McQuay VHC009 Installation Manual

Installation & Maintenance Manual
Vertical Stack Water Source Heat Pumps
Model VHC Vertical Stack Chassis Model VHF Vertical Stack Cabinet Unit Sizes 009 – 036 / R-410A Refrigerant
IM 986-2
Group: WSHP Part Number: 669646403 Date: May 2012
©2012 McQuay International • 800.432.1342 • www.daikinmcquay.com
Page 2 of 48 / IM 986-2
Table of Contents
Model Nomenclature ............................ 4-5
Vertical Stack Model VHF (Cabinet)...............4
Vertical Stack Model VHC (Chassis)...............5
Receiving, Storage & Handling ................... 6-7
Disassembling Upper & Lower Cabinet Sections..... 7-8
Dimensional Data .............................. 9-10
Unit Size 009-018 ..............................9
Unit Size 021-036 .............................10
Pre-Installation Considerations ....................11
Cabinet Configurations...........................12
Typical Framing & Discharge Arrangements.........13
Critical Dimensions ..............................14
Framing Locations to Unit Openings..............14
Vertical Riser Stub-Outs Locations to
Unit Knockouts...............................14
Return Air Grille/Panel Dimensions...............15
Installation Procedure.........................16-26
Risers & Cabinet........................... 16-17
Cleaning & Flushing Water System............ 17-19
Power Wiring From Building to Unit...........19-20
Connect Condensate Drain Hose to Drain Stubout ...20
Water Connections ......................... 20-21
Installing Unit Chassis .........................22
Making Cabinet to Chassis Wiring Connections . . . . . 22
Installing & Wiring the Remote Control Node ......23
Installing the Return Air Grille/Panel..............24
Installing the Discharge Air Diffuser ..............25
Twin Units Installation .........................26
Controls..................................... 27-34
MicroTech III Unit Controller ................... 27
Remote Reset Feature ..........................27
MicroTech III Controller Terminal Locations
& Descriptions ............................ 28-29
I/O Expansion Module .........................30
MicroTech III Controller with Lon Module.........31
MicroTech III Controller with BACnet Module .. 32-33 MicroTech III Controller with Lon Module on
Board Diagram ...............................34
Typical Wiring Diagrams ...................... 35-38
MicroTech III Unit Controller, 2-Speed Fan (Toggle or
Thermostat), PSC Motor 208-230/60Hz/1-Phase,
Unit Sizes 009-018............................35
MicroTech III Unit Controller, 2-Speed Fan (Toggle or
Thermostat), PSC Motor 265-277/60Hz/1-Phase,
Unit Sizes 009-036............................36
MicroTech III Unit Controller, 2-Speed Fan (Toggle or
Thermostat), X13 Motor 208-230/60Hz/1-Phase,
Unit Sizes 021-036............................37
MicroTech III Unit Controller, 2-Speed Fan (Toggle or
Thermostat), X13 Motor 265-277/60Hz/1-Phase,
Unit Sizes 021-036............................38
Start-up........................................39
Additional Accessories (General) ................ 39-43
Thermostats & Temperature Sensors ........... 39-43
Troubleshooting .............................. 44-47
The in and outs of R-410A ......................44
Refrigeration Circuit...........................45
The Water Source Heat Pump Unit ...............46
General Use & Information .....................47
IM 986-2 / Page 3 of 48
Model Nomenclature
Vertical Stack Water Source Heat Pump – Cabinet (VHF)
W VHF 1 009 B E DP LRY F 12 S 088
Product Category
W - WSHP
Product Code
VHF - Cabinet
Design Series
1 2
Unit Size - Tons
009 - 3/4 Ton 012 - 1 Ton 015 - 1-1/4 Ton 018 - 1-1/2 Ton 021 - 1-3/4 Ton 024 - 2 Ton 030 - 2-1/2 Ton 036 - 3 Ton
Controls
B - MicroTech III C - MicroTech III With LonWorks D - MicroTech III With BACnet
Voltage
A - 115/60/1 ph E - 208-230/60/1 ph J - 265-277/60/1 ph
Secondary Drain Pan
GL - Standard Galvanized Steel SS - Stainless Steel
Cabinet Type
080 - 80" Cabinet Height 088 - 88" Cabinet Height 092 - 92" Cabinet Height 096 - 96" Cabinet Height
Filter Option
S - Standard 1" Throwaway P - 2" Pleated (Merv 7) Y - None
Blower Motor
12 - 2-Speed PSC Motor 32 - ECM 2-speed 2.3 Motor 33 - ECM 2-speed X13 Motor
Power Connection
F - Fused Disconnect N - Non-Fused Disconnect H - HACR Breaker
Supply Air Conguration
LYY - Single Supply Outlet, Left Side RYY - Single Supply Outlet, Right Side FYY - Single Supply Outlet, Front Side BYY - Single Back Side Supply Outlet TYY - Single Top Supply Outlet LFY - Double Supply, Left Side and Front Side LRY - Double Supply, Left Side and Right Side LBY - Double Supply, Left Side and Back Side RFY - Double Supply, Right Side and Front Side RBY - Double Supply, Right Side and Back Side BFY - Double Supply, Back Side and Front Side LTY - Double Supply, Left Side and Top RTY - Double Supply, Right Side and Top BTY - Double Supply, Back Side and Top FTY - Double Supply, Front Side and Top LFT - Triple Supply, Left Side, Front Side and Top LRT - Triple Supply, Left Side, Right Side and Top FRT - Triple Supply, Front Side, Right Side and Top FBT - Triple Supply, Front Side, Back Side and Top BRT - Triple Supply, Back Side, Right Side and Top BLT - Triple Supply, Back Side, Left Side and Top YYY - Closed Supply Plenum for eld modication
Page 4 of 48 / IM 986-2
Note: For illustration purposes only. Not all options avail-
able with all models.
Please consult McQuay Sales Representative for
specic availability.
Model Nomenclature
Vertical Stack Water Source Heat Pump – Chassis (VHC)
W VHC 1 012 B E A C AMY C
Product Category
W - WSHP
Product Code
VHC - Chassis
Design Series
1 2
Unit Size - Tons
009 - 3/4 Ton 012 - 1 Ton 015 - 1-1/ 4 Ton 018 - 1-1/2 Ton 021 - 1-3/4 Ton 024 - 2 Ton 030 - 2-1/2 Ton 036 - 3 Ton
Controls
B - MicroTech III C - MicroTech III With L D - MicroTech III With BACnet
onWorks
Voltage
A - 115/60/1 ph E - 208-230/60/1 ph J - 265-277/60/1 ph
Coax Coil Construction
C - Copper Inner - Steel Outer S - CuproNickel Inner - Steel Outer X - Special
Chassis Construction
AYY - Standard Fiberglass Insulation EYY - IAQ - Cellular Insulation AMY - Standard w/Compressor Blanket EMY - IAQ w/Compressor Blanket AYC - Standard w/E-Coated Air Coil EYC - IAQ - Cellular w/E-Coated Air Coil AMC - Standard w/Comp Blanket and Coated Air Coil EMC - IAQ w/Comp Blanket and Coated Air Coil
Motorized 2-Way Isolation Valve
C - 2-Way Motorized 1/2" Iso-Valve, General Close-Off Pressure N.C. (Normally Closed) V - 2-Way Motorized 1/2" Iso-Valve, General Close-Off Pressure N.O. (Normally Open) H - 2-Way Motorized 1/2" Iso-Valve, High Close-Off Pressure N.C. (Normally Closed) D - 2-Way Motorized 3/4" Iso-Valve, General Close-Off Pressure N.C. (Normally Closed) K - 2-Way Motorized 3/4" Iso-Valve, General Close-Off Pressure N.O. (Normally Open) J - 2-Way Motorized 3/4" Iso-Valve, High Close-Off Pressure N.C. (Normally Closed) Y - None X - Special
Refrigerant
A - R-410A X - Special
Note: For illustration purposes only. Not all options
available with all models.
Please consult McQuay Sales Representative
for specic availability.
IM 986-2 / Page 5 of 48
Receiving and Storage
Upon receipt of the equipment, check the carton and pallets for visible damage. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted.
IMPORTANT
This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier’s refusal to honor a damage claim. The form required to le such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fteen (15) days of the delivery date and le a claim with the carrier.
Cabinet Skid (4-units per skid)
Never stack cabinets higher than as illustrated in Figure 1 at any time during transportation or storage or damage may occur.
Figure 1: Unit Cabinet Skid as Shipped and Stored
Chassis Skid (4 per skid, stored two skids high)
Never stack chassis´ higher than as illustrated in Figure 2 at any time during transportation or storage or damage
may occur.
Figure 2: Chassis Skids Stacked 2 High Maximum
For storing, each carton is marked with “up” arrows.
4'
6'
Storage and Operating Environment
Temporary storage at the job site must be indoor, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather patterns will not harm the units. Excessively high temperatures, 140°F (60°C) and higher, may deteriorate certain plastic materials and cause permanent damage.
Storage Temperature:
-40ºF (-40ºC) to 140ºF (60ºC)
Operating Temperature:
32ºF (0ºC) to 140ºF (60ºC)
Humidity:
10%RH to 90%RH Non-condensing
PCB Material and Flammability Rating:
IPC/ANSI FR or CEM material as required to meet UL
94V-0 ammability rating.
Page 6 of 48 / IM 986-2
Handling
Carefully check items against the bills of lading to verify all crates and cartons have been received. Cabinets and Chassis normally ship four to a pallet.
Carefully inspect all units for shipping damage. Report
damage immediately to the carrier and le a claim.
Check the unit data plate to be sure the unit electrical agrees with the power supply available (Figures 3).
Figure 3: Unit Components & Descriptions - Received as Assembled Cabinet with Chassis Shipped Separate
4
1a
1
2
1b
1b
3
Unit Data Plate
Stub-out Seals
DO NOT handle units by the riser piping. Riser clamps hold the riser in position; they are not designed to support the cabinet weight. The clamps are removed after the unit is installed.
Unit cabinets are factory assembled and wired and have individual thermostat control capability. They are installed by stacking one unit on top of the other. While installing, prevent dirt and other foreign matter from entering the risers and plugging lines or valves. See "Cleaning & Flushing Water System" on page 16.
General Information
McQuay Vertical Stack units are designed for use in
multiple oor apartments, ofce buildings, hotels,
nursing homes and other similar applications. They
require a minimum amount of oor space and are
designed for multiple discharge arrangement. Installation and maintenance must follow accepted
industry practices as described in the ASHRAE Handbook, the National Electric Code, and other applicable standards. Install this equipment in accordance with regulations of authorities having jurisdiction and with all applicable codes.
WARNING
Installation and maintenance are to be performed by qualied personnel who are familiar with local codes and regulations, and experienced with this type of equipment.
WARNING
The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only.
