SmartSource™ Two-Stage Horizontal Water Source Heat Pumps
SmartSource™ two-stage water source heat pumps are
developed using state of the art technology and design
techniques, resulting in products with the highest part load
efficiencies. These units typically operate at low compression
and low fan speeds the majority of the time, for higher energy
savings, quieter operation, and precise temperature and
humidity control, providing unmatched comfort.
High EERs that far exceed ASHRAE 90.1 standards make these
units perfect for LEED projects and rebate opportunities. All
units are available geothermal-ready from the factory with
many features to easily match your application requirements.
1. ECM Fan Motor: 4 field adjustable cfm settings and 28
programmed cfm values provide a wide range of airflow
selections for quieter operation and lower energy consumption.
2. Copeland UltraTech Two-Stage Compressor: available
in a variety of commercial voltages, mounted on a double
isolation system for reduced sound and vibration.
3. Refrigerant Circuit: Utilizes R-410A refrigerant with a bi-
flow thermal expansion valve for easy metering and four
way solenoid reversing valve.
4. MicroTech III Controls: Easy open-protocol integration
with optional LonWorks® or BACnet®.
5. Unit Status LED: Instant visuals on unit operation for
easy troubleshooting and advanced diagnostics.
6. 4-Sides Filter Rack with Standard 2” or Optional 4”
Filters: Designed for easy filter maintenance. MERV 8 &
13 filter options with gasketed filter rack meet LEED-NC
EQc5 applications with a leakage rate less than 4 CFM per
square foot of filter area at 0.5”ESP.
7. Stainless Steel Drain Plan: sloped with lipless drain con-
nection for positive condensate flow, meets ASHRAE 62.1
Section 5.11.
8. Flush Mounted Fittings: Easy one-wrench connection,
securely fastened to the cabinet corner posts.
9. Blower and Motor Orifice Ring: Easy service removal
without having to remove the blower housing or disconnecting the unit from the duct work.
10. Durable Cabinet Construction: Heavy gauge steel with
powder coated textured paint, lined with cleanable, foilfaced insulation on the airside..
9
6
7
1
10
4
3
2
5
8
Performance Data
Unit Size Stage CFM GPM
026
032
038
044
049
064
072
Water Loop (Boiler Tower) Ground Loop (Geothermal)
Cooling Heating Cooling Heating
Btu/hr EER Btu/hr COP Btu/hr EER Btu/hr COP
Stage 1 700 6.5 19,800 20.2 21,800 6.4 22,200 29.7 15,100 4.5
Stage 2 800 6.5 26,400 18.0 29,300 5.7 27,600 20.7 18,100 4.1
Stage 1 875 7.5 24,700 18.5 27,800 6.0 33,800 25.9 19,800 4.5
Stage 2 1,000 7.5 32,500 16.5 36,400 5.3 33,800 18.9 23,700 4.1
Stage 1 1,100 9.0 28,300 20.2 32,600 6.4 30,500 28.8 22,500 4.6
Stage 2 1,250 9.0 39,000 17.6 44,400 5.6 40,200 20.1 28,100 4.2
Stage 1 1,225 10.5 32,900 19.7 36,600 6.0 35,500 28.3 25,600 4.3
Stage 2 1,400 10.5 44,400 17.3 50,100 5.4 45,900 19.8 31,700 4.0
Stage 1 1,400 12.2 36,900 19.5 40,800 6.0 39,600 28.2 29,200 4.4
Stage 2 1,600 12.2 48,900 16.7 55,300 5.3 50,600 19.2 35,900 4.0
Stage 1 1,750 16.0 48,200 19.6 53,800 5.8 52,200 27.9 38,300 4.3
Stage 2 2,000 16.0 64,800 17.4 76,100 5.2 67,100 19.7 47,000 3.9
Stage 1 1,920 17.5 56,400 18.4 64,600 5.4 60,700 26.1 46,200 4.1
Stage 2 2,160 17.5 72,700 15.9 88,400 5.0 75,300 18.1 55,200 3.7
Many Factory-Mounted Options and Accessories
Four Unique Dehumidification Options:
• SmartDehumidification– Uses hot gas reheat, humidi-
stat, 2-stage thermostat & smart air flow management for
precise humidity control.
• SimplifiedDehumidification– Uses a 3-stage thermo-
stat to optimize unit capacity and fan speed for maximum
latent capacity while decreasing room humidity levels.
• HumidistatControlledDehumidification– Uses a hu-
1
2
3
4
1. Hot Gas Reheat 3. Field Adjustment of ECM Fan
2. Loop Circulating Pumps Motor
4. Waterside Economizer
Dimensions in inches (mm)
Unit Size
026, 032 22.40" (569) 63.30" (1608) 19.30" (490)
038 25.00" (635) 73.00" (1854) 21.30" (541)
044, 049 25.00" (635) 78.40" (1991) 21.30" (541)
064, 072 25.00" (635) 83.80" (2129) 21.30" (541)
Overall Cabinet Dimensions in inches (mm)
W L H
midistat and 2-stage thermostat to control room humidity
levels.
• DehumidificationOnly– Uses a humidistat in cooling
only mode.
Waterside Economizer - Reduces compressor energy con-
sumption by using a cold water coil for cooling under suitable
conditions.
LoopPumps– Convenient factory mounted pumps with flow
and head capabilities for most geothermal applications.
5,10,15&20kWElectricHeat– For alternate heat source
with controls for primary, supplemental, boilerless or emergency heat. (Available as a field-installed duct heater kit)
Non-FusedDisconnectOption– Convenient Power shut-off
and lockout at the unit.
Extended Range Coaxial Heat Exchanger Coil and Piping
Insulation– for geothermal application.
InsulationOptions– Foil faced, closed cell or 1/2” standard
fiberglass options for the air and compressor side of the unit.
EpoxyCoatedCoils– For extra corrosion protection to meet
ASTM B-11 3000 hour salt spray test.
DeluxeSoundPackage– Reduces sound levels for quieter
operation.
5-YearExtendedPartsWarrantyAvailable
Voltages
Unit Size
026-032
038-072
©2012 McQuay International
A/SP 31-353
Horizontal Unit
Volts Hz Phase
208-230 60 1
265 60 1
208-230 60 3
460 60 3
208-230 60 1
208-230 60 3
460 60 3