The information in this manual supersedes and replaces previous catalogues with regards to McQuay Water Source Heat Pump products.
Illustrations cover the general appearance of McQuay International products at the time of publication and McQuay International reserves the
right to make changes in design and construction at anytime without notice.
®
™
The following are trademarks or registered trademarks of their respective companies: LonTalk from Echelon Corporation, BACnet from ASHRAE, Protocol
Selectability, and MicroTech III from McQuay International.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 3
Introduction
Ennity
complete line of water source heat pumps for high efcien-
cy, individually-zoned comfort control in ofces, schools,
assisted living facilities, manufacturing facilities and other
commercial buildings. Our reputation for outstanding reliability and quiet operation has been reinforced in thousands
of successful installations.
our past and the best of what’s new. Using feedback from
building owners, consulting engineers, contractors and ser-
vice engineers, we designed Ennity products to give you
maximum exibility to design, install, operate and maintain
the ideal water source heat pump system for your building
project. And we incorporated non-ozone depleting R-410A
refrigerant, which–along with high Energy Efciency Ratios (EER’s)–helps preserve our environment and precious
energy resources.
™
Water Source Heat Pumps
More than 30 years ago, McQuay designed the rst
Ennity water source heat pumps incorporate the best of
With Ennity Water Source Heat Pumps,
you benet from:
High efciency that minimizes environmental impact
and lowers operating costs
Units exceed ASHRAE Standard 90.1 minimum
requirements
High efciency standard range or geothermal
application exibility
Easy, low-cost design and installation
Two congurations for each unit size (left or right
return) allow you to specify units to t space require
ments and to design the system using minimum ductwork and piping.
Four cabinet sizes, each with McQuay’s small footprint
design, make it easy to meet the space requirements of
your new construction or replacement application.
Flush FPT water ttings allow easy, one-wrench tight-
ening of hose kits and help reduce delays caused by
shipping damage.
Open Choices™ controls feature allows easy, low cost
integration with a Building control Automation System
of your choice.
Factory-installed lter rack saves time and expense to
eld-install a lter rack.
Factory-installed electric heat, desuperheater and ECM
motor options help you meet more specic application
requirements with minimum design or installation time
and expense.
Easy, low-cost maintenance
Easy access to the unit compressor (2-sides), fan sec-
tion (1-side), motor (1-side) and unit controls (front
access).
A removable orice ring allows the blower and motor
to be removed without removing the blower housing or
disconnecting the unit from the ductwork.
Quiet operation
Large fan wheel allows the fan motor to operate at
lower speed for quieter operation.
Two quiet compressor selections (depending on volt-
age and size variations) including rotary (sizes 007 to
015), and scroll compressors (sizes 019 to 070).
Superior Indoor Air Quality (IAQ)
Double-sloped, polymer drain pan promotes positive
condensate drainage.
Optional closed-cell foam insulation (no glass bers in
air stream).
Optional Hot Gas Reheat Coil provides superior
humidity control.
R-410A refrigerant with zero ozone depletion potential
or phase-out date
R-410A is classied as A1/A1 – lower toxicity, no
ame propagation – per ASHRAE Standard 31.
Exceeds ASHRAE 90.1 Minimum Efciencies
4 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features & Options
I/O Expansion
Module
LED Annunciator
MicroTech III Unit
Controller
L
Communication
Module
BACnet
Communication
Module
onWorks
1. Electric Heat (Optional) – Integral electric heat coil provides
supplemental or emergency heat when conditions require.
2. Electronically Commutated Motor (ECM-Optional) - ECM motor
provides quiet, efcient operation while maintaining constant
over its static operating range. Factory programmed for
CFM
3-speeds.
3
. MicroTech® III Unit Controller – Designed for exibility, the
main
control board is used in standalone applications. An
optional I/O expansion module can be used to control electric
heat
and multiple fan speeds. A separate L
net®
communication module can be easily snapped onto the
onWorks® or BAC-
board to accommodate the building automation system of your
choice.
4. LED Annunciator
– External
LED status lights display fault
conditions to provide easy troubleshooting and diagnosis.
5. Compact Cabinet – The
standard unit is constructed of
unpainted G-60 galvanized steel, with the smallest possible
footprint. Optional painted cabinet is ideal for aesthetic requirements
6.Desuperheater (Optional) –
of residential applications.
