Compressor Removal and Re-Attachment ........................................................................... 63
Compressor Removal and Re-Attachment ........................................................................... 64
Recognize Safety Symbols, Words, and Labels
The following label is used in this manual to indicate immediate or potential hazards. It is the
responsibility of the owner and i nst all er t o read a nd comply with all safet y information and inst ruct ions
accompanying these symbols. Improper installation, operation and maintenance can void the warranty.
Dangers indicate a hazardous situation which will result in death or serious injury if not
avoided.
Warnings indicate potentially hazardous situations, which can result in property damage,
severe personal injury, or death if not avoided.
Cautions indicate potentially hazardous situations, which can result in personal injury or
equipment damage if not avoided.
™® The following are trademarks or registered trademarks of their respective companies: Magnitude, MicroTech E, from
McQuay Internation al, Victaulic from Victaulic Company
2 Field Installation Procedure IM 1128-1
WSC Chiller Introduction
It is estimated that fifty percent of retrofit applications require partial or complete disassembly of the
chiller. Daikin McQuay offers three solutions to the disassembly and reassembly effort on Model
WSC, single compressor centrifugal chillers.
TYPE I: The compressor is removed and put on a skid. All associated wiring and piping possible will
remain on the vessel stack. The remaining loose parts will be packaged in a separate crate.
1. Block-offs will cover all openings on the compressor and vessels.
2. The compressor and vessels will receive a 5-psi helium holding charge.
3. The compressor will not be insulated at the factory. An insulation kit will be shipped with the unit.
4. The starter will ship loose. Bracket and cable kit to be included for unit-mounted starters and/or
cableway for mini-cabinet starters.
5. The evaporator will be insulated at the factory.
6. Refrigerant will not be shipped with the unit and must be secured locally and furnished and
installed by the installer.
7. Lubricant will be shipped in containers from the factory for field installation.
8. All field piping connections will be Victaulic, O-ring face seal or copper brazing.
9. All free piping ends will be capped.
10. Touch-up paint will be included.
11. The unit will undergo the rigorous, full Daikin McQuay test program at the factory.
12. Contact local McQuay Factory Service for pricing and scheduling of required installation
supervision.
TYPE II: The compressor with its terminal box is removed and placed on a skid. The condenser,
evaporator, oil pump, oil cooler and tube sheet supports will remain connected only by their attachment
bolts, ready for field disassembly and reassembly in the building. All wiring and piping that
interconnects the components will be removed. The loose parts will be packaged in a separate crate.
1. Block-offs will cover all openings on the compressor and vessels.
2. The compressor and vessels have a 5-psi helium holding charge.
3. The compressor will not be insulated at the factory. An insulation kit will be shipped with the unit
and will also include a container of adhesive.
4. Only the evaporator shell will be factory insulated. Loose insulation will be shipped for the
suction line and remaining surface areas.
5. The starter will ship loose.
6. Refrigerant will not be shipped with the unit and must be secured locally and furnished and
installed by the installer.
7. Lubricant will be shipped in containers from the factory for field installation.
8. All field piping connections will be Victaulic, flanged, O-ring face seal or copper brazing.
9. Bracket and cable kit will be included for all unit-mounted starters and/or cableway for mini-
cabinet starters.
10. All free piping ends will be capped.
11. Touch-up paint and stick-on wire ties will be included.
12. A bolted bracket instead of a weld will mount the oil pump.
13. The discharge piping assembly will have a bolted flange connection (instead of welded) at the
condenser. This assembly will ship loose.
14. Piping that remains attached to a component will be supported if it is not rigid.
15. The chiller will not be run-tested at the factory but the compressor, oil pump assembly and heat
exchangers will be tested as sub-assemblies.
IM 1128-1 Field Installation Procedure 3
16. The control panels are shipped separately but have all sensors wired in, labeled and tied up.
Matching labels will exist at the sensor connection on the unit.
17. Contact local McQuay Factory Service for pricing and scheduling of required installation
supervision.
