuts. Check the alignment of the
panel and tighten the nuts.
Figure 4
3.3.3. Installation of side tiles
INSTALLATION OF THE TILES MUST ALWAYS START
FROM THE BOTTOM.
1. Turn the screw K so that the rod H comes into contact with the
structure.
Figure 5 - phase 1
2. Insert the tile first from the side of the rod H, and then insert
the opposite part in the housing in the fixed hooks G.
phase 1
Figure 6 -
3. Turn the tile towards the exterior of the stove so that the front
edge that remains free rests on the upright.
4. Repeat steps 1-2-3 for all the tiles of the side.
Figure 6 - phase 2
Figure 6 - phase 3
5. Turn the screw K so that the connected rod H pushes the tile
towards the upright. Use another wrench to tighten nut L to
permanently secure the system.
Figure 6 - phase 4
6. Repeat the operations described on the other side.
G
Figure 3 – Installation of upper front panel
Figure 4 – Installation of lower front panel
K
L
G
H
Figure 5 – Side view of the fastening system
of the lateral ceramics
Legend for Figures 5 and 6
H
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Figure 6 – Top view of fastening system of
the lateral ceramics
G - Rear fixed hooks
H - Front blocking rod
L - Blocking nut
K - Blocking screw
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
3.3.4. Removal of sides on the ATHOS stove
The stove, in its packaging, already has the metal sides and the
ceramic top installed.
For any servicing the stove may require (see the following paragraphs),
you can remove the sides.
The right side is removed towards the front of the stove and then it
moves laterally towards the right side as shown in the figure.
Before removing the left side, you must lift the door up and remove it,
and then proceed as with the right side.
Removal of right side of ATHOS stove
Removal of left side of ATHOS stove
page
25
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
p
INSTALLATION AND USE MANUAL
3.3.5. Installation of ceramic top
Install the top by setting it on the four upper protuberances of the
stove. The part underneath is provided with four small cavities at the
rubber supports indicated in
figure 11.
3.4. PLUMBING SYSTEM CONNECTION
page
26
IMPORTANT!
The connection of the stove to the plumbing system
must be made ONLY
by specialized personnel who
Figure 11 – Supports for installation of
ceramic to
are capable of carrying out installation properly, in
compliance with current standards in the country of
installation.
MCZ will not be held responsible for damage to
persons or things in the event of failed operation if
the aforementioned warning is not complied with.
Connect the stove using the connections provided in the lower rear part
of the unit
CONNECTION DIAGRAM FOR POLAR/NOVA STOVE WITHOUT KIT FOR PRODUCTION OF DOMESTIC
HOT WATER
A1=Heating water delivery 3/4”M
A2=Heating water return 3/4”M
C=Vent 3/4”M
0
4
D=Refill 3/8”M
5
2
8
1
E= System empting and discharge 3/4”M
Ø48
Ø80
D
E
1
8
2
192
275
4
3
3
A1
A2
C
122
255
140
140
0
3
CONNECTION DIAGRAM FOR POLAR/NOVA STOVE WITH KIT FOR PRODUCTION OF DOMESTIC HOT
WATER
Ø80
Ø48
1
8
2
192
275
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
4
3
3
A1
B1
D
E
B2
C
A2
659775
140
140
5
8
1
0
3
192
A1=Heating water delivery 3/4”M
A2=Heating water return 3/4”M
0
B1=Domestic hotwater outlet 1/2”M
4
2
B2=Domestic hotwater inlet 1/2”M
C=Vent 3/4”M
D=Refill 3/8”M
E= System empting and discharge 3/4”M
PELLET STOVES Chapter 3
CONNECTION DIAGRAM FOR ATHOS HYDRO STOVE
INSTALLATION AND USE MANUAL
page
27
198
198
Ø80
0
5
3
0
3
3
A1
A1
C
122
D
E
C
A2
D
E
265
A2
265122
150
150
150
150
A1=Heating water delivery 3/4”M
A2=Heating water return 3/4”M
0
5
8
1
0
3
0
3
C=Vent 3/4”M
4
2
D=Refill 3/8”M
E= System empting and discharge 3/4”M
A1=Heating water delivery 3/4”M
A2=Heating water return 3/4”M
C=Vent 3/4”M
D=Refill 3/8”M
E= System empting and discharge 3/4”M
0
5
4
8
2
1
Ø48
1
8
2
364
CONNECTION DIAGRAM FOR ATHOS POWER STOVE WITHOUT KIT FOR PRODUCTION OF
DOMESTIC HOT WATER
1
8
2
364
CONNECTION DIAGRAM FOR ATHOS POWER STOVE WITH KIT FOR PRODUCTION OF DOMESTIC
HOT WATER
A1=Heating water delivery 3/4”M
DED
1
8
2
198
364
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
D=Refill 3/8”M
E= System empting and discharge 3/4”M
PELLET STOVES Chapter 3
g
INSTALLATION AND USE MANUAL
3.4.1. Connections to the system
Make the connections to the corresponding fittings shown in the
diagram on the previous page. Make sure the pipes are not placed
under tension or undersized.
IMPORTANT
IT IS STRONGLY RECOMMENDED TO WASH THE
ENTIRE SYSTEM BEFORE CONNECTING IT IN ORDER
TO GET RID OF RESIDUES AND DEPOSITS.
Upstream from the stove, always install shutters so
as to disconnect it from the plumbing system should
it be necessary to move it, or when it requires
routine and/or special maintenance.
Connect the stove using hoses so that the stove is
not too strictly connected to the system, and to allow
slight movements.
The pressure discharge pipe should be tentatively
placed in a pitcher or funnel to keep water from
wetting the floor or the structure in the event of
excessive pressure.
Pressure discharge pipe (3 bar)
page
28
3.4.2. System filling
To fill the system, the stove is equipped with a tap (D), with a nonreturn valve, for manual filling of the heating system. During this
operation, any air in the system is released by the automatic vent valve
at the upper left of the boiler body (under the ceramic top).
To ensure the valve vents correctly, it is advisable to loosen the grey
cap one turn and to keep the red cap blocked
(see figure)
The filling pressure of the system WHEN COLD must be
1 bar.
During operation, if the system pressure drops (due to evaporation of
dissolved gases in the water) to values lower than the minimum
indicated above, the user must use the filling valve to bring the
pressure back up to its normal pressure.
For proper operation of the stove WHEN HOT, the pressure in the
boiler must be 1.5 bar.
To monitor the pressure of the system, install down the line
from the bibcock (D) a pressure gauge with a scale of 0-5 bar.
This is to be done by the installer.
Upon completion of this operation, always close the tap.
3.4.3. Water characteristics
The characteristics of the water used to fill the system are very
important to prevent the build-up of mineral salts and the formation of
incrustations along the pipes, in the boiler and in the heat exchangers
(especially plate heat exchangers for the heating of domestic water see chapter 4.13)
Therefore, please GET YOUR PLUMBER'S ADVICE
CONCERNING:
C
Filling tap (D)
D
E
Red plu
blocked
Grey pl ug loosened
1 turn
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
• Hardness of water circulating in the system, to prevent
problems of incrustation and limescale, especially in the
domestic water heat exchanger. (> 25° French)
• Installation of a water softener (if water hardness
exceeds 25° French)
• Filling the system with treated water (demineralised).
• Possibly providing an anti-condensation circuit.
• Installation of plumbing bumpers to prevent banging
along the fittings and pipes.
If you have very extensive systems, with a large amount of water, or
which require frequent refilling, the installation of water softening
systems.
It should be remembered that incrustations
drastically reduce performance due to low thermal
conductivity.
3.5. EXAMPLE INSTALLATION DIAGRAMS
page
29
The following diagrams are to be used only as a
guideline. For proper connection, always follow the
notes for the plumbing and heating installer. The
plumbing system must meet local, regional or
national requirements. Installation and verification
of operation is to be performed only by specialized,
authorized personnel.
MCZ will not be held liable for non-compliance with
the provisions listed above.