Chassis
Data Plate
Component Descriptions (Assembled Cabinet)
1. Cabinet assembly complete (without chassis) 1a. Pipe riser sets (inlet, outlet and condensate) 1b. Inner front panel and lter bracket
2. Cooling and heating chassis (shipped separate)
3. Return air grille/panel (accessory)
4. Double-deection diffuser (accessory)
!
CAUTION
Sharp metal edges are a hazard, use care when servicing to avoid contact with them.
IM 986-2 / Page 7 of 48
Disassembling Upper and Lower Cabinet Sections
The Vertical Stack unit cabinet ships completely assembled. If required, it may be disassembled into two (2) sections (upper-fan/discharge cabinet) and (lower chassis/return air cabinet) to make it easier to handle. To disassemble, do the following.
1. Remove risers (if received attached).
2. Remove the three (bottom row) screws on the back of the unit as shown in Figure 4.
Note: Retain all screws for later use to reassemble unit in reverse order as described in steps 1-7. Number of screws will vary depending on unit size.
3. Carefully lay the unit down on its back and remove the remaining eight (8) screws on the left and right side of the cabinet (Figure 5).
5. Remove the ten (10) screws and lift off the front
panel/lter rack to gain access to the cabinet interior
(Figure 6).
Figure 5: Remove remaining eight (8) screws on the left and right sides of the cabinet
Four (4) screws located on left side of cabinet
Figure 6: Remove the ten (10) screws from the front panel/
lter rack.
6. Locate and remove the six (6) screws located inside the cabinet joining the upper and lower cabinet sections (Figure 7).
Note: Pull the insulaton away from the walls of the cabinet interior to get access to the screws.
7. Separate the lower return air cabinet section from the upper blower/discharge cabinet section (Figure 8).
Figure 4: Remove three (3) screws (bottom row) on the back
of the unit.
Back of Unit
Figure 7: Remove the six (6) screws located on the interior
of the unit.
Return air cabinet section interior
Figure 8: Separate the lower cabinet section from the upper cabinet
Page 8 of 48 / IM 986-2
Three screws (bottom row)
Dimensional Data
Figure 9: Model VHC/VHF – 18" × 18" Cabinet – Size 009-018
Left Side View
Front View
Top View
Dimensions
80" 18.07" 18.11" 37.50" .88" 58.09" 2.38" 3.125" 2" 2" 6.72" 12.4" 7.9" 3.3"
Unit Size
009–018
18" × 18"
Cabinet
A B C D E F G J K L M N P Q
88" 18.07" 18.11" 37.50" .88" 58.09" 2.38" 3.125" 2" 2" 6.72" 12.4" 7.9" 3.3"
92" 18.07" 18.11" 37.50" .88" 58.09" 2.38" 3.125" 2" 2" 6.72" 12.4" 7.9" 3.3"
96" 18.07" 18.11" 37.50" .88" 58.09"
A R S T U V
80" 3" 3" 3.3" 4.5" 4.5"
88" 3" 3" 3.3" 4.5" 4.5"
92" 3" 3" 3.3" 4.5" 4.5"
96" 3" 3" 3.3" 4.5" 4.5"
2.38" 3.125"
Table 1.
Discharge Openings
Unit Size
W H W H W H W H
009 – 012 015 – 018
2" 2" 6.72" 12.4" 7.9" 3.3"
Single Double Triple Single-Top Opening
14" 16" 14" 8" NR NR 12" 12"
14" 16" 14" 8" 14" 8" 12" 12"
NR = Not Recommended
IM 986-2 / Page 9 of 48
Dimensional Data
Figure 10: Model VHC/VHF – 24" × 24" Cabinet – Size 021-036
Front View
Left Side View
Top View
Dimensions
Unit Size
80" 24" 24.04" 37.50" .88" 58.08" 2.38" 4.54" 2" 3" 6.72" 12.13" 7.63" 3.13"
A B C D E F G J K L M N P Q
021–036
88" 24" 24.04" 37.50" .88" 58.08" 2.38" 4.54" 2" 3" 6.72" 12.13" 7.63" 3.13"
24" × 24"
92" 24" 24.04" 37.50" .88" 58.08" 2.38" 4.54" 2" 3" 6.72" 12.13 7.63" 3.13"
Cabinet
96"
A R S T U V
80" 3.09" 3.10" 3.12" 4.50" 4.50"
88" 3.09" 3.10" 3.12" 4.50" 4.50"
92" 3.09" 3.10" 3.12" 4.50" 4.50"
96" 3.09" 3.10" 3.12" 4.50" 4.50"
24" 24.04"
37.50" .88" 58.08"
2.38" 4.54"
2" 3" 6.72" 12.13" 7.63" 3.13"
Table 1.
Discharge Openings
Unit Size
W H W H W H W H
021 – 024 030 – 036
Single Double Triple Single-Top Opening
NR NR 18" 10" 18" 10" 18" 18"
NR NR 18" 14" 18" 10" 18" 18"
NR = Not Recommended
Page 10 of 48 / IM 986-2
Pre-Installation Considerations
1. To prevent damage to equipment, do not operate supplementary heating and cooling during the construction period.
2. Inspect the carton for any specic tagging numbers
indicated by the factory per a request from the installing contractor. At this time the voltage, phase and capacity should be checked against the plans.
3. Check the unit size against the plans to verify that the unit is being installed in the correct location.
4. Before installation, check the available dimensions of the area where the unit is to be installed versus the dimensions of the unit.
5. Note the location and routing of water piping, condensate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings.
6. The installing contractor will nd it benecial
to confer with piping, sheet metal, and electrical foremen before installing any unit.
Figure 11: Typical Side by Side Unit Installation
Note: Check the unit data plate for correct voltage with the plans before installing the equipment.
WARNING
Make sure all electrical ground connections are made in accordance with local code.
WARNING
The contractor shall cover the units to protect the machines during nishing of the building. This is critical while spraying reproong material on bar joists, sandblasting, spray painting and plastering.
For Optimum Unit Performance and to Help Minimize Noise and Vibration
● Adhere to the "Critical Dimensions" for locations of
framing and distances to the cabinet.
● Install a 1/4" thick vibration isolation pad under the
entire footprint of the unit cabinet base.
● Be sure there are no kinks and that the stainless
steel braided hoses do not come in contact with and vibrate on chassis and cause noise.
● Ensure there is no metal-to-metal contact between
return air grille and cabinet and the discharge diffuser and the cabinet, use provided gaskets.
● Air balancing in ducted applications is critical for proper airow at each diffuser.
NOTICE
Top air discharge units will require turning vanes and/or a volume damper for proper air flow and balancing, to mini­mize turbulence. These components must be field-installed and furnished in accordance with SMACNA guidelines.
IM 986-2 / Page 11 of 48
Cabinet Configurations
Figure 12: Single Side Discharge
Figure 13: Double Side Discharge
Figure 14: Side & T op Discharge (See Notice on page 11) Figure 15: Double Side & Top Discharge (See Notice on page 11)
Figure 16: Top Discharge (See Notice on page 11) Figure 17: Closed Plenum – Field Modication Required
= Return Riser = Supply Riser = Drain = Return Air = Discharge Air = Top Discharge
Page 12 of 48 / IM 986-2
Figure 18: Typical Framing & Discharge Arrangements
Double Side Discharge
= Return Air
= Discharge Air
Typical Ducted Application
NOTICE
Top air discharge units will require turning vanes and/or a volume damper for proper air flow and balancing, to mini­mize turbulence. These components must be field-installed and furnished in accordance with SMACNA guidelines.
Note: All ducted applications require a unit that utilizes an ECM-X13 or ECM 2.3 motor (sizes 021-036). X13 motors are factory set for 2-speeds, 2 and 4 tap. For ducted unit applications only position 1 and 2-speed motor taps should be used. Additionally, static pressure must not exceed 0.40 inch static. See table below.
ECM-X13 Motor CFM - Sizes 021 - 036 External Static Pressure (Ducted Applications)
External Static Pressure, WC" Unit Size Speed
Speed 1
Speed 1
021
024
Speed 2
030
Speed 2
036
Speed 2
Speed 1 Speed 2
Speed 1
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
830
770
830
770
1200
1080
1200
1080
820
760
820
760
1180
1060
1180
1060
800
740
800
740
1160
1030
1160
1030
780
720
780
720
1140
1010
1140
1010
770
700
770
700
1120
990
1120
990
760
690
760
690
1100
970
1100
970
730
660
730
660
1080
950
1080
950
850
780
850
780
1230
1100
1230
1100
710
640
710
640
1060
930
1060
930
IM 986-2 / Page 13 of 48
Critical Dimensions
Critical Dimensions
Location of studs is critical for proper installation and
t up and can help to reduce unit noise due to vibration
when properly installed.
Figure 19: Framing Locations to Unit Openings
Note: If the unit cabinet was shipped without risers attached it will be necessary to remove the appropriate riser knockouts prior to positioning the cabinet and connecting to the riser stub outs.
Figure 20: Vertical Riser Stub-Outs Locations to Unit Knockouts
Unit Size 021-036 = 4.54" Unit Size 009-018 = 3.125"
1/2" Conduit Fitting for Electrical Supply
Unit Front Return Air
Table 1: Reference Locations for Framing
Framing Locations
Unit Size
A
80" 18" 2.07" 6" 22.25" 58.75" 61" 79" 3.125" 3.125"
18" × 18"
92" 18" 2.07" 6" 22.25" 58.75" 73" 91" 3.125" 3.125"
96" 18" 2.07" 6" 22.25" 58.75" 77" 95" 3.125" 3.125"
80" 24" 2.125" 6" 28.25" 59.5" 63" 79" 4.54" 3.125"
24" × 24"
92" 24" 2.125" 6" 28.25" 59.5" 75" 91" 4.54" 3.125"
96" 24" 2.125" 6" 28.25" 59.5" 79" 95" 4.54" 3.125"
1
Dimension includes approximately 1/4" for vibration isolation pad
2
Dimension “E” ± 0.125
3
Dimension “G” will vary based on diffuser size. Refer to Table 2, Discharge Knockout Openings on page 16.
4
Dimension “H” will vary based on cabinet height selected.
88" 18" 2.07" 6" 22.25" 58.75" 69" 87" 3.125" 3.125"
88" 24" 2.125" 6" 28.25" 59.5" 71" 87" 4.54" 3.125"
B
C
1
D
2
E
1
F
Dimensions do not include 1/4" vibration isolation pad
1, 3
G
1, 4
H
J K L M N
58.08"
37.50"
2.38"
3.3" 7.9" 12.4"
3.13" 7.63" 12.13"
Page 14 of 48 / IM 986-2
Critical Dimensions
Return Air Grille/Panel Dimensions
Location of studs in relation to the unit and the return air grille panel are critical for proper installation and
t up. When installed, the return air grille gasket must
compress and seal completely against the outer edge of
the cabinet and around the inner front panel and lter
bracket. See page 24, “Installing The Return Air/Grill
Panel” and page 14, gure 19 “Framing Locations to
Unit Openings”.
