Contents
Parts List Revision History ............................................................................................................................. 3
Unit Nomenclature
Model Number Nomenclature ........................................................................................................................ 4
Serial Number Nomenclature ......................................................................................................................... 4
Model Number- Complete ........................................................................................................................ 5- 10
Main Control Box ...................................................................................................................................... 12
Liquid Line ........................................................................................................................................... 40, 41
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 2
Parts List Revision History
Revision Date Description
NEW 10/11 New
A 11/11 Page 10: Removed System Memory Bub #5 p/n: 300047100. Duplicate of CB p/n.
B 12/11 Page 24: Changed Ref #302 Discharge Hsg. p/n from 331553802 to 331553803.
C 01/12 Page 10: Changed Ref #8 300047103 to 333568101; Ref #9 300047104 to 333568201; Ref #11 300047105 to 333568301; Ref #13 300047106 to 333568401.
Page 11: Deleted duplicate Bub #11. Added new Bub #1 for 2nd VFD fan. Change Ref #5, 6 qty. from 1 to 2.
Page 25: Switched Bub #s 204 & 205 to correct locations on upper right dwg.
D 03/12 Cover & Page 3: Updated to Daikin McQuay logo format.
Page 13: Added Harness p/n 331795502 & dwg. Updated TOC.
Page 28: Added Relief Valve dwg. and updated main unit dwg. to current revision.
Page 29: Changed qty. of Ref # 020 from 2pc. to 1pc. Changed Ref 021 S/O valve from 735039977 to
332422302. Added footnote #3.
Page 41,47: Updated Water Box dwg. Removed component Bubs, except for gaskets. Renumbered Bubs.
Page 42- 44, 48, 49: Removed Water Box components except gaskets. Updated Water Box gaskets to
reflect change to 2pc. design Ref #352 & 366. Renumbered bubs to match Water Box dwg. Added
footnotes.
Page 45: Removed Water Box components except gaskets. Updated Water Box gaskets to reflect change
to 2pc. design Ref #352 & 366. Renumbered bubs to match Water Box dwg. Added footnotes. Added
p/ns for Ref #350, 351 to 3 Pass Flanged Standard Head table.
E 03/12 Page 5- 8 : Updated Code Nomenclature to R33369901 Rev 0A.
Page 9, 10 (NEW): Added 2 pages for additional codes. Repaginated form and updated TOC.
Page 46, 50 (OLD), 48, 52 (NEW): Deleted the Tube Count table. Added note to refer to Nomenclature
section. Re-numbered footnotes as needed.
F 05/12 Page 12: Changed BACNet kit from 332356901 to 332356951, Lon Kit from 332356902 to 332356952,
Modbus kit 332356903 to 332356953.
Page 28: Deleted original footnote #1. Renumbered remaining footnote.
Page 29: Deleted page of IGV actuator detail for 331553401. Repaginated form and updated TOC.
G 5/12 Page 31, 32: Deleted Knockdown kit p/n 332356112 and related footnote information.
H 6/12 Various: Changed "McQuay Parts" to "Daikin McQuay Parts"
Page 40: Added Bub #140 for complete Exp. Valve Assy.
Page 41: Added complete assy p/n 333271501 and corrected Ref #140A Body p/n from 333271501 to
3331552502.I 7/12 Page 5- 10: Updated Coding to Rev. B.
Page 15: Added Snubber Capacitor p/n 300048940, qty. of 6.
J 8/12 Page 25: Changed Impeller Seal ref # 502 from 332027501 to 332027502.K 8/12 Page 13: Added KAIC ratings to ref #8, CBKR. Re-arranged order of ref #8 per KAIC rating.
