McQuay Type WGZ water chillers are designed for indoor installations and are available with watercooled condensers (Model AW), or arranged for use with remote air-cooled or evaporative condensers
(Model AA). Each water-cooled unit is completely assembled and factory wired before evacuation,
charging and testing. They consist of hermetic scroll compressors, brazed-plate evaporator, watercooled condenser (WGZ-AW), and complete refrigerant piping.
Units manufactured for use with remote condensers (Models WGZ-AA) have all refrigerant specialties
factory-mounted and connection points for refrigerant discharge and liquid lines.
Liquid line components that are included are manual liquid line shutoff valves, charging valves, filterdriers, liquid line solenoid valves, sight glass/moisture indicators, and thermal expansion valves. Other
features include compressor crankcase heaters, and a MicroTech II¥ microprocessor controller.
The electrical control center includes all equipment protection and operating controls necessary for
dependable automatic operation.
The compressors are not fused as standard, but can be protected by optional circuit breakers or fuses,
or can rely on a field-installed, fused disconnect switch for protection.
BOOT & BIOS
BOOT Version: 3.0F BIOS Version 3.56
Manuals: Information in unit initial installation and routine maintenance is contained in Installation
and Maintenance Manual IMM WGZ-2.
Nomenclature
W G Z 100 - A W
Water-Cooled
Global
Scroll Compressor
W = Water-Cooled Condenser
=
Design Vintage
ominal Capacity (Tons
Water Pressure Drop
Water flow rates should be maintained as closely as possible to job design values. The vessel flow
rat es mu st f al l be twe en t he mi nimu m and maxi mum values shown on the appropriate evaporator and
condenser curves.
Measure the water pressure drop through the vessels at field-installed pressure taps and check the
flow rate using the following tables. Do not include valves or strainers in these readings.
The evaporator flow rates and pressure drops shown on the following page are for full load design
purposes. The maximum flow rate and pressure drop are based on a 6-degree temperature drop.
Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems
resulting from very small control bands and limited start up/shut off temperature changes.
The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16degrees.
Minimum Part Load Flow Rates: This full load design minimum flow is not to be confused with
the part load minimum flow rate that must be maintained for chillers operating in variable primary
flow pumping systems. As chiller capacity drops, the flow rate is reduced proportionally. See the
following table for the part load minimum flow rates.
The chiller unit has two refrigerant circuits, two tandem scroll compressors (total of four), a
single two-circuited brazed plate evaporator, a single two-circuited water-cooled condenser,
interconnecting refrigerant piping and a control panel with associated sensors and
transducers.
Figure 4, Schematic Piping Diagram (One of Two Circuits)
NOTE:
CONDENSER FAN MOTORS
CAN ALSO BE CONTROLLED
BY PRESSURE SWITCHES
ON THE CONDENSER.
CONTROL POWER
(BY OTHERS)
ICE MODE SWITCH
(BY OTHERS)
CHW FLOW SWITCH
4-20 MA FOR
CHW RESET
(BY OTHERS)
4-20 MA FOR
DEMAND LIMIT
(BY OTHERS)
330259001-R4
DISCONNECT
(BY OTHERS)
POWER
SUPPLY
FUSED CONTROL
TRANSFORMER
DISCONNECT
(BY OTHERS)
N
120VAC
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL
OPTION
ALARM BELL RELAY
TIME
CLOCK
ON
UTO
ON
--MANDATORY--
(BY OTHERS)
LIQUID LINE #1 SOLENOID
LIQUID LINE #2 SOLENOID
OPTIONAL
HOT GAS BYPASS #1 SOLENOID
HOT GAS BYPASS #2 SOLENOID
FAN MOTOR #1 COIL
FAN MOTOR #2 COIL
FAN MOTO R #3 COIL
FAN MOTO R #4 COIL
FAN MOTOR #5 COIL
FAN MOTO R #6 COIL
FAN MOTO R #7 COIL
FAN MOTOR #8 COIL
TERMINAL BLOCK
CIRCUIT
10A
FUSE
(BY OTHERS)
CHW PUMP RELAY
(BY OTHERS)
120 VAC 1.0 AMP MAX
OFF
UTO
MANUAL
OFF
MANUAL
NOR. OPEN PUMP AUX.