Figure 21: Unit Sizes 009 - 018 (18" x 18" Cabinet)
Figure 22: Unit Sizes 021 - 036 (24" x 24" Cabinet)
IM 986-2 / Page 15 of 48
Installation Procedure
CAUTION
!
Installation and maintenance is to be performed only by qualied personnel who are familiar with, and in compliance with state, local and national codes and regulations, and experienced with this type of equipment. Sharp edges and coil surfaces are potential injury hazards. Avoid contact with them.
Note: Refer to "Critical Dimensions", page 14 to determine the correct recess depth from the front of the unit to the drywall face. When the installation is complete, the return air grille/panel frame must meet to seal with the cabinet discharge opening and the discharge air diffuser duct must meet and seal with the discharge opening.
Risers and Cabinet
1. Position the cabinet and risers within the building
pipe chase and align with the unit on the oor above
and/or below (Figure 23).
Figure 23: Position the Cabinet and Risers
Riser Couplings Connect to Risers on Unit Above
Inlet, Outlet and Condensate Risers
2. Using the riser extensions, make preliminary riser connections between the units above and or below to assure proper riser alignment (supply, return and
condensate). See gure 20 on page 14.
3. After all components are aligned properly, anchor
the unit cabinet to the oor using the McQuay
provided mounting brackets (Figure 24).
4. Locate the two (2) mounting brackets in the parts bag and position them near the back corners of the unit, or one on a side and one on the back, whichever location or combination is most suitable,
as illustrated in gure 24. Cut away an area of the
1/4" isolation pad at the mounting bracket locations. Contractor is responsible for the appropriate
fasteners to secure the brackets to the oor, as local
codes dictate.
Figure 24: Position the Cabinet for Securing to the Floor with Mounting Brackets (2)
Stud Wall Floor Plate and Finish Wall Location
Risers Through Floor Opening
1/4" Isolation Pad
Riser Extensions Align and Connect to Couplings and Unit Above
IMPORTANT
A eld-supplied ¼” thick isolation pad should be installed now (Figure 23).
IMPORTANT
The cabinet must be centered between the wall studs and plumb vertically for the grille/panel frame and diffuser to properly align and seal to the cabinet. Use of a 4' level is recommended.
1/4" Vibration
Isolation Pad
Unit Cabinet 3
Finished Wall
Unit Front
1
/
8
" from Finished Wall
Back of
Unit
Provided Mounting
Brackets (2)
Fasteners (by others)
Stud Wall Floor Plate
Page 16 of 48 / IM 986-2
Note: Be sure that each riser stub-out (supply & return) are centered within the riser knockout in the cabinet (Figure 25). If there is a void between the stub-out and the stub-out seal on the cabinet interior, this indicates that the stub-out is not properly centered within the knockout.
Figure 25: Center the Riser Stub-Outs in the Knockouts and within Seals on the Cabinet Interior
Knockouts on Cabinet Exterior
Riser Knockouts
WARNING
Before furring-in units, hydrostatically test the risers and unit connection joints in accordance with local building codes, to make sure they are leak-proof.
Note: Perform "Cleaning and Flushing Water System" Procedure Below.
CAUTION
When furring-in units make sure that no screws or nails penetrate the unit cabinet.
8. Layout the stud wall oor plates and frame-in
unit referencing “T ypical Framing & Dischar ge Arrangements” on page 13 and “Critical Dimensions” on page 14 and table 1.
Note: Before cutting and hanging drywall, remove the appropriate discharge air opening knockout. See T able 2). Protect unit from construction debris with a protective cover.
Cabinet Interior
Stub-Out Connections with Valves Centered within Knockouts and Seals
Stub-Outs Seals
CAUTION
The unit is not designed to support the weight of the risers. Anchor them securely to the building structure.
5. Anchor risers to the building structure to prevent vertical riser movement greater than, plus or minus one inch to allow for riser expansion or contraction.
Table 2: Discharge Knockout Openings
Unit Size
W H W H W H W H
009–012 015–018
021–024 NR NR 18" 14" 18" 10" 18" 18"
030–036 NR NR
NR = Not Recommended
Single Double Triple Single-Top Opening
14" 16" 14" 8" NR NR 12" 12"
14" 16" 14" 8"
Discharge Openings
14" 8"
18" 14" 18" 10" 18" 18
12" 12"
Cleaning and Flushing Water System
CAUTION
Prior to first operation of any unit, the water circulating system must be cleaned and flushed of all construction dirt and debris or damage will occur.
1. Prior to rst operation of any unit, the water circulating system must be cleaned and ushed of all
construction dirt and debris.
If the units are equipped with water shutoff valves,
either electric or pressure operated, the supply and return runouts must be connected together at each unit location. This will prevent the introduction of dirt into the unit (Figure 26).
6. Solder all supply and return riser connections to units above and/or below.
7. Remove riser ties used to secure the risers to the cabinet during shipping.
IM 986-2 / Page 17 of 48
Figure 26: Connections for ushing system piping
Adapter, MPT x Straight Pipe Thread included with flexible hoses Note: Use for making connections to the supply & return valves for the "Cleaning and Flushing Water System" procedure.
2. Fill the system at the city water makeup connection
with all air vents open. After lling, close all air vents.
The contractor should start main circulator with
the pressure reducing valve open. Check vents in sequence to bleed off any trapped air, ensuring circulation through all components of the system.
Power to the heat rejector unit should be off, and the
supplementary heat control set at 80°F (27°C).
While circulating water, the contractor should check
and repair any leaks in the unit and surrounding piping. Drains at the lowest point(s) in the system
should be opened for initial ush and blow-down, making sure city water ll valves are set to make up
water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should continue for at least two hours or longer until the drain water is clean and clear.
Once the system has been lled with clean water and
antifreeze (if used), precautions should be taken to protect the system from dirty water conditions.
NOTICE
It is not McQuay International’s policy to make recommen­dations on water treatment. However, the general contrac­tor or owner should contact a local water treatment com­pany regarding water treatment. A fouled closed loop water system will lead to premature component failure.
Note: Contact a local water treatment company to
conrm water clarity prior to unit operation.
Dirty water will result in system wide degradation
of performance and solids may clog system-wide
valves, strainers, ow regulators, etc. Additionally,
the heat exchanger may become clogged which reduces compressor service life or causes premature failure.
6. Set the loop water controller heat add setpoint to 70°F (21°C) and the heat rejection setpoint to 85°F (29°C). Supply power to all motors and start
the circulating pumps. After full ow has been
established through all components including the heat rejector (regardless of season) and the vented air and loop temperatures have been stabilized, each of the units will be ready for check, test and start-up, air balancing, and water balancing.
Table 3: Air Limits
Cooling Heating Cooling Heating
Min. Ambient Air 50°F/10°C 50°F/10°C 40°F/5°C 40°F/5°C Normal Ambient Air 80°F/27°C 70°F/21°C 80°F/27°C 70°F/21°C Max. Ambient Air 100°F/38°C 85°F/29°C 100°F/38°C 85˚F/29°C Min. Entering. Air  50°F/10°C 50°F/10°C 50°F/10°C 40°F/5°C Normal Entering Air, 80°F/67°F 70°F 80°F/67°F 70°F db/wb 27/19°C 21°C 27/19°C 21°C Max. Entering Air 100/83°F 80°F 100/83°F 80°C
db/wb  38/28°C 27°C 38/28°C 27°C
Standard Range Geothermal Range
Units Units
3. Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be connected to the unit supply and return connections. Do not use sealers at the
swivel are connections of hoses.
4. Flush system with water for 2 hours or longer until water is clean.
5. Rell the system with clean water. Test the water
using litmus paper for acidity, and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5).
The specied percentage of antifreeze may also be
added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze (See Table 5 on page 19 for Antifreeze Correction Factors).
Page 18 of 48 / IM 986-2
Table 4: Water Limits
Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating
Min. Entering. Water  55°F/13°C 55°F/13°C 30°F/-1°C 20°F/-6°C Normal Entering. Water 85°F/29˚C 70˚F/21°C 77°F/25˚C 40˚F/5°C Max. Entering. Water  110°F/43°C 90°F/32°C 110°F/43°C 90°F/32°C
At ARI flow rate.
Maximum and minimum values may not be combined. If one value
is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum conditions, but not more than two, with all other conditions being normal conditions.
CAUTION
Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishan­dling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage.
Table 5: Antifreeze Correction Factors
Ethylene Glycol
Cooling Capacity 0.9950 0.9920 0.9870 0.9830 0.9790 Heating Capacity 0.9910 0.9820 0.9770 0.9690 0.9610 Pressure Drop 1.0700 1.1300 1.1800 1.2600 1.2800
10% 20% 30% 40% 50%
Propylene Glycol
Cooling Capacity 0.9900 0.9800 0.9700 0.9600 0.9500 Heating Capacity 0.9870 0.9750 0.9620 0.9420 0.9300 Pressure Drop 1.0700 1.1500 1.2500 1.3700 1.4200
10% 20% 30% 40% 50%
Methanol
10% 20% 30% 40% 50%
Cooling Capacity 0.9980 0.9720
Heating Capacity 0.9950 0.9700 Pressure Drop 1.0230 1.0570
Ethanol 10% 20% 30% 40% 50%
Cooling Capacity 0.9910 0.9510 Heating Capacity 0.9950 0.9600 Pressure Drop 1.0350 0.9600
Power Wiring From Building to Unit
DANGER
!
To avoid electrical shock, personal injury or death:
1. Installer must be qualied, experienced technician.
2. Disconnect power supply before installation to prevent electrical shock and damage to equipment.
1. Locate the electrical power supply wiring from the building and feed wiring through the 1/2" conduit
tting (strain relief) on the unit as shown in Figure
27 & 28, following local electrical codes and regulations.
Figure 27: Supply Electric Wiring from Building to Unit
1/2" Knockout for Supply Wiring
Figure 28: Wire to Unit Switch
2. If a remote wall-mounted thermostat is being used, install a 24-volt thermostat wiring cable with at least 6 wires from the unit low voltage terminal strip (Figure 29) to the thermostat location.
Flexible Metal Conduit & Strain Relief
3. If a wireless remote thermostat was ordered to control the unit, it is recommended that the Remote Control Node (RCN) be installed now.
IM 986-2 / Page 19 of 48
Figure 29: Low V oltage Terminal Strip for Thermostat Wiring
2-Speed Fan Switch
Thermostat Low Voltage Terminal Strip
Note: See specic thermostat installation manual
for wiring and operation of thermostat. Install wall mounted thermostat while completing dry wall
installation.