E3012= Evaporator, 30" Diameter/12' Long; E3612= Evaporator, 36" Diameter/12' Long
9. Evaporator Tube Count / Tube Type
First Digit= Tube Count; 3/4" Diameter Tube
30" Diameter: B= 300; C=262; X=Special
36" Diameter: B= 488; C= 414; D= 352; X= Special
First Digit= Tube Count; 1" Diameter Tube
30" Diameter: E= 178; F= 149; X= Special
36" Diameter: E= 271; F= 243; G= 209; X= Special
First Digit= Tube Count; Mixed Diameter Tube
30" Diameter: J= 155; K= 127; X= Special
36" Diameter: J= 244; K= 215; M= 179; X= Special
Second Digit= Tube Type
E= Turbo EHP .025 Wall, 3/4"; F= Turbo EHP .028 Wall, 3/4"; Q= Turbo EHP .035 Wall, 3/4"; T= TC SS 28FPI .028 Wall, 3/4";
Z= TC Titanium 32FPI .028 Wall, 3/4"; G= CU Turbo .025 Wall, 1"; D= CU Turbo .028 Wall, 1"; H= CU Turbo .035 Wall, 1";
X= Special
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 5
Nomenclature
Model Number- Complete, Continued
10. Evaporator Head / Waterbox Description
First Digit= Number of Water Passes
1= 1 Pass; 2= 2 Pass; 3= 3 Pass; X= Special
Second Digit= Inlet Nozzle Location
L= Left; R= Right
Third Digit= Nozzle Configuration
A= Dished Head Victaulic; B= Dished Head Flanged; C= Waterbox Top Victaulic; E= Waterbox Top Flanged;
G= Waterbox Rear Victaulic; H= Waterbox Rear Flanged; X= Special
11. Evaporator Design Pressures
C1= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 150 PSIG ASME
C2= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 250 PSIG ASME
C3= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 350 PSIG ASME
C4= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 150 PSIG Non-ASME
C5= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 300 PSIG Non-ASME
XX= Special
12. Evaporator Leaving Water Temperature
Code is listed in tenths of °F. (Example: 0440= 44.0 °F)
13. Evaporator Tube Sheet & Head Material
First Digit= Tube Sheet Material
C= Carbon Steel
N= Monel Clad
S= Stainless Steel Clad
T= Titanium Clad Steel
X= Special
Second Digit= Head Material
C= Carbon Steel
E= Epoxy Coated
X= Special
14. Tube Cleaning System
Y= None
15. Evaporator Revision Level
A= Revision A; B= Revision B
16. Condenser Shell Diameter & Length
C2612= Condenser, 26" Diameter/12' Long
C3012= Condenser, 30" Diameter/12' Long
C3612= Condenser, 36" Diameter/12' Long
17. Condenser Tube Type & Count
First Digit= Tube Count; 3/4" Diameter Tube
30" Diameter: B= 300; C=262; X=Special
36" Diameter: B= 488; C= 414; D= 352; X= Special
First Digit= Tube Count; 1" Diameter Tube
26" Diameter: E= 268; F= 232; X= Special
30" Diameter: E= 339; F= 295; G= 265; X= Special
36" Diameter: E= 534; F= 480; G= 417; X= Special
First Digit= Tube Count; Mixed Diameter Tube
26" Diameter: E= 268; F= 232; X= Special
30" Diameter: E= 339; F= 295; G= 265; X= Special
36" Diameter: E= 534; F= 480; G= 417; X= Special
Second Digit= Tube Type
L= Turbo CSL .025 Wall, 3/4"; N= Turbo CSL .028 Wall, 3/4"; P= Turbo CSL .035 Wall, 3/4";
T= TC SS 28FPI .028 Wall, 3/4"; Z= TC Titanium 32FPI .028 Wall, 3/4"; 1= 90-10 CU-NI .028 Wall, 3/4";
4= 90-10 CU-N .035 Wall, 3/4"; A= CU Turbo .025 Wall, 1"; B= CU Turbo .028 Wall, 1"; C= CU Turbo .035 Wall, 1";
X= Special
Digits 3 & 4
YY= None; XX= Special
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 6
Nomenclature
Model Number- Complete, Continued
18. Condenser Head / Waterbox Description
First Digit= Number of Water Passes
1= 1 Pass; 2= 2 Pass; 3= 3 Pass; X= Special