Saves energy by producing domestic hot water using a small heat exchanger and water pump located
in the compressor compartment. Superheated refrigerant
gas from the compressor, which would otherwise be wasted,
is used to heat water. This reduces the amount of additional
energy required to heat water and it may eliminate the require
for separate water heating equipment.
ment
Desuperheater
Heat Exchanger and
Water Pump Piping Circuit
Optional – Hot Gas Reheat
Piping Circuit
7. Filter & Filter Rack – Units come standard with a 1" (25.4 mm)
thick throwaway lter mounted in a 4-sided combination lter
rack
and return air duct collar. This eliminates the added labor
and cost to eld-mount brackets. Filters can be easily removed
from
any side. A 2" lter rack is available as a factory-installed
selectable option to accept higher efciency lters
8.
Removable Access Panels – Two front panels provide easy
access to the blower motor and unit controls. Two rear panels
provide easy access to the fan housing and compressor section.
9. Piping Connections
– Water connections are FPT water t-
tings, ush with the outside of the cabinet for easy one-wrench
connection
to units. A large condensate connection provides
proper condensate removal.
10. Coaxial Heat Exchanger
– Designed
for maximum heat transfer
at normal and low water ow rates with minimum pressure
drop. The inside tube is deeply uted to enhance heat transfer
and
minimize fouling. A cupro-nickel heat exchanger is avail-
able
as a selectable option.
11. Hot Gas Reheat Coil (Optional) – Provides superior humidity
control by using expelled heat from the refrigeration cycle
and redirecting it through an isolated circuit in the evaporator
section. For every 10°F of temperature rise across the hot gas
reheat coil there is approximately a 20% drop in the discharge
air relative humidity (%Rh). A wall-mounted humidistat is
-
used in conjunction with the unit to measure and adjust the
humidity in the space.
Catalog 1103-2McQuay Ennity Water Source Heat Pumps5
Vertical Floor-mounted Features and Options
Flexible Congurations
Top View
Right Hand
Return
Air
Control Box
Cabinet
The Ennity Vertical Water Source Heat Pump is
factory assembled and tested for reliability. Five unique
cabinet sizes make up our 1/2 through 6 ton (1.8 through
21.2 kW) vertical heat pump product line. The consistent
shape makes layout simple. Water, condensate and
duct connections are all in similar locations to simplify
installation.
The fan section is separated from the compressor
section with an insulated divider panel for maximum sound
attenuation. A large removable panel provides easy service
access to the blower and motor.
The cabinet is constructed of unpainted, G-60
galvanized steel. The interiors of the top and side panels
and the bottom of the unit are covered with 1/2" thick
(13 mm), 1
standard. An optional closed cell insulation is available for
applications with more stringent IAQ requirements.
1
/2 lb. (681 g) density coated glass ber as
Cabinet Congurations
For maximum exibility, each vertical unit is available
in either a left-hand or right-hand return air arrangement to
provide the optimum piping location and service access.
The mirror image design of the units lets you congure
the system using minimum ductwork and piping. This helps
reduce design, material and installation costs.
Left Hand
Water
Connections
Filter Rack
The lter is supported by factory-mounted brackets that
allow for face removal. Units come standard with a 1" (25.4
mm) thick throwaway lter mounted in a combination lter
rack and return air duct collar, thus eliminating eld mounted
brackets. The lter can be removed from the right or left
side.
Optional factory-mounted or eld-installed 2" lter rack
kit for higher ltration requirements.
Optional 2" Filter Rack
Remove lter from
the left or right
side without a tool
Blower Housing
The blower housing protrudes through the cabinet top
allowing adequate material for connection to a exible
duct.
Fan Housing Protrudes Through the Cabinet Top for
Connection of Flexible Duct
6 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features and Options
Electrical
The electrical components are located in the compressor
section of the unit. Separate holes are provided on the
cabinet to facilitate main power and low voltage control
wiring. All wiring connections are made internal to the
cabinet to reduce the risk of accidental contact. Each
unit is rated to accept time-delay fuses for branch circuit
overcurrent protection. Single phase units are also rated for
use with HACR circuit breakers.
The control box houses the major operating
electrical controls including the MicroTech III unit
controller, transformer, compressor relay and fan relay.
Each component can be accessed easily for service or
replacement.
Easy Access to the Vertical Unit Control Panel
Water Connections
The water and condensate connections are FPT ttings,
securely mounted ush to the corner post to allow for
connection to a exible hose without the use of a back-up
wrench. This helps reduce the time required to connect the
unit and helps prevent delays due to shipping damage. All
vertical units are internally trapped with clear vinyl tubing,
to allow inspection of condensate drain.
