McQuay VFC007 User Manual

Enfinity™ Vertical Water Source Heat Pumps Catalog 1103-2
Floor Model VFC & VFW
Unit Sizes 007 – 070 (1/2 to 6 Tons) • R-410A Refrigerant
Engineered for exibility and performance™
Table of Contents
Product Models Nomenclature . .......................................... 3
Introduction ...........................................................................4
Vertical Floor-mounted Design Features & Options ......... 5-9
Vertical Floor-mounted Design Control Options .................10
Vertical Floor-mounted Design Control Features ..........11-14
Microtech III Control System .......................................11
Microtech III with LONWorks Comm. Module .............13
Microtech III with BACnet
Applications - Systems ................................................ 15-17
Heating and Cooling Refrigeration Cycle ....................15
Boiler
Open Loop Well Water Application ..............................16
Closed Loop Geothermal Application ..........................17
Applications Considerations .........................................18-20
T
Unit Location ...............................................................18
Ductwork & Ettenuation ................. ............................ 19
Piping ..........................................................................19
Condensate Drain .......................................................19
Unit Selection ..............................................................20
ISO Performance Data .................................................21-23
W
Ground Loop ...............................................................22
Ground Water ..............................................................23
Capacity Data ............................................................... 24-45
Size 012 (400 cfm) ......................................... 26-27
Size 015 (500 cfm) ......................................... 28-29
Size 019 (600 cfm) ......................................... 30-31
Size 024 (800 cfm) ......................................... 32-33
Size 030 (1000 cfm) ....................................... 34-35
Size 036 (1300 cfm) ....................................... 36-37
Size 042 (1400 cfm) ....................................... 38-39
Size 048 (1600 cfm) ....................................... 40-41
Size 060 (2000 cfm) ....................................... 42-43
Size 070 (2160 cfm) ....................................... 44-45
Performance Data
Operating Limits .........................................................46
Correction Factors
Airow .........................................................................47
Antifreeze ...................................................................47
Electrical Data ..............................................................48-59
Unit without Options ...................................................48
Unit with Desuperheater .............................................49
Unit with ECM .............................................................50
Unit with Desuperheater and ECM .............................51
Unit with 10kW Electric Heat Coil ...............................52
Unit with 5kW Electric Heat Coil .................................53
Unit with ECM and 10kW Electric Heat Coil ...............54
Unit with ECM and 5kW Electric Heat Coil .................55
Unit with Desuperheater and 10kw Elec. Heat Coil....56
Unit with Desuperheater and 5kW Elec. Heat Coil .....57
Unit with Desuperheatert, ECM and 10kW
Electric Heat Coil ........................................................58
Unit with Desuperheater
Electric Heat Coil ........................................................59
Tower Application ..............................................16
ypical Vertical Installation ..........................................18
ater Loop ..................................................................21
Size 009 (300 cfm) ......................................... 24-25
®
Comm. Module..................14
, ECM and 5kW
Fan Performance
PSC Motor CFM - Sizes 007 - 070 .............................60
ECM Motor CFM - Sizes 007 - 070
Physical Data.....................................................................61
Dimensional Data .........................................................62-66
Vertical (Left & Right Hand) Sizes 009, 012 ............... 62
Vertical (Left & Right Hand) Sizes 015, 019, 024 .......63
Vertical (Left & Right Hand) Sizes 030, 036 ...............64
Vertical (Left & Right Hand) Sizes 042, 048 ...............65
Vertical (Left Hand) Sizes 042, 060, 070 ....................66
Field Installed Accessories ...........................................67-69
Programmable Electronic Thermostat Two-Stage
Heat/Two-Stage Cool, 7-Day Programmable .............67
Non-Programmable, Auto or Manual Changeover Two-Stage Heat/Two Stage Cool, Night Setback
Override.................................................................67-68
MicroTech III Water Source Heat Pump Room
Temperature Sensors .................................................68
Optional Remote Sensor ............................................68
Supply and Return Water Hoses ................................69
Condensate Hose Kit .................................................69
Combination Balancing and Shutoff (Ball) Valves ......69
Optional Two-inch Filter Rack ....................................69
Control Connection Diagrams ...........................................70
Programmable Electronic Thermostat Two-Stage
Heat/Two-Stage Cool, 7-Day Programmable .............70
Non-Programmable, Auto or Manual Changeover
Two Stage Heat/Two Stage Cool, Night Setback and
Override Feature ........................................................70
Optional Remote Sensor Wiring to Thermostat(s) .....70
Optional Water Source Heat Pump Room
Temperature Sensors Wiring ......................................70
Typical Wiring Diagrams ...............................................71-75
MicroTech III Unit Controller (Standalone) –
208/230/460/575/60Hz/3-Phase.................................71
MicroTech III Unit Controller with Optional ECM
Motor, Desuperheater and I/O Expansion Module
– 208/230/265/277/60 Hz/1-Phase.............................72
MicroTech III Unit Controller with Optional ECM Motor,
Desuperheater, Electric Heat Coil and I/O Expansion
Module – 208/230/460/60 Hz/3-Phase .......................73
MicroTech III Unit Controller with Optional ECM
Motor, Desuperheater, and I/O Expansion Module
208/230/460/60/3-Phase ............................................74
MicroTech III Unit Controller with PSC Motor,
Desuperheater and I/O Expansion Module for Hot Gas
Reheat Control (Unit Sizes 019-070) 208/230/60/1-
Phase .........................................................................75
Guide Specications .....................................................76-79
2 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Model Nomenclature
Vertical Floor Unit (Size *007 - 070)
Note: For illustration purposes only. Not all options available with all models.
Please consult McQuay Sales Representative for specic availability.
W VFC 1 019 B E Y L T Product Category
W = WSHP
Product Identier
VFC = Floor Mounted/Standard Range VFW = Floor Mounted/Geothermal
Design Series
1 = A Design 2 = B Design 3 = C Design 4 = D Design
Nominal Capacity
*007 = 7,000 BTU/h
009 = 9,000 BTU/h 012 = 12,000 BTU/h 015 = 15,000 BTU/h 019 = 19,000 BTU/h 024 = 24,000 BTU/h 030 = 30,000 BTU/h 036 = 36,000 BTU/h 042 = 42,000 BTU/h 048 = 48,000 BTU/h 060 = 60,000 BTU/h 070 = 70,000 BTU/h
*Unit size 007 not available at time of publication. Please consult your
local McQuay Representative for specic availability.
Vertical (Floor) Water Source Heat Pumps Sizes *007-070 (1/2 to 6 Tons)
Model VFC (Standard Range: 55°F to 110°F) Model VFW (Geothermal Range: 30°F to 110°F)
Controls
B = MicroTech III Unit Controller
C = MicroTech III Unit Controller w/LonWorks Communication Module
D = MicroTech III Unit Controller w/BACnet Communication Module
Discharge Air
T = Top
Return Air
L = Left R = Right
Future
(None)
Voltage
A = 115/60/1 E = 208-230/60/1 F = 208-230/60/3 J = 277-265/60/1 K = 460/60/3 L = 575/60/3
“McQuay” is a registered trademark of McQuay International.
©McQuay International 2009. All rights reserved throughout the world.
The information in this manual supersedes and replaces previous catalogues with regards to McQuay Water Source Heat Pump products. Illustrations cover the general appearance of McQuay International products at the time of publication and McQuay International reserves the right to make changes in design and construction at anytime without notice.
®
The following are trademarks or registered trademarks of their respective companies: LonTalk from Echelon Corporation, BACnet from ASHRAE, Protocol
Selectability, and MicroTech III from McQuay International.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 3
Introduction
Ennity
complete line of water source heat pumps for high efcien-
cy, individually-zoned comfort control in ofces, schools,
assisted living facilities, manufacturing facilities and other commercial buildings. Our reputation for outstanding reli­ability and quiet operation has been reinforced in thousands of successful installations.
our past and the best of what’s new. Using feedback from building owners, consulting engineers, contractors and ser-
vice engineers, we designed Ennity products to give you maximum exibility to design, install, operate and maintain
the ideal water source heat pump system for your building project. And we incorporated non-ozone depleting R-410A refrigerant, which–along with high Energy Efciency Ra­tios (EER’s)–helps preserve our environment and precious energy resources.