TYPE III: The uni t ships fully assembled and is field ready to knockdown. Included are the vessel
bolt-on connection brackets, the discharge stack bolt-on flanges at the condenser and the bolt-on oil
pump assembly.
1. The unit is shipped fully charged with refrigerant and lubricant.
2. The unit will be factory insulated and painted.
3. All electrical and sensor wiring will be fastened as usual.
4. The starter will ship per order instructions.
5. Touch up paint and stick-on wire ties will be included.
6. This unit will be fully tested at the factory.
7. Labels will be provided with the instructions to mark piping, electrical wiring and sensor wiring.
NOTE: If disassembly involves breaking any refrigerant connection, the refrigerant charge must be
pumped down and isolated in the condenser.
Typical WSC Centrifugal Chiller
4 Field Installation Procedure IM 1128-1
Type I Reassembly
!
WARNING
Description
TYPE I: The compressor with its terminal box is removed and placed on a skid as a separate package.
The suction piping is removed and shipped loose. All other piping will be disconnected from the
compressor and remain attached to the vessel stack, where possible. Wiring and sensors to the
compressor will be disconnect ed, rolled up and tied to the control pane ls. The remaining loose parts
will be packaged in a separate crate.
1. Block-offs will cover all openings on the compressor and vessels.
2. The compressor and vessels will receive a 5-psi helium holding charge.
3. The compressor will not be insulated at the factory. An insulation kit will be shipped with the unit
and will also include a container of adhesive.
4. The unit vessel stack will be insulated at the factory.
5. This unit will be tested with a full refrigerant charge at the factory and the charge will be removed
after testing.
6. Refrigerant will not be shipped with the unit and must be secured locally and furnished and
installed by the installer.
7. Bracket and cable kit will be included for all unit-mounted starters and/or cableway for mini-
cabinet starters.
8. All free piping ends will be capped.
9. Touch-up paint and stick-on wire ties will be included.
10. Lubricant will be shipped in containers from the factory.
11. The starter will ship loose.
12. All field piping connections will be Victaulic, flanged, O-ring face seal or copper brazing.
13. The unit control panel and compressor control panel will be attached to the unit with loose sensor
wires tied up behind the panel.
Reassembly Steps
NOTE: Additional instructions may be shown on the assembly drawings.
1. Mount the compressor on the stack. Be careful to avoid damaging lines already mounted on the unit.
Mounting bolts, washers and nuts are shipped loose. Leave the mounting bolts loose until the suction
and discharge lines are installed and aligned.
During assembly, bolts holding block-off plates (motor cooling connection, for example), are used for
reassembly of the component. See Figure 1 or Figure 2 for the location and description of the blockoffs.
2. Do not remove block-offs until ready to install piping. The compressor and vessels have a Schrader
valve on their block-off plates to be used for relieving the helium holding charge.
Remove compressor and vessel holding charge through the Schrader valve in the block-off plates
before attempting to loosen any fittings on them. Failure to do so can cause severe bodily injury.
3. Install the suction and discharge piping (see Figure 3). Before tightening the Victaulic couplings,
position the suction and discharge piping so that the compressor can be aligned to give the best fit-up.
When this is achieved, secure the compressor mounting bolts and proceed with installing the Victaulic
couplings using a light coating of Victaulic lubrication.
IM 1128-1 Field Installation Procedure 5
4. Install the liquid injection line (see Figure 4). The liquid injection line is attached to the condenser
and has shipping straps securing it to the evaporator and condenser. It, and the compressor, each have
a block-off. Note that any given injection line may be configured somewhat differently than shown on
the drawing.
5. Install the motor cooling line (see Figure 5) using the same procedure as the liquid injection line.
6. Install the motor drain line (see Figure 6) using the same procedure as the liquid injection line.
7. Piping for the optional hot gas bypass is shipped mounted on the unit except for models WSC100,
WSC113 and WSC126 with vessel stacks sizes E36C30, E36C36, E42C36, E42C42, E48C42 and
E48C48. These units have the piping assembly shipped loose for field mounting. See Figure 7.