CONTACTS (OPTIONAL)
24 VAC AMP MAX
24 VAC AMP MAX
24 VAC AMP MAX
24 VAC AMP MAX
(BY OTHERS)
120 VAC 1.0 AMP MAX
(BY OTHERS)
120 VAC 1.0 AMP MAX
(BY OTHERS)
120 VAC 1.0 AMP MAX
(BY OTHERS)
120 VAC 1.0 AMP MAX
120 VAC 1.0 AMP MAX
120 VAC 1.0 AMP MAX
(BY OTHERS)
120 VAC 1.0 AMP MAX
(BY OTHERS)
VAC 1.0 AMP MAX
12
120
VAC
(BY OTHERS)
(BY OTHERS)
GND LUG
TB1
1
2
11
14
10
15
TB2
40
53
42
55
33
43
38
48
49
38
50
51
TB3
62
65
63
65
67
70
68
70
CONTROLLER
J15-N08
TB1-12
J16-N09
J16-N010
J16-N011
J18-N013
J22-N016
J22-N017
J22-N018
TO COMPRESSOR(S)
TB1-20
CONTROL
CIRCUIT
FUSE
120 VAC
N
120VAC
GND
IF REMOTE STOP CONTROL
897
IS USED, REMOVE LEAD 897
FROM TERM 40 TO 53.
IF ICE MODE IS USED
900
REMOVE LEAD
FROM TERM 42 TO 55.
CONTROLLER
J11
GND
N
N
N
N
N
1
2
3
24 VAC
24 VAC
24 VAC
24 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
Rx-/TxRx+/Tx+
GND
GND
*
COMMUNICATIO
PORT
OM WGZ-2 WGZ 030A through 120A 9
Control Panel Layout
Figure 7, Typical Control Panel
MicroTech II Unit
Controller
(3) 24V Controller
Transformers
Terminal Strips
S1, PS1, PS2
(4) Compressor
Grounding Lug
Switches
Contactors
110V Control
Space for
Optional Circuit
Breakers and
Multi-point
Connection
Disconnect
Switch
NOTES:
1. Additional space provided in the upper right section for extra components required for
optional multiple point power connection and optional circuit breakers.
2. Front door has opening on top for access to the MicroTech II controller for viewing
display and making keypad entries without opening the panel door.
Motor Protection Module
The motor protection system consists of an external control module, located on each
compressor, connected to a series of thermistors located in the motor windings and the
compressor discharge port. If the windings experience an over-temperature condition or the
discharge temperature is excessive, the module will trip and shut off the compressor for a
30-minute time delay.
10 WGZ 030A through 120A OM WGZ-2
Start-Up and Shutdown
Pre Start-up
1. The chilled-water system should be flushed and cleaned. Proper water treatment is
required to prevent corrosion and organic growth.
2. With main disconnect open, check all electrical connections in control panel and starter
to be sure they are tight and provide good electrical contact. Although connections are
tightened at the factory, they can loosen enough in shipment to cause a malfunction.
3. Check and inspect all water piping. Make sure flow direction is correct and piping is
made to correct connection on evaporator and condenser.
4. Open all water flow valves to the condenser and evaporator.
5. Flush the cooling tower and system piping to be sure the system is clean. Start
evaporator pump and manually start condenser pump and cooling tower. Check all
piping for leaks. Vent the air from the evaporator and condenser water circuit, as well
as from the entire water system. The cooler circuit should contain clean, treated, noncorrosive water.