Water Source Heat Pumps
More than 30 years ago, McQuay designed the rst
Ennity water source heat pumps incorporate the best of
With Ennity Water Source Heat Pumps, you benet from:
High efciency that minimizes environmental impact
and lowers operating costs
Units exceed ASHRAE Standard 90.1 minimum
requirements
High efciency standard range or geothermal
application exibility
Easy, low-cost design and installation
Two congurations for each unit size (left or right
return) allow you to specify units to t space require
ments and to design the system using minimum duct­work and piping.
Four cabinet sizes, each with McQuay’s small footprint
design, make it easy to meet the space requirements of your new construction or replacement application.
Flush FPT water ttings allow easy, one-wrench tight-
ening of hose kits and help reduce delays caused by shipping damage.
Open Choices™ controls feature allows easy, low cost
integration with a Building control Automation System of your choice.
Factory-installed lter rack saves time and expense to
eld-install a lter rack.
Factory-installed electric heat, desuperheater and ECM
motor options help you meet more specic application
requirements with minimum design or installation time
and expense.
Easy, low-cost maintenance
Easy access to the unit compressor (2-sides), fan sec-
tion (1-side), motor (1-side) and unit controls (front
access).
A removable orice ring allows the blower and motor
to be removed without removing the blower housing or
disconnecting the unit from the ductwork.
Quiet operation
Large fan wheel allows the fan motor to operate at
lower speed for quieter operation.
Two quiet compressor selections (depending on volt-
age and size variations) including rotary (sizes 007 to
015), and scroll compressors (sizes 019 to 070).
Superior Indoor Air Quality (IAQ)
Double-sloped, polymer drain pan promotes positive
condensate drainage.
Optional closed-cell foam insulation (no glass bers in
air stream).
Optional Hot Gas Reheat Coil provides superior
humidity control.
R-410A refrigerant with zero ozone depletion potential or phase-out date
R-410A is classied as A1/A1 – lower toxicity, no
ame propagation – per ASHRAE Standard 31.
Exceeds ASHRAE 90.1 Minimum Efciencies
4 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features & Options
I/O Expansion Module
LED Annunciator
MicroTech III Unit Controller
L Communication Module
BACnet Communication Module
onWorks
1. Electric Heat (Optional) – Integral electric heat coil provides
supplemental or emergency heat when conditions require.
2. Electronically Commutated Motor (ECM-Optional) - ECM motor
provides quiet, efcient operation while maintaining constant
over its static operating range. Factory programmed for
CFM 3-speeds.
3
. MicroTech® III Unit Controller – Designed for exibility, the
main
control board is used in standalone applications. An
optional I/O expansion module can be used to control electric
heat
and multiple fan speeds. A separate L
net®
communication module can be easily snapped onto the
onWorks® or BAC-
board to accommodate the building automation system of your choice.
4. LED Annunciator
– External
LED status lights display fault
conditions to provide easy troubleshooting and diagnosis.
5. Compact Cabinet – The
standard unit is constructed of unpainted G-60 galvanized steel, with the smallest possible footprint. Optional painted cabinet is ideal for aesthetic re­quirements
6. Desuperheater (Optional)
of residential applications.
Saves energy by producing domes­tic hot water using a small heat exchanger and water pump lo­cated
in the compressor compartment. Superheated refrigerant gas from the compressor, which would otherwise be wasted, is used to heat water. This reduces the amount of additional energy required to heat water and it may eliminate the require
for separate water heating equipment.
ment
Desuperheater Heat Exchanger and Water Pump Piping Circuit
Optional – Hot Gas Reheat Piping Circuit
7. Filter & Filter Rack – Units come standard with a 1" (25.4 mm)
thick throwaway lter mounted in a 4-sided combination lter
rack
and return air duct collar. This eliminates the added labor
and cost to eld-mount brackets. Filters can be easily removed
from
any side. A 2" lter rack is available as a factory-installed
selectable option to accept higher efciency lters
8.
Removable Access Panels – Two front panels provide easy
access to the blower motor and unit controls. Two rear panels provide easy access to the fan housing and compressor section.
9. Piping Connections
– Water connections are FPT water t-
tings, ush with the outside of the cabinet for easy one-wrench
connection
to units. A large condensate connection provides
proper condensate removal.
10. Coaxial Heat Exchanger
– Designed
for maximum heat transfer
at normal and low water ow rates with minimum pressure drop. The inside tube is deeply uted to enhance heat transfer
and
minimize fouling. A cupro-nickel heat exchanger is avail-
able
as a selectable option.
11. Hot Gas Reheat Coil (Optional) – Provides superior humidity
control by using expelled heat from the refrigeration cycle and redirecting it through an isolated circuit in the evaporator section. For every 10°F of temperature rise across the hot gas reheat coil there is approximately a 20% drop in the discharge air relative humidity (%Rh). A wall-mounted humidistat is
-
used in conjunction with the unit to measure and adjust the humidity in the space.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 5
Vertical Floor-mounted Features and Options
Flexible Congurations
Top View
Right Hand
Return
Air
Control Box
Cabinet
The Ennity Vertical Water Source Heat Pump is
factory assembled and tested for reliability. Five unique
cabinet sizes make up our 1/2 through 6 ton (1.8 through
21.2 kW) vertical heat pump product line. The consistent shape makes layout simple. Water, condensate and duct connections are all in similar locations to simplify installation.
The fan section is separated from the compressor section with an insulated divider panel for maximum sound attenuation. A large removable panel provides easy service access to the blower and motor.
The cabinet is constructed of unpainted, G-60 galvanized steel. The interiors of the top and side panels
and the bottom of the unit are covered with 1/2" thick
(13 mm), 1 standard. An optional closed cell insulation is available for applications with more stringent IAQ requirements.
1
/2 lb. (681 g) density coated glass ber as
Cabinet Congurations
For maximum exibility, each vertical unit is available
in either a left-hand or right-hand return air arrangement to provide the optimum piping location and service access.
The mirror image design of the units lets you congure
the system using minimum ductwork and piping. This helps reduce design, material and installation costs.
Left Hand
Water
Connections
Filter Rack
The lter is supported by factory-mounted brackets that
allow for face removal. Units come standard with a 1" (25.4
mm) thick throwaway lter mounted in a combination lter rack and return air duct collar, thus eliminating eld mounted brackets. The lter can be removed from the right or left
side.
Optional factory-mounted or eld-installed 2" lter rack
kit for higher ltration requirements.
Optional 2" Filter Rack
Remove lter from the left or right side without a tool
Blower Housing
The blower housing protrudes through the cabinet top
allowing adequate material for connection to a exible
duct.
Fan Housing Protrudes Through the Cabinet Top for Connection of Flexible Duct
6 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features and Options
Electrical
The electrical components are located in the compressor section of the unit. Separate holes are provided on the cabinet to facilitate main power and low voltage control wiring. All wiring connections are made internal to the cabinet to reduce the risk of accidental contact. Each unit is rated to accept time-delay fuses for branch circuit overcurrent protection. Single phase units are also rated for use with HACR circuit breakers.
The control box houses the major operating electrical controls including the MicroTech III unit controller, transformer, compressor relay and fan relay. Each component can be accessed easily for service or replacement.
Easy Access to the Vertical Unit Control Panel
Water Connections
The water and condensate connections are FPT ttings, securely mounted ush to the corner post to allow for connection to a exible hose without the use of a back-up
wrench. This helps reduce the time required to connect the unit and helps prevent delays due to shipping damage. All vertical units are internally trapped with clear vinyl tubing, to allow inspection of condensate drain.