8. Install the compressor lubrication lines. There are four lines as shown in Figure 8:
a. Thrust pump return, injects lubricant from the compressor thrust pump (thrust bearing) into
the lubricant supply line.
b. Oil drain, drains lubricant from the compressor to the sump.
c. Vent line, vents refrigerant from the sump back to the compressor suction.
d. Oil supply, supplies lubricant from the pump in the sump to the compressor.
There is a variety of fitting types employed on the oil lines. Reconnect the compression fittings, bolt
on the flanges using new gaskets furnished, and re-sweat the sweat connections.
9. Install the four-way solenoid on the compressor suction housing.
10. Install compressor wiring using Figure 9 (including notes) as a guide. Figure 9 shows connections for
both Type I and Type II arrangements. Only the connections listed below are required to be made for
Type I. The wire end that has been disconnected, and its attachment point on the compressor, will
each have a label attached (VC for the vane close switch, for example) for matching purposes.
a. Guardistor, G1 (and G2 on some units), terminal box located on side of motor housing.
b. Compressor heaters, CP1 (and CP2 on some units), located on the bottom of the compressor.
c. Vane load/unload solenoids, SA and SB, located on the four-way solenoid assembly.
d. Vane close switch, VC, located on compressor next to the discharge housing.
e. Vane open switch, VO, located on suction end of compressor.
f. High pressure switch, HPS, located on compressor discharge nozzle.
11. If the unit has been ordered with a starter or VFD as unit mounted, brackets for mounting it and
interconnection cables to the compressor motor will be included as ship loose items. Control wiring as
shown in Figure 9 and Figure 13 (field wiring diagram), will also be required. The field wiring
diagram located on the control panel door should also be consulted as it will be current. If the unit has
a free standing starter, use normal field procedures for mounting and wiring.
Normal procedure of leak testing, triple evacuation, and charging with refrigerant and lubricant must
be followed prior to the start up procedure.
12. Insulate the compressor motor, suction line, and other miscellaneous areas with the included insulation
and adhesive after leak testing. See Field Insulation Guide on page 29.
This completes the reassembly procedure.
6 Field Installation Procedure IM 1128-1
Figure 1, WSC 063 - 087 Compressor Connections
RIGHT VIEW
R331311301C0100
15" MTR. HSG.
LEFT VIEW
(20" MTR.HSG.)
MOTOR COOLING
REFRIGERANT
FROM COND. BTM
OIL LINE VENT
FROM TOP FRONT
OF OIL PUMP
ATT ACH TAG TO ONE
TERMINAL INSIDE BOX
4-WAY SOLENOID VALVE
LIQUID
INJECTION
FROM COND. BTM.
OIL THRUST RETURN
TO OIL LINE TEE
OIL DRAIN
TO TOP BACK
OF OIL PUMP
MOTOR DRAIN
TO EVAP BOTTOM
MOTOR DRAIN
OIL OUT TO SA AND SB
SOLENOID VALVES AND
MOTOR DRAIN
TO EVAP BOTTOM
MOTOR COOLING
FROM COND. BTM.
OIL SUPPLY
FROM OIL COOLER
Notes:
1. New O-rings and gaskets are in a plastic bag.
2. Compressor is charged with 5-psi of helium.
IM 1128-1 Field Installation Procedure 7
Figure 2, WSC 100-126 Compressor Connections
LEFT VIEW
(22" MTR. HSG.)
20" MTR. HSG.
RIGHT VIEW
BOTTOM VIEW
OIL VENT
OIL SUPPLY
MOTOR COOLING
OIL DRAIN
DISCHARGE
BLOCKOFF
REF. DRAIN
REF.DRAIN
REF. DRAIN
MOTOR COOLING
MOTOR DRAIN
MOTOR DRAIN
LIQUID INJECTION
UNSWEAT LINE AND
SHUT VALVE
FROM TOP FRT.
OF OIL PUMP
FROM CONDENSER
BOTTOM
TO TOP BACK
OF OIL PUMP
TO EVAP.