Second Digit= Inlet Nozzle Location
L= Left; R= Right
Third Digit= Nozzle Configuration
A= Dished Head Victaulic; B= Dished Head Flanged; D= Waterbox Top Victaulic; F= Waterbox Top Flanged;
G= Waterbox Front Victaulic; H= Waterbox Front Flanged; X= Special
19. Condenser Design Pressures
C1= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 150 PSIG ASME
C2= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 250 PSIG ASME
C3= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 350 PSIG ASME
C4= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 150 PSIG Non-ASME
C5= Refrigerant Side Pressure: 200 PSIG; Waterside Pressure: 300 PSIG Non-ASME
XX= Special
20. Maximum Condenser Leaving Water Temperature
Code is listed in tenths of °F. (Example: 1050= 105.0 °F)
21. Condenser Tube Sheet & Head Material
First Digit= Tube Sheet Material
C= Carbon Steel
N= Monel Clad
S= Stainless Steel Clad
T= Titanium Clad Steel
X= Special
Second Digit= Head Material
C= Carbon Steel
E= Epoxy Coated
X= Special
22. Condenser Tube Cleaning System
Y= None
23. Condenser Model Revision
A= Revision A; B= Revision B
24. Pressure Vessel Code
A= ASME; C= PED; P= Chinese; 1= British Columbia; 2= Alberta; 3= Saskatchewan; 4= Manitoba; 5= Ontario; 6= Quebec;
7= New Brunswick; 8= Nova Scotia; 9= Prince Edward Island; 0= Newfoundland; U= Yukon
25. Refrigerant Type
134= R134A Refrigerant
26. Refrigerant Weight
Total Refrigerant weight (lbs.) divided by 10 rounded to the next whole number. (Example: 815/10= 81.5, Round up to 082)
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 7
Nomenclature
Model Number- Complete, Continued
31. Controls Options
YYYY= None
32. Insulation
First Digit= Condenser & Evaporator Shell Insulation
H= ¾" Closed Cell Foam Insulation
3= 1½" Closed Cell Foam Insulation
Y= None
X= Special
Second Digit= Condenser & Evaporator Head Insulation
1= Return Head(s) Only
2= Return & Connection Heads
Y= None
X= Special
33. Water Flow Indication
B= Evaporator & Condenser Flow Control; X= Special
34. Paint
1= Standard Paint; X= Special
35. Packaging
2= Open Export Crate; 3= Totally Enclosed Export Crate; 4= Shipping Bag with Standard Wood Skid;
6= Shipping Bag with Totally Enclosed Export Crate; 7= Shipping Bag with Open Export Crate; X= Special
36. Refrigerant Tag
A= Full Factory Charge; N= Holding Charge, Nitrogen; X= Special
37. Special Features
M= Stock Modification; Y= None; X= Special
38. Not a WME Code Item
Y= None
39. Knockdown Option
1= Compressor & VFD removed, run tested, Nitrogen holding charge; 2= Full Knockdown option, Nitrogen holding charge;
3= Refrigerant in Compressor, Full Factory charge; Y= None; X= Special
40. Testing
Y= None
1= Run test only
2, 9, A, B, C, D, E, F, G, H, J, Q, S= Various Witness Tests
3, 4, 5, 6, 7, K, L, M, N, P, R, T= Various Certified Performance Tests
8= Non certified Sound Test
X= Special
0000= Data Calculated from Selection Program (Example: 0150= 150 Tons)
44. Startup
U= Domestic Startup; 7= Canadian Startup; Y= Export, No Startup
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 8
Nomenclature
Model Number- Complete, Continued
45. First Year Warranty
Y= Entire Unit Parts + Labor (Standard); C= Entire Unit Parts + Compressor Labor Only; P= Entire Unit Parts Only (Export standard)
46. Extended Warranty
(Codes C thru K apply to Parts and/or Labor for the complete unit.)