Flush FPT Water Fittings
Access panels lift up and out easily
Vertical Unit Double-Sloped Drain Pan
Double Sloped Channels
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 7
Vertical Floor-mounted Features and Options
R-410A Refrigerant
R-410A refrigerant has zero ozone depletion potential,
no scheduled phase-out and is classied in ASHRAE
Standard 31 as A1/A1 – lower toxicity, no ame
propagation.
Compressors
Ennity water source heat pumps are designed around
the most advanced compressors in the industry. A wide variety of compressor types are used to offer the best system design for the dedicated refrigerants and tonnage.
This allows Ennity water source heat pumps to deliver
rated capacity with low noise levels.
Rotary compressor with R-410A is used in vertical units size 007 to 015. R-410A, non-CFC refrigerant is used in all unit sizes 007 to 070. Unit sizes 019 to 070 use a scroll compressor.
Scroll Compressor
Rotary Compressor
Thermal Expansion Valve
All Ennity water source heat pump units include a
thermal expansion valve for refrigerant metering. The Thermal Expansion Valve (TXV) allows the unit to operate
at optimum efciency with uid temperatures ranging from
30ºF to 110ºF, and entering air temperatures ranging from 40ºF to 90ºF. The TXV precisely meters the exact amount
of refrigerant ow through the system to meet the load and
deliver rated heating and cooling capacity.
Thermal Expansion Valve (TXV)
Reversing Valve
A 4-way reversing valve is included with all Enn­ity water source heat pumps. The valve is energized in the heating mode and will “fail-safe” to the cooling mode which is the predominant mode of operation for commercial applications.
4-Way Reversing Valve
Fluid-to-Refrigerant Coil
The copper or cupronickel (optional) tube-in-tube
coaxial heat exchanger used in Ennity water source heat
pumps are designed for maximum heat transfer at normal
and low water ow rates with minimum pressure drop. The inside tube is deeply uted to enhance heat transfer and
minimize fouling. All coaxial coils are tested to 400 psig on the water side and 500 psig on the refrigerant side. Geothermal range (VFW) units include coil and piping in­sulation to protect against condensation in low-temperature geothermal applications.
Coaxial Heat Exchanger
8 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features and Options
Noise Reduction
Ennity Water Source Heat Pumps include multiple
features and options to reduce unwanted noise generation including scroll and rotary compression, viscoelastic acous­tical mass plate, vibration isolated fan mounts, optional compressor sound blankets and soft starting ECM motors. While good design and installation practices are always required to prevent objectionable noise, McQuay, as a leader in engineered products can also provide many other customized solutions to meet your applications requirements.
Schrader Connections
Two Schrader valves are located inside the end access panel – one on the low side and one on the high side of the refrigeration circuit – for charging and servicing. All valves
are 7/16" SAE ttings.
Schrader Valve
to lock out compressor operation at extreme conditions. For additional protection, unit sizes 015 and larger have a 7 psi (48 kPa) low-pressure switch to protect the compres­sor from low refrigerant charge. The low setting prevents nuisance trips while providing additional protection.
Blower Section
The blower section includes the blower housing, wheel, motor and drain pan. It is separated from the compressor section by an insulated divider panel for maximum sound attenuation. The large size of the blower wheel allows it to rotate more slowly, reducing motor work to improve
efciency and provide for quiet operation. A large panel
provides service access to the blower and motor. All
blower/motor assemblies have a removable orice ring on
the housing to accommodate motor and blower removal without disconnecting the unit from the ductwork.
Blower Motors
The standard blower motor is a multi-speed, Permanent Split Capacitor (PSC) type with thermal overload protec­tion. It is permanently lubricated. The motor is factory
wired to maximize performance and efciency. Unit sizes
019 and larger have a terminal strip on the motor for simple motor speed change without going back to the control box. The motor is isolated from the fan housing using rubber isolators to minimize vibration transmission. All
blower/motor assemblies have a removable orice ring on
the housing to accommodate motor and blower removal without disconnecting the unit from the ductwork. Optional Electronically Commutated Motor (ECM) provides soft start, maintains consistent CFM over its static operating range and fan speed can be adjusted automatically based on mode of operation.
High Efciency Blower Motor Options
Air-to-Refrigerant Coil
The air-to-refrigerant heat exchanger is a large face
area coil with copper tubes and aluminum ns. The ns are lanced and mechanically bonded to the tubes using nned
edges on the inside which expand during assembly to enhance heat transfer capabilities. The maximum working pressure of the heat exchanger is 500 psig (3447 kPa). The coil is designed for optimal performance in both heating
and cooling while maintaining the benet of a compact
size. Coils can be provided with an optional E-coating.
Electronically Commutated Motor (ECM)
Refrigeration System
Units have a coaxial heat exchanger with a copper inner
tube and a steel outer tube. The air coil is a large face area
coil with copper tubes and aluminum ns. Safety controls
include a high-pressure switch and low-temperature sensor
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 9
Permanent Split Capacitor Motor (PSC)
Control Options – Control Choices and Added Functionality
The control box is accessible through the left or right end corner panel. It houses the major operating electrical controls including the MicroTech® III unit controller, transformer, compressor relay and fan relay. Each component is easily accessed for service or replacement.
Four unique control choices are offered with the Micro­Tech III unit controller:
■ Standalone operation using a MicroTech III unit controller
■ MicroTech III unit controller with I/O Expansion module
■ MicroTech III unit controller with a Lonworks® commu-
nication module
■ MicroTech III unit controller with a BACnet® communica­tion module
Each option features direct quick-connect wiring to all unit-controlled components for “clean” wiring inside the control box. Each control circuit board receives power from a 50 VA transformer.
Control Description Application Protocol
Uni t-mounte d or wall-mounted thermostat
MicroTech III
(Standalone)
Unit Controller
The MicroTech III unit controller is a standalone microprocessor-based control board conveniently located in the unit control box for accessibil
. The board is designed to provide
ity standalone control of a Water Source Heat Pump using a wall thermostat or a wall mounted temperature sen
or. Each unit controller is factory
s programmed, wired, and tested. For
added functionality an optional I/O
expansion MicroTech III controller for complete control and operation of your McQuay water source heat pump.
module interconnects to the
Each unit controller is factory programmed, wired, and tested for complete control of single zone, stand­alone
operation of your McQuay Water Source Heat
Pump.
-
-
I/O Expansion
Module
LonWorks
Communication
Module
BACnet
Communication
Module
The I/O Expansion Module is an exten­s
ion of the Microtech III unit controller and provides additional functionality to the Microtech III control system. The interconnect cable from the I/O expan-
module to the MicroTech III unit
sion controller provides two-stage operation of the water source heat pump.
The MicroTech III unit controller can accept a plug-in LonWorks commu­nication module to provide network communications and added functional ity
to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit.
The MicroTech III unit controller can accept a plug-in BACnet commu­nication module to provide network communications and added functional­ity to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit.
Allows
for:
• Monitoring of entering water temperature for boilerless electric heat control.
• Outputs for optional electric heat
• Output for multi-speed fans on a standard water source heat pump.
• Independent LED annunciator to easily identify operation fault conditions for two-stage units.
LonTalk application protocol is designed for units that are integrated into a LonWorks communication network for centralized scheduling and management of multiple heat pumps.
-
Designed to be linked with a centralized building automation system (BAS) through a BACnet com munications management of multiple heat pumps.
network for centralized scheduling and
Uni t-mounte d or wall-mounted thermostat
onMark 3.4
L
BaCnet
-
10 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Control Features – MicroTech® III Control System
The MicroTech III Unit Controller is a microprocessor­based control board conveniently located in the unit control box for easy access through a removable access panel. The standalone unit controller is a hard wired interface and pro-
vides all the necessary eld connections. The board can be
wired for 24-volt AC output to the wall thermostat by using terminals R & C. An LED annunciator is located on the front corner of the unit chassis to quickly check the operating status of the unit.