BOTTOM
TO EVAP.
BOTTOM
TO EVAP.
BOTTOM
TO EVAP.
BOTTOM
TO EVAP.
BOTTOM
FROM COND.
BOTTOM
FROM COND. BOTTOM
4 WAY SOLENOID VALVE
OIL THRUST
RETURN TO
OIL LINE TEE
TO OIL COOLER
R331311301D0200
OIL OUT TO SA AND SB
SOLENOID VAL VES AND
OIL PRESSURE TRANSDUCER
Notes:
1. New O-rings and gaskets are in a plastic bag.
2. Compressor is charged with 5-psi of helium.
8Field Installation Procedure IM 1128-1
Figure 3, Suction and Discharge Piping
R331311308C0100
BOLT-ON
BLOCKOFF PLATE
TYPE II
UNITS RECEIVE
SLIP-ON ASME
FLANGES
TYPES II & III
TYPES I & II
TYPES I & II
VICTAULIC
BLOCKOFF PLATE
INSTALL SUCTION
PIPING
EVAPORATOR AND CONDENSER ARE EVACUATED
AND CHARGED WITH 30 PSI OF HELIUM.
TYPES I & II
IM 1128-1 Field Installation Procedure 9
Figure 4, Liquid Injecti on Li nes
MECHANICAL
TORQUE TO
58 FT/LBS
R331311304C0100
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
MOTOR COOLING LINES
(NOT ALL VARIA TIONS SHOWN)
TYPE I
BLOCKOFF
TYPE I
BLOCKOFF
BREAK POINT
TYPE I
BLOCKOFF
R331311303C0100
MECHANICAL
BREAK POINT
TYPE I
BLOCKOFF
LIQUID INJECTION LINES
(NOT ALL VARIATIONS SHOWN)
NOTE:
The liquid injection line (above) and the motor c ooling line (below) are attached to the condenser and have
shipping straps securing them to the evaporator and condenser. The lines and the compressor, each have blockoff plates, resulting in extra bolts.
Figure 5, Motor Cooling Lines
10 Field Installation Procedure IM 1128-1
Figure 6, Motor Drain Line
R331311305C0100
20" MOTOR REF. DRAIN
CONNECTION
(REAR VIEW)
15" MOTOR REF. DRAIN
CONNECTION
(REAR VIEW)
MOTOR HOUSING
DRAIN LINE
MOTOR DRAIN LINE
(NOT ALL VARIATIONS SHOWN)
MECHANICAL
BREAK POINT
IM 1128-1 Field Installation Procedure 11
Figure 7, Optional Hot Gas Bypass Piping
R331311307C0100
HOT GAS
BYPASS
LINE
HOT GAS
BYPASS
PILOT
LINE
SHUT OFF
VALVE
EXPANSION
VALVE
CONNECTION TO
DISCHARGE NOZZLE
E
V
A
P
O
R
A
T
OR
B
O
TT
O
M
MECHANICAL
BREAK POINTS
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
FLOW
FLOW
FLOW
NOTE: THIS LINE IS NOT ALWAYS
PRESENT. SOME UNITS HAVE
ELECTRONIC VAL V ES.
BLOCKOFF
TYPE II UNITS
INSTALL HOT GAS PIPING
TYPE I UNITS
INSTALL HOT GAS PIPING ON WSC MODELS
100, 113, & 126 WITH STACK SIZES
E36C30, E36C36, E42C36, E42C42,
E48C42, E48C48
R331311302C0200
OIL VENT
OF THRUST RETURN LINE
OIL SUPPLY
RESWEAT LINE
ABOVE REDUCER
RESWEAT LINE
ABOVE TEE
TYPES I & II
TYPES I & II
INSTALL T OP PORTION
TYPES I AND II
INSTALL
INSTALL WATER LINES
TYPE II
INSTALL TOP PORTION
OF LINE
TYPES I & II
TYPES I AND II
INSTALL
OIL DRAIN
Figure 8, Oil and Water Lines
12 Field Installation Procedure IM 1128-1
Figure 9, Electrical and Sensors, Compr essor Contr ol Box and Connections
R331311501C0100
N7
N7
155
155
155
154
GUARDISTOR
CONNECT LEAD 155
TO TERMINAL IF 2nd
BOX IS NOT USED.