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
V
V
V
INSTALLATION AND USE MANUAL
page
30
3.5.1. Heating installation diagram Heating system installation diagram without
water kit (POLAR-NOVA-ATHOS POWER)
PERFORMANCE:
HEATING WITH STOVE
230V 50HZ
SE
RARARARA
S
T
T
VE
VS
P
VD
V
V
VD
M
SYSTEM DELIVERY
V
PRESSURE SAFETY DISCHARGE
SYSTEM RETURN
SYSTEM REFILL
A
RP
Flt
sc
CONFIGURATION: POLAR / NOVA WITH DOMESTIC HOT WATER KIT
SYSTEM OF SYSTEM WITH CLOSED TANK ONLY FOR HEATING BY MEANS OF RADIATORS
SIGNATURFORKLARING:
SE Electronic card
S Automatic vent
M Pressure gauge
VS Vent valve, 3 bar
V Valve
P Pump
VD One-way valve
T Measurement of boiler temperature
VE Expansion tank, 1.5 bar of 6 l
W 3-way motorized valve
SC Plate heat exchanger
F Flow switch
C Methane gas boiler
B Boiler
BA Storage boiler
RA Radiators
PR Radiant panels
PS Solar panels
A Pounding absorber
RP Pressure reduction valve
Vsc Boiler/system discharge valve
Flt System filter
Add Softener
3.5.2. Heating installation diagram with domestic hot water kit (POLAR–NOVA-
ATHOS POWER)
PERFORMANCE:
HEATING WITH STOVE
PRODUCTION OF DOMESTIC HOT WATER WITH STOVE
RARARARA
230V 50HZ
SE
S
T
VS
VD
P
V
VV
V
M
V
SYSTEM DELIVERY
SC
V
SYSTEM RETURN
VE
T
VD
V
SYSTEM REFILL
PRESSURE SAFETY DISCHARGE
Vsc
V
COLD DOMESTIC WATER INLET
HOT DOME STIC WATER OUTLET
R
RP
A
Flt
Add
CONFIGURATION: POLAR / NOVA WITH DOMESTIC HOT WATER KIT
SYSTEM DIAGRAM WITH CLOSED TANK FOR HEATING WITH RADIATORS OR FOR THE PRODUCTION OF DOMESTIC HOT WATER
SIGNATURFORKLARING:
SE Electronic card
S Automatic vent
M Pressure gauge
VS Vent valve, 3 bar
V Valve
P Pump
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
VD One-way valve
T Measurement of boiler temperature
VE Expansion tank, 1.5 bar of 6 l
W 3-way motorized valve
SC Plate heat exchanger
F Flow switch
C Methane gas boiler
B Boiler
BA Storage boiler
RA Radiators
PR Radiant panels
PS Solar panels
A Pounding absorber
RP Pressure reduction valve
Vsc Boiler/system discharge valve
Flt System filter
Add Softener
PELLET STOVES Chapter 3
INSTALLATION AND USE MANUAL
page
31
3.5.3. Diagram for installation combined with external boiler (POLAR-NOVA-
ATHOS POWER)
PERFORMANCE:
HEATING WITH STOVE
HEATING WITH BOILER
PRODUCTION OF DOMESTIC HOT WATER WITH STOVE
PRODUCTION OF DOMESTIC HOT WATER WITH BOILER
230V 50HZ
CONFIGURATION: POLAR / NOVA WITH DOMESTIC HOT WATER KIT PARALLEL WITH GAS BOILER
SYSTEM DIAGRAM WITH CLOSED TANK PRE-HEATING WITH RADIATORS OR FOR THE PRODUCTION OF DOMESTIC HOT WATER
SIGNATURFORKLARING:
SE
SE Electronic card
S Automatic vent
M Pressure gauge
VS Vent valve, 3 bar
V Valve
P Pump
SVS
T
P
VD
V
V
T
VE
VD
V
Vsc
VD One-way valve
T Measurement of boiler temperature
VE Expansion tank, 1.5 bar of 6 l
W 3-way motorized valve
SC Plate heat exchanger
F Flow switch
COLD DOMESTIC
M
V
WATER INLET
SYSTEM DELIVERY
VV
SC
V
V
HOT DOME STIC WATER OU TLET
SYSTEM RETURN
R
C Methane gas boiler
B Boiler
BA Storage boiler
RA Radiators
PR Radiant panels
PS Solar panels
A
Add
RARARARA
A Pounding absorber
RP Pressure reduction valve
Vsc Boiler/system discharge valve
Flt System filter
Add Softener
Flt
RP
3.5.4. Heating installation diagram in combination with a boiler (POLAR-NOVA-
ATHOS-ATHOS POWER)
PERFORMANCE:
HEATING WITH STOVE
PRODUCTION OF DOMESTIC
HOT WATER WITH BOILER
230V 50HZ
CONFIGURATION: POLAR / NOVA/ATHOS WITHOUT DOME STIC HOT WATER KIT COMBINED WITH BOILER
HEATING WITH STORAGE SYSTEM PRODUCTION OF DOMES TIC HOT WATER WIT H STORAGE SYSTEM
SIGNATURFORKLARING:
SE
SE Electronic card
S Automatic vent
M Pressure gauge
VS Vent valve, 3 bar
V Valve
P Pump
S
VS
P
VD
V
M
V
T
PRESSURE SAFETY
DISCARGE
T
VE
VD
V
SYSTEM REFILL
V
Vsc
VD One-way valve
T Measurement of boiler temperature
VE Expansion tank, 1.5 bar of 6 l
W 3-way motorized valve
SC Plate heat exchanger
F Flow switch
B
SYSTEM DELIVERY
SYSTEM RETURN
C Methane gas boiler
B Boiler
BA Storage boiler
RA Radiators
PR Radiant panels
PS Solar panels
HOT DOMESTIC WATER OUTLET
R
RP
COLD DOMESTIC
Flt
A
WATER INLET
Add
RARARARA
A Pounding absorber
RP Pressure reduction valve
Vsc Boiler/system discharge valve
Flt System filter
Add Softener
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 3
A
ARA
V
V
INSTALLATION AND USE MANUAL
page
32
3.5.5. Heating installation in combination with a storage tank (POLAR-NOVA-
ATHOS-ATHOS POWER)
R
PS
PERFORMANCE:
HEATING WITH STORAGE SYSTEM
PRODUCTION OF DOMESTIC HOT
C
WATER WITH STORAGE SYSTEM
230V 50HZ
CONFIGURATION: POLAR / NOVA/ATHOS WITHOUT DOMESTIC HOT WATER KIT COMBINED WITH STORAGE SYSTEM WITH BOILER AND SOLAR PANELS
SYSTEM DIAGRAM WITH CLOSED TANK FOR HEATING WITH RADIATORS OR RADIANT PANELS AND FOR THE PRODUCT ION OF DOME STIC HOT WATER
SIGNATURFORKLARING:
SE
S
SE Electronic card
S Automatic vent
M Pressure gauge
VS Vent valve, 3 bar
V Valve
P Pump
HOT DOMESTIC
WATER OUTLET
VS
P
VT
T
VE
VD
V
Vsc
M
VD
V
SYSTEM DELIVER Y
PRESSURE SAFETY
DISCHARGE
SYSTEM RETURN
SYSTEM REFILL
BA
R
A
VD One-way valve
T Measurement of boiler temperature
VE Expansion tank, 1.5 bar of 6 l
W 3-way motorized valve
SC Plate heat exchanger
F Flow switch
C Methane gas boiler
B Boiler
BA Storage boiler
RA Radiators
PR Radiant panels
PS Solar panels
RAR
Flt
Add
A Pounding absorber
RP Pressure reduction valve
Vsc Boiler/system discharge valve
Flt System filter
Add Softener
RP
PR
PR
COLD DOMESTIC
WATER INLET
3.6. OPENING/CLOSING OF ATHOS STOVE DOOR
The Athos stove is equipped with an Allen key for the opening/closing
of the door; just insert the key, exert light continuous pressure towards
the door and rotate the handle (anticlockwise to open and clockwise to
close the door).
The door is closed when the key will not turn any further. It is normal
for this operation to require the key to be turned 180° several times.
ATTENTION!
In order for the stove to operate correctly, it is
essential that the door be closed completely. Turn the
key clockwise until it will clearly not turn any further.
3.7. MAKING THE ELECTRICAL CONNECTIONS
Connect the supply cable first at the rear of the stove and then to an
electrical outlet on the wall.
Figure 12.
rear of the stove should be switched on only when you want to light
the stove.
If you do not intend to use the stove, it is advisable to keep it
switched off.
The main switch located on the
Opening/closing of Athos stove door
Figure 12 – Stove power cable
Installation and assembly Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
INSTALLATION AND USE MANUAL
4. OPERATION
4.1. PRE-LIGHTING WARNINGS
ATTENTION!
Installation is to be made only with connection to a
flue pipe. Therefore, the following evaluation criteria
for identification of installation are to be considered
compliant with standards.
For complex or articulated installations, we
recommend you contact specialized personnel or
authorized MCZ service centres.
MCZ does not recommend other types of installation,
where smoke is not discharged into a flue pipe, and
will not be held liable for any malfunctions or
anomalies.
• Do not touch the stove during the first lighting, as it is
during this phase that the paint sets. If you touch the
paint, you may expose the steel surface.
• If necessary, touch up the paint with the aerosol spray in
the original colour (see the section "Accessories for pellet
stoves").
• It is good practice to provide plenty of ventilation in the
room during the initial lighting, as the stove will give off a
small amount of smoke and smell of paint.
• Do not stay near the stove, and as previously mentioned,
ventilate the room. The smoke and the smell of paint will
vanish after about one hour of operation. There are no
health risks involved.
• Make sure the plumbing system is sealed perfectly and
that there are no leaks or pressure drops.
• Make sure that all cut-off valves between the stove and
the system are open.
• Make sure you have vented all air out of the system
before start-up.
• Make sure that internal devices work properly (flow
switches, thermostats, etc.). Make sure that the
combustion chamber and the flue pipe are clean, and that
the plumbing circuit is free of obstructions.
The stove will be subject to expansion and
contraction during the stages of lighting and cooling
down, and may therefore make slight creaking noises.
This phenomenon is absolutely normal, the structure
being made of sheet steel, and must not be
considered a defect but rather a characteristics.
PELLET STOVES Chapter 4
page
33
The basic settings ensure proper operation and
prevent overheating during the first ignitions.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.2. PRE-LIGHTING CHECK
Check that all the safety conditions described above have been met.
Make sure you have read and completely understood the contents of
this instruction booklet.
Remove all components from the firebox of the stove
and from the door. They may catch fire otherwise. This
includes the instruction booklet and various stickers.
Check that the grate for pellet combustion is correctly positioned, rests
properly on the base, and that it has not moved during handling of the
product.
Check that the electrical connection is correct (230 V 50 Hz), and turn
on the main switch located on the rear panel of the stove.
Check that on the control panel the display is lit up with the message
OFF / "CURRENT TIME".
4.3. LOADING THE PELLETS
page
34
Fuel is loaded from the upper part of the stove by opening a door. Pour
the pellets in the hopper. When empty, it will hold about two 15-kg
sacks.
This is easier if performed in two steps:
•Pour half of the contents into the hopper and wait for the fuel
to settle on the bottom.
•Then pour in the rest
Never remove the protective grille from inside the
hopper. When loading pellets, keep the bag from
coming into contact with hot surfaces.
4.4. CONTROL PANEL
INDEX OF BUTTONS AND INDICATOR LIGHTS
BUTTONS
1. Decrease set temperature / programming functions
2. Increase set temperature / programming functions
3. Scrolling of programming menu to increase/variation of speed
ventilation to increase
4. Scrolling of programming menu to decrease/diagnostics of smoke fan
ventilation to decrease
5. Stove lighting / shutdown
6. Set temperature of air and water thermostats / access programmi ng me nus
INDICATOR LIGHTS
7. General alarm (see specification)
8. Display D1-D2
9. Timer active/inactive indicator light
10. Indicator light that indicates when the thermostat calls for power
11. Water pump active/inactive indicator light
12. Heating system active indicator light
13. Domestic water system active indicator light
14. Heat exchanger in operation indicator light
15. Feed screw active/ inactive indicator light
16. NOT ACTIVE
17. Ignition plug in operation indicator light
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
2
!
5
SET
1
64
TURBO
3
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.5. SETTINGS TO CARRY OUT BEFORE FIRST
LIGHTING
Set the main switch on the rear of the stove to position (I).
The display (8) of the control panel will show the message OFF and the
CURRENT TIME.
If the time shown is not correct, it can be reset by the procedure
described below.
You should keep in mind that the current time is only
needed when you carry out weekly programming
using the TIMER (see corresponding chapter). If the
time is not set correctly, this does not in any way
affect stove operation.
4.5.1. SETTING CURRENT TIME
page
35
2
1
SWITCH
Ut 01
!
SET
64
day 1
3
5
TURBO
In rapid sequence, press the buttons o and p to access technical
parameter
UT02, which shows the hours. Use the buttons
UT01
. If you again press the buttonp , you will access item
n or o to decrease or
increase the hours.
To confirm the hour selected and move on to selection of the minute,
press key
Use keys
To confirm the set time and exit, press
p. (you will see the item
UT03
)
n or o to decrease/increase the minute (steps of 1 minute).
r
4.6. SELECTION OF RECIPE
This is an exclusive MCZ evaluation criteria. It lets the user
identify the type of pellet to be used and as a result to provide
the stove with the most suitable settings. This prevent fuel
waste, ensures expected heating capability and protects the
condition of the product.