MicroTech III Operating Features
Assumes cycle fan operation-not continuous fan operation:
Start-up – The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
Cooling mode – On a call for cooling, the compressor
and fan will start 0 to 30 seconds later. When the load is
satised, the compressor and fan shut off.
Heating Mode – On a call for heating, the reversing valve
is energized after 60 seconds and the compressor and fan
start. When the load is satised, the compressor and fan
shut off. The reversing valve is de-energized 60 seconds later.
Short Cycle Protection & Random Start – Each time
the compressor stops, a new random compressor start-
delay time between 180 and 240 seconds is generated.
This prevents compressor short cycling and prevents units from starting simultaneously after coming back from an unoccupied cycle.
Unoccupied Mode – A simple “grounded” signal between
terminals U and C (no power source required), puts the unit into the unoccupied mode for night setback operation.
Override Mode – A switch on the deluxe automatic
changeover thermostat can be activated during the unoc­cupied mode to put the unit back into the occupied mode for two hours for after-hours heating or cooling.
Motorized Valve/Pump Restart – The IV/PR (H8) ter-
minals on the The MicroTech III unit controller are used to energize (open) a motorized valve or start a water pump to get water circulating prior to starting the compressor
on call for heating or cooling. The IV/PR (H8) terminal
may
be “daisy chained” between 200 units.
Brownout Protection – The MicroTech III unit controller
measures the input voltage and will suspend compressor
and fan operation if the voltage falls below 80% of the
unit nameplate rated value. A unique LED status is gen­erated and an output is available to a “fault” LED at the thermostat.
Unit Shutdown – A simple grounded signal puts the unit
into the shutdown mode. Compressor and fan operations are suspended. A unique LED status is generated and an output signal is made available for connection to a “fault” LED at the thermostat.
Condensate Overow Protection – The
MicroTech III
unit controller incorporates a liquid sensor at the top of the
drain pan. Upon sensing water ow, cooling operation is
suspended. A unique LED status is generated and output is available to a “fault” LED at the thermostat. Heating operation is not suspended.
Remote Reset of Automatic Lockouts – The Remote Re-
set feature provides the means to remotely reset automatic lockouts generated by high-pressure and/or low-tempera­ture faults. When the MicroTech III unit controller is in automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the control board to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated.
Intelligent Reset – The Fault Retry feature helps to
minimize nuisance trips of automatic lockouts caused by
high-pressure and/or low-temperature faults. This feature clears faults the rst two times they occur within a 24-hour
period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours.
Equipment Protection Control – The MicroTech III
unit controller receives separate input signals from the refrigerant high-pressure switch and the low suction line temperature sensor. In a high-pressure situation, compres­sor operation is suspended. In a low temperature situation,
the unit goes into a defrost cycle where the unit is put into cooling operation for 60 seconds until the coaxial heat exchanger is free of ice. Each switch generates its own unique LED status and output is available to a “fault” LED at the thermostat if either situation exists.
Note: Most unit fault conditions are the result of operating
the equipment outside the unit specications.
MicroTech III unit controller LED & fault outputs
Mode / Fault
Occupied, Bypass, Standby Override Unoccupied On On Off Energized Condensate Overow On Off Off De-energized High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM Corrupted
Network “Ofine” Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’
, or Tenant Off On Off Energized
Air or Low
1
ellow Green Red Output-Terminal “A”
Y
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-energized
On On Off De-energized
On On On De-energized
Off Off Off De-energized
s
Thermostat Alarm Light
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 11
Control Features – I/O Expansion Module
I/O Expansion Module
The I/O Expansion Module is a factory installed option.
It is an extension of the MicroTech III unit controller and provides extra functionality.
The I/O Expansion Module has 4 main purposes:
The Microtech III unit controller in combination with
the I/O Expansion Module will be the standard control
system for dual-circuit Water Source Heat Pump equipment. For example: large vertical units.
The I/O Expansion Module has outputs to control
electric heat on a standard Water Source Heat Pump.
The I/O Expansion Module has outputs for multi-speed
fans on a standard Water Source Heat Pump.
The I/O Expansion Module has an independent LED
annunciator to identify operational fault conditions on dual-circuit equipment.
I/O Expansion Module Conguration Jumper Settings
Jumper Description Options
JP1 Number of
JP2
Water Reheat Shorted to enable reheat JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open, JP4 shorted for & JP4 Heat Type boilerless electric heat JP3 and JP4 shorted is an invalid setting JP5 and JP6 open for single-speed fan
JP5
& JP6 Selection JP5 shorted and JP6 open for two-speed fan JP 5 and JP6 shorted is an invalid setting
JP7
Speed Type Shorted for two-speed compressor
JP8 Future Spare
Compressors Shorted for dual compressor
Hot Gas/
Fan Speed three-speed fan
JP5 open, JP6 shorted for
Compressor Open for single-speed compressor
Open for single compressor
Open to disable reheat
I/O Expansion Module Conguration Jumper Terminals
I/O Expansion Module LED & Fault Outputs
Invalid Conguration Jumper Setting
Base Board Communication Fail
High Pressure #2 Fault Off Off Flash De-energized
Low Pressure #2 Fault Off Off On De-energized
Unoccupied Mode On On Off Energized
Occupied, Bypass, Standby, or Tenant Override Modes
Mode / Fault
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction Low Suction
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Normal Operation
Y
Temp #2, Flash Flash On De-energized
Off On Off De-energized
Status LED's
ellow Green Red
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Terminal “A”
Thermostat Alarm
Light Output
Note: Mode / Faults are listed in order of priority.
1
Boilerless electric heat only
2
Alarm/fault LED indications take precedence over service test mode LED
indication. The controller shall use service test mode if the service test mode jumper is installed, even if the LED’s indicate an alarm/fault.
Jumper Terminals
Features
Standard Heat Pumps / Single Circuit Units
Monitors entering water temperature for boilerless
electric heat control
Outputs for medium and high speed fan controls.
Second Circuit Units
High pressure switch Low pressure switch Low suction line temperature sensor Compressor output Reversing valve
12 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Control Features – MicroTech III Controller with LonWorks Module
MicroTech III / unit control board LED & fault outputs
Mode / Fault
Occupied, Bypass, Standby Override Unoccupied On On Off Energized Condensate Overow On Off Off De-engergized High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM Corrupted
Network “Ofine” Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’
, or Tenant Off On Off Energized
Air or Low
1
ellow Green Red Output-Terminal “A”
Y
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-engergized
On On Off De-energized
On On On De-energized
Off Off Off De-enegized
MicroTech III Unit Controller with LonWorks® Communication Module
Each McQuay water source heat pump can be equipped
with a LonWorks communication module that is LonMark
3.4 certied. The controller is microprocessor-based and is
designed to communicate over a LonWorks communica-
tions network. It can be factory or eld-installed.
The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communica­tion module to provide limited local control of the Water Source Heat Pump. The unit controller monitors water and air temperatures and passes information to the communica­tion module. The module communicates with the BAS, to
provide network control of the Water Source Heat Pump.
s
Thermostat Alarm Light
MicroTech III Unit Controller with LonWorks Communication Module orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint
based on a room sensor
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
The MicroTech III unit controller with communication module includes:
A unit-mounted return air sensor*
 
A unit-mounted discharge air sensor*
A leaving water temperature sensor
* Discharge air and return air sensors must be
eld-installed per IM 956.
communication module provides access to
The setpoints for operational control
Available wall sensors include: Room sensor with LED status and tenant override
button
Room
sensor with LED status, tenant override
button, and ±3°F setpoint adjustment
Room
sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
The MicroTech III unit controller with communica­tion module includes a unit-mounted return air, discharge air and leaving water temperature sensor. Wall mounted temperature sensors include setpoint adjustment and tenant override. The user has the capability of substituting the wall sensor with a duct-mounted return air sensor.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 13
Control Features – MicroTech III Controller with BACnet Module
MicroTech III Controller with BACnet Communication Module
McQuay water source heat pumps are available with
McQuay BACnet MS/TP communication module that is designed to communicate over a BACnet MS/TP
communications network to a building automation system
(BAS). It can be factory or eld-installed.