Connect Condensate Drain Hose to Drain Stub Out
1. Remove the two (2) screws located along the back edge of the drain pan, holding it in place (Figure 30).
Water Connections
All piping connections should be made using good plumbing practices and in accordance with any and all local codes that may apply.
Unit Piping Connection
Unit sizes 009 through 018 coil connections are gooseneck style, made of copper tubing with 1/2" FPT. Unit sizes 021 through 036 have 3/4" FPT connections (Figure 31).
Shutoff/Balancing Valve
Each heat pump requires a shutoff valve on both the supply and return risers for easy serviceability and removal of the chassis when necessary. We suggest using a factory installed 2-way motorized isolation valve on the return line of the chassis and a Auto Flow Regulator (AFR) installed on the supply line
which allows proper water ow in a given size unit.
Each valve package has 1/2" FPT or 3/4" FPT threaded connections (Figure 32).
Figure 31: Typical Motorized Valve Piping
2. Adjust the direction of the condensate drain hose and slip it over the drain stub out. Using the provided clamp, secure the hose by tightening the clamp.
3. Reinstall the secondary drain pan with the two (2) screws removed in step 1.
Figure 30: Connect Drain Hose to Drain Stub Out
Two (2) Screws Holding
Pan in Place
Drain
Stub Out
Hose Clamp
FPT Return
Connection
2-Way Motorized Valve
FPT Supply
Auto Flow Regulator
Connection
Adding A Motorized Valve & Auto Flow Regulator
The Vertical stack water source heat pump chassis can
be congured with a 2-way motorized valve. The 2-way
motorized valve is mounted on the return line of each unit and the Auto Flow Regulator (AFR) is mounted to the supply line. Valve assemblies terminate with either a 1/2" (unit sizes 009-018) or 3/4" (unit sizes 021-036) NPT threaded connection and will accommodate factory supplied hoses.
Page 20 of 48 / IM 986-2
Make Flexible Hose Connections to the Supply and Return Valves From Riser
Stub-Outs
1. Using the specied supply and return hoses make
supply and return hose connections to the riser stub­outs (Figure 32).
Note: The MPT straight pipe adapters can be
removed from the swivel end of the exible hoses
now and threaded onto the chassis FPT supply and return pipe connections (Figure 33). This will make hose connections to the chassis easier when the chassis is partially installed.
Note: To complete the exible hose connections
to the chassis, only partially install the chassis
into the cabinet as shown on page 22, gure 35
“Installing Unit Chassis”.
Important When Handling Chassis
Note: If using a hand truck to move chassis, tip the chassis forward or back only, pivoting on the ends of the chassis rails. Tipping and pivoting the chassis side to side on the long edge of the rails will damage the rails and the rubber vibration isolators.
!
CAUTION
2. Attach the (MPT) xed hose ends to the female
connections on the valves. Using two crescent wrenches, one to hold the valve pipe connection and the second on the hose end, tighten the connections.
Figure 32: Make supply and return hose connections to the valves from the riser stub-outs
Flexible Hose
2-Position Hand Valve
Slots in the chassis rails that may be used as hand holds have sharp metal edges. To avoid personal injury, heavy protective gloves should be used while moving and lifting the unit chassis.
Figure 34: Tip Chassis Front to Back Only, Pivoting on the Ends of the Rails
Do not tilt chassis side to side on long edge of rails or damage will occur
Tilt chassis front to back on end of rails when handling and moving
Figure 33: Flexible Return and Supply Hoses (Field-installed)
Assembled Length
Fixed End, MPT
Female Swivel
Adapter, MPT x Straight Pipe Thread Note: Connects to the chassis FPT supply & return connections.
IM 986-2 / Page 21 of 48
Installing Unit Chassis
1. Thread the MPT adapters removed from the swivel
ends of the exible hoses onto the chassis FPT
supply and return pipe connections. Using two crescent wrenches, one to hold the chassis pipe
connection and the second on the adapter tting,
tighten the connections.
2. Install the chassis by sliding it into the cabinet opening until the chassis support rails sit on the cabinet rails. Slide the chassis into the cabinet until there is approximately a 10" space between the chassis coil and the cabinet. This will allow
adequate clearance to connect the exible hoses to
the chassis coil. For safety, place a 6" high block under the chassis rails to support the chassis as shown in Figure 35.
Figure 35: Slide chassis partially into the unit cabinet
Approximately 10" gap to make hose connections
Figure 36: Slide Chassis into Cabinet Leaving a 10" Gap for Clearance to Make Flexible Hose Connections
Supply
Connection
Return Connection
Making Cabinet to Chassis Wiring Connections
6" high blocks to support chassis
2. Thread the female swivel ends of the hoses on to the water supply and return connections. Using two crescent wrenches, one to hold the straight MPT
adapter and the second on the exible hose swivel,
tighten the connections. (Figure 36).
1. Locate the wires and plugs in the upper fan section of the unit that connect to the unit chassis.
2. Plug in the wires from the top cabinet section into the proper molex connectors on the chassis (Figure 37).
Figure 37: Plug unit component wiring from the top cabinet section into the proper connectors on the chassis (Unit Size 021-036 Chassis Shown)
Main Power Connector Note: On unit sizes
009-018 the Main Power Receptacle and Thermostat Connector locations are switched
Fan Control
Connector
Thermostat Wiring
Connector
2. Push the chassis into the cabinet until it makes contact with the stops on the rails at the rear of the cabinet.
Page 22 of 48 / IM 986-2
Note: Be sure there are no kinks and that the stainless steel braided hoses do not come in contact with and vibrate on chassis and cause noise. Also be sure not to pinch wires between cabinet and chassis when inserting chassis.
Installing the (Optional) Remote Control Node (RCN) For Use With The Optional Wireless Thermostat
DANGER
!
Disconnect all electrical power before servicing unit. Electrical shock will cause severe injury or death.
Figure 39: Connect Wires to the RCN Terminals and snap the plastic standoffs onto Board
Plastic Standoffs (4)
Remote Control Node (RCN)
1. Remove the panel with the low voltage terminal strip by removing two (2) screws at the front of the cover and three (3) located on the underside. (Figure
38). The wires connected to the manual fan speed switch may be removed for easier access.
Note: There are two methods for installing the RCN to the unit. The RCN mounts on the back of the bezel (blank control pad) and this assembly snaps into the knockout on the face of the unit. This method is not recommended since future replacement is
more difcult. The preferred method for a new unit
installation is illustrated below (Figures 38 – 40).
Figure 38: Remove the Cover Plate with the Low Voltage Terminal Strip
Terminals on Back of Low Voltage Terminal Strip
RCN Terminals
3. Snap the plastic standoffs into the RCN as illustrated in Figure 39.
4. Reach inside the area behind the removed terminal strip cover and up behind the knockout. Align the standoffs on the board with the provided standoff holes on the knockout plate and snap the standoffs into the holes (Figure 40).
Figure 40: Secure the RCN to the Unit with the Standoffs
2. Connect the provided wiring to the RCN terminals as shown in Figure 39.
Plastic Standoffs (4)
RCN
RCN to Low Voltage Terminal Connectors
5. Connect the RCN wires with connectors to the low voltage terminals and reinstall the terminal strip cover.
IM 986-2 / Page 23 of 48
Installing The Return Air Grille/Panel
1. Install the return air grille/panel assembly (Figure
41). Center, level and plumb the frame inside the framed opening. Push the assembly into the opening until the gaskets compress against the cabinet, and
the frame face is tight to the nished wall.
Note: Shims should be used to make up the space between the studs and the panel frame at the locations of the fasteners on the panel frame (4). Adhere them to the panel frame to keep them in place (Figure 41).
Figure 41: Installing the Panel Door Frame
Note: Be sure the bottom ange of the door frame
slides beneath the cabinet ange, as shown in Figure
41. This seal must compress between the bottom
panel ange and the bottom cabinet ange when
the installation of the panel door frame is complete.
2. Check that the panel door frame is centered within the opening and seals completely to the cabinet
return air opening. Also conrm that the room side ange of the frame is level, plumb and rmly
against the drywall. Secure the hinged panel door frame with the 4 screws provided.
Seal Gasket on the Back of the Panel Door Frame along top and two sides
Shims to Make Up Space Between Framed Opening and Panel Door Frame
Door Panel Bottom
Flange to Slide Beneath Cabinet Flange
Seal Gasket on Underside of Cabinet Flange. Door Panel Flange Slides Underneath and Compresses to Cabinet
Page 24 of 48 / IM 986-2
Installing The Discharge Air Diffuser
1. Adhere eld-provided 1/2" foam seal to the face of
the cabinet around the perimeter of the discharge air opening (Figure 42).
3. Push the diffuser frame in until it compresses against the foam seal and the room side frame is
ush against the drywall. Be sure the diffuser frame
is level and plumb and secure it with the two (2) screws provided.
2. Insert the diffuser into the wall opening and align the frame with the foam seal.
Note: To avoid bending the adjustable discharge louvers do not press on them
Figure 42: Installing the Discharge Air Diffuser
Foam seal applied to the cabinet face, around perimeter of discharge
air opening
Note: When installed correctly the diffuser frame should seal to the cabinet discharge air opening and no discharge air will be lost between the unit and the wall cavity.
Foam seal (field-furnished & installed)
Diffuser flange compresses into the foam seal
Double-deflection Diffuser
IM 986-2 / Page 25 of 48
Twin Units Installation
Twin opposite hand units share a common riser system; i.e., supply, return, and drain riser. This is commonly called a “master/secondary” arrangement. The master unit is shipped with the risers attached. These special risers have stub-outs for both the master unit and the
secondary unit which must be eld connected and the
following procedures must be followed for all twin unit installations.
1. Secondary units ship without risers and share common risers with the master unit. Knockout holes on the cabinet are provided for the 6" stub outs to make piping connections to the coil supply and return and the condensate drain.
Figure 43: Twin Unit Arrangement (Side by Side)
2. Master units are offered in two-pipe systems with either right-hand or left-hand connections.
Secondary units are offered to accommodate internal connections to any of these riser systems or locations.
3. The riser location (right or left) is determined by facing the return air grille panel. The risers are located on either the right or left of the unit. This
denes the riser location. See Unit Congurations
on page 12.
4. The riser block-off plates are located in the base of the secondary unit. Block-offs must be installed on the secondary unit before putting it into position.
Master Unit
Secondary Unit in Adjoining Room
6" Stubs on Master Unit Risers for Secondary Unit
Stud Wall Separating Rooms
Common
Risers
Page 26 of 48 / IM 986-2
MicroTech® III Unit Controller
The MicroTech III Unit Controller includes built-in features such as random start, compressor time delay,
shutdown, condensate overow protection, defrost
cycle, brownout, and LED/fault outputs. Table 6 shows the LED and fault output sequences.
The unit has been designed for operation with either a unit mounted thermostat or a microelectronic wall thermostat, selected by the manufacturer. Do not operate the unit with any other type of wall thermostat.