RECIPE SELECTION IS TO BE MADE
AT INITIAL INSTALLATION AND ANY
TIME THE TYPE OF PELLET IS
CHANGED.
(E.g. when you change supplier or when you notice differences in
colour or size of the pellets)
4.6.1. OPERATIONS FOR IDENTIFICATION OF THE
RECIPE:
• Identification of type of fuel
2
SET
1
2
SET
1
Sequence to access setting of hours and
minutes.
Ut 02
!
64
16
:
Ut 03
!
64
:
10
3
5
TURBO
3
5
TURBO
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.6.1.1. Identification of type of pellet
To identify the type of fuel:
Requirements:
• Scales (measuring up to ½ kg) with graduations down to 10 g
• MCZ pellet measuring container supplied with stove (PelletBox®)
• A batten
• Pellets (fuel)
Fill the PelletBox® generously with pellets without compacting it
(i.e. without banging the measure on the table or pressing the pellets
down with the hands).
Figure 1
Rest the batten (or ruler, blade or pencil) on the top edge of the
container and level the material by removing the excess.
Weigh the total (container + pellets) and note the weight.
Figure 2
Figure 3
Take the measure, empty it, and look at the table designed for the
selection of the recipe.
Figure 4
4.6.2. Procedure for recipe selection
page
PelletBox®
Figure 1 Figure 2
Figure 3
PelletBox®
36
In the left-hand column, marked 'Weight', identify which row contains
the weight which was noted earlier.
On the same line, identify in the right-hand column of the table the
correct parameter (recipe) for your fuel.
Example:
Suppose you are using fuel that weighs 680 grams.
First of all, identify the model of stove in question (in the example, a
Polar Hydro). Then look at the corresponding table on the face of the
measuring cup. In the “Weight” column, you will see that 680 g is
included in the line “from 660 to 700”.
Moving to the column alongside the one for weight, you will see that
Figure 4
the recipe to be used to programme the stove is C2.
4.6.3. Memorization of recipe on stove.
THE PROCEDURE FOR SELECTING THE RECIPE IS
ACTIVE ONLY WHEN THE STOVE IS NOT LIT.
Press in rapid succession, or simultaneously, the buttons p and q.
The message "ric" will appear, alternating with the number of the
previously set recipe (to recall the previous example, “n C2” will be
2
SET
1
First access to recipe selection menu
2
1
ric
!
64
- - - -
ric
!
SET
64
n C4
shown).
Alternatively, if the display shows the message "- - - -", it indicates that
no recipe is currently selected (first lighting).
To exit from the menu without making changes, press key
p or key
q, or wait 120 seconds without pressing a key.
To modify or set a new recipe, press the buttons
n or o in order to
Phase 1: Example of access to recipe menu
and display of previous setting
2
SET
1
RIC
!
64
n C2
find the desired recipe according to the diagram on the BoxPellet®
(measuring cup). The diagram is reproduced here.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Phase 2: To choose the desired recipe, press
the indicated button
3
5
TURBO
3
5
TURBO
3
5
TURBO
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
To confirm the selection you have made, you must
press the button
shows the time and the message “OFF”.
r until the display once again
The default recipe for the stove is C1, for all versions
and for all countries.
4.7. CONTROL OF WATER TEMPERATURE IN
BOILER
The stove is already set with a series of standard parameters that allow
it to operate properly (water temperature 65°C and ambient
temperature 22°C). However, the user can change these parameters in
the following way:
The following parameters can be set:
T Ambient This is the temperature that you want to attain in the
room where the stove is installed. To adjust it, press
ONCE on the button
values using the buttons
O = Maximum temperature of water in boiler. Upon reaching
T H
2
this temperature, the stove will reduce its performance to
prevent overheating. The default temperature is 65°C
and it can not be set below 40°C or over 80°C.
To adjust it, press TWICE in rapid succession on the
button
buttons
s “SET” and change the values using the
n or o
It is not advisable to set the temperature below
50/55°C so as to prevent the formation of
condensation in the boiler
s “SET” and change the
n or o
System pressure temperature setting
2
SET
1
Setting of ambient temperature
2
SET
1
AM B
!
64
22°C
H2O
!
64
70°C
page
5
TURBO
5
TURBO
37
3
3
4.8. FIRST LIGHTING
You are now ready to light your stove.
The following is a brief description of how to light and extinguish your
stove to satisfy your curiosity and expectations.
4.8.1. Lighting the stove
To light the stove from the panel, press the button r for a few
seconds.
After about 15 minutes, the display (8) will show the ambient
2
SET
1
on
!
64
temperature on the upper display and the water temperature
in the boiler on the lower display. The stove is now LIT.
If you have completed the lighting phase and there is no flame (the
stove is not lit), the display (8) will show the message “Alarm no ignition” accompanied by an intermittent sound alarm. In this case,
turn the stove off by pressing for a few seconds on the button
r.
The display (8) will show the message “Off / current time".
Check the grate. Are there pellets?
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
2
SET
1
Stove on and working at full power
18°C
!
64
43°C
3
5
TURBO
3
5
TURBO
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
If this is the first lighting, the fuel which has to
travel from the hopper to the grate is not arriving in
time or in the properly programmed amount. In this
case the grate will either be empty or will contain
very few pellets.
REMOVE ANY PELLETS FROM THE BURNER AND
REPEAT IGNITION BY PRESSING FOR A FEW
SECONDS ON THE BUTTON
r.
After repeated ignitions, if no flame appears even though there is a
correct supply of pellets, there may be a problem with the components
of the stove or installation may not be correct.
REMOVE THE PELLETS FROM THE BURNER AND
CONTACT AN AUTHORISED MCZ TECHNICIAN.
4.8.2. Extinguishing the stove
page
38
The stove can be extinguished at any time and in any position.
To extinguish the stove, press the key
r for several seconds.
NEVER SHUT THE STOVE DOWN BY CUTTING OFF THE
ELECTRICITY SUPPLY: Always let it complete the
shutdown cycle, otherwise damage could be caused
to the structure, and also problems with lighting in
the future.
4.9. VIEW OF THE FLAMES
In order to get proper operation from the stove, you need to be able to
interpret the appearance of the flame. Characteristics which the user
should take into consideration are basically the following:
• The shape
• The colour
• The character
4.9.1. The shape
In normal combustion the flame should have a tapered shape, a
lively character, with the tips of the flames basically vertical or pushed
towards the back of the firebox. You should get the impression that the
flame is being drawn upwards.
Conversely, a flame which swells outwards at the base, with a thin
character, with a point that appears to wander, could be a symptom of
bad setting as regards loading of the fuel and/or extraction of the
fumes, or could indicate that the flue is obstructed or that there are
down-draughts which impede the proper evacuation of the smoke.
In this case there will ALWAYS be operating problems. Request
assistance from specialized personnel or advice from MCZ technicians.
2
SET
1
OFF
!
64
20 41
:
3
5
TURBO
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.9.2. The colour
The colour is in some ways linked to the shape of the flame. A colour
which varies from orange to yellow, with dark tips to the flame, is liable
to be a swollen flame (as described above), lacking in oxygen or at
least indicative of faulty combustion. As the colour changes towards
light yellow - white, the shape of the flame alters, becoming thinner
and showing the presence of higher levels of oxygen.
4.9.3. The character
Liveliness or weakness is in any case closely connected to the shape of
the flame.
4.10. OPERATION
4.10.1. Operating concept
When you light the stove using the button r, after the initial ignition
phase of about 15 minutes, during which the display (8) shows the
intermediate phases “FAN ACC – LOAD WOOD – FIRE ON“, the stove
will start running in AUTOMATIC mode at medium power, and it will
make a first check of the temperature to be reached.
The ambient temperature is shown on the upper display (8) of the
panel, whereas the temperature of the water in the boiler is indicated
on the lower one alternating with the message H
In this operating mode, you can vary only the desired room
temperature using the buttons
n and o.
The main purpose of the stove is to bring the room
temperature as measured by the thermostat (internal or
external) up to the temperature set by the user.
Then, based on the room temperature, it performs the
following evaluation:
Room temperature < Thermostat temperature ?
• YES
This means that the stove must heat the room. Therefore, it will
begin gradually raising its flame power until it is at its maximum.
• NO
This means that the stove has achieved its objective in heating the
room. Therefore, it will decrease its power to a minimum, and it
will leave it there until the room temperature again drops below
the temperature set in the thermostat, unless the ECO-STO
function is enabled (see paragraph 4.9.3)
For proper operation, it is indispensable for the room
thermostat (internal or external) to measure the
temperature reliably, since the correct operation is
based almost exclusively on the aforementioned
control.
Adjustment of thermostat temperature (temperature to
be reached in the room)
18°C
!
64
43°C
SET
!
SET
64
22°C
3
5
TURBO
3
5
TURBO
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.10.2. Operating modes
The AUTOMATIC mode lets you set a certain temperature to be
reached. In this operating mode the stove will automatically vary the
thermal power provided so as to keep the temperature in the room
constantly at the previously set value.
As previously described, the temperature is adjusted using the buttons
n and o, in steps of 1 degree centigrade.
Also front ventilation, which is active in automatic mode only when the
stove is hot, is divided into 5 speeds. It can be controlled using the
buttons
seconds on the display (8).
This setting will be maintained at the next lighting.
Operating example:
If the ambient temperature measured by the local probe on the stove is
15°C, and the temperature set on the thermostat is 22°C, the stove will
sequentially go to maximum power. Upon reaching the requested fixed
temperature (22°C), the stove will go back to minimum power or it will
enter ECO-STOP mode
It must be remembered however that the temperature keyed into the
thermostat is only indicative, and it is up to the user to find the correct
setting in the location where the stove is installed (for example, to
achieve 22°C in the room, it may be necessary to set the thermostat on
the stove to 20°C). This is because the ambient thermostat is located
near the body of the stove; therefore, it detects the heat radiated from
the stove.
In this mode, lighting and shutdown are performed by the user, by
pressing button
It is advisable to inspect the contents of the hopper from time to time,
to keep the fire from going out due to lack of fuel.
pand q. The speed of the fan will be shown for a few
(See paragraph 4.9.3)
r for a few seconds.
ATTENTION!
If, while the stove is running, conditions occur which
modify the normal state of operation, the general
alarm LED (7) lights up, accompanied by an audible
'beep' (see the paragraph on "Lockout of the stove"),
and the stove reacts by starting the process of
complete shutdown.
page
40
2
SET
1
Adjustment of thermostat temperature (temperature to
be reached in the room)
2
SET
1
Adjustment of the speed of the front fan
2
SET
1
SET
!