2nd TERMINAL BOX
USED ON SELECTED
MOTORS.
HIGH
PRESSURE
SWITCH
E9
E7
NUMBER OF HEATERS MAY VARY
DUE TO COMPRESSOR SIZE.
JUNCTION BOX NOT ON ALL UNITS.
SECOND HEATER CABLE FROM COMPR.
ON WSC063-087 ONLY.
}
3
2
1
E4
E6
05
0708
E5
OIL PUMP
HEATERS
{TO STARTER
COMPRESSOR
HEATERS
CS04
CS05
CS07
CS09
CS10
CS06
CS03
CS02
CS01
HOT GAS
SOLENOID
LIQ. INJ.
SOLENOID
OPTION
135
136
133
134
141
142
139
140
132
131
137
138
OIL COOLER
SOLENOID
VANE CONTROL
SOLENOIDS
VANE
CLOSE
SWITCH
146
145
VANE
OPEN
SWITCH
103
104
VFD SPEED
SIGNAL
102
101
(ON VFD ONLY)
LI
HG
VO
VC
SA
SB
OC
VFD
LEAVING EVAP WATER TEMP.
OIL FEED TEMP.
COMPR. DISCHARGE TEMP.
COMPR. SUCTION TEMP.
OIL SUMP TEMP.
COND. PRESS. SENSOR
EVAP. PRESS. SENSOR
OIL FEED PRESS. SENSOR
OIL SUMP PRESS. SENSOR
VANE
LOAD
VANE
UNLOAD
JUNCTION BOX ON COMPRESSOR
MOUNTING BRACKET NEAR THE
SUCTION PIPE.
OPH
G2
G1
CP1
CP2
HPS
COMPRESSOR CONTROL BOX
CCB POWER
10 LEADS4 LEADS
(ON COMPRESSOR)
(ON VFD)
(ON SUPPLY
WATER LINE)
(ON COMPR.
FRONT)
(ON COMPR. NEXT
TO DISCHARGE)
(ON COMPR.
FRONT)
(ON HOT
GAS LINE)
(ON LIQUID
INJ. LINE)
(ON DISCHARGE
NOZZLE)
Note:
1. Reference compressor controller schematic for detailed wiring connections.
IM 1128-1 Field Installation Procedure 13
EVAPORATOR
TUBE SHEET
TUBE SHEET
SUPPORT
PLATE
CONDENSER
TUBE SHEET
BOLTED
BOLTED
WELDED
TWO ANGLE PLATES,
ONE WELDED TO EVAP.
ONE WELDED TO COND.
THEN BOLTED TOGETHER.
Type II Reassembly
Description
TYPE II: The compressor with its terminal box is removed and shipped on a skid. The condenser,
evaporator, oil sump, oil cooler and tube sheet support plates will remain connected only by their
attachment bolts, ready for field disassembly on site and subsequent r eassembly in the building. All
wiring and piping that interconnects the components will have been removed and will require
reinstallation. The loose parts will be packaged in a separate crate.
1. Block-offs will cover all openings on the compressor and vessels.
2. The compressor and vessels will receive a 5-psi helium holding charge.
3. The compressor will not be insulated at the factory. An insulation kit will be shipped with the unit
and will also include a container of adhesive.
4. Only the evaporator shell will be factory insulated. Loose insulation will be shipped for the
remaining surface areas.
5. The starter will ship loose.
6. The refrigerant will be field supplied.
7. All field piping connections will be Victaulic, flanged, O-ring face seal or copper brazing.
8. Bracket and cable kit will be included for all unit-mounted starters and/or cableway for mini-cabs.
9. All free piping ends will be capped.
10. Touch-up paint and stick-on wire ties will be included.
11. A bolted bracket instead of a weld will mount the oil pump.
12. The discharge piping assembly will have a bolted flange connection (instead of welded) at the
condenser. This assembly will ship loose.
