McQuay WGTV User Manual

SmartSource™ Two-Stage Vertical Water Source Heat Pumps
SmartSource™ two-stage water source heat pumps are devel­oped using state of the art technology and design techniques to create products with the highest part load efficiencies. These units typically operate at low compression and low fan speeds the majority of the time. The result is higher energy savings, quieter operation, and precise temperature and humidity control, providing unmatched comfort. High EERs that far exceed ASHRAE 90.1 standards make these units perfect for LEED projects and rebate opportunities. All units are available geothermal ready from the factory with many features to easily match your application requirements.
1. ECM Fan Motor: 4 field adjustable cfm settings and 28
programmed cfm values provide a wide range of airflow selections for quieter operation and lower energy con­sumption.
2. Copeland UltraTech Two-Stage Compressor: available
in a variety of commercial voltages, mounted on a double isolation system for reduced sound and vibration.
3. Refrigerant Circuit: Utilizes R-410A refrigerant with a bi-
flow thermal expansion valve for easy metering and four way solenoid reversing valve.
4. MicroTech III Controls: Easy open-protocol integration
with optional LonWorks® or BACnet®.
5. Unit Status LED: Instant visuals on unit operation for
easy troubleshooting and advanced diagnostics.
6. 4-Sides Filter Rack with Standard 2” or Optional 4” Filters: Designed for easy filter maintenance. MERV 8 &
13 filter options with gasketed filter rack meet LEED-NC EQc5 applications with leakage rate at less than 4 CFM per square foot of filter area at 0.5”ESP.
7. Stainless Steel Drain Plan: Sloped with lipless drain con-
nection for positive condensate flow, meets ASHRAE 62.1 Section 5.11.
8. Flush Mounted Fittings: Easy one wrench connection,
securely fastened to the cabinet corner posts.
9. Blower and Motor Orifice Ring: Easy service removal
without having to remove the blower housing or discon­necting the unit from the duct work.
10. Durable Cabinet Construction: Heavy gauge steel with
powder coated textured paint, lined with cleanable foil faced insulation on the airside.
9
6
7
10
2
3
5
8
4
1
Performance Data
Unit Size Stage CFM GPM
026
032
038
044
049
064
072
Water Loop (Boiler Tower) Ground Loop (Geothermal)
Cooling Heating Cooling Heating
Btu/hr EER Btu/hr COP Btu/hr EER Btu/hr COP
Stage 1 700 6.5 19,800 20.2 21,800 6.4 22,200 29.7 15,100 4.5
Stage 2 800 6.5 26,400 18.0 29,300 5.7 27,600 20.7 18,100 4.1
Stage 1 875 7.5 24,700 18.5 27,800 6.0 33,800 25.9 19,800 4.5
Stage 2 1,000 7.5 32,500 16.5 36,400 5.3 33,800 18.9 23,700 4.1
Stage 1 1,100 9.0 28,300 20.2 32,600 6.4 30,500 28.8 22,500 4.6
Stage 2 1,250 9.0 39,000 17.6 44,400 5.6 40,200 20.1 28,100 4.2
Stage 1 1,225 10.5 32,900 19.7 36,600 6.0 35,500 28.3 25,600 4.3
Stage 2 1,400 10.5 44,400 17.3 50,100 5.4 45,900 19.8 31,700 4.0
Stage 1 1,400 12.2 36,900 19.5 40,800 6.0 39,600 28.2 29,200 4.4
Stage 2 1,600 12.2 48,900 16.7 55,300 5.3 50,600 19.2 35,900 4.0
Stage 1 1,750 16.0 48,200 19.6 53,800 5.8 52,200 27.9 38,300 4.3
Stage 2 2,000 16.0 64,800 17.4 76,100 5.2 67,100 19.7 47,000 3.9
Stage 1 1,920 17.5 56,400 18.4 64,600 5.4 60,700 26.1 46,200 4.1
Stage 2 2,160 17.5 72,700 15.9 88,400 5.0 75,300 18.1 55,200 3.7
Many Factory-Mounted Options and Accessories
Four Unique Dehumidification Options:
• SmartDehumidification– Uses hot gas reheat, humidi-
stat, 2-stage thermostat & smart air flow management for precise humidity control.
• SimplifiedDehumidification– Uses a 3-stage thermo-
stat to optimize unit capacity and fan speed for maximum latent capacity while decreasing room humidity levels.
• HumidistatControlledDehumidification– Uses a hu-
midistat and 2-stage thermostat to control room humidity levels.
1
2
3
1. Hot Gas Reheat
2. Desuperheater
3. Waterside Economizer
4
4. Loop Circulating Pumps
Dimensions in inches (mm)
Unit Size
026, 032 22.40" (569) 26.00" (660) 48.00" (1219)
038 25.00" (635) 32.50" (826) 50.50" (1283)
044, 049 25.00" (635) 32.50" (826) 54.50" (1384)
064, 072 25.00" (635) 32.50" (826) 58.50" (1486)
Overall Cabinet Dimensions in inches (mm)
W D H
• DehumidificationOnly– Uses a humidistat in cooling
only mode.
WatersideEconomizer– Reduces compressor energy con-
sumption by using a cold water coil for cooling under suitable conditions.
LoopPumps– Convenient factory-mounted pumps with flow
and head capabilities for most geothermal applications.
5,10,15&20kWElectricHeat– Integral electric heat coil
with controls for primary, supplemental, boilerless or emergency heat.
Desuperheater– For “free” domestic hot water. Non-FusedDisconnectOption– Convenient Power shut-off
and lockout at the unit.
Extended Range Coaxial Heat Exchanger Coil and Piping
Insulation– for geothermal application. InsulationOptions– Foil faced, closed cell or 1/2” standard
fiberglass options for the air and compressor side of the unit.
EpoxyCoatedCoils– For extra corrosion protection to meet
ASTM B-11 3000 hour salt spray test.
DeluxeSoundPackage– Reduces sound levels for quieter
operation.
5-YearExtendedPartsWarrantyAvailable
Voltages
Unit Size
026-032
038-072
©2012 McQuay International A/SP 31-354
Horizontal Unit
Volts Hz Phase
208-230 60 1
265 60 1
208-230 60 3
460 60 3
208-230 60 1
208-230 60 3
460 60 3
Loading...