The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the water source heat pump. The unit controller monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS, to provide network control of the water source heat pump.
The module makes operational data and commands available on a communications network using BACnet objects and properties:
The network cable is a shielded twisted-pair cable
Network communications run up to 76.8 Kbps
DIP switches on the controller enable the MS/TP MAC
address to be set in the range 0-127
Four green status LEDs on the communication module
indicate communication activity on the MS/TP com­munication network and with the unit controller
MicroTech III Unit Controller with BACnet MS/TP
Communication Module orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint
based on a room sensor
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
The MicroTech III unit controller with communication module includes:
A unit-mounted return air sensor*
 
A unit-mounted discharge air sensor*
A leaving water temperature sensor
* Discharge air and return air sensors must be
eld-installed per IM 956.
communication module provides access to
The setpoints for operational control
Available wall sensors include:
Figure 13. MicroTech III BACnet Water Source Heat Pump Snap-in Communication Module
Room sensor with LED status and tenant override
button
Room
sensor with LED status, tenant override
button, and ±3°F setpoint adjustment
Room
sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
14 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications – Systems
Typical Cooling and Heating Refrigeration Cycles
Note: For standard heat pump operation only
Cooling Refrigeration Cycle
When the wall thermostat calls for COOLING, the reversing valve
directs the ow of the refrigerant, a
hot gas, from the compressor to the water-to-refrigerant heat exchanger. There, the heat is removed by the water, and the hot gas condenses to become a liquid. The liquid then
ows through a thermal expansion
valve to the air-to-refrigerant heat exchanger coil. The liquid then evaporates and becomes a gas, at the same time absorbing heat and cooling the air passing over the surfaces of
the coil. The refrigerant then ows as
a low pressure gas through the revers­ing valve and back to the suction side of the compressor to complete the cycle.
Heating Refrigeration Cycle
When the wall thermostat calls for HEATING, the reversing valve
directs the ow of the refrigerant, a
hot gas, from the compressor to the air-to-refrigerant heat exchanger coil. There, the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses and becomes a liquid. The liquid then
ows through a thermal expansion
valve to the water-to-refrigerant heat exchanger. The liquid then evaporates and becomes a gas, at the same time absorbing heat and cooling the water.
The refrigerant then ows as a low
pressure valve and back to the suction side of the compressor to complete the cycle.
gas through the reversing
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Return Air
Conditioned Air
(Cooling)
Return Air
Conditioned Air
(Heating)
Thermal
Expansion Valve
Reversing Valve
Thermal
Expansion Valve
Reversing Valve
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 15
Applications – Systems
Water source heat pump systems are one of the most ef-
cient, environmentally friendly systems available for heating and cooling buildings. High-efciency, self contained units
(sizes 7,000 btuh to 420,000 btuh) can be placed in virtually any location within a building. Each unit responds only to the heating or cooling load of the individual zone it serves. This permits an excellent comfort level for occupants, better control of energy use for building owners and lower seasonal operating costs. The Air-Conditioning Refrigeration Institute (ARI) and the International Standards Organization (ISO) publish standards so that water source heat pumps are rated
for specic applications. The ARI/ISO loop options shown in
this catalog are typical water source heat pump loop choices
available in today’s market. These systems offer benets rang-
ing from low cost installation to the highest energy efciency
available in the market today.
Boiler / Tower Applications: ARI 320 / ISO
13256-1
A “Boiler/Tower” application uses a simple two-pipe
water circulating system that adds heat, removes heat or transfers rejected heat to other units throughout the build­ing. The water temperature for heating is generally main­tained between 65ºF – 70ºF and is usually provided by a natural gas or electric boiler located in a mechanical room. The condensing water temperature, during cooling months,
is maintained between 85ºF and 95ºF and requires the use
of a cooling tower to dissipate waste heat. Cooling tow­ers can be located on the roof, or inside or adjacent to the building. This application can be the lowest cost of the loop options available. Note: ASHRAE 90.1 standards require that circulating pumps over 10 HP will require use of “variable frequency drive” equipment and pipe insulation to be used whenever water temperatures are below 60 degrees and above 105 degrees. See ASHRAE 90.1 Standards for details.
Open Loop Well Water Applications: ARI
325 / ISO 13256-1
“Open Loop” well water systems use ground water
to remove or add heat to the interior water loop. The
key benet of an open loop system is the constant water temperature, usually 50ºF to 60ºF, which provides efcient operation at a low rst cost. Most commercial designers
incorporate a heat exchanger to isolate the building loop from the well water. Using heat exchangers can reduce maintenance issues while still allowing the transfer of heat from unit to unit as with the “Boiler/Tower System”. A suc­cessful design provides an ample amount of groundwater (approximately 2 GPM per ton) and adequate provisions for discharging water back to the aquifer or surface. Open Loop applications are commonly used in coastal areas where soil characteristics allow reinjection wells to return the water back to the aquifer. Note that some states have re­quirements on the depths of return water reinjection wells, and such wells must be approved by the United States En­vironmental Protection Agency. Also, bad water quality can increase problems with heat exchanger scaling. Suspended solids can erode the heat exchanger. Strainers can be used to contain suspended solids.
Open Loop Well Application
Boiler/Tower Application
16 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications – Systems
Closed Loop Geothermal Applications ARI 330/ISO 13256-1
“Vertical Closed Loop” applications are installed by drilling vertical bore holes into the earth and inserting
a plastic polyethylene supply/return pipe into the holes.
The vertical wells are connected in parallel reverse return fashion to allow the water from the building to circulate evenly throughout the boreeld. The circulating uid dis­sipates heat to the ground in a similar manner as a “tower” and adds heat back to the loop like a boiler. If properly
designed, the loop eld can maintain the loop temperatures
necessary to condition the building without the use of a boiler or a tower. Loop temperatures usually range from 37ºF to 95ºF in Northern climates. Southern applications can see temperatures ranging from 40ºF to 100ºF. The number of bore holes and their depth should be determined
by using commercial software that is specically designed
for vertical geothermal applications. Typical bore depths of a vertical loop range from 150 to 400 feet and generally require about 250 feet of surface area per ton of cooling.
Vertical Loop Application
Horizontal Loop Application
“Surface Water” or “Lake” closed loop system is a
A geothermal loop that is directly installed in a lake or body of water that is near the building. In many cases, the body of water is constructed on the building site to meet drain­age or aesthetic requirements. Surface loops use bundled polyethylene coils that are connected in the same manner as a vertical or horizontal loop using a parallel reverse return design. The size and the depth of the lake is critical. Commercial design services should be used to certify that a
given body of water is sufcient to withstand the building
loads. Loop temperatures usually range from 35ºF to 90ºF and prove to be the best cooling performer and lowest cost loop option of the three geothermal loops. Some applica­tions may not be good candidates due to public access or
debris problems from ooding.
Surface Water Loop Application
A closed loop “Horizontal” geothermal application is similar to a vertical loop application with the exception that the loops are installed in trenches approximately 5 feet below the ground surface. The piping may be installed using a “four-pipe” or “six-pipe” design and could require 1,500 to 2,000 square feet of surface area per ton of cooling. Loop temperatures for a commercial application can range from 35ºF to 95ºF in Northern climates. Southern climates can see temperatures ranging from 40ºF to 100ºF. Horizontal loops are generally not applied in urban areas because land use and costs can be prohibitive. New advances in installation procedures have improved the
assembly time of horizontal loops while keeping the rst
cost lower than a vertical loop.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 17
Applications Considerations
Typical Vertical Installation
Unit Location
The VFC, VFW water source heat pump can be installed “free standing” in an equipment room; however, closet installations are more common for the small vertical type units. Generally, the unit is located in the corner of a closet with the non-ducted return air facing 90º to the door and the major access panels facing the door as shown in the illustration at right. Alternatively, the unit can have a ducted return air with the opening facing the door and the major access panels facing 90º to the door.