13. Piping that remains attached to a component will be supported if it is not rigid.
14. The chiller will not be run-tested at the factory but the compressor, oil pump assembly and heat
exchangers will be tested as sub-assemblies.
15. The control panels are shipped separately but have all sensors wired in, labeled and tied up.
Matching labels will exist at the sensor connection to the unit.
Reassembly Steps
NOTE: Additional instructions may be shown on the assembly drawings.
The Type II arrangement is shipped with the evaporator, condenser, tube sheet support plate, oil cooler
and oil sump bolted together. This provides structural support during transit and also allows several
options for disassembly.
Figure 10, Component Disassembly
In most cases for narrow entry, the condenser will be
separated by unbolting it from the evaporator angle
bracket and from the tube sheet support plate. This
leaves the evaporator and the support plate that has
the mounting foot extended under where the
condenser used to be. Therefore, the evaporator is
usually unbolted from the two support plates, which
can then be easily handled by themselves.
14 Field Installation Procedure IM 1128-1
!
WARNING
Remove compressor and vessel holding charge through the Schrader valve in the block-off plates
before attempting to loosen any fittings on them. Failure to do so can cause severe bodily injury.
1. Disassemble the unit to the e xtent required by the site conditions. Rig the components to their final
location and reassemble them using the fasteners that came with the unit.
2. The compressor and its suction and discha rge piping should be installed on the stack before any other
lines are attached. Mount t he compressor on the stack. Mounting bolts, washers and nuts are shipped
loose. Leave the mounting bolts loose until the suction and discharge lines are in place and aligned.
Install the suction and discharge piping. Before tightening the Victaulic couplings, position the suction
and discharge piping so that the compressor can be aligned to give the best fit-up. When this is
achieved, secure the compressor mounting bolts and proceed with installing the Victaulics using a light
coating of Victaulic lubricant. See Figure 3.
3. Install the liquid line using Figure 11 as a guide. Commonly used arrangements are illustrated. The
bottom two arrangements illustrate lines with electronic valves used on some size units. Due to the
variety of vessel combinations available, variation on specific units will occur.
4. Install the motor cooling line using Figure 5 as a guide.
5. Install the liquid injection line (see Figure 4). Note that any given injection line may be configured
somewhat differently than shown on the drawing.
6. If the oil cool er and oi l sump have been removed on the job site, reinsta ll them using the fasteners tha t
came on the unit. See Figure 12 for piping between the cooler and sump and the cooling water pi ping.
See Figure 8 for the balance of the four oil lines connected to the compressor. There are a variety of
fitting types employed on the oil lines. Reconnect the compression fit tings, bolt on the flanges using
new gaskets/O-rings furnished, and re-sweat the sweat connections.
Due to the wide variety of model arrangements, some or all of the oil piping may be shipped loose.
When possible, the cooler and sump will be shipped mounted to their back plate with as much piping
remaining as possible.
7. Install the four-way solenoid valve assembly on the compressor suction housing.
8. Install the two control panels; the compressor panel is mounted adjacent to the oil sump and the unit
panel is on top of the evaporator. Wire and sensor leads have been disconnected at their terminus and
labeled. They remain connected at the panels and rolled up. Their destinations have matching labels,
which simplifies the installation. Compressor panel sensor labels are prefixed with CS, unit panel labels
with US. Use the following drawings as a guide for installing wiring and sensors:
9. If the unit has been ordered with a starter or VFD as unit mounted, brackets for mounting it and
interconnection cables to the compressor motor will be i ncluded as shi p loose ite ms. Control wiring as
shown in Figure 9 will also be required. If the unit has a free-standing starter, use normal field
procedures for mounting and wiring.
Normal procedure of leak testing, triple evacuation, and charging with refrigerant and lubricant must be
followed prior to the start up procedure.