Flush FPT Water Fittings
Access panels lift
up and out easily
Vertical Unit Double-Sloped Drain Pan
Double Sloped Channels
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 7
Vertical Floor-mounted Features and Options
R-410A Refrigerant
R-410A refrigerant has zero ozone depletion potential,
no scheduled phase-out and is classied in ASHRAE
Standard 31 as A1/A1 – lower toxicity, no ame
propagation.
Compressors
Ennity water source heat pumps are designed around
the most advanced compressors in the industry. A wide
variety of compressor types are used to offer the best
system design for the dedicated refrigerants and tonnage.
This allows Ennity water source heat pumps to deliver
rated capacity with low noise levels.
Rotary compressor with R-410A is used in vertical units
size 007 to 015. R-410A, non-CFC refrigerant is used in
all unit sizes 007 to 070. Unit sizes 019 to 070 use a scroll
compressor.
Scroll Compressor
Rotary Compressor
Thermal Expansion Valve
All Ennity water source heat pump units include a
thermal expansion valve for refrigerant metering. The
Thermal Expansion Valve (TXV) allows the unit to operate
at optimum efciency with uid temperatures ranging from
30ºF to 110ºF, and entering air temperatures ranging from
40ºF to 90ºF. The TXV precisely meters the exact amount
of refrigerant ow through the system to meet the load and
deliver rated heating and cooling capacity.
Thermal Expansion Valve (TXV)
Reversing Valve
A 4-way reversing valve is included with all Ennity water source heat pumps. The valve is energized in
the heating mode and will “fail-safe” to the cooling mode
which is the predominant mode of operation for
commercial applications.
4-Way Reversing Valve
Fluid-to-Refrigerant Coil
The copper or cupronickel (optional) tube-in-tube
coaxial heat exchanger used in Ennity water source heat
pumps are designed for maximum heat transfer at normal
and low water ow rates with minimum pressure drop. The
inside tube is deeply uted to enhance heat transfer and
minimize fouling. All coaxial coils are tested to 400 psig on
the water side and 500 psig on the refrigerant side.
Geothermal range (VFW) units include coil and piping insulation to protect against condensation in low-temperature
geothermal applications.
Coaxial Heat Exchanger
8 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Vertical Floor-mounted Features and Options
Noise Reduction
Ennity Water Source Heat Pumps include multiple
features and options to reduce unwanted noise generation
including scroll and rotary compression, viscoelastic acoustical mass plate, vibration isolated fan mounts, optional
compressor sound blankets and soft starting ECM motors.
While good design and installation practices are always
required to prevent objectionable noise, McQuay, as a
leader in engineered products can also provide many other
customized solutions to meet your applications
requirements.
Schrader Connections
Two Schrader valves are located inside the end access
panel – one on the low side and one on the high side of the
refrigeration circuit – for charging and servicing. All valves
are 7/16" SAE ttings.
Schrader Valve
to lock out compressor operation at extreme conditions.
For additional protection, unit sizes 015 and larger have a
7 psi (48 kPa) low-pressure switch to protect the compressor from low refrigerant charge. The low setting prevents
nuisance trips while providing additional protection.
Blower Section
The blower section includes the blower housing, wheel,
motor and drain pan. It is separated from the compressor
section by an insulated divider panel for maximum sound
attenuation. The large size of the blower wheel allows it
to rotate more slowly, reducing motor work to improve
efciency and provide for quiet operation. A large panel
provides service access to the blower and motor. All
blower/motor assemblies have a removable orice ring on
the housing to accommodate motor and blower removal
without disconnecting the unit from the ductwork.
Blower Motors
The standard blower motor is a multi-speed, Permanent
Split Capacitor (PSC) type with thermal overload protection. It is permanently lubricated. The motor is factory
wired to maximize performance and efciency. Unit sizes
019 and larger have a terminal strip on the motor for simple
motor speed change without going back to the control
box. The motor is isolated from the fan housing using
rubber isolators to minimize vibration transmission. All
blower/motor assemblies have a removable orice ring on
the housing to accommodate motor and blower removal
without disconnecting the unit from the ductwork. Optional
Electronically Commutated Motor (ECM) provides soft
start, maintains consistent CFM over its static operating
range and fan speed can be adjusted automatically based on
mode of operation.