Each unit has a printed circuit board control system. The low voltage output from the low voltage terminal strip is AC voltage to the wall thermostat. R is A/C voltage output to the wall stat.
The 24 volt low voltage terminal strip is set up so R-G energizes the fan only. R-Y1 energizes the compressor for cooling operation, R-W1 energizes the compressor and reversing valve for heating operation. The reversing valve is energized in the heating mode. The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on if the thermostat logic fails to do so.
The output to the wall stat is AC current. Terminal (R) on the wall stat can be connected to terminal (R) on the PC board for AC voltage.
R = AC current R to G = fan only R to Y1 = cooling R to W1 = heat
The MicroTech III unit controller has a lockout circuit to stop compressor operation if any one of its safety devices is triggered (high pressure switch and low temperature sensor). If the low temperature sensor is triggered, the unit will go into the cooling mode for 60 seconds to defrost any slush in the water-to-refrigerant heat exchanger. After 60 seconds the compressor is
locked out. If the condensate sensor detects a lled drain
pan, the compressor operation will be suspended only in the cooling mode. The unit is reset by opening and closing the disconnect switch on the main power supply to the unit in the event the unit compressor operation has been suspended due to low temperature sensor or high pressure switch. The unit does not have to be reset
on a condensate overow detection.
The MicroTech III unit controller fault output sends a signal to an LED on a wall thermostat. Table 6 shows for which functions the fault output is “on” (sending a signal to the LED).
Table 6: MicroTech III unit controller LED & fault outputs
Mode / Fault
Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Unoccupied On On Off Energized Condensate Overow On Off Off De-engergized
High Pressure 1 Fault Off Off Flash De-energized Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown Off Flash Off De-energized
Room/Return Air or Low Temp Sensor 1 Failure
Service Test Mode
Corrupted
Received
1
1
Enabled
Serial EEPROM
Network “Ofine”
Compressor relay/compressor terminal is labeled COMP, switched line of the
same electric input as any of the L1 terminals.
Yellow Green Red
Flash Flash On De-engergized
Status LED’s Thermostat Alarm Light
Off Flash Off De-energized
On On Off De-energized
On On On De-energized
Off Off Off De-enegized
Output-Terminal “A”
Remote Reset Feature
The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high­pressure and/or low-temperature (in heating) faults. When the MicroTech III unit controller is in automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the MicroTech III unit controller to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated.
The Intelligent reset feature helps to minimize nuisance trips of automatic reset lockouts caused by high­pressure and/or low-temperature (in heating) faults. This
feature clears faults the rst two times they occur within
a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours.
The MicroTech III unit controller has built-in night setback operation. A “grounded’ signal to the “U” terminal on TB3 of the unit control puts the unit into the unoccupied mode for night setback operation. Fan operation terminates and unit control will only respond to signal at the W2 terminal. Daytime heating and cooling operation is locked out. +24VAC to W2 energizes the compressor and reversing valve for heating operation. Night setback operation can be overridden for two hours by energizing the O on the TB2 terminal of the unit control for 3 seconds. Day thermostat setpoints then control the heating and cooling operation. The MicroTech III unit controller also accommodates shutdown operation on receipt of a “grounded” signal to the “E” input, respectively, on TB3 input terminal of the unit control.
IM 986-2 / Page 27 of 48
MicroTech® III Unit Controller Terminal Locations and Descriptions
H1 - 1 24 24 VAC Power Input
H1 - 2 C 24 VAC Common
H2 - 1 SL1 Fan Output - Switched L1
H2 - 2 Blank Terminal
H2 - 3 N Fan Neutral
H3 - 1 HP1-1 High Pressure Switch 1 Input Terminal 1
H3 -2 HP1-2 High Pressure Switch 1 Input Terminal 2
H4 - 1 Discharge Air Temp Common
H4 - 2 Discharge Air Temp Signal
H4 - 3 Leaving Water Temp Common
H4 - 4 Leaving Water Temp Signal
H5 - 1 1 I/O Exp Module Common (Gnd)
H5 - 2 I/O Exp Module Common (Gnd)
H5 - 3 I/O Exp Module +5 VDC
H5 - 4 I/O Exp Module SPI CE1
H5 - 5 I/O Exp Module SPI CLK
H5 - 6 I/O Exp Module SPI OUT
H5 - 7 I/O Exp Module SPI IN
H5 - 8 I/O Exp Module +12 VDC
H5 - 9 I/O Exp Module 24 VAC
H5 - 10 I/O Exp Module 24 VAC
H5 - 11 Spare
H5 - 12 Spare
H6 - 1 1 Condensate Overow Signal Input
H6 - 2 Low Temp 1 Sensor Common
H6 - 3 Low Temp 1 Sensor Signal
H6 - 4 Low Pressure Switch 1 Source Voltage
H6 - 5 Low Pressure Switch 1 Signal
H6 - 6 Reversing Valve 1 Common
H6 - 7 Reversing Valve 1 Output
H7 - 1 1 Dummy Terminal
H7 - 2 Dummy Terminal
H7 - 3 Red LED Output
H7 - 4 Green LED Output
H7 - 5 Yellow LED Output
H7 - 6 Red-Green-Yellow LED Common
H8 - 1 1 Isolation Valve/Pump Request Relay N/O
H8 - 2 Isolation Valve/Pump Request Relay N/C
H8 - 3 24 VAC Common
H9 - 1 1 Return Air Temperature Signal
H9 - 2 Return Air Temperature Common
TB1 - 1 1 Room Sensor LED Output
TB1 - 2 2 Fan Mode / Heat-Cool-Auto Input
TB1 - 3 3 Setpoint Adjust Input
TB1 - 4 4 Room Temperature Sensor / Tenant Override
TB1 - 5 5 DC Signal Common
Test-1 R 24 VAC
Test-2 W2 Heat Stage 2 Input
Test-3 W1 Heat Stage 1 Input
Test-4 Y2 Cool Stage 2 Input
Test-5 Y1 Cool Stage 1 Input
Test-6 G Fan
TB2 - 1 R 24 VAC
TB2 - 2 A Alarm Output
TB2 - 3 W2 Heat Stage 2 Input
TB2 - 4 W1 Heat Stage 1 Input
TB2 - 5 Y2 Cool Stage 2 Input
TB2 - 6 Y1 Cool Stage 1 Input
TB2 - 7 G Fan Input
TB2 - 8 O Tenant Override Input
TB2 - 9 C 24 VAC Common
TB3 - 1 E Mark IV Emergency Shutdown Input
TB3 - 2 U Mark IV Unoccupied/Occupied Input
L1 - 1 L1 - 1 Line Voltage Terminal 1
L1 - 2 L1 - 2 Line Voltage Terminal 2
L1 - 3 L1 - 3 Line Voltage Terminal 3
N1 N1 Neutral Terminal 1
N2 N2 Neutral Terminal 2
N3 N3 Neutral Terminal 3
Table 7: Conguration Jumper Settings
Jumper Description Options
JP1 Mode
Shorted for service/test operation mode JP2 Fan operation only applies to Open for continuous fan operation network controls Shorted for cycling fan operation
JP3 Freeze protection
Shorted for antifreeze protection JP4 Future spare Future spare JP5 Set point adjustment range only Open for adjustment range of -3.0° to +3.0° F applies to network controls with a Shorted for 50° to 90° F adjustment range room temperature sensor
JP6 Room control type
Shorted for room temperature sensor control, MicroTech III only JP7 Future spare Future spare
JP8 Future spare Future spare
Page 28 of 48 / IM 986-2
Open for normal operation mode
Open for water freeze protection
Open for thermostatic room control
Note: A random start delay time between 180 and 240 seconds is generated at power up.
Figure 44: MicroT ech III Unit Controller Terminal Locations
Location of Conguration Jumpers on the MicroTech III Unit Controller
IM 986-2 / Page 29 of 48
I/O Expansion Module
Table 8: I/O Expansion Module LED & Fault Outputs
Mode / Fault
Terminal “A”
Yellow Green Red
Status LED's
Thermostat Alarm
Light Output
For installation and operation information on MicroTech III unit controller and other ancillary components, see:
• IM 927 - MicroTech III Unit Controller for Water
Source Heat Pumps (LonWorks).
The I/O Expansion Module is a eld-installed or factory
installed option. It is an extension of the MicroTech III unit controller and provides extra functionality. The I/O Expansion Module has 2 main purposes:
• The I/O Expansion Module has outputs to control
electric heat on a standard Water Source Heat Pump.
• The I/O Expansion Module has an independent LED
annunciator to identify operational fault conditions on second stage equipment.
Figure 45: I/O Expansion Module Conguration Jumper
Terminals
Jumper Terminals
Features
Second Circuit
• High pressure switch
• Low pressure switch
• Low suction line temperature sensor
• Compressor output
• Reversing valve
Standard Heat Pumps / Single Circuit Units
• Monitors entering water temperature for
boilerless electric heat control
• Outputs for medium and high speed fan controls.
Invalid Conguration Jumper Setting
Base Board Communication Fail
High Pressure #2 Fault Off Off Flash De-energized
Low Pressure #2 Fault Off Off On De-energized
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction
Low Suction Temp #2, Flash Flash On De-energized
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Unoccupied Mode On On Off Energized
Occupied, Bypass, Standby, or Tenant Override Modes
Normal Operation Off On Off De-energized
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Note: Mode / Faults are listed in order of priority.
1
Boilerless electric heat only
2
Alarm/fault LED indications take precedence over service test mode LED
indication. The controller shall use service test mode if the service test mode jumper is installed, even if the LED’s indicate an alarm/fault.
Table 9: I/O Expansion Module Jumper Designations
Jumper Description Options
JP1 Number of
JP2
Water Reheat Shorted to enable reheat JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open, JP4 shorted for & JP4 Heat Type boilerless electric heat JP3 and JP4 shorted is an invalid setting JP5 and JP6 open for single-speed fan
JP5
& JP6 Selection JP5 shorted and JP6 open for two-speed fan JP 5 and JP6 shorted is an invalid setting
JP7
Speed Type Shorted for two-speed compressor
JP8 Future Spare
Compressors Shorted for dual compressor
Hot Gas/
Fan Speed three-speed fan
JP5 open, JP6 shorted for
Compressor Open for single-speed compressor
Open for single compressor
Open to disable reheat
Adding an I/O Expansion Module (with an interconnect cable) to the main controller allows two-stage operation of the Water Source Heat Pump.
Page 30 of 48 / IM 986-2
MicroTech III Controller With LonWorks® Communication Module
For installation and operation information on
onWorks Communication Module and other ancillary
L control components, see:
• IM 927 - MicroTech III Unit Controller for Water
Source Heat Pumps (LonWorks).
• IM 933 - LonMaker Integration Plug-in Tool: For
use with the MicroTech III Unit Controller.
