S - Standard 1" Throwaway
P - 2" Pleated (Merv 7)
Y - None
Blower Motor
12 - 2-Speed PSC Motor
32 - ECM 2-speed 2.3 Motor
33 - ECM 2-speed X13 Motor
Power Connection
F - Fused Disconnect
N - Non-Fused Disconnect
H - HACR Breaker
Supply Air Conguration
LYY - Single Supply Outlet, Left Side
RYY - Single Supply Outlet, Right Side
FYY - Single Supply Outlet, Front Side
BYY - Single Back Side Supply Outlet
TYY - Single Top Supply Outlet
LFY - Double Supply, Left Side and Front Side
LRY - Double Supply, Left Side and Right Side
LBY - Double Supply, Left Side and Back Side
RFY - Double Supply, Right Side and Front Side
RBY - Double Supply, Right Side and Back Side
BFY - Double Supply, Back Side and Front Side
LTY - Double Supply, Left Side and Top
RTY - Double Supply, Right Side and Top
BTY - Double Supply, Back Side and Top
FTY - Double Supply, Front Side and Top
LFT - Triple Supply, Left Side, Front Side and Top
LRT - Triple Supply, Left Side, Right Side and Top
FRT - Triple Supply, Front Side, Right Side and Top
FBT - Triple Supply, Front Side, Back Side and Top
BRT - Triple Supply, Back Side, Right Side and Top
BLT - Triple Supply, Back Side, Left Side and Top
YYY - Closed Supply Plenum for eld modication
Page 4 of 48 / IM 986-2
Note: For illustration purposes only. Not all options avail-
able with all models.
Please consult McQuay Sales Representative for
specic availability.
Model Nomenclature
Vertical Stack Water Source Heat Pump – Chassis (VHC)
W VHC 1 012 B E A C AMY C
Product
Category
W - WSHP
Product Code
VHC - Chassis
Design Series
1
2
Unit Size - Tons
009 - 3/4 Ton
012 - 1 Ton
015 - 1-1/ 4 Ton
018 - 1-1/2 Ton
021 - 1-3/4 Ton
024 - 2 Ton
030 - 2-1/2 Ton
036 - 3 Ton
Controls
B - MicroTech III
C - MicroTech III With L
D - MicroTech III With BACnet
onWorks
Voltage
A - 115/60/1 ph
E - 208-230/60/1 ph
J - 265-277/60/1 ph
Coax Coil Construction
C - Copper Inner - Steel Outer
S - CuproNickel Inner - Steel Outer
X - Special
Chassis Construction
AYY - Standard Fiberglass Insulation
EYY - IAQ - Cellular Insulation
AMY - Standard w/Compressor Blanket
EMY - IAQ w/Compressor Blanket
AYC - Standard w/E-Coated Air Coil
EYC - IAQ - Cellular w/E-Coated Air Coil
AMC - Standard w/Comp Blanket and Coated Air Coil
EMC - IAQ w/Comp Blanket and Coated Air Coil
Motorized 2-Way Isolation Valve
C - 2-Way Motorized 1/2" Iso-Valve, General Close-Off Pressure N.C.
(Normally Closed)
V - 2-Way Motorized 1/2" Iso-Valve, General Close-Off Pressure N.O.
(Normally Open)
H - 2-Way Motorized 1/2" Iso-Valve, High Close-Off Pressure N.C.
(Normally Closed)
D - 2-Way Motorized 3/4" Iso-Valve, General Close-Off Pressure N.C.
(Normally Closed)
K - 2-Way Motorized 3/4" Iso-Valve, General Close-Off Pressure N.O.
(Normally Open)
J - 2-Way Motorized 3/4" Iso-Valve, High Close-Off Pressure N.C.
(Normally Closed)
Y - None
X - Special
Refrigerant
A - R-410A
X - Special
Note: For illustration purposes only. Not all options
available with all models.
Please consult McQuay Sales Representative
for specic availability.
IM 986-2 / Page 5 of 48
Receiving and Storage
Upon receipt of the equipment, check the carton and
pallets for visible damage. Make a notation on the
shipper’s delivery ticket before signing. If there is any
evidence of rough handling, immediately open the
cartons to check for concealed damage. If any damage
is found, notify the carrier within 48 hours to establish
your claim and request their inspection and a report.
The Warranty Claims Department should then be
contacted.
