Location and Mounting....................................................................................................................................4
Evaporator and Condenser Water Piping.......................................................................................................7
Water Treatment.................................................................................................................................................7
Head Pressure Control, Tower System...........................................................................................................7
Head Pressure Control, Well Water System ...................................................................................................8
Condenser Protection and Design Considerations......................................................................................9
Chilled Water Thermostat.................................................................................................................................9
Detection of Loss of Flow..............................................................................................................................10
Chilled Water Quantity....................................................................................................................................11
Evaporator and Condenser Water Flow and Pressure Drop...................................12
Field Wiring...............................................................................................................22
General Information.....................................................................................................................................22
Off Conditions..................................................................................................................................................27
"McQuay" is a registered trademark of McQuay International
"Illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to
make changes in design and construction at anytime without notice"
1997 McQuay International
2WHS 155A- 220AIOMM WHS
Introduction
McQuay StarGate™ water-cooled chillers are completely assembled, factory wired, evacuated,
charged, tested and ready for installation. Each unit consists of a water-cooled condenser with
integral subcooler, dual accessible semi-hermetic single screw compressors with suction and
discharge shutoff valves, replaceable tube shell-and-tube evaporator, and complete refrigerant piping.
Liquid line components included are manual liquid line shutoff valves, charging valves, filter-dryers,
liquid line solenoid valves, sightglass/moisture indicators, and electronic expansion valves. Other
features include compressor heaters, and an advanced fully integrated microprocessor control system.
The electrical control center includes all safety and operating controls necessary for dependable
automatic operation, (the high and low pressure controls are external from the electrical control
center). Compressors are protected by solid-state overload protection and over temperature
protection.
Receiving and Handling
Inspect the unit immediately after receipt for possible damage. The unit is shipped FOB factory and all
claims for handling and shipping damage are the responsibility of the consignee. Leave the shipping
skid in place until the unit is in final position. This will aid in handling the equipment. Use extreme
care when rigging the equipment to prevent damage to the control center, or refrigerant piping. See
Dimensional Data for the center of gravity of the unit.
Lift the unit by fastening the rigging hooks to the four corners of the evaporator where the rigging
eyes are located (see Figure 1). Use spreader bars between the rigging lines to prevent damage to the
control center.
Figure 1, Rigging Eyes
Rigging Eyes
Rigging Eyes
IOMM WHSWHS 155A - 220A3
Installation
CAUTION
Installation must be performed by qualified personnel who are familiar with local codes,
regulations, and experienced with this type of equipment.
Start-up by McQuayService is included on all units sold for installation within North America
excluding Mexico. Two weeks prior notification of start-up is required. The contractor should obtain
a copy of the Start-up Scheduled Request Form from the sales representative or from the nearest
McQuayService office.
Location and Mounting
Mount the unit on level concrete or steel base. Service and tube pull clearance (at either end of the
unit) is 14 feet (4.3 m). Evaporator and condenser tubes are rolled into the tube sheets to permit
replacement. Clearance at the sides and other end, including the top, is 3 feet (1 m).
Make certain the floor or structural support is adequate to support the full operating weight of the
complete unit. Optional rubber-in-shear pads, or spring isolators can be ordered for use under each
corner of the base members. It is not necessary to bolt the unit to the mounting slab or frame work;
although mounting holes are provided in the unit support at the four corners.
Compressor Condensation
Condensation occurs on the compressor surface when the temperature of the compressor surface is
lower than the ambient dew point temperature. Drain pans with drain connections are provided
underneath each compressor to collect the condensate. The compressor motor housing extends past
the drain pans. Install a floor drain close to the unit to collect condensate from motor housing and
condensate pans.
Vibration Isolators
Waffle type vibration isolator pads are shipped with the unit for field installation. These pads provide
minimal isolation. Vibration isolators are recommended on all upper level installations where vibration
transmission is a consideration. When vibration isolators are used, install springs under the main unit
supports. Adjust spring so the upper housing clears lower housing by at least 1/4” (6mm) and not
more than 1/2” (13mm). If hold-down bolts are not used, install a rubber anti-skid under isolators.
Install vibration eliminators in water piping to reduce piping strain, vibration, and noise. Table 1 lists
spring and rubber-in-shear isolators for all WHS unit sizes.