• IM 955 - MicroTech III Wall Sensor For use with
MicroTech III Unit Controller with LonWorks
Figure 46: LonWorks Communication Module
The LonWorks communication module will plug into the MicroTech III unit controller at the CN_LON1
Header (see gure 48, page 34).
Each McQuay water source heat pump can be equipped with a L controller is microprocessor-based and is designed to communicate over a L network. The unit controller is factory programmed and tested with all the logic required to monitor and control the unit. The wall thermostat sets the unit mode of operation. The unit controller monitors water and air temperatures, and can communicate fault conditions to a L
The MicroTech III unit controller include unit-mounted return air, discharge air and leaving water temperature sensors. Options include setpoint adjustment and tenant override and the capability of substituting the return air sensor with a wall-mounted temperature sensor. Each unit controller orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint
Enable fan and compressor operation. Monitor all equipment protection controls.
onWorks communication module. The
onWorks communications
onWork communications network.
based on a room sensor.
Monitor leaving water temperature. Relay status of all vital unit functions. Support optional control outputs.
A set of three status LED's aid in diagnostics by indicating the water source heat pump operating mode and alarm conditions. If there are no current alarm conditions, the Green LED will indicate the normal unit operating mode as shown in the table below. If there are one or more alarm conditions present, various LED's
will ash to indicate an alarm condition.
MicroTech III heat pumps with a MicroTech III unit
controller are LonMark certied and designed to be
linked with a centralized building automation system through a L
onWorks communications network for
centralized scheduling and management of multiple heat pumps. Wall-mounted room sensors are available to control the heating and cooling operation of each MicroTech III Water Source Heat Pump Unit Controller. Available room sensors include: room sensor with LED status and tenant override button, room sensor with LED status, timed-override button, room sensor with LED status, timed-override button, and setpoint adjustment, and room sensor with LED status, timed­override button, setpoint adjustment.
The MicroTech III water source heat pump unit controller provides control of McQuay water source heat pumps. The controller enables the mode of operation, monitors the water and air temperatures, and indicates fault conditions. Each unit controller is factory programmed, wired, and tested for effective operation of your McQuay water source heat pump.
The MicroTech III water source heat pump controller
onWorks technology. One of the following two
uses L versions of the application software is loaded into the controller at the factory.
LonMark® 3.4 certied application code is the current
standard application code for MicroTech III units. Use LonMark application code in new applications including:
Units that operate stand alone.
Monitor discharge air temperature.
IM 986-2 / Page 31 of 48
MicroTech III Controller With BACnet Communication Module for Native BACnet Communications
McQuay water source heat pumps are available with a factory mounted and tested McQuay BACnet com­munication module The module is factory programmed and tested with all the logic required to control the unit, and is designed to communicate over a BACnet MS/TP communications network to a building automation sys­tem (BAS). The module operates the compressor, fan, and reversing valve as required to maintain the space temperature within the current setpoints. Data regarding equipment status, water and air temperatures, and fault conditions can be monitored by any BAS. Setpoints and other system preferences may be changed remotely us­ing a front end workstation or service tool software.
Each BACnet-compliant controller has the following
operating features:
Start-up – The unit will not operate until all the
inputs and safety controls are checked for normal conditions.
Fan operation – Fan operation can be customized in
software to run continuously during occupied mode, or to cycle ON or OFF appropriately on a call for heating and cooling.
Cooling mode – On a call for cooling, the compres-
sor and fan start immediately. Compressor run­time is calculated as a percent of full cycle time (17 minutes) using proportional-integral control to
maximize efciency.
The module makes operational data and commands available on a communications network using BACnet objects and properties. Each heat pump controller con­nects to the communication network using a BACnet MS/TP communication network, which is a simple twisted-pair communications connection that operates at up to 76.8 Kbps. DIP switches on the controller enable the MS/TP MAC address to be set in the range 0-127. A status LED on the unit indicates communication activity on the MS/TP communication network.
Figure 47: MicroTech III BACnet W ater Source Heat Pump Snap-in Communication Module
Each BACnet-compliant unit includes discharge air and leaving water temperature sensors, as well as all equipment protection sensors, signals, and switches. Wall-mounted room sensors are available to control heating and cooling operation. Sensors are available for status override; wall-mounted sensors with tenant setpoint adjustment lever and timed-override button; wall-mounted sensors with LED status, timed-override button, tenant setpoint adjustment buttons, password-
protected eld service access to operational data, and
optional humidity sensor; and wall-mounted sensors with LCD and programmable operation.
Heating mode – On a call for heating, the com-
pressor and fan start immediately, and compressor run-time is calculated as a percent of full cycle time (17 minutes) using proportional-integral control to
maximize efciency.
Short Cycle Protection and Random Start – A start
delay of 180 seconds plus the compressor’s MAC address in seconds prevents short-cycling and simultaneous start-up. A minimum 2-minute on time and 5-minute off time for the compressor further ensures short-cycle protection.
Occupied Mode – A simple software control signal
from the building automation system or a wall­mounted unit puts the unit into occupied mode. The unit controls compressor and fan operation to maintain occupied setpoints. High and low limits
for occupied setpoints are software congurable.
Unoccupied Mode – A simple software control
signal from the building automation system or a wall-mounted unit puts the unit into unoccupied mode for night setback operation. The unit controls compressor and fan operation to maintain unoccu­pied heating and cooling setpoints, which are also
software congurable.
Page 32 of 48 / IM 986-2
After-hours Override Mode – A simple software
control signal from the building automation system or a wall-mounted unit can initiate after-hours heat­ing or cooling in half-hour increments. Maximum
override time is software congurable up to 9.5
hours. This feature can also be disabled in software.
Reversing valve delay – On a call for cooling,
the compressor and fan will start 0 to 30 seconds later. If the reversing valve output is energized, the reversing valve output will de-energize 5 seconds after the compressor energizes. When the load is
satised, the compressor and fan shut off. On a
call for heating, the compressor and fan start. If the reversing valve output is de-energized, the revers­ing valve output will be energized 5 seconds after
the compressor starts. When the load is satised, the
compressor and fan shut off. The reversing valve remains energized.
Load Shed – Load shedding can be orchestrated by
the building automation system using the occupied/ unoccupied command in software.
Brownout Protection – An on-board sensor mea-
sures input voltage and suspends compressor and fan operation if the supply voltage drops below 82% of the normal line voltage for a minimum of 10 sec­onds, creating an alarm available in software. The alarm automatically resets when the supply voltage returns to above 90% of normal.
Condensate Overow Protection – A liquid sensor
at the top of the drain pan senses a high water level. Upon sensing water, cooling operation is suspended, while heating operation is allowed. The controller creates an alarm available in software. The alarm automatically resets when the water level returns to normal.
Attained T emperature and Water Temperature
Alarms –Attained temperature, water temperature alarms with software-adjustable setpoints are avail­able in software. The controller samples supply air and records attained temperatures for heating and cooling. If after two hours of operation, the attained temperature does not meet the software-congu­rable setpoint for heating or cooling as appropriate, a software alarm occurs. The alarm automatically resets when the attained temperature is within set­points. The controller also monitors leaving water temperature. If the leaving water temperature is outside software-congurable setpoints, compres­sor operation is suspended and high or low water temperature alarms occur. The alarm automatically resets when the water temperature returns to within 6 deg. F of the setpoint.
Unit Self-test Mode – While the unit is in occu-
pied mode, a self-test can be initiated via software. Upon initiation of the test, compressor operation is
suspended for a minimum of ve minutes, cooling
attained temperatures are cleared, and attained tem­perature alarms are cleared. The unit then switches to full heat for four minutes and then records the attained supply air temperature. Compressor opera-
tion is then suspended for ve minutes. The unit
then switches to full cooling for four minutes and the attained supply air temperature is recorded. Attained temperature alarms are set if the attained temperatures failed to reach alarm setpoints during heating or cooling.
Safety Control – The unit monitors refrigerant pres-
sure and generates separate high-pressure and low­pressure alarms available in software. While either alarm is active, compressor operation is suspended. In a refrigerant low-temperature condition, an alarm occurs and the unit operates in cooling mode for 60 seconds to defrost the heat exchanger, after which compressor operation is suspended. These alarms can be reset in software or by cycling power to the controller.
IM 986-2 / Page 33 of 48
Figure 48: LonWorks Communication Module Placement on MicroTech III Unit Controller
Page 34 of 48 / IM 986-2
Typical Wiring Diagram
Figure 49: MicroTech III Unit Controller, 2-Speed Fan (Toggle or Thermostat), PSC Motor 208-230/60Hz/1-Phase, Unit Sizes 009-018
Drawing No. 669349301
Legend
Description
Item
C1 C2 CM COS Condensate Overow Sensor DSC FMP FMR Fan Motor Connect Receptacle FCP FCR FSR Fan Speed Relay FSS FS1 Fuse 1 FS2 Fuse 2 HP ISO LED1 LP MIII MicroTech III Main Board MPP MPR OVL Compressor Overload Protector PDPG Primary Drain Pan Ground RV SOS SLTS TS1 Fan Speed Terminal Strip TS2 Thermostat Terminal Strip TSP TSR Terminal Strip Connector Terminal X1
Capacitor-Compressor Capacitor-Fan Compressor - Motor
Disconnect Switch Fan Motor Connector Plug
Fan Connector Plug Fan Connector Receptacle
Fan Speed Switch - Optional
High Pressure Switch
Isolation Valve - Optional LED Annunciator / Harness
Low Pressure Switch
Main Power Connector Plug Main Power Connector Receptacle
Reversing Valve Solenoid Secondary Overow Sensor Suction Line Temp Sensor
Terminal Strip Connector Plug
Transformer
Table B
208V 230V ORG
RED
Note:
T
ransformer:
Unused wire to be capped.