Locate a vertical unit to allow for easy removal of
the lter and access panels. Allow a minimum of 18" (46
cm) clearance on each side of the unit for service and maintenance access. Always be sure to leave at least one
side of the lter rack unobstructed so that the service personnel will be able to slide the lter out.
Install a eld supplied line voltage disconnect for
branch circuit protection.
To reduce noise emissions, install a eld-provided 1/2
inch thick, isolator pad below the entire base of the vertical unit. The pad should be equal to the overall foot-print size of the unit to provide sound dampening of the unit while in operation.
Typical VFC Installation – Closet, Non-Ducted Return
Typical Closet Installation - Non-ducted Application
Left-Hand Return Air
Arrangement
Return
Air
Return Air Thru
Louvered Door
Risers
A - Condensate B- Desuperheater Water Return (Optional) C
- Desuperheater Water Supply (Optional)
D
- Water Return
E
- Water Supply
F
- Low Voltage Control Wiring (Electric Entrance)
Right-Hand Return Air
Arrangement
Return
Air
Return Air Thru Louvered Door
1. Discharge air
2. Acoustic thermal duct lining - 10 feet
3. Line voltage disconnect
4. Low voltage wiring to unit control box
5. Flexible duct collar
6. Louvered closet door
7. Condensate drain
8. Flexible, braided, stainless steel return hose with ow controller/ball valve with port
9. Flexible, braided, stainless steel supply hose with Y-
strainer/ball valve with port
10. Access to unit control box
11. LED annunciator lights indicate unit operation status and faults
12. Full vibration isolation pad between unit and oor
13. Minimum distance between return air duct collar and wall for non-ducted return applications
Size 007-012 – 5 inches
Size 015-024 – 5 inches
Size 030-036 – 6 inches
Size 042-048 – 8 inches
Size 060-070 – 10 inches
18 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications Considerations
Ductwork and Attenuation
All ductwork should conform to industry standards of
good practice as described in ASHRAE Systems Guide.
The discharge duct system will normally consist of a
exible connector at the unit, a non-insulated transition
piece to the full duct size, a short run of duct, an elbow without vanes, and a trunk duct teeing into a branch circuit with discharge diffusers as illustrated below.
Return air ducts can be brought in through a wall grille
and then to the unit. The return duct system will normally
consist of a exible connector at the unit and a trunk duct to
the return air grille. With metal duct material, the return air duct should be internally lined with acoustic insulation for sound attenuation.
Return air ductwork to the unit requires the optional
return air duct collar/2" (51mm) lter rack kit.
Suggested Discharge Air Ducting
Trunk Duct
Square Elbow (Both Sides Internally Lined With Acoustic Insulation)
Branch Duct
Flexible
Duct Collar
Duct
Transition
(Internally Lined)
2 ft. x 2 ft. Diffuser
Discharge Collar
devices are commercially available and can be installed to eliminate the need for memory stop shut off valves. Include
Pressure / Temperature ports to allow the service technician to measure water ow and unit operation.
Control Access Panel
A - Condensate B- Desuperheater Water Return (Optional) C
- Desuperheater Water Supply (Optional)
D
- Water Return
E
- Water Supply
F
- Low Voltage Control Wiring (Electric Entrance)
G
- Line Voltage Unit Power (Electric Entrance)
McQuay has available optional hose kit combinations
to better facilitate system ow balancing. These exible
hoses reduce vibration between the unit and the rigid piping system.
Fire Rated Supply or Return Hoses
Heat Pump
Piping
The water source heat pump unit is typically connected
to the supply / return piping using a “reverse return” piping system which includes a ow control device so that ow
requirements are met for each zone. A short, high pressure
“exible hose” is used to connect the unit to the building’s
hard piping and acts as a sound attenuator for both the unit operating noise and hydronic pumping noise. One end of
the hose has a swivel tting to facilitate removal of the
unit for replacement or service. Include supply and return shutoff valves in the design to allow removal of a unit without the need to shut down the entire heat pump system. The return valve may be used for balancing and will typically have a “memory stop” so that it can be reopened
to the proper position for the ow required. Fixed ow
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 19
Condensate Drain
The factory provided condensate drain trap on the vertical unit is located inside the cabinet. Condensate removal piping must be pitched away from the unit not
less than 1/4" per foot. A vent is required after the trap so
that the condensate will drain away from the unit. The vent can also act as a clean out if the trap becomes clogged. To avoid having waste gases entering the building, the
condensate drain should not be directly piped to a drain/ waste/vent stack. See local codes for the correct application
of condensate piping to drains.
Applications – Unit Selection
Achieving optimal performance with water source heat pump systems requires both accurate system design and proper equipment selection. Use a building load program to determine the heating and cooling loads of each zone prior to making equipment selections. With this information, the McQuay SelectTools™ software selection program for Water Source Heat Pumps can be used to provide fast, ac­curate and complete selections of all McQuay water source heat pump products. SelectTools software is available by contacting your local McQuay Representative.
While we recommend that you use McQuay SelectTools software for all unit selections, manual selections can be accomplished using the same zone load information and the capacity tables available in this catalog.
Boiler / Tower Application Manual Selections:
The following example illustrates a typical selection for
a zone in a boiler/tower system for a commercial building.
A building load program determines that this zone needs
38,255 BTUH of total cooling, 31,832 BTUH of sensible
cooling and 36,988 BTUH of total heating. The water tem-
peratures for the boiler/tower system are 90ºF for cooling and 70ºF for heating. The return air temperature is 80ºF dry
bulb with 67ºF wet bulb for cooling and 70ºF for heating.
Zone requirements:
Total Cooling Load = 38,255 BTUH Sensible Cooling Load = 31,832 BTUH Total Heating Load = 36,988 BTUH
Air Flow Required = 1510 CFM
Return Air Cooling = 80ºFDB/ 67ºFWB
Return Air - Heating = 70ºFDB
Since a McQuay Model VFC 036 produces approxi-
mately 36,000 BTUH of cooling, it is not sufcient for
this zone and a model VFC 042 should be considered.
Model VFC is chosen because it is specically designed for a boiler/tower application. Typical water ow rates for boiler/tower applications are 2.0 to 2.5 GPM per ton and in
this example no antifreeze is used.
Selection:
Model .............................VFC 042 (Boiler / Tower model)
Total Cooling Capacity @ 90 EWT = 40,816 BTUH
Sensible cooling capacity @ 90 EWT = 32,704 BTUH Total Heating Capacity @ 70 EWT = 52,019 BTUH CFM = 1510 @ .5 ESP (Wet Coil)
Water Flow required to meet capacity = 8 GPM
Water Pressure drop = 6.9 (FT. H2O)
Final Selection ....................................................VFC 042
Geothermal Applications:
The following example illustrates the same zone in a
geothermal application.
The load requirements for the zone are the same as the
above example – 38,255 BTUH of total cooling and 31,832 BTUH of sensible cooling and 36,988 BTUH of heating.
Geothermal loop software programs are available to help
determine the size of the loop eld based on:
Desired entering water temperatures for the system.
Specic acreage available for the loop which produces
specic min./max loop temps for the unit selection.
Entering water temperatures for geothermal systems can
be as high as 90º to 100ºF and as low as 30ºF based on the
geographical location of the building. Water ow rates are
typically 2.5 to 3 GPM per ton and the use of antifreeze is required in most northern applications.
Zone requirements:
Total Cooling Load = 38,255 BTUH Sensible Cooling Load = 31,832 BTUH Total Heating Load = 36,988 BTUH
Air Flow Required = 1510 CFM
Return Air Cooling = 80 DB / 67 WB
Return Air - Heating = 70 DB
A McQuay Model VFW is chosen for this geothermal application. Model VFW offers insulated water piping for condensation considerations and a different freezestat set­ting to allow entering water temperatures lower than 40ºF (with antifreeze). Output capacities should be recalculated using the antifreeze reduction tables that are shown on page
49. The Model VFW 042 is rst considered but may not
meet the heating load because of the reduced entering water temperatures (35ºF) and an antifreeze solution of 21 % propylene (see page 49).