6. Check to see that the evaporator water thermostat sensor is securely installed.
7. Making sure control stop switch S1 is open (off) and pumpdown switches PS1 and PS2
are on “manual pumpdown,” place the main power and control disconnect switches to
“on.” This will energize the crankcase heaters. Wait a minimum of 12 hours before
starting the unit.
8. Check compressor oil level. Prior to start-up, the oil level should cover at least onethird of the oil sight glass located in the equalizing line between the compressors or on
the compressor.
9. Note the water pressure drop across evaporator and condenser on pages Error! Bookmark not defined. and Error! Bookmark not defined. and check that water
flow is correct per the system design flow rates.
10. Check the actual line voltage to the unit to make sure it is the same as called for on the
compressor nameplate, within + 10%, and that phase voltage unbalance does not
exceed 3%. Verify that adequate power supply and capacity is available to handle load.
11. Make sure all wiring and fuses are of the proper size. Also make sure that all interlock
wiring is completed per McQuay diagrams.
12. Verify that all mechanical and electrical inspections by code authorities have been
completed.
13. Make sure all auxiliary load and control equipment is operative and that an adequate
cooling load is available for initial start-up.
Start-up
1. Open the compressor discharge shutoff valves until backseated. Always replace valve
seal caps.
2. Open the two manual liquid line shutoff valves.
3. Check to see that the unit circuit breakers are in the “off” position.
4. Check to see that the pumpdown switches, PS1 and PS2, are in the “manual
pumpdown” position and the control system switch S1 is in the “off” position.
5. Put the main power and control circuit disconnects to the “on” position.
OM WGZ-2 WGZ 030A through 120A 11
6. Verify crankcase heaters have operated for at least 12 hours prior to start-up.
Crankcase should be warm to the touch.
7. Check that the MicroTech II controller is set to the desired chilled water temperature.
8. Start the system auxiliary equipment for the installation by turning on the time clock,
ambient thermostat and/or remote on/off switch and water pumps.
9. Check resets of all equipment protection controls.
10. Switch on the unit circuit breakers.
11. Set pumpdown switches PS1 and PS2 to “auto” for restart and normal operation.
12. Start the system by setting the system switch S1 to on.
13. After running the unit for a short time, check the oil level in each compressor
crankcase, rotation of condenser fans (if any), and check for flashing in the refrigerant
sight glass.
14. After system performance has stabilized, it is necessary that the “Compressorized
Equipment Warranty Form” (Form No. 206036A) be completed to establish
commencement of the warranty period. Be sure to list the pressure drop across both
vessels. This form is shipped with the unit and after completion should be returned to
the McQuayService Department through your sales representative.
Weekend or Temporary Shutdown
Move pumpdown switches PS1 and PS2 to the “manual pumpdown” position. After the
compressors have pumped down, turn off the chilled water pump. Note: With the unit in
this condition, it will not restart until these switches are turned back on. The unit has onetime pumpdown. It is important that the compressors pump down before the water flow to
the unit is interrupted to avoid freeze-up in the evaporator.
Leave S1 on and power to the unit so that the crankcase heaters will remain energized.
Start-up after Temporary Shutdown
1. Start the water pumps.
2. With the control system switch S1 in the “on” position, move the pumpdown switches
PS1 and PS2 to the “auto pumpdown” position.
3. Observe the unit operation for a short time, noting unusual sounds or possible cycling
of compressors.
4. Check compressor crankcase heaters.
Extended Shutdown
1. Close the manual liquid line shutoff valves.
2. After the compressors have pumped down, turn off the water pumps.
3. Turn off all power to the unit.
4. Move the control service switch S1 to the “off” position.
5. Close the discharge shutoff valves on the compressor(s) and the liquid outlet valves at
the condenser.
6. Tag all opened disconnect switches to warn against start-up before opening the
compressor suction and discharge valves.
7. Drain all water from the unit evaporator, condenser, and chilled water piping if the unit
is to be shut down during the winter and exposed to below freezing temperatures. Do
not leave the vessels or piping open to the atmosphere over the shutdown period.