IM 986-2 / Page 35 of 48
Typical Wiring Diagram
Figure 50: MicroTech III Unit Controller, 2-Speed Fan (Toggle or Thermostat), PSC Motor 265-277/60Hz/1-Phase, Unit Sizes 009-036
Drawing No. 669349401
Legend
Description
Item
C1 C2 CC CM DSC FMP FMR Fan Motor Connect Receptacle FCP FCR FPR Fan Power Relay FSR Fan Speed Relay FSS FS1 Fuse 1 FS2 Fuse 2 HP ISO LED1 LP MIII MicroTech III Main Board MPP MPR COS Condensate Overow Sensor PDPG Primary Drain Pan Ground RV SOS SLTS TS1 Fan Speed Terminal Strip TS2 Thermostat Terminal Strip TSP TSR Terminal Strip Connector Terminal X1
Capacitor-Compressor Capacitor-Fan Compressor Contactor Compressor - Motor Disconnect Switch Fan Motor Connector Plug
Fan Connector Plug Fan Connector Receptacle
Fan Speed Switch - Optional
High Pressure Switch
Isolation Valve - Optional LED Annunciator / Harness
Low Pressure Switch
Main Power Connector Plug Main Power Connector Receptacle
Reversing Valve Solenoid Secondary Overow Sensor Suction Line Temp Sensor
Terminal Strip Connector Plug
Transformer
Page 36 of 48 / IM 986-2
Typical Wiring Diagram
Figure 51: MicroTech III Unit Controller, 2-Speed Fan (Toggle or Thermostat), X13 Motor 208-230/60Hz/1-Phase, Unit Sizes 021-036
Drawing No. 669349701
Legend
Description
Item
C1 C2 CC CM COS Condensate Overow Sensor DSC FMP FMR Fan Motor Connect Receptacle FCP FCR FPR Fan Power Relay FSR Fan Speed Relay FSS FS1 Fuse 1 FS2 Fuse 2 HP ISO LED1 LP MIII MicroTech III Main Board MPP MPR PDPG Primary Drain Pan Ground RV SOS SLTS TB3 Terminal Block TS1 Fan Speed Terminal Strip TS2 Thermostat Terminal Strip TSP TSR Terminal Strip Connector Terminal X1
Capacitor-Compressor Capacitor-Fan Compressor Contactor Compressor - Motor
Disconnect Switch Fan Motor Connector Plug
Fan Connector Plug Fan Connector Receptacle
Fan Speed Switch - Optional
High Pressure Switch
Isolation Valve - Optional LED Annunciator / Harness
Low Pressure Switch
Main Power Connector Plug Main Power Connector Receptacle
Reversing Valve Solenoid Secondary Overow Sensor Suction Line Temp Sensor
Terminal Strip Connector Plug
Transformer
Table B
208V 230V ORG
RED
Note:
T
ransformer:
Unused wire to be capped.
IM 986-2 / Page 37 of 48
Typical Wiring Diagram
Figure 52: MicroTech III Unit Controller, 2-Speed Fan (Toggle or Thermostat), X13 Motor 265-277/60Hz/1-Phase, Unit Sizes 021-036
Drawing No. 669349801
Legend
Description
Item
C1 C2 CC CM COS Condensate Overow Sensor DSC FMP FMR Fan Motor Connect Receptacle FCP FCR FPR Fan Power Relay FSR Fan Speed Relay FSS FS1 Fuse 1 FS2 Fuse 2 HP ISO LED1 LP MIII MicroTech III Main Board MPP MPR PDPG Primary Drain Pan Ground RV SOS SLTS TB3 Terminal Block TS1 Fan Speed Terminal Strip TS2 Thermostat Terminal Strip TSP TSR Terminal Strip Connector Terminal X1
Capacitor-Compressor Capacitor-Fan Compressor Contactor Compressor - Motor
Disconnect Switch Fan Motor Connector Plug
Fan Connector Plug Fan Connector Receptacle
Fan Speed Switch - Optional
High Pressure Switch
Isolation Valve - Optional LED Annunciator / Harness
Low Pressure Switch
Main Power Connector Plug Main Power Connector Receptacle
Reversing Valve Solenoid Secondary Overow Sensor
Suction Line Temp Sensor
Terminal Strip Connector Plug
Transformer
Page 38 of 48 / IM 986-2
Start-up
CAUTION
Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishan­dling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage.
Cooling or Heating – Manual Operation
Adjust the thermostat heating or cooling setpoint to maintain desired space temperature.
The MicroTech III unit controller has built-in features such as random start, compressor time delay, night
setback, load shed, shutdown, condensate overow
protection, defrost cycle, brownout, and LED/fault outputs. Table 10 shows the LED and fault output sequences. The 24 volt low voltage terminal strip is set so R-G energizes the fan. R-W1 energizes the fan and compressor and reversing valve for heating operation. R-Y1 energizes the fan and compressor for cooling mode of operation.
T able 10: LED Fault Indicators
Normal Mode Off On Off Off High Pressure Fault Off Off Flash On Low Temperature Fault* Flash Off Off On Condensate Overflow On Dim Off On Brownout Off Flash Off On Load Shed Off Off On Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On
LEDs
Indication
Yellow Green Red
Fault
Output
IMPORTANT
Each water source heat pump unit has a compressor and
blower motor. Each component part has and internal
temperature and amperage sensitive overload. If the over­load opens it will suspend unit operation. Check component parts by measuring the winding resistance and looking for an open circuit.
Additional Accessories – General Thermostats and Wall Sensors
Easy-to-operate comfort command centers provide a complete range of deluxe features.
The reversing valve is set up to be energized in the heating mode. The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on.
The MicroTech III unit controller has a lockout circuit to stop compressor operation if any one of its safeties opens (high pressure or suction line sensor). If the suction line low temperature sensor opens, the unit will go into the cooling mode for 60 seconds to defrost any slush in the water-to-refrigerant heat exchanger.
After 60 seconds, the compressor is locked out. If
the condensate sensor detects a lled drain pan, the
compressor operation will be suspended only in the cooling mode. The unit is reset by opening and closing the disconnect switch on the main power supply to the unit in the event the unit compressor operation has been suspended due to low suction line sensor reaching its set point, or a high pressure switch.
The MicroTech III unit controller has a fault output signal to an LED on a wall thermostat. Table 10 shows in which function the fault output is “on” (sending a signal to the LED).
Wall-Mounted Programmable Electronic Thermostat (P/N 668810301) 1 Heat/1 Cool, Auto Changeover, Hardwired
• 7-Day, 5-2-Day 5-1-1 Day Programmable
• Congurable
• Single-Stage Heat/Cool Systems
• Single-Stage Heat Pump Systems
• Large Display With Backlight
• Selectable Fahrenheit or Celsius
• Compatible with Gas, Oil, or Electric
• SimpleSet™ Field Programming
• Status Indicator Light
• Relay Outputs (minimum voltage drop in thermostat)
• Remote Sensor Compatible
• Ideally Suited for:
– Residential (New Construction/Replacement) – Light Commercial
IM 986-2 / Page 39 of 48
Specifications–668810301
Electrical rating: • 24 VAC (18-30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System congurations: 1-stage heat, 1-stage cool, heat pump, gas, oil, electric
• Relay Outputs (minimum voltage drop in thermostat)
• Remote Sensor Compatible
• Ideally Suited for:
– Residential (New Construction/Replacement) – Light Commercial
Specifications–668811201
Electrical rating: • 24 VAC (18-30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
Timing:
Anti-short Cycle: 4 minutes
Backlight Operation Terminations: S1, S2, Y, W/O/B, G2, G1, RC, RH, C For detailed installation, operation and application refer
to Operation & Application Guide LIA303
Figure 53: Thermostat Parts Diagram - Part No. 668810301
Up button
Down button
Right (fan) button
Left (system) button
Field programming pins
Conguration switch
Reset switch
RC/RH Jumper
Non-Programmable Electronic Thermostat (P/N 668811201)
1 Heat/1 Cool, Auto Changeover, Fan Speed Control, Hardwired
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System congurations: 1-stage heat, 1-stage cool, heat pump, gas, oil, electric
Timing:
Anti-short Cycle: 4 minutes
Backlight Operation Terminations: S1, S2, Y, W/O/B, G2, G1, RC, RH, C For detailed installation, operation and application refer
to Operation & Application Guide LIAF014
Figure 54: Thermostat Parts Diagram - Part No. 668811201
Up button
Down button
Right (fan) button
Left (system) button
Reset switch
Conguration switch
Reset switch
Fan switch
Field programming pins
RC/RH Jumper
• Congurable
• Single-Stage Heat/Cool Systems
• Single-Stage Heat Pump Systems
• Fan Speed Control
• Large Display With Backlight
• Selectable Fahrenheit or Celsius
• Compatible with Gas, Oil, or Electric
• SimpleSet™ Field Programming
• Status Indicator Light
Page 40 of 48 / IM 986-2
Wireless Temperature Control (T9000)
The T9000 Wireless Temperature Control is designed to provide precision temperature control without the installation labor and expense of wiring.
Powered by AA batteries
Mounts in any suitable location that will provide
good temperature control.
Large LCD display provides the user with
current room temperature, set point temperature, time, program interval, and other system status information.
For detailed installation, operation refer to Operation &
Maintenance Bulletin OM 984. The second part of the T9000 system is called a Remote Control Node or “RCN”. An RCN interfaces with
specic desired HVAC equipment, and communicates
with its thermostat using unlicensed 900 MHz, radio frequency energy. At the time of installation, the T9000 thermostat is linked to one or more RCN controls. The thermostat and RCN that have been linked will not interfere with, or be affected by, any other thermostat or RCN in adjacent rooms, apartments, or neighboring homes.
Remote Control Node (RCN)
Used with the Wireless Temperature Control, the
RCN interfaces with specic HVAC equipment, and
communicates with its thermostat using unlicensed 900 MHz, radio frequency energy. Contact your local McQuay Representative for details.
Programmable Non-programmable
Figure 55: T9000 Overview
IM 986-2 / Page 41 of 48
MicroT ech III Wall-Mounted Room T emperature Sensors
(Kit P/N 669529101, 669529201, 669529001)
Figure 56: MicroT ech III Wall-Mounted Room Temperature Sensors (669088201 Not Shown)
Sensor 669529101 Sensor 669529201 Not Shown
Sensor 669529001
General
CAUTION
When the optional wall-mounted room temperature sen­sor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. The wall­mounted room temperature sensor and return air sensor must not be connected simultaneously or the unit will not operate properly.
Specifications
Thermistor resistance (10kΩ)
(Conforms to advance thermal products curve 2) Ambient T emperature Limits: Shipping and Storage: 40°F to 160°F (–40°C to 71°C) Operating: 40°F to 140°F (4°C to 60°C) Humidity: 5 to 95% RH, non-condensing Locations: NEMA Type 1, Indoor only Connections: Color Coded Leads
Wiring Sensors to the MicroTech III Unit Controller
Figure 58: T emperature Sensor W iring to MicroT ech III Unit Controller (669529101, 669529201)
Temperature Sensor Terminals
MicroT ech III Wall-Mounted Room Temperature Sensors provide electronic sensing of room temperatures at wall locations. All sensor models feature
a thermistor (10kΩ) and a green LED for unit status.
Tenant ove r r i d e , s e t p o i n t adjustment potentiometer, thermometer, and a communications port are optional features available in any combination
This manual provides general information for the MicroT ech III Wall-Mounted Room Temperature Sensors. For installation instructions refer to IM 955
Figure 57: MicroTech III Wall Sensor Details
0 to 10 K ohm
Potentiometer
4.59"
Status LED (Green)
Fan Control Slide Switch
MicroTech III Unit Controller TB1 Terminals
Figure 59: T emperature Sensor W iring to MicroT ech III Unit Controller (669529001)
Temperature Sensor Terminals
Mode Control Slide Switch
Page 42 of 48 / IM 986-2
Tenant Override Momentary Push Button Switch
MicroTech III Unit Controller TB1 Terminals
Optional Remote Sensor (P/N 66720401)
The fast, easy solution for temperature sensing problems.