Selection:
Model ..................................VFW 042 (Geothermal model)
Total cooling capacity @ 100 EWT = 40,434 BTUH x
.980 = 39,625
Sensible cooling capacity @ 100 EWT = 32,164 BTUH x
.980 = 31,520 Total heating capacity @ 35 EWT = 38,335 BTUH x
.975 = 37,377 CFM = 1510 @ .6 ESP (Dry Coil)
Water Flow required to meet capacity = 10.8 GPM
Water Pressure drop = 12.7 x 1.5 = 14.61 (FT. H2O)
Final Selection ....................................................VFW 042
Note:
In applications where the zone may be a corner ofce or have excessive glass area, the heating load could be greater than the heating output capacity of the VFW 042 model (say 41,985 BTUH). The choices are to upsize the unit to the next model available (048), or add an electric duct heater to supplement the output of the 042 unit.
20 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Ennity Vertical ISO Performance Data – Water Loop
Water Loop Performance Data – Rated in Accordance with ISO Standard 13256-1 Boiler/Tower
Standard Unit ECM at High Static
*007
009
012
042
* Not available at time of publication. Please consult your McQuay Representative for specific availability n/a = ECM not available in unit sizes 007, 009, 012.
Unit Size
015
019
024
030
036
048
060
070
CFM
*
300
400
500
600
800
1000
1300
1400
1600
2000
2160
Airow Waterow
Cooling Heating Cooling Heating
Voltage
L/S GPM L/S Btuh Watts EER COP Btuh Watts COP Btuh Watts EER COP Btuh Watts COP
*
142
189
236
283
378
472
614
661
755
944
1019
*
2.3
3.0
3.6
4.68
5.81
7.25
9.50
11.00
12.00
15.50
19.00
*
0.15
0.19
0.23
0.30
0.37
0.46
0.60
0.69
0.76
0.98
1.20
115-1-60
208/230-1-60
265-1-60 115-1-60
208/230-1-60
265-1-60 115-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60 208/230-3-60 208/230-1-60 208/230-3-60
460-3-60 208/230-1-60 208/230-3-60
460-3-60
575-3-60 208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60 208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60 208/230-3-60
460-3-60
575-3-60
*
9060
12000
14700
19200
23800
30000
39500
43900
48100
63200
75400
*
2650
3510
4300
5620
6980
8800
11500
12800
14100
18500
22100
14.0
14.4
16.0
15.2
15.1
17.0
14.8
15.0
14.7
15.1
13.5
n/a
n/a
n/a
16.6
16.3
17.0
15.0
16.2
16.0
15.7
14.0
n/a
n/a
n/a
n/a
n/a
n/a
*
*
*
4.9
18000
4.8
26300
5.0
33400
4.4
44500
4.7
52300
4.7
56400
4.6
67700
4.1
86300
*
*
4.1
10600
4.2
14000
4.7
16100
4.5
18300
4.4
26700
5.0
33400
4.3
45000
4.4
52500
4.3
56800
4.4
68300
4.0
87300
*
4.7
4.8
5.1
4.4
4.9
5.2
4.6
4.8
4.8
4.7
4.4
*
*
3110
4110
4720
5370
7820
9780
13200
15400
16600
20000
25500
n/a
n/a
n/a
*
19500
24100
29900
39900
44200
48700
63600
76200
n/a
n/a
n/a
*
5710
7050
8750
11700
12900
14200
18600
22300
n/a
n/a
n/a
*
5270
7700
9780
13000
15300
16500
19800
25300
n/a
n/a
n/a
*
4.6
5.2
5.4
4.6
5.1
5.1
5.0
4.5
Notes: EER = Energy Efciency Ratio COP = Coefcient of Performance L/s = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 21
Ennity Vertical ISO Performance Data – Ground Loop
Ground Loop Performance Data Rated in Accordance with ISO Standard 13256-1 Ground Coupled
Standard Unit ECM at High Static
*007
009
012
* Not available at time of publication. Please consult your McQuay Representative for specific availability n/a = ECM not available in unit sizes 007, 009, 012.
Unit Size
015
019
024
030
036
042
048
060
070
CFM
*
300
400
500
600
800
1000
1300
1400
1600
2000
2160
Airow Waterow
Cooling Heating Cooling Heating
Voltage
L/S GPM L/S Btuh Watts EER COP Btuh Watts COP Btuh Watts EER COP Btuh Watts COP
*
142
189
236
283
378
472
614
661
755
944
1019
*
2.3
3.0
3.6
4.68
5.81
7.25
9.50
11.00
12.00
15.50
19.00
*
0.15
0.19
0.23
0.30
0.37
0.46
0.60
0.69
0.76
0.98
1.20
115-1-60
208/230-1-60
265-1-60
115-1-60
208/230-1-60
265-1-60
115-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-3-60 208/230-1-60 208/230-3-60
460-3-60
208/230-1-60 208/230-3-60
460-3-60
575-3-60
208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60
208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
*
9720
12700
15700
19400
24800
30700
40300
45400
51600
65100
76500
*
2850
3720
4600
5690
7260
9000
11800
13300
15100
19100
22400
*
4.9
5.0
5.7
5.1
5.2
5.6
5.1
5.0
4.6
4.8
4.0
*
*
2050
7020
2720
9300
2920
10000
4010
13700
5210
17800
6530
22300
8900
30300
10300
35100
11800
40300
13700
47000
17200
58900
*
16.7
16.9
19.6
17.3
17.7
19.1
17.3
17.0
15.8
16.3
13.7
*
3.3
3.5
3.5
3.5
3.6
3.9
3.4
3.6
3.4
3.5
3.1
n/a
n/a
n/a
*
19700
25100
30600
40500
46100
50200
66000
78400
n/a
n/a
n/a
*
5770
7350
8960
11800
13500
14700
19300
22900
n/a
n/a
19.0
19.2
19.3
16.6
18.9
18.2
18.0
16.2
n/a
n/a
n/a
n/a
n/a
*
*
5.6
5.6
5.7
4.9
5.5
5.3
5.3
4.7
*
13400
17500
22300
30000
34400
37600
46000
56800
n/a
n/a
n/a
n/a
n/a
*
3920
5120
6530
8790
10100
11000
13500
16600
n/a
n/a
n/a
*
3.7
3.8
4.0
3.3
3.8
3.8
3.8
3.6
Notes: EER = Energy Efciency Ratio COP = Coefcient of Performance L/S = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 77°F (25°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 32°F (0°C) entering water temperature.
22 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Ennity Vertical ISO Performance Data – Ground Water
Ground Water Performance Data Rated in Accordance with ISO Standard 13256-1.
Standard Unit ECM at High Static
*007
009
012
* Not available at time of publication. Please consult your McQuay Representative for specific availability n/a = ECM not available in unit sizes 007, 009, 012.