12 WGZ 030A through 120A OM WGZ-2
Start-up after Extended Shutdown
1. Inspect all equipment to see that it is in satisfactory operating condition.
2. Remove all debris that has collected on the surface of the condenser coils (remote
condenser models) or check the cooling tower, if present.
3. Open the compressor discharge valves until backseated. Always replace valve seal caps.
4. Open the manual liquid line shutoff valves.
5. Check circuit breakers. They must be in the “off” position.
6. Check to see that the pumpdown switches PS1 and PS2 are in the “manual shutdown”
position and the control system switch S1 is in the “off” position.
7. Put the main power and control circuit disconnects to the “on” position.
8. Allow the crankcase heaters to operate for at least 12 hours prior to start-up.
9. Start the chilled water pump and purge the water piping as well as the evaporator in the
unit.
10. Start the system auxiliary equipment for the installation by turning on the time clock,
ambient thermostat and/or remote on/off switch.
11. Check that the MicroTech II controller is set to the desired chilled water temperature.
12. Check resets of all equipment protection controls.
13. Switch the unit circuit breakers to “on.”
14. Start the system by setting the system switch S1 to “on.”
CAUTION
Most relays and terminals in the control center are powered when S1 is
closed and the control circuit disconnect i s on. Therefore, do not close S1
until ready for start-up or serious equipment damage can occur.
15. Set pumpdown switches PS1 and PS2 to the “auto pumpdown” position for restart and
normal operation.
16. After running the unit for a short time, check the oil level in the compressor oil sight
glass or in the compressor’s equalizing lines for flashing, indicating possible refrigerant
in the oil.
Low Ambient Start
The low ambient start logic is for starting units with remote air-cooled condensers during
periods of low ambient air temperatures.
A low ambient start takes place if the saturated condenser temperature is less than 85.0°F
when the first compressor starts. The low ambient start is active for a time defined by the
Low OAT Start Timer set point. This set point is found on screen three in the alarm set
points menus.
During the low ambient start, the freezestat logic for the low-pressure stop alarm and the
low-pressure events are disabled. The low-pressure stop alarm can still be triggered if the
evaporator pressure drops below 5.0 psi at any time while the circuit is in the ‘Run’ state.
Also, during the low ambient start, the second compressor is not allowed to start. The
evaporator pressure is checked at the end of the low ambient start time frame. If the
pressure is less than the low pressure unload set point, then the low ambient start is not
successful and the compressor will shut off. This will not be a manual reset alarm until
three consecutive attempts have failed. The circuit alarm triggered after the third failed
OM WGZ-2 WGZ 030A through 120A 13
F
F
F
F
attempt is a Low OAT Restart fault. The Low OAT Restart faults are Circuit alarms so each
circuit will attempt to start either compressor three times before the Low OAT Restart fault
is indicated.
Fan High Ambient Rapid Start
The following logic exists to get condenser fans started earlier than normal during unit
starts with warm ambient air temperatures.
• If the outside air temperature higher than 75.0°F the condenser fan staging logic
changes to bring on the first fan on when the condenser pressure is greater than 140 psi.
• The standard condenser fan staging logic would start the first condenser fan when the
condenser pressure is higher than 200.0 psi.
• The last condenser fan on each circuit will not shut down until the condenser pressure
drops below 140.0 psi regardless of the outside air temperature
Sequence of Operation
The following sequence of operation is typical for WGZ water chiller models. The
sequence can vary slightly depending upon options.
Compressor Heaters
With the control circuit power on and the control stop switch S1 off, 115V power is applied
through the control circuit fuse Fl to the compressor crankcase heaters HTR1, HTR2,
HTR3, and HTR4.
Start-up/Compressor Staging
When compressors start and stop.
Stage Up Temp is the LWT temperature at which the next compressor to start will stage up
(start) after at least one compressor on the unit has started and is running.