64
22°C
AIR4
!
64
22°C
Al ar
!
64
5
TURBO
3
5
TURBO
3
3
5
TURBO
In the event of an electrical power outage during
Stove in alarm and in lockout status
lighting or operation, the stove goes into a cooling-off
stage and later automatically relights itself.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.10.2.1. Internal thermostat - Position of internal room sensor
Only when installation is complete, be sure to check that the
room probe is removed from its place and set far away from
the stove, to prevent it from detecting incorrect temperatures.
The probe is located on the back part of the stove.
When you use the internal thermostat, you should always set a
temperature that is a few degrees higher (for example, if you want to
attain 20°C you should set to 22°C) because the probe is affected by
the heat from the body of the stove.
4.10.2.2. Operation by means of external thermostat
EXTERNAL THERMOSTAT (not included with the stove, to be
provided by the user)
The temperature of the stove can also be controlled by an external
room thermostat. It is located in a central position of the room where
the stove is installed. It provides a closer match between the heating
temperature requested of the stove and what it actually provides.
Internal room probe
page
41
4.10.2.3. Connection of external thermostat
Connect the two wires coming from the wall-mounted thermostat to the
terminal of the MCZ connector.
Insert the connector in the socket located on the back of the stove.
Figure 7
Once the thermostat is connected, you will need to
disconnect the internal thermostat that the stove is
equipped with.
In order to do this, proceed as follows:
• Press the button
o immediately followed by the button p on the
control panel. The display of the control panel will show the
message UT01/OFF
•Press the button
UT16";
“
the display of the control panel shows UT16
•Press and hold the button
to item
“UT20”
•Using the buttons
p repeatedly until the display on the panel shows
q and then press the button p and go
; the display will show the message UT19/OFF
n or o , set this parameter to “ON” or “OFF”. If
it is set to “ON”, the internal thermostat is enabled. Conversely, if it
the parameter is set to “OFF”, the external thermostat is enabled
and the internal one is disabled.
•Therefore, if you need to enable the external thermostat, you will
need to set parameter “UT20” to “OFF”.
To exit the menu, press the button
ror wait 60 seconds
Wiring from
external thermostat
Figure 7 - Connection of the serial connector of the
serial connector of the external thermostat in the socket
on the back of the stove
2
1
External thermostat enabled and internal thermostat
disabled
Ut 20
!
SET
64
OFF
MCZ serial
connector
3
5
TURBO
4.10.3. Setting of ECO-STOP mode
The thermostat manages stove operation by shutting the stove
down once the set temperature is reached and then lighting
again when this is necessary.
You can activate or de-activate this function, or select the intervals with
which the stove is to shut down.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
1st situation: ECO-STOP inactive (default)
If you de-activate this function, when the set temperature is reached,
the stove will continue operating at minimum power until power is
again requested by the thermostat or until the user decides to shut the
stove down manually.
The default setting for the stove is with ECO-STOP deactivated as in the previous example.
2nd situation: ECO-STOP active and time-controlled
If this function is activated, when the set temperature is reached the
stove will go to minimum for a time set by the user, which may be from
1 minute to 30 minutes. During this time, if there is no temperaturerelated request, the stove will then shut down automatically. The stove
will re-light automatically only if the thermostat requests heating.
Example with ECO-STOP active and time-controlled
If the room temperature measured by the thermostat probe (internal or
external) is 15°C and the temperature set on the thermostat is 20°C,
the stove will follow a pre-set ramp-up in power. Once the target
temperature is reached (20°C), the stove will go to minimum power.
The stove will remain in this mode for 15 minutes. If the room
temperature remains above the set temperature, the stove will
automatically shut down temporarily. The message “
Eco Stop
” will be
shown. When room temperature drops below the thermostat set value
(for example 18°C) the stove will prepare for automatic relighting
(“COOL-FIRE”). It will then start operating until a temperature of 20°C
is once again reached.
If the stove is equipped with the kit for the production of domestic hot
water, and hot water is requested for over 30 seconds (by means of
the flow switch), the stove will relight immediately without going
through the aforementioned cooling phases (“COOL-FIRE”)
All automatic relighting operations, either due to a
drop in room temperature or a request for hot water,
are possible if the stove is on or in ECO-STOP mode.
If the user shuts the stove down manually with the
button
r, the stove will not relight automatically
upon variation of the temperature or if hot water is
requested
If there is a kit for the production of domestic hot
water, you should disable the ECO-STOP mode in
order to reduce response times when hot water is
requested.
It must be remembered however that the temperature keyed into the
thermostat is only indicative, and it is up to the user to find the correct
setting in the location where the stove is installed (for example, you
need to set 22°C on the thermostat to attain an actual temperature of
20°C). In this mode, the user can light the stove by resetting the
thermostat to a temperature greater than room temperature, or by
pressing for a few seconds on the button
r.You will go to "Off" mode,
and then the same button is pressed to relight the stove.
page
42
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
k
INSTALLATION AND USE MANUAL
STOVE BEHAVIOUR WITH TIME ACTIVE:
Stove status
Timer intervenes
to…
The stove…
ECO STOP Shut down the stove Shuts down permanently
and turns OFF
ECO STOP Light the stove Remains in ECO STOP
status
page
43
4.10.3.1.
Activation /de-activation of ECO-STOP mode
4.10.3.2. OPERATION TO BE CARRIED OUT BY THE INSTALLER
•Press the main switch on the back of the stove and place it in the
position “I”. The display of the control panel will show the message
OFF/CURRENT TIME
•Press the button
o immediately followed by the button p on the
control panel. The display of the control panel will show the
message UT01/OFF
•Press the button
UT16";
“
the display of the control panel shows UT16/OFF
•Press and hold the button
to item
“UT19”
•Press the button
p repeatedly until the display on the panel shows
q and then press the button p and go
; the display will show the message UT19/OFF
n or oto activate or deactivate the function, or
to change the time of intervention of the ECO-STOP mode. The
display of the panel will show the message UT19/OFF or UT19/1’,
UT19/2’, UT19/3’………. UT19/30’
•Press the button
r for a few seconds to confirm until the panel
shows the message OFF/CURRENT TIME
4.10.4. Programmed mode (with timer)
This operating mode, shown by the indicator light (9) on the display,
lets you programme stove lighting or extinguishing on a weekly basis.
Normally, the POLAR and NOVA stoves have the PROGRAMMED
mode deactivated. (indicator light 9 is off)
The basic characteristics in PROGRAMMED mode are:
• Start day
• Clock
• Programme (4 daily programmes are available)
4.10.4.1.
The current day is set first, and will act as a reference for the
programming sequence. This means you will need to ask yourself: what
day is it today?
Suppose that as you read this paragraph it is Friday. Using the table
shown here (
You will need to assign the stove the starting day of DAY 5.
To set this value, press in sequence buttons
will appear, alternating with the message “OFF”. Now press once
01”
on the button
immediately note that the indicator light (9) of the display is on.
Start day (code on display UT 01)
Figure 8
), you will see that Friday corresponds to DAY 5.
o and p. The code
n and you will see the message “DAY 7”. You will
“UT
2
SET
1
Italiano
Figure 8 – Table of correspondence for days of
wee
Deutsch Francais Espanol
LUN
MAR
MER
GIO
VEN
SAB
DOM
17°C
!
64
63°C
LUN
MAR
MER
JEU
VEN
SAM
DIM
(9)
LUN
MAR
MIE
JUE
VIE
SAB
DOM
MON
DIE
MIT
DON
FRE
SAM
SON
Display
5
TURBO
~
3
English
MON
TUE
WED
THR
FRI
SAT
SUN
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
Press twice more on button n and you will see in sequence the
messages “DAY 6 → DAY 5”.
The display (8) will now show the message “DAY 5” alternating with
the code
“UT 01”.
The same procedure can be implemented using the button
o. The only
difference is that the menu scrolls in the opposite direction as shown:
“OFF →DAY 1→DAY 2→DAY 3→DAY 4→DAY 5”
To memorize the setting, press the button
p.
SUMMARY:
To ACTIVATE the PROGRAMMED mode (indicator light 9 on) press in
sequence the buttons
the buttons
n or o to increase or decrease the start day. To
memorize, press the button
o and p to show the code
p.
“UT 01”
. Then press
ATTENTION!
Any day memorized except for the message “OFF”
activates PROGRAMMED mode.
To DE-ACTIVATE PROGRAMMED mode (indicator light 9 off), press in
sequence buttons
the buttons
pressing the button
o and p to display the code “UT 01”. Then press
n or o until the message “OFF” is shown; confirm by
p.
Only the memorized message “OFF” de-activates the
PROGRAMMED mode.
page
44
Selection of current day and activation of
programmed mode.
2
SET
1
Buttons for menu access.
2
SET
1
Ut 01
!
64
63 °C
Ut 01
!
64
day5
3
5
TURBO
3
5
TURBO
4.10.4.2.
Clock (code on display UT 02 and UT 03)
See paragraph 4.5.1. on time setting to find out how to set the current
time.
The following are the main points.
• Setting of HOURS (code on display UT 02)
Press the buttons
parameter “UT 01”. Use the button
o and p to access the setting menu and
p to access the parameter
“UT02” which corresponds to the time on the clock expressed in
HOURS.
The display (8) will alternately show the code “UT 02” and the
indication of the internal time of the stove present at that moment.
Use the button
To memorize, press the button
n (increase) or o (decrease) to set the hours.
p, which will take you to the next
display, “UT 03”, to set the minutes.
• Setting of MINUTES (code on display UT 03)
The display (8) will alternately show the code “UT 03” and the
current minutes on the clock.
Use the button
To memorize, press the button
n (increase) or o (decrease) to set the minutes.
p. This will take you to the display
of “UT 04”.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page
45
The code “UT 04” is not part of PROGRAMMED mode.
It is to be used only by the installer or a qualified
technician from MCZ by means of an access key.
Press button 3 again to proceed and to display the
code “UT 05”.
4.10.4.3.
Programme
The POLAR, NOVA and ATHOS stoves can run up to 4 operating
programmes distributed over the course of the day or for the entire
week.
Each programme features three basic steps:
•The time the stove comes on (it must be between 00:00
and 23:40)
•The time the stove shuts down (it must be greater than
the start time, up to a maximum 23:50)
•The days in which the lighting or extinguishing of the
stove must be ACTIVATED or DEACTIVATED
Please look at PROGRAMME 1 (summarized in the following table). It
is the first of four programmes in the programming sequence.