Unit Size
015
019
024
030
036
042
048
060
070
CFM
*
300
400
500
600
800
1000
1300
1400
1600
2000
2160
Airow Waterow
Cooling Heating Cooling Heating
Voltage
L/S GPM L/S Btuh Watts EER COP Btuh Watts COP Btuh Watts EER COP Btuh Watts COP
115-1-60
*
142
189
236
283
378
472
614
661
755
944
1019
*
2.3
3.0
3.6
4.68
5.81
7.25
9.50
11.00
12.00
15.50
19.00
*
0.15
0.19
0.23
0.30
0.37
0.46
0.60
0.69
0.76
0.98
1.20
208/230-1-60
265-1-60 115-1-60
208/230-1-60
265-1-60 115-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60 208/230-3-60 208/230-1-60 208/230-3-60
460-3-60 208/230-1-60 208/230-3-60
460-3-60
575-3-60 208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60 208/230-1-60 208/230-3-60
265-1-60
460-3-60
575-3-60 208/230-3-60
460-3-60
575-3-60
*
10900
14100
17100
21400
26600
33000
42900
48800
56100
69000
79100
*
3200
4130
5010
6270
7790
9600
12500
14300
16400
20200
23100
*
8820
*
2580
3450
3830
4950
6360
8320
11000
12500
14300
17100
21300
*
4.0
4.2
4.3
4.1
4.2
4.6
4.1
4.2
4.0
4.1
3.6
*
*
7.0
23.8
7.0
8.2
6.9
6.8
7.4
6.5
6.5
5.9
6.0
4.9
11800
13100
16900
21700
28400
37700
42900
48900
58400
72700
23.8
28.1
23.5
23.3
25.1
22.3
22.1
20.3
20.5
16.6
n/a
n/a
n/a
*
21600
26900
32900
43000
49100
54300
69900
80600
n/a
n/a
n/a
*
6320
7880
9630
12600
14400
15900
20500
23600
n/a
n/a
n/a
n/a
*
26.1
25.8
25.5
21.3
24.8
23.8
22.9
19.6
n/a
n/a
7.7
7.6
7.5
6.2
7.3
7.0
6.7
5.7
n/a
n/a
n/a
*
*
16600
21300
28400
37400
43000
47100
57400
70500
n/a
n/a
n/a
*
4860
6240
8300
10900
12600
13800
16800
20600
n/a
n/a
n/a
*
4.4
4.5
4.8
4.0
4.5
4.5
4.4
4.1
Notes: EER = Energy Efciency Ratio COP = Coefcient of Performance L/S = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 59°F (15°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 50°F (10°C) entering water temperature.
Capacity Tables Notes: EWT = Entering Water Temperature (ºF) L/sec. = Airow in Liters per second WPD = Water Pressure Drop (Ft. Hd) EA = Entering Air Temperature (ºF) LWT = Leaving Water Temperature (ºF) TOT = Total Heat (Btu) SEN = Sensible Heat (Btu) kW = Kilowatts COP = Coefcient of Performance THA = Total Heat of Absorption (Btu) THR = Total Heat of Rejection (Btu) GPM = Gallons Per Minute
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 23
Capacity Data – Vertical Unit Size 009 (300 CFM)
EWT
20
30
40
50
60
70
GPM
1.6
2
.3
3.0
1.6
2.3
3.0
1.6
2.3
3.0
1.6
2.3
3.0
1.6
2.3
3.0
1.6
2.3
3.0
WPD
4
.1
7.4
11.4
4.1
7.4
11.4
4.1
7.4
11.4
4.1
7.4
11.4
4.1
7.4
11.4
4.1
7.4
11.4
EA
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71 70/59 75/63 80/67 85/71
LWT
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
44.0
45.0
46.0
47.0
39.8
40.4
41.1
41.9
37.5
38.0
38.5
39.1
53.9
54.9
55.9
57.0
49.7
50.4
51.1
51.8
47.5
48.0
48.5
49.1
63.7
64.7
65.7
66.8
59.6
60.3
61.0
61.7
57.4
57.9
58.4
59.0
73.4
74.3
75.4
76.5
69.4
70.1
70.8
71.5
67.2
67.7
68.3
68.9
83.0
83.9
84.9
86.0
79.1
79.8
80.5
81.3
77.0
77.5
78.1
78.7
Cooling Heating
TOT
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
10569 11515 12461 13408 10700 11646 12593 13539 10831 11777 12724 13670 10061 10963 11865 12767 10192 11094 11996 12898 10323 11225 12128 13030
9548 10405 11263 12121
9679 10537 11394 12252
9810 10668 11526 12383
9028
9842 10655 11469
9160
9973 10787 11600
9291 10104 10918 11731
8504
9273 10042 10811
8635
9404 10173 10942
8766
9535 10304 11073
SEN
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
7704 7917 8130 8343 7757 7970 8183 8396 7810 8023 8236 8449 7472 7691 7910 8128 7526 7744 7963 8181 7579 7797 8016 8235 7237 7461 7685 7909 7290 7514 7738 7962 7343 7567 7791 8016 6997 7227 7456 7686 7050 7280 7510 7739 7103 7333 7563 7792 6753 6988 7223 7459 6806 7041 7276 7512 6859 7094 7330 7565
kW
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
0.208
0.166
0.125
0.084
0.207
0.166
0.125
0.084
0.207
0.166
0.124
0.083
0.313
0.280
0.248
0.215
0.312
0.280
0.247
0.215
0.312
0.279
0.247
0.214
0.406
0.383
0.359
0.335
0.406
0.382
0.358
0.334
0.406
0.382
0.358
0.334
0.489
0.473
0.458
0.443
0.488
0.473
0.458
0.443
0.488
0.473
0.457
0.442
0.559
0.553
0.546
0.540
0.559
0.552
0.546
0.539
0.558
0.552
0.545
0.539
THR
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
11240 12065 12889 13714 11308 12133 12957 13782 11376 12200 13025 13850 11120 11937 12755 13573 11187 12005 12823 13640 11255 12073 12891 13708 10938 11748 12559 13370 11005 11816 12627 13438 11073 11884 12695 13506 10694 11498 12302 13106 10762 11566 12370 13174 10830 11634 12438 13242 10390 11187 11984 12781 10458 11255 12052 12849 10525 11323 12120 12917
EA
50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80 50 60 70 80
LWT
14.5
14.8
15.1
15.4
16.2
16.4
16.6
16.8
17.1
17.2
17.4
17.5
23.4
23.7
24.1
24.4
25.4
25.6
25.9
26.1
26.4
26.6
26.8
27.0
32.3
32.7
33.0
33.4
34.5
34.8
35.0
35.3
35.8
36.0
36.2
36.4
41.1
41.5
41.9
42.3
43.7
43.9
44.2
44.5
45.1
45.3
45.5
45.8
49.8
50.2
50.7
51.2
52.7
53.0
53.4
53.7
54.3
54.6
54.8
55.1
58.4
58.9
59.4
59.9
61.7
62.0
62.4
62.8
63.5
63.8
64.1
64.4
TOT
6014 5916 5818 5719 6197 6099 6001 5903 6380 6282 6184 6086 6899 6801 6703 6604 7082 6984 6886 6788 7265 7167 7069 6971 7837 7739 7641 7543 8020 7922 7824 7726 8203 8105 8007 7909 8828 8730 8632 8534 9011 8913 8815 8717 9194 9096 8998 8900 9872 9774 9676 9578
10055
9957 9859
9761 10239 10140 10042
9944 10969 10871 10773 10675 11152 11054 10956 10858 11336 11238 11139 11041
kW
0.453
0.524
0.594
0.665
0.473
0.544
0.614
0.685
0.493
0.564
0.634
0.705
0.458
0.536
0.614
0.691
0.478
0.556
0.633
0.711
0.498
0.576
0.653
0.731
0.461
0.545
0.630
0.715
0.481
0.565
0.650
0.735
0.500
0.585
0.670
0.755
0.460
0.552
0.644
0.736
0.480
0.572
0.664
0.756
0.500
0.592
0.684
0.776
0.458
0.557
0.655
0.754
0.478
0.576
0.675
0.774
0.497
0.596
0.695
0.794
0.452
0.558
0.664
0.770
0.472
0.578
0.684
0.790
0.492
0.598
0.704
0.810
THA
4250 4028 3806 3583 4434 4212 3989 3767 4618 4395 4173 3951 5153 4885 4617 4349 5336 5068 4800 4532 5520 5252 4984 4716 6117 5803 5490 5176 6301 5987 5674 5360 6484 6171 5857
5544
7143 6784 6425 6066 7327 6968 6609 6249 7511 7151 6792 6433 8231 7827 7422 7017 8415 8010 7606 7201 8599 8194 7789 7384 9382 8931 8481 8030 9565 9115 8665 8214 9749 9299 8848 8398
24 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Loading...
+ 56 hidden pages