Start Up Temp is the LWT at which the first compressor starts. The start up temperature
equals the stage up temperature plus the Start Delta temperature. A high Start Delta will
keep the unit off longer and reduce unit cycling at low loads. However, this high Start
Delta will cause a larger excursion from the LWT setpoint before the unit starts.
Stated another way, the Start Delta is the number of degrees above the Evap LWT setpoint,
plus ½ the Dead Band, that determines when the first compressor starts. The Start Delta is
in effect for only the first start after all compressors have been off. Additional compressor
starts and stops are determined by the LWT in respect to the dead band only. The dead
band is automatically set of 30% of the EvapDeltaT selected in menu 3. The following
sequence would occur for the settings shown below:
EvapDelta T=10.0°F Dead Band=3.0°F StartDelta=5.0°F StopDelta=2.0°F
LWT=40.0°F
Figure 8, Staging/Starting Temperatures
EWT
Evap Delta-T Set
LWT Set
50.0°F
10.0°F
40.0°F
Start Del ta T
½DB
½DB
46.5°
41.5°
40.0°
38.5°
For a warm start-up (no
compressors running), the
first compressor will start
at any temperature above
46.5°F. Each subsequent
compressor will start after
the Stage Up Timer has
timed out and if the
temperature is above the
14 WGZ 030A through 120A OM WGZ-2
dead band, 41.5°F in this case. If the LWT stays above 41.5°F, all of three remaining
compressors will eventually stage on after the Stage Up Timer times out between each
stage.
At some point, the chilled water temperature will be dropping and begin to approach the
point when compressors should begin staging off, which is the LWT setpoint minus ½ of
the Dead Band, 38.5°F in this case. If the LWT remains below LWT setpoint minus ½
Dead Band and the Stage Down Timer times out, additional compressor will stage off. The
last compressor will stage off when the LWT falls below the LWT Setpoint minus ½ the
Dead Band minus the Stop Delta T. The stop Delta T is in effect for only the last
compressor running.
If the temperature climbs above 38.5°F all running compressors will remain on. No
compressor staging occurs within the Dead Band. The next-on compressor will start when
the chilled water temperature reaches 41.5°F and the Stage Up Timer times out.
However, in some circumstances this methodology can cause the LWT to drop to
dangerously low levels, with the evaporating temperature below the freeze point, before
stopping. In the example shown in Figure 8, the Shutdown Temp (last compressor off)
would be 36°F.
This would result in a refrigerant evaporating temperature approaching freezing, so the rule
is amended to read:
If the Cool Leaving Water Temperature (LWT) set point is less than half the
Control Band above 39.0° F the Stage Down temperature is calculated as:
Stage Down Temperature = Cool LWT – (Cool LWT - 39.0
Shutdown Temperature = Cool LWT – (Cool LWT - 39.0
°
F), and the
°
F) – Stop Delta T
This keeps the Stage Down Temp above 39°F and the Shutdown Temp above 36°F, as the
maximum Stop Delta T allowed is 3-degrees.
Which compressor starts and stops. One compressor per circuit will start before starting
the second compressor on any circuit. In other words, the compressor with the lowest
number of starts will start first. The compressor with the lowest number of starts on the
other circuit will start next, so that one compressor on each circuit will be running. The
third compressor on will be the compressor on either circuit with the fewest starts. The
remaining compressor will be the last on. If a circuit is unavailable for any reason, the
second compressor. on the operating circuit will stage on. Only two compressors (on the
one circuit) will be operating.
There is a 150 second delay after power-up before any compressor is allowed to start.
When staging down, one compressor on each circuit will be left on until each circuit has
only one compressor running. In other words, the compressor, on either circuit, with the
most run-hours will stop first. The compressor with the most run-hours on the other circuit
will stop next. One compressor on each circuit will be running. The third compressor off
will be the one, on either circuit, with the most run-hours. The remaining compressor will
be the last off. See the following description of pumpdown.