PROGRAMME 1
Symbol on display
(8)
Data to be inserted Schedule
PROGRAMME 1
This is step
: setting of stove lighting time.
UT 05
between the message
minutes. Use the keys
of lighting of the stove for this programme. Each time the key is
pressed, the time increases or decreases by 10 minutes. If you hold the
key down, the increase or decrease is gradually faster. This lets you
make large changes rapidly. Once you have set the time you want,
memorize it by pressing the key
the next step,
UT 06
PROGRAMME 1: setting of stove shutdown time.
This is step
UT 06
between the message
minutes. Use the keys
of shutdown of the stove for this programme. Each time the key is
pressed, the time increases or decreases by 10 minutes. If you hold the
key down, the increase or decrease is gradually faster. This lets you
make large changes rapidly. Once you have set the time you want,
memorize it by pressing the key
the next step,
UT 07
PROGRAMME 1: setting of activated or de-activated days.
This is step
the code
UT 07
UT 07
and one of the following: ON 1, OFF 1, ON 2, OFF 2,
UT 05 UT 06 UT 07
Lighting the
stove
Schedule
Shutdown
Days activated or
deactivated
On/Off 1,2,3,4,5,6,7
. The display (8) of the stove panel alternates
UT 05
and a time value expressed in hours and
n (increase) or o (decrease) to set the time
p. This will take you automatically to
.
. The display (8) of the stove panel alternates
UT 06
and a time value expressed in hours and
n (increase) or o (decrease) to set the time
p. This will take you automatically to
.
. The display (8) of the stove will alternate between
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
ON 3, OFF 3, ON 4, OFF 4, ON 5, OFF 5, ON 6, OFF 6, ON 7, OFF 7,
where the numerals refer to the days of the week (see table), ON
means "ACTIVE" and OFF means "INACTIVE". In step
INSTALLATION AND USE MANUAL
UT 07
, the key
page
46
o scrolls the number that refers to the days, and the key n activates
them or deactivates them. Scroll through the days using the key
Then use the key
inactive. After making this setting, memorize it with the key
you will automatically go to
Example Set the times for lighting (7:30) and extinguishing (9:30) for
programme 1. This is step
stove so that it follows this programme on Monday, Wednesday and
Friday.
•Press the key
If you see ON 1, do nothing. If you see OFF 1, press the key
read ON 1 (Monday active).
•Now press once on the key
and again press or not the key
active).
•Press once on the key
or not key
•Press once on the key
or not key
•Press once on the key
or not key
•Press once on the key
or not key
•Press once on the key
or not key
•Finally, press the key
activations of programme 1, and you will go automatically to step
UT 08,
thus entering PROGRAMME 2.
n to establish which days are to be active or
UT 08
.
1 Corresponds to MONDAY
2 Corresponds to TUESDAY
3 Corresponds to WEDNESDAY
4 Corresponds to THURSDAY
5 Corresponds to FRIDAY
6 Corresponds to SATURDAY
7 Corresponds to SUNDAY
UT 07
. Suppose you want to programme the
o, until you come to either position ON 1, or OFF 1.
o to go to position ON 2, or OFF 2
n to read OFF 2 (Tuesday not
o to go to ON 3, or OFF 3 and then press
n to read ON 3 (Wednesday active).
o to go to ON 4, or OFF 4 and then press
n to read ON 4 (Thursday inactive).
o to go to ON 5, or OFF 5 and then press
n to read ON 5 (Friday active).
o to go to ON 6, or OFF 6 and then press
n to read ON 6 (Saturday inactive).
o to go to ON 7, or OFF 7 and then press
n to read ON 4 (Sunday inactive).
p to memorize complete setting of
o .
p, and
n to
PROGRAMME 2
Symbol on display
(8)
Data to be inserted Schedule
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
UT 08 UT 09 UT 10
Lighting the
stove
Schedule
Shutdown
Days activated or
deactivated
On/Off 1,2,3,4,5,6,7
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
This is the second of four available programmes. The methods of
setting are the same as those for the previously described programme.
PROGRAMME 3
Symbol on display
(8)
Data to be inserted Schedule
This is the third of four available programmes. The methods of setting
are the same as those for PROGRAMME 1.
UT 11 UT 12 UT 13
Lighting the
stove
Schedule
Shutdown
Days activated or
deactivated
On/Off 1,2,3,4,5,6,7
PROGRAMME 4
Symbol on display
(8)
Data to be inserted Schedule
This is the last of four available programmes. The methods of setting
are the same as those for PROGRAMME 1.
TO EXIT THE PROGRAMMING SEQUENCE, YOU WILL ONCE
AGAIN NEED TO PRESS BUTTON 3 AFTER YOU COME TO STEP
“UT 16”.
UT 14 UT 15 UT 16
Lighting the
stove
Schedule
Shutdown
Days activated or
deactivated
On/Off 1,2,3,4,5,6,7
page
47
IMPORTANT NOTE
The stove requires about 20 minutes before sufficiently warm
air comes out, and another 10 minutes before it is up to full
power. Take this into account when setting the start time.
Likewise, stove shutdown requires about 30 minutes, during
which the heat stored up by the stove is released into the
room. Keep this in mind for substantial fuel savings.
4.11. EXAMPLE OF PROGRAMMING
Here is a complete example of programming. It refers to a weekly
heating cycle in a home which is always inhabited, with the residents
coming home at lunchtime and in the late afternoon.
On weekdays, heating is desired first thing in the morning, during the
lunch break, and upon returning home from work. On weekends,
heating is to be in operation at all times.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
PROGRAMME 1 (6:30-8:00, Mon. to Fri.)
DESCRIPTION ACTIVATION STEP DISPLAY CONFIRMATION
Entry into programming sequence Key 3 UT 01 Day 1…Day 7..Off
Today is Thursday (Day 4) Button 1 or Butto n 2 UT 01 Day 4 Button 3
It is now six o'clock p.m. ... Button 1 or Button 2 UT 02 18 Button 3
and 12 minutes Button 1 or Button 2 UT 03 12 Button 3
Step not used (for maintenance) UT 04 Button 3
Programme 1: stove lighting time 6:30 a.m. (hot at 7:00 a.m.) Button 1 or Button 2 UT 05 6:30 Button 3
Programme 1: stove shotdown time 8:00 a.m. (cold at 8:30) Button 1 or Button 2 UT 06 08:00 Button 3
Programme 1: active day Monday Button 2 UT 07 ON 1 or OFF 1
Programme 1: active day Monday Button 1 UT 07 ON 1
Programme 1: active day Tuesday Button 2 UT 07 ON 2 or OFF 2
Programme 1: active day Tuesday Button 1 UT 07 ON 2
Programme 1: active day Wednesday Button 2 UT 07 ON 3 or OFF 3
Programme 1: active day Wednesday Button 1 UT 07 ON 3
Programme 1: active day Thursday Button 2 UT 07 ON 4 or OFF 4
Programme 1: active day Thursday Button 1 UT 07 ON 4
Programme 1: active day Friday Button 2 UT 07 ON 5 or OFF 5
Programme 1: active day Friday Button 1 UT 07 ON 5
Programme 1: inactive day Saturday Button 2 UT 07 ON 6 or OFF 6
Programme 1: inactive day Saturday Button 1 UT 07 OFF 6
Programme 1: inactive day Sunday Button 2 UT 07 ON 7 or OFF 7
Programme 1: inactive day Sunday Button 1 UT 07 OFF 7
Programme 1: CONFIRM UT 08 Button 3
page
48
PROGRAMME 2 (11:30 a.m. - 1:00 p.m., Mon. to Fri.)
DESCRIPTION ACTIVATION STEP DISPLAY CONFIRMATION
Programme 2: stove lighting time 11:30 a.m. (hot at 12:00) Button 1 or Button 2 UT 05 11 : 30 Button 3
Programme 2:stove sh u t d own t i m e 1:00 p.m. ( c o l d a t 1 : 3 0 p . m . ) Button 1 or Button 2 UT 06 13 :00 Butto n 3
Programme 2: active day Monday Button 2 UT 07 ON 1 or OFF 1
Programme 2: active day Monday Button 1 UT 07 ON 1
Programme 2: active day Tuesday Button 2 UT 07 ON 2 or OFF 2
Programme 2: active day Tuesday Button 1 UT 07 ON 2
Programme 2: active day Wednesday Button 2 UT 07 ON 3 or OFF 3
Programme 2: active day Wednesday Button 1 UT 07 ON 3
Programme 2: active day Thursday Button 2 UT 07 ON 4 or OFF 4
Programme 2: active day Thursday Button 1 UT 07 ON 4
Programme 2: active day Friday Button 2 UT 07 ON 5 or OFF 5
Programme 2: active day Friday Button 1 UT 07 ON 5
Programme 2: inactive day Saturday Button 2 UT 07 ON 6 or OFF 6
Programme 2: inactive day Saturday Button 1 UT 07 OFF 6
Programme 2: inactive day Sunday Button 2 UT 07 ON 7 or OFF 7
Programme 2: inactive day Sunday Button 1 UT 07 OFF 7
Programme 2: CONFIRM UT 08 Button 3
PROGRAMME 3 (4:30 p.m.-9:30 p.m., Mon. to Fri.)
DESCRIPTION ACTIVATION STEP DISPLAY CONFIRMATION
Programme 3: stove lighting time 4:30 p.m. (hot at 5:00 p.m.) Button 1 or Butt on 2 UT 05 16 : 30 Button 3
Programme 3:stove sh u t d own t i m e 9:30 p.m. ( c o l d a t 1 0 : 0 0 p . m . ) Button 1 or Button 2 UT 06 21 :30 Button 3
Programme 3: active day Monday Button 2 UT 07 ON 1 or OFF 1
Programme 3: active day Monday Button 1 UT 07 ON 1
Programme 3: active day Tuesday Button 2 UT 07 ON 2 or OFF 2
Programme 3: active day Tuesday Button 1 UT 07 ON 2
Programme 3: active day Wednesday Button 2 UT 07 ON 3 or OFF 3
Programme 3: active day Wednesday Button 1 UT 07 ON 3
Programme 3: active day Thursday Button 2 UT 07 ON 4 or OFF 4
Programme 3: active day Thursday Button 1 UT 07 ON 4
Programme 3: active day Friday Button 2 UT 07 ON 5 or OFF 5
Programme 3: active day Friday Button 1 UT 07 ON 5
Programme 3: inactive day Saturday Button 2 UT 07 ON 6 or OFF 6
Programme 3: inactive day Saturday Button 1 UT 07 OFF 6
Programme 3: inactive day Sunday Button 2 UT 07 ON 7 or OFF 7
Programme 3: inactive day Sunday Button 1 UT 07 OFF 7
Programme 3: CONFIRM UT 08 Button 3
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page
49
PROGRAMME 4 (7:30 a.m. - 10:30 p.m. Saturday and
Sunday)
DESCRIPTION ACTIVATION STEP DISPLAY CONFIRMATION
Programme 4: stove lighting time 7:30 a.m. (hot at 8:00 a.m.) Button 1 or Button 2 UT 05 7 : 30 Button 3
Programme 4:stove shutdown time 10:30 p.m. (cold at 11:00
p.m.)