C= Extended 1 year parts; D= Extended 1 year parts + Labor; E= Extended 2 year parts; F= Extended 2 year parts + Labor;
G= Extended 3 year parts; H= Extended 3 year parts + Labor; J= Extended 4 year parts; K= Extended 4 year parts + Labor;
(Codes L thru S apply to the Compressor & Drive Train Only.)
L= Extended 1 year parts; M= Extended 1 year parts + Labor; N= Extended 2 year parts; O= Extended 2 year parts + Labor;
P= Extended 3 year parts; Q= Extended 3 year parts + Labor; R= Extended 4 year parts; S= Extended 4 year parts + Labor;
Y= None; X= Special
LL= Short Circuit Current Rating 25KA (use with 575V); ST= Short Circuit Current Rating 35KA;
MH= Short Circuit Current Rating 50KA (use with 575V); HH= Short Circuit Current Rating 65KA
VH= Short Circuit Current Rating 100KA; XX= Special
62. VFD input RLA Compressor 1
0000= Data Calculated from Selection Program
63. VFD input RLA Compressor 2
0000= Data Calculated from Selection Program (always 0000 unless Code 03= D)
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 9
0000= Data Calculated from Selection Program (always 0000 unless Code 03= D)
75. Starter Special
Y= None; X= Special
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 10
Electrical Legend
Sch. Sym. Description Location
BAS Communication Card Main Control Box
CB1 Circuit Breaker- TX2 Primary VFD Power Supply Plate
CB2- 4 Circuit Breaker- Fans VFD Power Supply Plate
CB4 Circuit Breaker- MCB Trip, Power Meter, ELR, Solenoid VFD Power Supply Plate
CFT1- CFT2 Cooling Fan Control VFD Power Supply Plate
CT1- 6 Current Transducers VFD Chassis
CPU Main Control Board Main Control Box
D1 Diode VFD Chassis
ES Switch- Ethernet Main Control Box
ELR Relay- Earth Leakage VFD Power Supply Plate
EMC EMC Filter VFD Enclosure
EXV1 Electronic Expansion Valve #1 Liquid Line
EXV2 Electronic Expansion Valve #2 Liquid Line
F1- F2 Fuse- Controls Transformer, 2A 600VAC VFD Power Supply Plate
F3- F5 Fuse- IPS, 6A 600VAC VFD Power Supply Plate
F6- F7 Fuse- 150VDC to DC Power Supply, 10A 600VAC VFD Power Supply Plate
F8- F10 Fuse- Power Meter, 10A 600VAC VFD Power Supply Plate
INPUT I/O Board Main Control Box
IPS Intermediate Power Supply VFD Enclosure
L1- 3 Chopper Chokes/Inductors VFD Chassis
LCD LCD Touch Screen Monitor (OITS) Evaporator
LR Line Reactor VFD Enclosure
MCB Main Circuit Breaker VFD Enclosure
P1- P14 DC Power Distribution Terminals VFD Power Supply Plate
PM Power and Current Meter VFD Power Supply Plate
PS2- PS4 Power Supply- VFD VFD Power Supply Plate
PS5 Power Supply- Chiller I/O VFD Power Supply Plate
PS6 Power Supply- Compressor I/O VFD Power Supply Plate
PS7- PS8 Power Supply- Magnetic Bearings VFD Power Supply Plate
Q1- 3 Chopper/IGBT Driver VFD Chassis
Q4- 6 Steering Bridge IGBT VFD Chassis
R1- 4 Resistors VFD Chassis
S01 Sensor- Evaporator Entering Water Temperature Evaporator Inlet
S02 Sensor- Evaporator Leaving Water Temperature Evaporator Outlet
S04 Switch- Evaporator Entering Flow Evaporator Inlet
S05 Sensor- Condenser Entering Water Temperature Condenser Inlet
S06 Sensor- Condenser Leaving Water Temperature Condenser Outlet
S07 Sensor- Condenser Refrigerant Pressure Condenser
S08 Switch- Condenser Entering Flow Condenser Inlet
S09 Sensor- Liquid Line Temperature Liquid Line
S10 Sensor- Compressor Suction Temperature Compressor
S11 Sensor- Compressor Suction Pressure Compressor
S12 Sensor- Compressor Discharge Temperature Compressor Discharge Housing
S13 Sensor- Compressor Discharge Pressure Compressor Discharge Housing
S14 Sensor- Motor Gap Temperature Compressor
S15 Switch- High Pressure Discharge Piping
SW1 Switch- Compressor #1 Main Control Box
SW3 Switch- Remote Start/Stop Remote Mounting
SW4 Switch- Mode Remote Mounting
SW5 Switch- Unit Enable Main Control Box
TDM1- 3 Diode/Thyristor Module VFD Chassis
TS1 Thermal Switch VFD Chassis
TH1, 2 Thermistors VFD Chassis
TX2 Transformer- 480/240/120 VAC, 500A VFD Power Supply Plate
VFD1 VFD Chassis Assembly VFD Enclosure
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 11
24
Controls
Main Control Box
Communication Card
Location
4
7
9
8
18
15
Ref. Schem.