4WHS 155A- 220AIOMM WHS
Table 1, Vibration Isolators (WHS 155A - 200A)
IsolatorIsolator Per Location
1234
Rubber-in-ShearRP-4RP-4RP-4RP-4
SpringCP-4-28CP-4-28CP-4-28CP-4-28
Figure 2, Isolator location
Table 2, Isolators (WHS 220A)
ColorRecom.
IsolatorTypeOfMcQuayMax Ld
StripePart No.Lb. (Kg)
Rubber-In-ShearRP-4Green00216398033300 (1497)
SpringCP-4-28Green00580513283600 (1633)
Note: The spring is fully compressed at about 5400 lb (2449 Kg).
Figure 3 and Figure 4 give dimensions required to secure each McQuay isolator section to the
mounting surface. The maximum loads for each unit are shown in Table 3.
Figure 3 , Rubber-in-Shear Isolator
IOMM WHSWHS 155A - 220A5
Figure 4, Spring Flex Isolator
Table 3, Corner Weights for Standard Shell Units lb (kg)
WHS evaporators and condensers are equipped with either victaulic or flange connections. The
installing contractor must provide matching connections.
CAUTION
Remove the solid-state temperature sensor and thermostat bulbs from the wells to prevent
damage to those components when welding on the victaulic or flange connections.
Connect the condenser with the inlet water entering at the bottom to maximize subcooling. The
condenser water will discharge from the top connection.
Support piping to reduce weight and strain on the fittings and connections. Be sure piping is
adequately insulated. Install a cleanable 20-mesh water strainer in evaporator and condenser water
piping. Install enough shutoff valves to permit draining water from the evaporator or condenser
without draining the complete system.
CAUTION
Freeze Notice: The evaporator and condenser are not self-draining. Both must be blown out.
Include thermometers at the inlet and outlet connections and air vents at the high points of piping.
The water heads can be interchanged (end for end) allowing water connections to be made at either
end of the unit. Use new head gaskets when interchanging water heads. When water pump noise is
objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration
eliminator sections in the condenser inlet and outlet water lines are not normally required. Where
noise and vibration are critical, and unit is mounted on spring isolators, flexible piping connections are
necessary.
Water Treatment
If unit is operating with a cooling tower, clean and flush cooling tower. Make sure tower "blowdown"
or bleedoff is operating. Atmospheric air contains many contaminants which increases the need for
water treatment. The use of untreated water may result in corrosion, erosion, sliming, scaling, or algae
formation. A water treatment service is recommended. McQuay International is not responsible for
damage or faulty operation from untreated or improperly treated water.
Head Pressure Control, Tower System
The minimum entering water temperature to the condenser must not be lower than 75°F (23.9°C) at full
tower water flow. If lower temperature water is used, the flow must be reduced proportionally. Use a
three-way bypass valve around the tower to modulate the condenser water flow. Figure 6 shows a
three-way pressure actuator water regulating valve used for cooling applications. This regulating
valve will assure an adequate condensing pressure if the inlet condenser water temperature falls below
75°F (23.9°C). An optional AOX-4 board located in the MicroTech panel will control a cooling tower
bypass valve or a variable speed condenser pump.
IOMM WHSWHS 155A - 220A7
Head Pressure Control, Well Water System
When using city or well water for condensing refrigerant, install a normally closed direct acting water
regulating valve in the outlet piping of the condenser. This regulating valve will assure an adequate
condensing pressure if the inlet condenser water temperature falls below 75°F (23.9°C). The
condenser service valve provides a pressure tap for the regulating valve. The valve can modulate in
response to head pressure. On shutdown, the valve closes, preventing water from siphoning out of
the condenser. Siphoning causes condenser waterside drying and accelerates fouling. If a valve is
not used, Figure 7 illustrates the recommendation of a loop at the outlet. Size the loop height (H) to
offset the negative pressure caused by the siphoning effect. A vacuum breaker may be required.
Figure 6, Bypass valve
Figure 7, Well Water System
Relief Valve Piping
Follow the requirements of ANSI/ASHRAE Standard 15-1994 for relief valve piping. The condenser
relief valve assembly consists of a tree valve and two relief valves. The tree valve must be fully front
or back seated to ensure only one relief valve is available for discharge.