Programme 4: inactive day Monday Button 2 UT 07 ON 1 or OFF 1
Programme 4: inactive day Monday Button 1 UT 07 OFF 1
Programme 4: inactive day Tuesday Button 2 UT 07 ON 2 or OFF 2
Programme 4: inactive day Tuesday Button 1 UT 07 OFF 2
Programme 4: inactive day Wednesday Button 2 UT 07 ON 3 or OFF 3
Programme 4: inactive day Wednesday Button 1 UT 07 OFF 3
Programme 4: inactive day Thursday Button 2 UT 07 ON 4 or OFF 4
Programme 4: inactive day Thursday Button 1 UT 07 OFF 4
Programme 4: inactive day Friday Button 2 UT 07 ON 5 or OFF 5
Programme 4: inactive day Friday Button 1 UT 07 OFF 5
Programme 4: Active day Saturday Button 2 UT 07 ON 6 or OFF 6
Programme 4: Active day Saturday Button 1 UT 07 ON 6
Programme 4: Active day Sunday Button 2 UT 07 ON 7 or OFF 7
Programme 4: Active day Sunday Button 1 UT 07 ON 7
Programme 4: CONFIRM UT 08 Button 3
Button 1 or Button 2 UT 06 22 :30 But ton 3
If a programme is not used, all days of the week relating to that programme must
be set to "OFF"
DESCRIPTION ACTIVATION STEP DISPLAY CONFIRMATION
Programme 4: stove lighting time - NOT USED UT .. ANY Button 3
Programme 4: stove shutdown time - NOT USED UT .. ANY Button 3
Programme 4: inactive day Monday Button 2 UT .. ON 1 or OFF 1
Programme 4: inactive day Monday Button 1 UT .. OFF 1
Programme 4: inactive day Tuesday Button 2 UT .. ON 2 or OFF 2
Programme 4: inactive day Tuesday Button 1 UT .. OFF 2
Programme 4: inactive day Wednesday Button 2 UT .. ON 3 or OFF 3
Programme 4: inactive day Wednesday Button 1 UT .. OFF 3
Programme 4: inactive day Thursday Button 2 UT .. ON 4 or OFF 4
Programme 4: inactive day Thursday Button 1 UT .. OFF 4
Programme 4: inactive day Friday Button 2 UT .. ON 5 or OFF 5
Programme 4: inactive day Friday Button 1 UT .. OFF 5
Programme 4: inactive day Saturday Button 2 UT .. ON 6 or OFF 6
Programme 4: inactive day Saturday Button 1 UT .. OFF 6
Programme 4: inactive day Sunday Button 2 UT .. ON 7 or OFF 7
Programme 4: inactive day Sunday Button 1 UT .. OFF 7
Programme 4: CONFIRM UT .. Button 3
4.12. SAFETY DEVICES
The stove is fitted with the following safety devices:
• PRESSURE SWITCH
Monitors pressure in the smoke duct. It is designed to shut down
the pellet feed screw in the event of an obstructed flue or
significant back-pressure (from the wind).
• SMOKE TEMPERATURE SENSOR
Monitors the temperature of the smoke, and gives permission for
startup or shuts the stove down when the smoke temperature falls
below the preset value.
•BULB TEMPERATURE PROBE OR CONTACT THERMOSTAT IN
THE FUEL HOPPER (KLIXON)
If the temperature exceeds the preset safety level, it immediately
shuts down the running of the stove, and has to be reset manually
before the stove will restart
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
(see paragraph 4.20.3)
.
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
•BULB TEMPERATURE PROBE IN THE WATER TANK
If the temperature exceeds the preset safety level, it immediately
shuts down the running of the stove, and has to be reset manually
before the stove will restart
(see paragraph 4.20.3)
.
• WATER TEMPERATURE PROBE
If the temperature of the water approached shutdown temperature
(85°C), the probe causes the stove to go through a series of
cooling cycles or “ECO-STOP” automatic shutdown to prevent
blocking of the bulb temperature probe as described above.
• ELECTRICAL SAFETY
The stove is protected against violent surges of current by the
main fuse, which is located on the control panel at the rear of the
stove. Other fuses to protect the electronic boards (main board
and heat-exchanger board) are to be found on the boards
themselves.
• SMOKE FAN
If the fan stops, the electronic board shuts off the supply of pellets
in good time, and an alarm message is displayed.
• REDUCTION MOTOR
If the reduction motor stops, the stove will continue to run until
the flame goes out due to lack of fuel and until a minimum level of
cooling is reached.
page
50
• TEMPORARY POWER OUTAGE
After a brief power outage, it automatically goes into cooling
mode.
• FAILURE TO LIGHT
If during ignition no flame develops, the stove will go into alarm
condition.
• ANTI-FREEZE FUNCTION
If the probe in the boiler detects a water temperature of less than
5°C, the circulation pump is automatically activated to keep teh
system from freezing.
• PUMP ANTI-SEIZURE FUNCTION
If the pump is not used for prolonged periods, it is activated
periodically for 10 seconds to keep it from seizing up.
TAMPERING WITH THE SAFETY DEVICES IS
PROHIBITED
Only after eliminating the cause of the intervention of the
safety is it possible to relight the stove and thus restore its
operation. To understand which anomaly has occurred,
consult this manual
to do based on the alarm message the stove displays.
(paragraph 4.10.1)
which explains what
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
g
T
T
g
g
INSTALLATION AND USE MANUAL
Attention!
If the stove is NOT used as described in this instruction
booklet, the manufacturer refuses to accept any responsibility
for damage to persons and property that may arise. The
manufacturer furthermore refuses to accept responsibility for
damage to persons and property arising from the failure to
observe all the rules contained in the manual and in particular
inthe following situations:
•Failure when carrying out works of maintenance,
cleaning and repair to adopt all necessary measures and
precautions.
• Safey devices are removed or tampered with.
• The stove is not connected to a workign, efficient smoke
exhaust system.
• The room of installation is not properly ventilated
• The plumbing system is not compliant with current law in
the country of installation
page
51
4.12.1. Alarm signalling
If an operating anomaly occurs, the stove is equipped with a
computerized monitoring system that informs the user via the display
(8) of the nature of the problem and where it has occurred.
The following table summarises the principal alarms which may be
2
SET
1
ALAR
!
64
indicated
Message on the
display (8)
ALAR DEP FAIL Obstruction of smoke discharge duct or negative pressure
ALAR FAN FAIL Fan speed too low or fan off
ALAR SMOKE PROBE Smoke sensor short circuit Replace smoke sensor
ALAR SAFE FAIL
ALAR HOT TEMP This occurs when the smoke temperature exceeds 180°
ALAR NO ACC Occurs on first failed attempt at lighting If this is the first attempt at lighting, relight or check the
ALAR NO FIRE Occurs when the stove goes out and when the
ALLAR
TEMP.PELLET
caused by wind.
The smoke fan is blocked.
he safety has tripped that controls the pellet hopper.
Overheating has occurred due to a malfunction
for an excessive length of time.
temperature of the smoke sensor is below the preset
threshold.
Pellet hopper temperature exceeds foreseen safety limit.
Overheating of the stove body.
Type of problemSolution
Check and clean the ENTIRE smoke duct, or check that
the wind outdoors is not preventing the release of
smoke. Install a wind cowl.
Check for cleanliness and whether the is slowing the fan.
If cleanin
smoke fan
Check the parameters of the recipe used.
Heat exchanger not working.
he stove is used for too long at maximum operating
power.
Clean the inside of the heat exchanger and run the stove
at full power for shorter periods of time. Also check the
quality of the pellets.
level of pellets in the hopper.
Check the ignition plug.
It is caused when the flame is extinguished due to
clogging or when there are no longer any pellets in the
hopper.
The stove body is too hot because the product has been
operatin
ventilated or the air fans are faulty. Shut down the stove
by pressin
cool. After it has cooled down, the stove can be relit.
does not solve the problem, repalce the
for too long at maximum power, it is poorly
key 5 on the control panel, and wait for it to
3
5
TURBO
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.12.2. Other signals on the display
The following table summarizes that messages that may be shown on the dispaly panel
MESSAGE ON DISPLAY MEANING
off The stove is off
fan acc Initial lighting sequence
load wood Pellet loading
fire on Lighting sequence and adjsutment/stabilizing of flame
Eco Stop The stove automatically shuts down upon reaching the temperature
20 C° Example of room temperature
62 C° Example of water temperature
UT 01, UT02,… user paramters for programming time, time periods, etc.
day1,,,7 Days of the week
set Setting of stove operating mode (e.g. SET MA N = Stove set to m a nual)
Alar fan fail The smoke fan is not operating correctly
stop fire Automatic cleaning of the brazier in the set period of time
mcz spa mcz spa
cool fire The stove is in cooling mode
alar dep fail The pressure switch has tripped, indicating difficulty in smoke expulsion
alarm smoke probe The smoke probe is not working correctly
alar no acc An ignition attempt has failed.
alar no fire There is no fire stove
alar fail sic Thermal alarm Excessive heat in the structure
page
52
4.12.3. Lockout of the stove
The following things can cause the stove to lock out:
• Overheating of the structure and of the pellet hopper
• Overheating of the water in the boiler (T>85°C)
• High pressure in the outlet fumes (as read by the pressure
switch) and therefore possible obstruction of the smoke
discharge system or external back-pressure.
•Pressure in system less than or greater than the minimum or
maximum parameters of operation
The lockout is indicated by the LED (7) lighting up, accompanied by a
beep.
In this situation the shutdown cycle is automatically activated.
Once this process has started, any attempt to reset the system is
useless. The cause of the lockout is shown on the display (8).
4.12.3.1.
The stove goes into a safety ALARM state called “ALAR SIC FAIL” due
to the water temperature being too high.
MANUAL RESET THERMOSTAT
With the stove cold
must unscrew the cap of the thermostatic probe on the back and
press the red button to reset. You will hear a "click" of the
thermostat. Then put the protection cap back in place.
8.
Boiler bulb thermostat
, in order to carry out the manual reset, you
Figure 7 and
Figure 7 - Touche de réarmement de la sonde à
boule
Figure 8 - Comment réarmer le thermostat à
boule une fois que le poêle est froid.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
4.12.3.2.