Table 3, Staging in Cool and Glycol Mode
Description Occurs When: Action Taken
Stage #1 ON
(See Notes Below)
Stage #2 ON After Stage Up Delay times out then, LVG Evap
Stage #3 ON After Stage Up Delay times out, then LVG Evap
Stage #4 ON After Stage Up Delay times out then, LVG Evap
Lvg Evap T > Evap LWT SP + (DB/ 2) + S t artup
Delta T
T > Evap LWT SP + (DB/2)
T > Evap LWT SP + (DB/2)
T > Evap LWT SP + (DB/2)
Available compressor with l east
starts, ON
Available compressor on the other
circuit with least starts, ON
Available compressor on ei ther circuit
with least starts, ON
Remaining compressor, ON
Continued next page.
OM WGZ-2 WGZ 030A through 120A 15
Description Occurs When: Action Taken
Stage #4 OFF After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (CB/2)
Stage #3 OFF After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)
Stage #2 OFF After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)
Stage #1 OFF After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)-StopDelta T
Note 1: DB (Dead Band) = Evap W ater Delta T x .3
Compressor with most run hours,
OFF
Compressor on the other ci rcuit with
most run hours, OFF
Compressor on either circuit with
most run hours, OFF
Remaining compressor, OFF
Manual Compressor Disable Logic
Logic is available that allows the operator to manually enable and disable compressors.
When a compressor is disabled, it is considered unavailable to start in the staging logic.
This allows a damaged compressor to be taken offline while the remaining compressor can
still provide some cooling
• The Compressor Disable set points are found on Compressor Set Points screens three
and four.
• A running compressor cannot be disabled until it has been shutdown.
• If all of the compressors on a circuit are disabled, then the circuit will be disabled.
• If both circuits have all of their compressors disabled, then the Unit State will remain
Off
Automatic Pumpdown
WGZ units are equipped with single pumpdown control. When the last compressor running
on either circuit is ready to shut off, the liquid line solenoid valve (LLSV) is closed first
and the compressor continues to run until the pumpdown pressure is reached, at which time
the compressor shuts off. The shut off pressure is set at 15 psi below the Low Evaporator
pressure Unload setpoint.
When the first compressor on a circuit starts, the LLSV opens simultaneously.
Manual Pumpdown
When the Pumpdown Switch is in the pumpdown position, Compressor #3 or #4
(depending on circuit) will shut off. Then the Liquid Line and Hot Gas Bypass Valves will
close. The operating compressor will pump out the refrigerant. When the Suction Pressure
is at 40 psig, the compressor will stop.
Chilled Water and Condenser Water Pumps
The chiller MicroTech II controller can be programmed to start and stop the system chilled
water and condenser water pumps. They may also be controlled by the BAS or manually.
Programming directions and the sequence of operation can be found beginning on page 30.
Cooling Tower Control
The cooling tower fans and/or the tower bypass valve can be controlled by the MicroTech II
controller. This provides a simple and direct method to control the unit’s discharge
pressure. Programming directions and the sequence of operation can be found on page 44.
Some means of discharge pressure control must be installed if the condenser water
temperature can fall below 60°F (16°C).
16 WGZ 030A through 120A OM WGZ-2
Condenser Fan Control
Model AA chillers equipped with air-cooled or evaporative-cooled condensers usually
require some form of discharge pressure control. The MicroTech II controller can be
programmed to provide this function by cycling condenser fans based on the unit discharge
pressure. Directions on the pressure settings can be found on page 44.
ICE
In ICE mode, the compressors stage to 100% load until the LWT is less than the ICE LWT
SP. Then Compressors #3 and #4 shut down. Following that, Compressors #1 and #2 shut
down after going through normal pumpdown on both circuits. There is a programmable,
start-to-start, Ice Mode Start Delay that limits the frequency of starts when in the ice mode.
The timer can be manually cleared to force a restart.
OM WGZ-2 WGZ 030A through 120A 17
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.