8WHS 155A- 220AIOMM WHS
Temperature and Water Flow Limitations
WHS units are designed to operate in conditions from 20°F (-6.7°C) to 50°F (10°C) leaving water
temperature on the evaporator side and 75°F (23.9°C) to 95°F (35°C) entering water temperature on the
condenser side.
Glycol in the evaporator is required on all applications below 40°F (4.4°C) leaving evaporator fluid
temperature. The maximum allowable water temperature to the cooler in a non-operating cycle is 105°F
(40.6°C). The non-operating leaving condenser water temperature maximum is 115°F (46.1°C). Flow
rates below the minimum values shown in the evaporator and condenser pressure drop curves may
cause freeze-up problems, scaling and poor control. Flow rates above the maximum values shown in
the evaporator and condenser pressure drop curves will result in unacceptable pressure drops,
excessive nozzle and tube erosion and possibly cause tube failure.
Startup With Cold Condenser Water
WHS screw compressor chillers are designed to permit startup with elevated chilled water
temperatures and cold condenser water. Following a weekend shutdown, for example, in relatively
cool, low wet bulb ambient, the building chilled water temperature could be 70°F to 80°F (21°C to 27°C)
with a condenser water temperature of 55°F (13°C). Start up under these conditions is expected. If the
cooling load is excessive, or condenser water temperatures substantially less, modification of alarm
timer settings by the McQuayService Technician may be required.
Evaporator Freeze Protection
When freeze protection is a concern, do the following:
1. If the unit will not be operated during the winter, drain and flush the evaporator and chilled water
piping with glycol. Drain and vent connections are provided on the evaporator.
2. When using a cooling tower, add glycol solution to the chilled water system. Freeze point should
be approximately 10°F (5.6°C) below minimum design ambient temperature.
Note: Freeze damage is not considered a warranty failure and is not the responsibility of
McQuay International.
3.Insulate field water piping, especially on the chilled water side.
Condenser Protection and Design Considerations
If pond or river water is used as a condensing medium and the water valves leak, the condenser and
liquid line refrigerant temperature could drop below the equipment room temperature on the "off"
cycle. This problem occurs when cold water continues to circulate through the condenser and the
unit remains off due to satisfied cooling load. If this occurs:
1. Cycle the condenser pump off with the unit.
2. Verify the liquid line solenoid valves are operating properly.
Chilled Water Thermostat
The WHS water-cooled chiller is equipped with the MicroTech leaving water controller. Be careful
when working around the unit to avoid damaging lead wires and sensor cables. Check lead wires
before running the unit. Avoid rubbing the lead wires on the frame or other components. Verify the
lead wires are firmly anchored. If the sensor is removed from the well for servicing, do not wipe off the
heat conducting compound supplied in the well.
IOMM WHSWHS 155A - 220A9
Refrigerant Charge
All units are designed for use with R-22 or R-410A and are shipped with a full operating charge. The
operating charge for each unit is shown in the Physical Data Table.
Detection of Loss of Flow
NOTE: Water pressure differential switches are not recommended for outdoor applications.
The preferred means for detecting loss of flow is the use of factory-mounted pressure differential
switches for the evaporator and condenser.
A flow switch is available from McQuay (part number 00175033-00). It is a “paddle” type switch and
adaptable to any pipe size from 3” (76mm) to 8” (203mm) nominal. Two flow switches are required.
Mount the flow switch in either the entering or leaving water line of the evaporator and condenser.
Certain minimum flow rates are required to close the switch and are listed in Table 4. Installation
should be as shown in Figure 8.
Figure 8, Flow Switch
Connect the normally open contacts of the flow switch in the unit control center at terminals 62 and
63. Flow switch contact must be suitable for 24 VAC, low current (16ma).
Table 4, Flow Switch Minimum Flow Rates
Nominal Pipe SizeMin. Required Flow to
(inches)Activate Switch - GPM (L/s)
558.7 (3.7)
679.2 (5)
Glycol Solutions
A glycol anti-freeze solution is required for operation below 40°F leaving chilled fluid temperature.
The introduction of a glycol solution reduces the capacity of the chiller and any air handling
equipment. Contact the local McQuay sales office for determination of the affect of glycol on the
chiller capacity, power input and pressure drop.
CAUTION
Use industrial grade glycols only. Do not use an automotive grade antifreeze. Automotive
antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller
evaporator. The type and handling of glycol used must be consistent with local codes.
10WHS 155A- 220AIOMM WHS
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.