IM 1128-1 Field Installation Procedure 15
10.Insulate the compressor, suction line, and other miscellaneous areas with the included insulation and
SHOWN IS E36/C36 STACK
WITH 20-INCH MOTOR
R331311306C0100
VIEW B
SEE VIEW B
TOP OF
EVAPORATOR
FROM PILOT
TX VALVE
EVAPORATOR
CONNECTION
CONDENSER
SHUTOFF VALVE
CONNECTION
TO TOP OF
EVAPORATOR
TO TOP OF
EVAPORATOR
EVAPORATOR
CONNECTION
CONDENSER
SHUTOFF VALVE
CONNECTION
FLOW
FLOW
PLUG
EVAP. BLOCKOFF
LIQUID LINES
(NOT ALL
VARIATIONS
SHOWN)
LIQUID
LINES
FLOW
FLOW
(VIEW 'B')
(VIEW 'B')
LIQUID LINE
LIQUID LINE
PILOT LINE
PILOT LINE
RESWEAT PILOT LINE
ABOVE THE SHUTOFF
VALVE
RESWEAT PILOT LINE
ABOVE THE SHUTOFF
VALVE
PILOT LINE
SHUT OFF
VALVE
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
MECHANICAL
BREAK POINT
CONDENSER
SHUTOFF
VALVE
TYPE II
KNOCKDOWN
ONLY
glue after leak testing. See Field Insulation Guide on page 29.
This completes the reassembly procedure.
Figure 11, Liquid Line Inst allation
NOTE: The bottom two liquid lines show the typical arrangement with electronic expansion valves. Liquid flow can be
in different directions depending on the valve size.
16 Field Installation Procedure IM 1128-1
Figure 12, 16 Inch Oil Sump / O il Cooler Assembly
R331311302C0100
F
L
O
W
FLOW
F
LO
W
F
LO
W
PR
E
S
SU
R
E
E
Q
U
A
LI
Z
A
T
I
O
N
PLUG
PLUG
OIL
COOLER
OIL VENT LINE
OIL DRAIN LINE
THRUST RETURN
OIL LINE
FLOW
OIL SUPPLY TO
VALVE ON COMP.
FLOW
FLOW
OIL
SUPPLY
WATER
RETURN
OW
L
F
WATER
SUPPLY
DUE TO DIFFERENT PIPE ROUTINGS
SOME OR ALL PIPING SHOWN MAY
BE SHIPPED LOOSE
ER
T
A
W
Y
PPL
SU
N
R
U
T
E
R
ER
T
A
W
Notes:
1. Piping arrangements will vary according to specific model.
2. Oil sump is shipped without oil on Type I and Type II knockdown units.
3. Type III knockdown units are shipped with oil.
IM 1128-1 Field Installation Procedure 17
80
CP2
CP1
H
O
A
C4
H
A
O
C3
H
A
O
79
78
77
74
73
54
CF
86
EF
86
C
25
1
2
11
11
12
22
1
2
6
11
12
22
NOTE 2
NOTE 2
(115V) (24V)
25
55
70
H
A
O
H
A
O
H
O
A
C
H
O
A
C
H
O
A
C
C2
C1
T3-S
PE
L1
L2
CP2
CP1
24
23(5A)
24(5)
23
3
4
3
4
76
75
PE
85
86
81
84
A
82(NO)
83(NC)
POWER
EP2
EP1
L1 L2 L3
GND
T4 T5 T6
T1 T2 T3
T4 T5 T6T1 T2 T3
T1T2T3
T3T1T2
UVW
T4 T3 T5T1 T6 T2
T1T2T3
T4 T3 T5T1 T6 T2
GND
LESS
THAN
30V
OR
24VA C
53
71
71
52
1-10 VDC
1-10 VDC
MICROTECH CONTROL
BOX TERMINALS
* COOLING
TOWER
FOURTH
STAGE
STARTER
* COOLING
TOWER
THIRD