IMPORTANT
This product was carefully packed and thoroughly
inspected before leaving the factory. Responsibility for its
safe delivery was assumed by the carrier upon acceptance
of the shipment. Claims for loss or damage sustained in
transit must therefore be made upon the carrier as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted
on the freight bill or carrier’s receipt, and signed by the
carrier’s agent. Failure to adequately describe such
external evidence of loss or damage may result in the
carrier’s refusal to honor a damage claim. The form
required to le such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which
does not become apparent until the product has been
unpacked. The contents may be damaged in transit due
to rough handling even though the carton may not show
external damages. When the damage is discovered upon
unpacking, make a written request for inspection by the
carrier’s agent within fteen (15) days of the delivery date
and le a claim with the carrier.
Cabinet Skid (4-units per skid)
Never stack cabinets higher than as illustrated in Figure
1 at any time during transportation or storage or damage
may occur.
Figure 1: Unit Cabinet Skid as Shipped and Stored
Chassis Skid (4 per skid, stored two skids high)
Never stack chassis´ higher than as illustrated in Figure
2 at any time during transportation or storage or damage
may occur.
Figure 2: Chassis Skids Stacked 2 High Maximum
For storing, each carton is marked with “up” arrows.
4'
6'
Storage and Operating Environment
Temporary storage at the job site must be indoor,
completely sheltered from rain, snow, etc. High or low
temperatures naturally associated with weather patterns
will not harm the units. Excessively high temperatures,
140°F (60°C) and higher, may deteriorate certain plastic
materials and cause permanent damage.
Storage Temperature:
-40ºF (-40ºC) to 140ºF (60ºC)
Operating Temperature:
32ºF (0ºC) to 140ºF (60ºC)
Humidity:
10%RH to 90%RH Non-condensing
PCB Material and Flammability Rating:
IPC/ANSI FR or CEM material as required to meet UL
94V-0 ammability rating.
Page 6 of 48 / IM 986-2
Handling
Carefully check items against the bills of lading to
verify all crates and cartons have been received.
Cabinets and Chassis normally ship four to a pallet.
Carefully inspect all units for shipping damage. Report
damage immediately to the carrier and le a claim.
Check the unit data plate to be sure the unit electrical
agrees with the power supply available (Figures 3).
Figure 3: Unit Components & Descriptions - Received as
Assembled Cabinet with Chassis Shipped Separate
4
1a
1
2
1b
1b
3
Unit
Data Plate
Stub-out
Seals
DO NOT handle units by the riser piping. Riser clamps
hold the riser in position; they are not designed to
support the cabinet weight. The clamps are removed
after the unit is installed.
Unit cabinets are factory assembled and wired and
have individual thermostat control capability. They are
installed by stacking one unit on top of the other. While
installing, prevent dirt and other foreign matter from
entering the risers and plugging lines or valves. See
"Cleaning & Flushing Water System" on page 16.
General Information
McQuay Vertical Stack units are designed for use in
nursing homes and other similar applications. They
require a minimum amount of oor space and are
designed for multiple discharge arrangement.
Installation and maintenance must follow accepted
industry practices as described in the ASHRAE
Handbook, the National Electric Code, and other
applicable standards. Install this equipment in
accordance with regulations of authorities having
jurisdiction and with all applicable codes.
WARNING
Installation and maintenance are to be performed by
qualied personnel who are familiar with local codes and
regulations, and experienced with this type of equipment.
WARNING
The installer must determine and follow all applicable
codes and regulations. This equipment presents hazards
of electricity, rotating parts, sharp edges, heat and weight.
Failure to read and follow these instructions can result in
property damage, severe personal injury or death. This
equipment must be installed by experienced, trained
personnel only.
Chassis
Data Plate
Component Descriptions (Assembled
Cabinet)
1. Cabinet assembly complete (without chassis)
1a. Pipe riser sets (inlet, outlet and condensate)
1b. Inner front panel and lter bracket
2. Cooling and heating chassis (shipped separate)
3. Return air grille/panel (accessory)
4. Double-deection diffuser (accessory)
!
CAUTION
Sharp metal edges are a hazard, use care when servicing
to avoid contact with them.
IM 986-2 / Page 7 of 48
Disassembling Upper and Lower
Cabinet Sections
The Vertical Stack unit cabinet ships completely
assembled. If required, it may be disassembled into two
(2) sections (upper-fan/discharge cabinet) and (lower
chassis/return air cabinet) to make it easier to handle. To
disassemble, do the following.
1. Remove risers (if received attached).
2. Remove the three (bottom row) screws on the back
of the unit as shown in Figure 4.