Pellet hopper safety thermostat
If the pellet hopper overheats, the stove goes into a safety ALARM
state called “ALAR SIC FAIL”.
The MCZ stoves are provided with two types of safety thermostats:
• manual reset
• self-reset
If there are two thermostats (see fig. 7 and fig. 8) on the back of the
stove, near the ON button, then the hopper thermostat is a manual
reset thermostat. If, instead, there is only the hopper safety thermostat
on the back panel, then it is self-resetting. (fig.9).
MANUAL RESET THERMOSTAT
With the stove cold
, in order to carry out the manual reset, you
must unscrew the cap of the thermostatic probe on the back and
press the red button to reset. You will hear a "click" of the
thermostat. Then put the protection cap back in place.
8.
Figure 7 and
SELF-RESETTING THERMOSTAT
In this case the stove is equipped with a self-resetting sensor
which intervenes in case of high temperature.
To cancel the alarm condition, the user must shut down the stove
using the button “5” and wait for the stove body and the hopper to
cool in order to allow the self-resetting of the thermostat (about 20
minutes after the occurrence of the alarm). At this point it is
possible to light the stove again.
4.12.3.3.
•If you see the message “ALAR DEP FAIL”:
Smoke expulsion
check the ENTIRE smoke duct, including the combustion chamber,
to see that they are clean and free of obstructions. (it is
recommended that this operation be conducted by a specialist MCZ
technician).
Only after the cause of the blockage has been permanently
eliminated can a fresh attempt to relight the stove be made.
Manual reset
Self-reset
page
53
4.13. SHUTTING THE STOVE DOWN
The stove can be extinguished at any time and in any position.
NEVER SHUT THE STOVE DOWN BY CUTTING OFF THE
ELECTRICITY SUPPLY:
Always leave it to complete the shutdown cycle,
otherwise damage could be caused to the structure,
2
SET
1
OFF
!
64
20 41
:
and also problems with lighting in the future.
To extinguish the stove, press for a few seconds on the key r.
The display (8) will show the message “OFF”. At this moment the
shutdown cycle begins, in which the pellet loading screw stops, while
the smoke extractor and the hot air exchanger remain on until the
temperature of the stove has dropped.
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
3
5
TURBO
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page
54
The actual shutdown of the stove only occurs 20 - 30 minutes later,
and in any case not before the smoke temperature drops below 50 °C.
This occurs to allow the combustion fumes to be ducted into the flue
pipe by means of the extractor.
It also means that there is total recovery of the heat yielded by
combustion to the structure of the stove.
4.14. DOMESTIC WATER PRODUCTION KIT (optional) For POLAR-NOVA-ATHOS
POWER stoves only
The POLAR and NOVA stoves can also be equipped with a complete kit
for the production of domestic hot water, which is composed of:
• Plate heat exchanger
• 3-way deviator valve
• Flow switch
• Pipes and fittings for connection
The kit is pre-assembled by the manufacturer, MCZ. Its purpose is to
heat domestic water from the water line of the home.
When a hot water faucet is opened, the internal flow meter orders the
deviator valve to send the hot water in the boiler to the plate heat
exchanger. The temperature of the hot water depends a great deal on
the temperature of the heating system. As a guideline, it can be
calculated by subtracting 10°-15°C from the value shown on the control
panel of the stove (temperature of water in boiler).
If the stove is in ECO-STOP status and there is a request for domestic
hot water, 30 seconds after the request the stove automatically starts
the lighting sequence to heat the water in the boiler and then the
domestic hot water.
For long-lasting operation of the plate heat
exchanger, you need to know the water hardness of
your system in order to prevent incrustations.
If the water in your home is very hard, you should
install a water softener upstream (see chapter 3.4.3)
On a yearly basis, you should have the plate heat
exchanger serviced to remove salt and calcium
sediment, or replace the heating plates with new
ones. These spare parts are supplied by MCZ.
Plate heat
exchanger
3-way
deviator
valve
Flow switch
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 5
INSTALLATION AND USE MANUAL
5. MAINTENANCE AND CLEANING
ATTENTION!
All cleaning of all parts must be carried out with the
stove completely cold and unplugged.
The stove does not need much maintenance if used
with certified quality pellets. The necessity for
maintenance increases with use and depending on
the performance requested of it.
5.1. CLEANING TO BE PERFORMED BY THE USER
5.1.1. Cleaning prior to each lighting
Clean the grate with a steel brush, removing any incrustation which could
obstruct the passage of air.
Remember that only a clean, neat grate can ensure
proper operation of your pellet stove.
A simple visual check, carried out daily, will reveal
whether the grate is in good working order.
For good cleaning of the grate, pull it completely out of its housing and
thoroughly clean the grate and holes on the bottom. If you use goodquality pellets, you will normally only need to use a paintbrush to
restore the perfect condition of the component. For tough incrustations,
use the steel tool provided with the stove and a steel brush.
Fig. 1-2
Figure 1 – Example of dirty grate
Figure 2 – Example of clean grate
page
55
5.1.2. Check every 2/3 days
Clean and empty the ash drawers, watching out for hot ash.
Only if the ash is completely cold, it is possible to use a vacuum
cleaner to remove it. Use a drum-type vacuum cleaner that is suitable
for picking up particles of a certain size.
Experience, and the quality of the pellets used, will determine the
frequency of cleaning.
It is however advisable not to let it exceed 2 or 3 days.
When the job is completed, re-close the ash drawers, making sure that
they are properly shut.
Figure 2
5.1.3. Cleaning the glass
For cleaning the ceramic glass, the use of a dry brush is recommended,
or if it is very dirty, the special spray detergent, applying a small
quantity then cleaning with a cloth.
Figure 4
ATTENTION!
Do not spray the product on the painted parts or on
the gaskets of the door (ceramic fibre cord)
Figure 3 - Cleaning of ash collection compartment
Figure 4 - Glass cleaning
Maintenance and cleaning Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 5
INSTALLATION AND USE MANUAL
5.1.4. Cleaning the heat exchanger and the pipe unit
The cleaning of the heat exchanger and the pipe unit is very important
to ensure constantly high performance and heat yield of the stove, as
ensured by MCZ.
It is therefore advisable to:
Every 30 days, with the stove cold, clean the inner walls of the
steel firebox, especially the back, with a scraper, to eliminate
encrustations caused by soot. Incrustations act as insulation. The
thicker they are, the less heat is transferred to the water and the
structure in general.
Every 7 days and with the stove cold clean the internal pipe unit.
To do this, use slight force on the handle located behind the door
above the fire door (behind the upper front ceramic). Push and pull the
handle 5-6 times so that the internal scraper removes the soot
deposited on the pipes.
Constant cleaning of the pipe unit prevents
incrustations on it, and keeps the cleaning device
from clogging and jamming.
Figure 5
page
56
Figure 5 - Cleaning of internal pipe unit with scraper
5.1.5. Cleaning of stainless steel and satin-finish surfaces
Normally these surfaces do not need to be treated, but if they do, avoid
cleaning them with abrasive materials. For surfaces in stainless and
satin brushed steel we recommend cleaning with a paper towel or a
clean dry cloth moistened with a detergent based on non-ionic
surfactants (< 5%). A spray glass cleaner may be used.
5.1.6. Cleaning of painted parts
Do not clean the painted parts with wet rags when the unit is in
operation or hot to prevent thermal shock to the paint which may cause
it to detach. Do not use abrasive or aggressive products or materials.
Clean with damp cotton or paper towels.
The silicon paints used on MCZ products possess technical
characteristics that make them resistant to very high
temperatures.
There is however a physical limit (380°-400°) beyond which
the paint begins to fade or (over 450°) to vitrify; it may then
flake and detach from the steel surface.
If this happens, it means that temperatures have been
reached that are far above those at which the unit should
operate properly.
Maintenance and cleaning Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 5
INSTALLATION AND USE MANUAL
5.2. CLEANING TO BE PERFORMED BY
SPECIALIZED TECHNICIAN
5.2.1. Cleaning of the heat exchanger
With the stove cold, remove the upper side ceramics in majolica to
access the cleaning plugs of the heat exchanger. Open the upper plugs
Figure 6)
(
the fire box so that the ashes drop into the part below.
Still with the stove cold, open the lower door of the ash compartment,
extract the ash drawer, behind which the large cleaning plug is located
Figure 7
(
ash and soot which has built up in the heat exchanger and in the
smoke extraction fan.
Clean the smoke discharge system, especially in the area of the tee
connectors and of any horizontal stretches of pipe.
For information refer to a chimney sweep.
Check the seal of the ceramic fibre gaskets on the door of the stove.
If necessary order new gaskets from your dealer as replacements.
At the end of the season it is necessary to clean the compartment
under the grate and the heat exchanger inside it.
This general cleaning should be carried out at the end of the season in
order to facilitate the general removal of all residues of combustion,
without waiting too long, because with time and humidity these
residues can become compacted.
Using a stiff rod or a bottle brush, scrape the inner walls of
). Open this plug as well. With a vacuum cleaner, remove all
ATTENTION: for your safety, the frequency of
cleaning the smoke discharge system must be
determined on the basis of the use you make of the
stove.
Figure 6 – Lateral plugs for internal cleaning
page
57
5.2.2. Shutting the stove down (end of season)
In the period when the stove is out of use it must be
disconnected from the electricity mains. For greater safety,
especially if there are children around, we recommend
removing the power cable from the rear of the stove.
(Figure 8)
Before placing the stove in storage, you should remove all pellets from
the hopper with a vacuum cleaner with a long extension. If the fuel is
left in the hopper, it may get damp, stick together, and be difficult to
light at the beginning of the next season
If the stove is removed form its place of installation it MUST be
placed in a location that is protected from atmospheric agents.
If pressing the main switch (located on the back of the stove) does not
make the control panel display light up, it could mean that the service
fuse needs replacing.
ATTENTION!
Disconnect the electrical cable.
Maintenance and cleaning Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Figure 7 – Lower plug
Figure 8 – Disconnect the stove from the electrical
mains
PELLET STOVES Chapter 5
INSTALLATION AND USE MANUAL
page
58
On the rear of the stove there is a fuse holding compartment which is
located underneath the supply socket. With a screwdriver open the
cover of the fuse holding compartment, and replace the fuse if
necessary (3.15 AT delayed type).
Figure 9
Plug the unit back in and press the main switch.
Fuse
box
If the problem persists or occurs again, contact your MCZ retailer.
5.3. CHECK OF INTERNAL COMPONENTS
Figure 9 – Switch with fuse box
ATTENTION!
The check of the internal electromechanical
components must be carried out only by qualified
personnel with technical knowledge of electricity and
combustion. If necessary, contact authorized MCZ
retailers.