• For tamper prone areas
• Poor airow areas
Motorized Isolation Valve & Relay
The motorized valve kit may be ordered as a eld-
installed accessory. Wired as shown in Figure 60, the motorized valve will
open on a call for compressor operation. Valves for unit sizes 009 to 018 are 1/2".
• Troubled applications
• Foam gasket prevents drafts through wall opening
• Mounts to standard 2" x 4" outlet box
• 2¾"W x 4½"H
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the
remote sensor.
3. Mount remote sensor unit using hardware provided.
4. Install two strand shielded wire between remote
sensor and thermostat. Shielded wire must be used.
Do not run remote sensor wire in conduit with other wires.
• Wire 1 should run between the S1 terminal on the
thermostat and the S1 terminal on the remote sensor
• Wire 2 should run between the S2 terminal on the
thermostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal
on the thermostat
5. Disable the main sensor (R12) on the thermostat by
cutting it from the circuit board.
Using a Normally Closed (N/C), power open valve,
wire as illustrated in gure 61.
Figure 60: Normally Closed, Power Open Motorized Valve & Relay Wiring
Actuator & Valve Assembly
Figure 61: Normally Closed, Power Open Motorized Valve & Relay Wiring Detail
Anti-short Bushing
Connector
Conduit
Anti-short Bushing
Connector
Pin(s), female connect to terminal H8
Note: Connectors on valve must be cut off and stripped back and the wires twisted to make connections to the IV/PR Terminals
Pump Restart Relay Kit P/N 061419001
The MicroTech III unit controller has an internal Pump Restart Relay connected to H8, Pin 2 for the Normally Open (N/O) terminal of the internal relay.
Connect to H8, Pin 1 for the Normally Closed (N/C) terminal of the internal relay.
The output of the internal pump restart relay is 24­volts AC and the output is not available when the H8 connection is used to control a motorized valve.
IM 986-2 / Page 43 of 48
Troubleshooting
The in and outs of R-410A
R-410A is a non-ozone depleting blend of two
refrigerants - HFC-125 and HFC-32 in a fty percent
mixture. R-410A exhibits higher operating pressure and refrigeration capacity than R-22. R-410A is intended for use in new air conditioning applications that have traditionally been used HCFC-22 (R-22). Due to higher capacity and pressure of R-410A, it must not be used in existing R-22 systems.
Although R-410A is non-ammable at ambient
temperature and atmospheric pressure, it can become combustible under pressure when mixed with air.
Note: Because a water source heat pump operates under a wide range of water and air temperatures, the values printed below are to be taken as suggested pressure and temperatures. All McQuay water source heat pumps are designed for commercial use. The units are designed for the cooling mode of operation and fail safe to cooling. The reversing valve is energized for the heating mode of operation.
Superheat Head Pressure Water Delta T
8 to 14 degrees 335-355 PSIG 10° to 14°
All information above is based on ISO standard 13256-1 and tested at these conditions.
Note: R-410A should not be mixed with air under pressure for leak testing. Pressure mixtures of dry nitrogen and R-410A can be used for leak testing.
Lubrication
R-410A should be used only with polyester (POE) oil. The HFC refrigerant components in R-410A will not be compatible with mineral oil or alkylbenzene lubricants. R-410A systems will be charged with the OEM recommended lubricant, ready for use with R­410A.
Charging
Due to the zeotropic nature of R- 410A, it should be charged as a liquid. In situations where vapor is normally charged into a system, a valve should be
installed in the charging line to ash the liquid to vapor
while charging.
Make certain that the recycle or recovery equipment used is designed for R-410A. The pressure of R-410A refrigerant is approximately 60 percent greater than that of R-22. Pressure gauges require a range up to 800 PSIG high side and 250 PSIG low side. Recovery cylinders require a 400 PSIG rating – do not put R­410A in a 300 PSIG rated cylinder.
WARNING
Recycle/recovery equipment must be designated for R­410A. R-410A pressure is greater than R-22. Improper equipment can cause severe injury or death.
General Maintenance
1. Normal maintenance on all units is generally
limited to lter changes. Units are provided with
permanently lubricated motors and require no oiling even though oil caps may be provided.
2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels produce a lot of lint from carpeting and
linen changes, and will require more frequent lter changes. Check lters at 60-day intervals for the rst
year until experience is acquired. If light cannot be
seen through the lter when held up to sunlight or
a bright light, it should be changed. A more critical standard may be desirable.
3. The condensate drain pan should be checked
annually and cleaned and ushed as required.
4. Record performance measurements of volts, amps, and water temperature differences (both heating and cooling). A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition.
5. Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the unit is a normal protective result. Check for dirt in the
water system, water ow rates, water temperatures, airow rates (may be a dirty lter), and air
temperatures. If the lockout occurs in the morning following a return from night setback, entering air below machine limits may be the cause.
Page 44 of 48 / IM 986-2
Troubleshooting Refrigeration Circuit
Charge
Symptom
Head Suction Compressor Super
Pressure Pressure Amp Draw
Subcooling
Temp (loops) Temp Lock
Heat
Air Water Safety
Differential Differential Out
Undercharge System Low Low Low High Low Low Low Low Pressure (Possible Leak)
Overcharge System High High High Normal High Normal High Pressure
Low Air Flow Heating
Low Air Flow Cooling
Low Water Flow Heating Low Water Flow Cooling High High High High Low Low High High Pressure
High Air Flow Heating High Air Flow Cooling High Water Flow Heating
High Water Flow Cooling TXV Restricted High Low High High Low Low
High High High Low Low Low
Low
Normal
Low
Normal
Low Low High Low High Low Temp
Low Low Low Low High Low Low Low Temp Low High Normal High Low Low Normal High Pressure
Normal Low Normal High Normal Normal Low High Pressure
Low Low Low Low High Normal Low Low Temp
Normal Low
High
Normal
Low
Normal
Low High Low High Pressure High High Low Low Temp
Normal
Low
Figure 62: Cooling Mode
Return Air
Coil –
Air to
Refrigerant
Heat
Exchanger
Blower
Conditioned Air
(Cooling)
Cooling Refrigeration Cycle
When the wall thermostat is calling for COOLING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor, to the water-to-refrigerant heat exchanger. Here the heat is removed by the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion metering system to the air-to­refrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same time absorbing heat and cool­ing the air passing over the surfaces of the coil. The refriger­ant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Thermal
Expansion Valve
Coaxial Heat
Exchanger
Water In
Water Out
Reversing Valve
Sensing Bulb and Capillary Tube
Compressor
Figure 63: Heating Mode
Return Air
Thermal
Coil –
Air to
Refrigerant
Heat
Exchanger
Blower
Conditioned Air
(Heating)
Expansion Valve
Heating Refrigeration Cycle
When the wall thermostat is calling for HEATING, the revers­ing valve directs the flow of the refrigerant, a hot gas, leaving the compressor, to the air-to-refrigerant heat exchanger coil. Here the heat is removed by the air passing over the surfac­es of the coil and the hot gas condenses to become a liquid. The liquid then flows through a capillary thermal expansion metering system to the water-to-refrigerant heat exchanger. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Coaxial Heat
Exchanger
Water In
Water Out
Reversing Valve
Sensing Bulb and Capillary Tube
Compressor
IM 986-2 / Page 45 of 48
Troubleshooting the Water Source Heat Pump Unit
Figure 64: Troubleshooting Guide - Unit Operation
Low voltage, check power supply voltage
Check wiring - loose or broken and check for faulty connection
Check relays and contacts, also capacitor and wiring
Check high pressure switch, low pressure switch and low temperature switch to see if unit is cycling on the safety
Check to see if the reversing valve is not hung up and is operating correctly
Check condensate overflow switch in cool mode of operation
Check thermostat for proper location
Fuse may be blown, circuit breaker is open
Neither fan, nor compressor runs and all LED lights are off
Compressor runs in short cycle
Wire may be loose or broken. Replace or tighten wires
Fan operates,
Unit
compressor does not
Unit control, check thermostat for correct wiring or faulty thermostat
Check capacitor
Check wiring - loose or broken and check for bad connection
High or Low pressure lockout A. Cool mode, check water flow B. Heating mode, check air flow C. Check reversing valve for
proper valve position
Check compressor overload - make sure it is closed
Check compressor to ground, or for internal short to ground
Compressor winding may be open. Check continuity with ohm meter
Compressor attempts to start but does not
Check compressor wiring for defective wiring or loose connection
Check for defective compressor internal windings with ohm meter
Check for faulty compressor capacitor
Check for lock rotor amp draw
Insufficient cooling or heating
Check thermostat for improper location
Check for proper air flow ­filter could be dirty
Check blower assembly for dirt or faulty fan motor capacity
Check for low refrigerant charge
Check amp draw on blower assembly
Check for proper water flow and delta T (°F)
Page 46 of 48 / IM 986-2
DANGER
To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s).
Power supply to unit must be disconnected when
making field connections. To avoid electrical shock, per­sonal injury or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
General Use and Information
The MicroTech III unit controller is provided with two drive terminals, R(24VAC) and C(0 VAC) that can be used by the end user to drive the thermostat inputs (G, Y1, Y2, W1, and W2) and control inputs (U, E, and O). Any combination of a single board drive terminal (R or C) may be used to operate the MicroTech III unit controller’s control or thermostat inputs. However, only one drive terminal (R or C) can be connected to any individual input terminal or damage may result. Some control inputs are not accessible to the end user (for example, HP, LP, SLTS, and COF).
Typically the MicroTech III unit controller’s R (24VAC) terminal is used to drive the board’s thermostat inputs and control inputs by connecting it to the R terminal of an industry standard thermostat. The control outputs of the standard thermostat are then connected to the MicroTech III unit controller thermostat inputs and control inputs as needed. Any remaining board input(s) may be operated by additional thermostat outputs or remote relays (dry contacts only).
All MicroTech III unit controller inputs must be operated by dry contacts powered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate the MicroTech III unit controller inputs. No outside power source may be used to operate the MicroTech III unit controller inputs.
IM 986-2 / Page 47 of 48
Daikin McQuay Training and Development
Now that you have made an investment in modern, efficient Daikin McQuay equipment, its care should be a high priority. For training information on all Daikin McQuay HVAC products, please visit us at www. daikinmcquay.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin McQuay Representative, go to www.daikinmcquay.com.
Aftermarket Services
To find your local parts office, visit www.daikinmcquay.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.daikinmcquay.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.daikinmcquay.com.
Products manufactured in an ISO certified facility.
©2012 McQuay International • www.daikinmcquay.com • 800.432.1342 IM 986-2 Page 48 of 48 (5/12)
Loading...