No. Sym. Description Part No. Qty.
4 Board- Chiller I/O Backplane 300047099 1
7 CPU Board- Chiller Controller 300047102 1
N/S Connector, Chiller Controller, Beige 300048948 21
N/S Connector, Chiller Controller, Orange 300048949 4
8 Board- Digital I/O 333568101 1
9 Board- Analog Output 333568201 1
11 Board- IGV Stepper Motor 333568301 1
13 Board- Analog Input 333568401 2
15 Cable- Touch Monitor Power 300047108 1
18 SW5 Switch- Unit Enable 300047109 1
24 SW1 Switch- Unit and Compressor #1 300047110 2
N/S BAS BACnet MS/TP/E Installation Kit 1 332356951 1
N/S BAS Lonmark Installation Kit 1 332356952 1
N/S BAS Modbus Installation Kit 1 332356953 1
N/S= Not Shown on Diagram.
1
Includes the Communication Card and Installation Manual.
13
11
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 12
Controls
VFD Enclosure
1
3
1
8
7
3
10
4
11
5
6
Ref. Schem.
No. Sym. Description Part No. Qty.
1 Fan 120 VAC 600 CFM 300047091 2
3 VFD1 VFD Chassis Assembly- Phases 1- 3 1 300047093 1
4 Fuse 20A/1000VAC 300047094 2
5 Coil- Solenoid 120/60, 10 watt 300047095 2
6 LR Line Reactor 3PH 300047096 2
7 IPS Intermediate Power Supply 300047097 1
8 MCB CBKR Molded Case 25KAIC 600V 400A 300048927 1
CBKR Molded Case 25KAIC 600V 600A 300048929 1
CBKR Molded Case 35KAIC 480V 500A 300047098 1
CBKR Molded Case 35KAIC 600V 500A 300047071 1
CBKR Molded Case 35KAIC 600V 600A 300047100 1
CBKR Molded Case 35KAIC 600V 800A 300048924 1
CBKR Molded Case 50KAIC 600V 400A 300048928 1
CBKR Molded Case 50KAIC 600V 600A 300048930 1
CBKR Molded Case 65KAIC 600V 500A 300047088 1
CBKR Molded Case 65KAIC 600V 600A 300047108 1
CBKR Molded Case 65KAIC 600V 800A 300048925 1
CBKR Molded Case 100KAIC 480V 400A 300047069 1
CBKR Molded Case 100KAIC 480V 600A 300048923 1
CBKR Molded Case 100KAIC 480V 800A 300048926 1
10 Surge Suppressor 480V 300047076 1
11 VFD1 VFD Chassis Assembly- Phases 4- 6 1 300048873 1
1
Refer to VFD Chassis Assembly detail on the following pages.
2
This chassis is present ONLY when Code 04= M3.
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 13
Controls
VFD Chassis- Diagrams
1
4
3
2
15
5
12
6
13
14
7
13
8
11
WME0700S- Water Cooled Chiller Rev. K 08/12 RPL 700022800 / Page 14