Note: Retain all screws for later use to reassemble
unit in reverse order as described in steps 1-7.
Number of screws will vary depending on unit size.
3. Carefully lay the unit down on its back and remove
the remaining eight (8) screws on the left and right
side of the cabinet (Figure 5).
5. Remove the ten (10) screws and lift off the front
panel/lter rack to gain access to the cabinet interior
(Figure 6).
Figure 5: Remove remaining eight (8) screws on the left and
right sides of the cabinet
Four (4) screws located
on left side of cabinet
Figure 6: Remove the ten (10) screws from the front panel/
lter rack.
6. Locate and remove the six (6) screws located inside
the cabinet joining the upper and lower cabinet
sections (Figure 7).
Note: Pull the insulaton away from the walls of the
cabinet interior to get access to the screws.
7. Separate the lower return air cabinet section from
the upper blower/discharge cabinet section
(Figure 8).
Figure 4: Remove three (3) screws (bottom row) on the back
of the unit.
Back of Unit
Figure 7: Remove the six (6) screws located on the interior
of the unit.
Return air cabinet
section interior
Figure 8: Separate the lower cabinet section from the upper
cabinet
1. To prevent damage to equipment, do not operate
supplementary heating and cooling during the
construction period.
2. Inspect the carton for any specic tagging numbers
indicated by the factory per a request from the
installing contractor. At this time the voltage, phase
and capacity should be checked against the plans.
3. Check the unit size against the plans to verify that
the unit is being installed in the correct location.
4. Before installation, check the available dimensions
of the area where the unit is to be installed versus
the dimensions of the unit.
5. Note the location and routing of water piping,
condensate drain piping, and electrical wiring.
The locations of these items are clearly marked on
submittal drawings.
6. The installing contractor will nd it benecial
to confer with piping, sheet metal, and electrical
foremen before installing any unit.
Figure 11: Typical Side by Side Unit Installation
Note: Check the unit data plate for correct voltage
with the plans before installing the equipment.
WARNING
Make sure all electrical ground connections are made in
accordance with local code.
WARNING
The contractor shall cover the units to protect the machines
during nishing of the building. This is critical while spraying
reproong material on bar joists, sandblasting, spray painting
and plastering.
For Optimum Unit Performance and to
Help Minimize Noise and Vibration
● Adhere to the "Critical Dimensions" for locations of
framing and distances to the cabinet.
● Install a 1/4" thick vibration isolation pad under the
entire footprint of the unit cabinet base.
● Be sure there are no kinks and that the stainless
steel braided hoses do not come in contact with and
vibrate on chassis and cause noise.
● Ensure there is no metal-to-metal contact between
return air grille and cabinet and the discharge
diffuser and the cabinet, use provided gaskets.
● Air balancing in ducted applications is critical for
proper airow at each diffuser.
NOTICE
Top air discharge units will require turning vanes and/or a
volume damper for proper air flow and balancing, to minimize turbulence. These components must be field-installed
and furnished in accordance with SMACNA guidelines.
IM 986-2 / Page 11 of 48
Cabinet Configurations
Figure 12: Single Side Discharge
Figure 13: Double Side Discharge
Figure 14: Side & T op Discharge (See Notice on page 11) Figure 15: Double Side & Top Discharge (See Notice on page 11)
Figure 16: Top Discharge (See Notice on page 11) Figure 17: Closed Plenum – Field Modication Required
= Return Riser = Supply Riser = Drain = Return Air = Discharge Air = Top Discharge
Top air discharge units will require turning vanes and/or a
volume damper for proper air flow and balancing, to minimize turbulence. These components must be field-installed
and furnished in accordance with SMACNA guidelines.
Note: All ducted applications require a unit that utilizes an ECM-X13 or ECM 2.3 motor (sizes 021-036).
X13 motors are factory set for 2-speeds, 2 and 4 tap. For ducted unit applications only position 1 and 2-speed
motor taps should be used.
Additionally, static pressure must not exceed 0.40 inch static. See table below.
Location of studs is critical for proper installation and
t up and can help to reduce unit noise due to vibration
when properly installed.
Figure 19: Framing Locations to Unit Openings
Note: If the unit cabinet was shipped without
risers attached it will be necessary to remove the
appropriate riser knockouts prior to positioning the
cabinet and connecting to the riser stub outs.
Figure 20: Vertical Riser Stub-Outs Locations to Unit
Knockouts
Unit Size 021-036 = 4.54"
Unit Size 009-018 = 3.125"