STAGE
STARTER
* COOLING
TOWER
SECOND
STAGE
STARTER
* COOLING
TOWER
FIRST
STAGE
STARTER
COOLING TOWER
BYPASS VALVE
COOLING TOWER VFD
ALARM RELAY
(NOTE 4)
MICROTECH
COMPRESSOR CONTROL
BOX TERMINALS
CTB1
-LOAD-
COMPRESSOR
MOTOR
STARTER
(NOTE 1)
115 VAC
STARTER LOAD SIDE TERMINBALS
VFD
STARTER LOAD SIDE TERMINBALS
WYE -DELTA
STARTER LOAD SIDE TERMINBALS
SOLID STATE
STARTER LOAD SIDE TERMINBALS
MEDIUM AND HIGH VOLTAGE
COMPRESSOR TERMINALS
COMPRESSOR TERMINALS
COMPRESSOR TERMINALS
COMPRESSOR TERMINALS
NOTE 12
- FOR DC VOLTAGE AND 4-20 MA
CONNECTIONS (SEE NOTE 3)
- FOR DETAILS OF CONTROL REFER
TO UNIT CONTROL SCHEMATIC
330342103
- COMPRESSOR CONTROL
SCHEMATIC 330342203
- LEGEND: 330343003
* FIELD SUPPLIED ITEM
* NOTE 7
* NOTE 10
* NOTE 10
* NOTE 10
* NOTE 10
330387901-0A
COMMON
NEUTRAL
POWER
Figure 13, Typical Field Connection Diagram, WSC Unit
18 Field Installation Procedure IM 1128-1
Figure 14, Compressor Control Panel Elect rical and Sensor Connections
R331311501C0100
N7
N7
155
155
155
154
GUARDISTOR
CONNECT LEAD 155
TO TERMINAL IF 2nd
BOX IS NOT USED.
2nd TERMINAL BOX
USED ON SELECTED
MOTORS.
HIGH
PRESSURE
SWITCH
E9
E7
NUMBER OF HEATERS MAY VARY
DUE TO COMPRESSOR SIZE.
JUNCTION BOX NOT ON ALL UNITS.
SECOND HEATER CABLE FROM COMPR.
ON WSC063-087 ONLY.
}
3
2
1
E4
E6
05
0708
E5
OIL PUMP
HEATERS
{TO STARTER
COMPRESSOR
HEATERS
CS04
CS05
CS07
CS09
CS10
CS06
CS03
CS02
CS01
HOT GAS
SOLENOID
LIQ. INJ.
SOLENOID
OPTION
135
136
133
134
141
142
139
140
132
131
137
138
OIL COOLER
SOLENOID
VANE CONTROL
SOLENOIDS
VANE
CLOSE
SWITCH
146
145
VANE
OPEN
SWITCH
103
104
VFD SPEED
SIGNAL
102
101
(ON VFD ONLY)
LI
HG
VO
VC
SA
SB
OC
VFD
LEAVING EVAP WATER TEMP.
OIL FEED TEMP.
COMPR. DISCHARGE TEMP.
COMPR. SUCTION TEMP.
OIL SUMP TEMP.
COND. PRESS. SENSOR
EVAP. PRESS. SENSOR
OIL FEED PRESS. SENSOR
OIL SUMP PRESS. SENSOR
VANE
LOAD
VANE
UNLOAD
JUNCTION BOX ON COMPRESSOR
MOUNTING BRACKET NEAR THE
SUCTION PIPE.
OPH
G2
G1
CP1
CP2
HPS
COMPRESSOR CONTROL BOX
CCB POWER
10 LEADS4 LEADS
(ON COMPRESSOR)
(ON VFD)
(ON SUPPLY
WATER LINE)
(ON COMPR.
FRONT)
(ON COMPR. NEXT
TO DISCHARGE)
(ON COMPR.
FRONT)
(ON HOT
GAS LINE)
(ON LIQUID
INJ. LINE)
(ON DISCHARGE
NOZZLE)
Note:
Refer to the compressor controller schematic for detailed wiring connections.
IM 1128-1 Field Installation Procedure 19
Figure 15, Unit Controller El ect r i cal and Sensor Connections