We recommend that an annual maintenance service is carried out,
preferably under a programmed service contract. The essential part of
this service is a visual and functional check on the following
components:
The following is a summary of the checks and/or maintenance tasks which are indispensable for the correct
operation of the stove.
Parts / interval Every
day
Every
2-3 days
Every
30 days
Every
60-90 days
Every
1 year
Burner ●
Ash drawer ●
Glass ●
Lower exchanger ●
Complete exchanger ●
Smoke duct ●
Ash drawer door gasket ●
Internal parts ●
Flue pipe ●
Circulation pump ●
Plate heat exchanger ●
Plumbing components ●
Electro-mechanical components ●
Maintenance and cleaning Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 6
INSTALLATION AND USE MANUAL
6. PROBLEMS / CAUSES / SOLUTIONS
ATTENTION: All repairs must be carried out
exclusively by a specialised technician, with
the stove completely cold and the electric
plug pulled out.
PROBLEM POSSIBLE CAUSES REMEDY
Pellets not being fed
into the combustion
chamber.
The fire goes out or
the stove stops
automatically.
The stove runs for a
few minutes and
then goes out.
Pellets build up in
grate, door glass
gets dirty and flame
is weak.
1. Pellet hopper empty.
2. Screw feed blocked.
3. Reducing motor for screw feed
faulty.
4. Defective electronic board.
1. Pellet hopper empty.
2. Pellets not being fed in.
3. Intervention of pellet temperature
sensor.
4. Door not closed properly or gaskets
worn.
5. Unsuitable pellets.
6. Low pellet feed rate.
7. Combustion chamber dirty.
8. Smoke outlet obstructed.
9. Pressure switch broken or defective.
10. Smoke extraction motor failed.
1. Lighting cycle not completed.
2. Temporary failure of electricity
supply.
3. Smoke duct obstructed.
4. Temperature sensors defective or
broken.
5. Sparkplug failure.
1. Insufficient combustion air.
2. Pellets damp or unsuitable.
3. Smoke extractor motor broken.
page
59
1. Refill pellet hopper.
2. Empty the hopper and free the feed
screw.
3. Replace reduction motor.
Replace electronic board.
4.
1. Refill pellet hopper.
2. See previous problem..
3. Let the stove cool down completely,
reset the thermostat till lockout
ceases, relight stove; if problem
persists, contact technical assistance.
4. Close the door
with original spare parts
5. Change to a type of pellet
recommended by the manufacturer.
6. Check the recipe and the calibration.
7. Clean the combustion chamber,
following instructions in the manual.
8. Clean the smoke duct.
or replace the gaskets
.
9. Replace the pressure switch.
Check the motor and replace if
10.
necessary.
1. Re-run lighting cycle.
2. See previous instruction.
3. Clean smoke duct.
4. Check and replace sensors as
necessary.
5. Check and replace sparkplug if
necessary.
1. Clean the grate and check that all the
airways are clear.
Carry out a general cleaning of the
combustion chamber and the smoke
duct.
Check that the entry of air is not
obstructed.
Check the state of the door gaskets.
2. Change the type of pellet.
3. Check the motor and replace if
necessary.
Problems / Causes / Solutions Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PROBLEM POSSIBLE CAUSES REMEDY
The smoke
extraction motor
does not work.
1. No electrical supply to the stove.
2. The motor is broken.
3. Defective motherboard.
4. Control panel broken.
PELLET STOVES Chapter 6
INSTALLATION AND USE MANUAL
1. Check the supply voltage and the
protection fuse.
2. Check the motor and capacitor and
replace if necessary.
3. Replace electronic board.
Replace the control panel.
4.
page
60
The convection air
fan runs
continuously.
In the automatic
position the stove
always runs at full
power.
The stove does not
run
1. Temperature sensor defective or
broken.
2. Fan broken.
3. Silencer card of fan defective
1. Thermostat set to minimum
2. Room thermostat in position that
always detects cold.
3. Temperature sensor defective.
4. Control panel defective or broken.
1. Lack of electricity supply.
2. Pellet sensor in lockout.
3. Fuse blown.
4. Pressure switch broken (lockout
indicated).
5. Smoke outlet or duct blocked.
1.
Check the operation of the sensor
and replace if necessary.
Check the operation of the motor
2.
and replace if necessary.
Replace silencer card
3.
1. Reset the thermostat temperature.
2. Change the position of the probe
3. Check the operation of the sensor
and replace if necessary.
4.
Check the panel and replace if
necessary.
1. Check that the electric socket is
plugged in and that the main switch
is in position “I”.
Clear lockout by resetting the rear
2.
thermostat,
if it happens again.
3. Replace the fuse.
4. Replace the pressure switch.
5. Clean the smoke outlet and/or
smoke duct.
replace the thermostat
ANOMALIES RELATED TO THE PLUMBING CIRCUIT
PROBLEM POSSIBLE CAUSES REMEDY
No increase in
temperature with
stove in operation
Condensation in
boiler
Problems / Causes / Solutions Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
1. Incorrect combustion adjustment.
2. Boiler / system dirty.
3. Insufficient stove power.
4. Poor pellet quality
1. Incorrect temperature setting.
2. Insufficient fuel consumption.
1. Check recipe and parameters.
2. Check and clean the boiler.
3. Check that the stove is properly
sized for the requirements of the
system.
4. Use MCZ pellets
1. Set the stove to a higher
temperature.
Check the recipe and/or technical
2.
parameters.
PELLET STOVES Chapter 6
PROBLEM POSSIBLE CAUSES REMEDY
INSTALLATION AND USE MANUAL
page
61
Radiators cold in
winter
High variability of
temperature of
domestic hot water
Little domestic hot
water is provided
Hot water is not
provided
1. Room thermostat (local or remote)
2. Circulator does not run because
3. Circulator does not run.
4. Radiators have air in them
1. Water flow rate too low.
1. Insufficient mains pressure
2. Tap or mixer clogged with limescale
3. Water group clogged
1. Circulator (pump) blocked
set too low. If remote thermostat,
check if it is defective.
blocked.
1. Set to higher temperature or
replace. (if remote)
Free up the circulator by removing
2.
the plug and turning the shaft with a
screwdriver.
Check the electrical connections of
3.
the circulator; replace if necessary.
Vent the radiators
4.
1. Increase the water flow rate
(minimum 3 litres per minute)
1. Check the calibration of the
pressure reducer.
Install and autoclave
2.
Check and clean
3.
Clean or replace the plate heat
4.
exchanger
1. Free the circulator (pump)
ATTENTION!
The operations
specialised MCZ personnel.
The manufacturer refuses to accept any responsibility
and the guarantee lapses if this condition is not
respected.
in italics
must be carried out by
Problems / Causes / Solutions Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 7
INSTALLATION AND USE MANUAL
page
62
7. ELECTRICAL DIAGRAMS
7.1. ELECTRICAL DIAGRAM OF POLAR-NOVA-ATHOS POWER Hydro WITH NO
DOMESTIC HOT WATER KIT
4
2
3
1
21
20
22
25
26
17
18
19
5
10
11
12
8
6
7
9
14
13
15
12
16
24
23
1. PROGRAMMING
2. MOTHERBOARD
3. CONSOLE
4. WARM AIR FAN
5. NEUTRAL
6. ABOUT 230V
7. PHASE
8. SMOKE FAN
9. EXCHANGER
10. RESETTABLE PELLET SAFETY
11. PRESSURE SWITCH
12. SPARKPLUG
13. FEED SCREW
14. SMOKE SENSOR
15. SMOKE EXHAUST FAN
11
16. GEARMOTOR
17. SMOKE SENSOR RED +
18. BLUE -
19. EXTERNAL THERMOSTAT
20. ROOM TEMPERATURE SENSOR
21. H2O PROBE
22. TEMPERATURE PROBE
23. SERIAL CONNECTOR
24. PUMP
25. KLIXON
26. BULB THERMOSTAT
LIVE ELECTRICAL
CABLES
ELlectrical Diagrams Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 7
INSTALLATION AND USE MANUAL
page
63
7.2. ELECTRICAL DIAGRAM OF POLAR-NOVA-ATHOS POWER Hydro WITH
DOMESTIC HOT WATER KIT
3
2
1
6
7
8
9
10
13
11
5
28
27
26
4
22
23
25
24
17
16
18
19
20
21
15
16
12
13
14
1. SERVICES CARD
2. MOTHERBOARD
3. WARM AIR FAN
4. PROGRAMMING
5. CONSOLE
6. NEUTRAL
7. ABOUT 230V
8. PHASE
9. SMOKE FAN
10. EXCHANGER
11. SMOKE SENSOR
12. SMOKE EXHAUST FAN
LIVE ELECTRICAL
CABLES
17. RESETTABLE PELLET SAFETY
18. SMOKE SENSOR RED +
19. BLUE -
20. EXTERNAL THERMOSTAT
21. ROOM TEMPERATURE SENSOR
22. H2O PROBE
23. TEMPERATURE PROBE
24. BULB THERMOSTAT
25. KLIXON
26. SERIAL CONNECTOR
27. DOMESTIC WATER KIT
28. PUMP
13. SPARKPLUG
14. GEARMOTOR
15. FEED SCREW
16. PRESSURE SWITCH
ELlectrical Diagrams Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
PELLET STOVES Chapter 7
INSTALLATION AND USE MANUAL
page
7.3. WIRING DIAGRAM for ATHOS Hydro without DOMESTIC HOT WATER KIT
3
4
5
6
64
1
2
7
8
19
18
17
16
22
13
23
21
15
8
11
12
9
14
LIVE ELECTRICAL
CABLES
1. CONSOLE
2. PROGRAMMING
3. MOTHERBOARD
4. NEUTRAL
5. ABOUT 230V
6. PHASE
7. RESETTABLE PELLET SAFETY
8. PRESSURE SWITCH
9. SPARKPLUG
15. TEMPERATURE PROBE
16. H2O PROBE
17. ROOM TEMPERATURE SENSOR
18. EXTERNAL THERMOSTAT
19. BLUE -
20. SMOKE SENSOR RED +
21. BULB THERMOSTAT
22. KLIXON
23. SERIAL CONNECTOR
10. FEED SCREW
11. SMOKE SENSOR
12. SMOKE EXHAUST FAN
13. PUMP
14. GEARMOTOR
ELlectrical Diagrams Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
MCZ S.p.A.
Via Guglielmo Oberdan n°86
33074 Vigonovo di Fontanafredda (PN) – ITALY
Telephone: 0434/599599 r.a.
Fax: 0434/599598
Internet: www.mcz.it
e-mail: mcz@mcz.it
8900902200 Rev 0 04/2009
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.