High Efciency Blower Motor Options
Air-to-Refrigerant Coil
The air-to-refrigerant heat exchanger is a large face
area coil with copper tubes and aluminum ns. The ns are
lanced and mechanically bonded to the tubes using nned
edges on the inside which expand during assembly to
enhance heat transfer capabilities. The maximum working
pressure of the heat exchanger is 500 psig (3447 kPa). The
coil is designed for optimal performance in both heating
and cooling while maintaining the benet of a compact
size. Coils can be provided with an optional E-coating.
Electronically Commutated
Motor (ECM)
Refrigeration System
Units have a coaxial heat exchanger with a copper inner
tube and a steel outer tube. The air coil is a large face area
coil with copper tubes and aluminum ns. Safety controls
include a high-pressure switch and low-temperature sensor
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 9
Permanent Split Capacitor
Motor (PSC)
Control Options – Control Choices and Added Functionality
The control box is accessible through the left or right end
corner panel. It houses the major operating electrical controls
including the MicroTech® III unit controller, transformer,
compressor relay and fan relay. Each component is easily
accessed for service or replacement.
Four unique control choices are offered with the MicroTech III unit controller:
■ Standalone operation using a MicroTech III unit controller
■ MicroTech III unit controller with I/O Expansion module
■ MicroTech III unit controller with a Lonworks® commu-
nication module
■ MicroTech III unit controller with a BACnet® communication module
Each option features direct quick-connect wiring to all
unit-controlled components for “clean” wiring inside the
control box. Each control circuit board receives power from
a 50 VA transformer.
Control Description Application Protocol
Uni t-mounte d
or wall-mounted
thermostat
MicroTech III
(Standalone)
Unit Controller
The MicroTech III unit controller is
a standalone microprocessor-based
control board conveniently located
in the unit control box for accessibil
. The board is designed to provide
ity
standalone control of a Water Source
Heat Pump using a wall thermostat
or a wall mounted temperature sen
or. Each unit controller is factory
s
programmed, wired, and tested. For
added functionality an optional I/O
expansion
MicroTech III controller for complete
control and operation of your McQuay
water source heat pump.
module interconnects to the
Each unit controller is factory programmed, wired,
and tested for complete control of single zone, standalone
operation of your McQuay Water Source Heat
Pump.
-
-
I/O Expansion
Module
LonWorks
Communication
Module
BACnet
Communication
Module
The I/O Expansion Module is an extens
ion of the Microtech III unit controller
and provides additional functionality to
the Microtech III control system. The
interconnect cable from the I/O expan-
module to the MicroTech III unit
sion
controller provides two-stage operation
of the water source heat pump.
The MicroTech III unit controller can
accept a plug-in LonWorks communication module to provide network
communications and added functional
ity
to easily integrate with an existing
BAS. The communication module can
be factory- or field-installed and is
tested with all logic required to monitor
and control the unit.
The MicroTech III unit controller
can accept a plug-in BACnet communication module to provide network
communications and added functionality to easily integrate with an existing
BAS. The communication module can
be factory- or field-installed and is
tested with all logic required to monitor
and control the unit.
Allows
for:
• Monitoring of entering water temperature for
boilerless electric heat control.
• Outputs for optional electric heat
• Output for multi-speed fans on a standard water
source heat pump.
• Independent LED annunciator to easily identify
operation fault conditions for two-stage units.
LonTalk application protocol is designed for units
that are integrated into a LonWorks communication
network for centralized scheduling and management
of multiple heat pumps.
-
Designed to be linked with a centralized building
automation system (BAS) through a BACnet com
munications
management of multiple heat pumps.
network for centralized scheduling and
Uni t-mounte d
or wall-mounted
thermostat
onMark 3.4
L
BaCnet
-
10 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Control Features – MicroTech® III Control System
The MicroTech III Unit Controller is a microprocessorbased control board conveniently located in the unit control
box for easy access through a removable access panel. The
standalone unit controller is a hard wired interface and pro-
vides all the necessary eld connections. The board can be
wired for 24-volt AC output to the wall thermostat by using
terminals R & C. An LED annunciator is located on the front
corner of the unit chassis to quickly check the operating status
of the unit.
MicroTech III Operating Features
Assumes cycle fan operation-not continuous fan operation:
■ Start-up – The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
■ Cooling mode – On a call for cooling, the compressor
and fan will start 0 to 30 seconds later. When the load is
satised, the compressor and fan shut off.
■ Heating Mode – On a call for heating, the reversing valve
is energized after 60 seconds and the compressor and fan
start. When the load is satised, the compressor and fan
shut off. The reversing valve is de-energized 60 seconds
later.
■ Short Cycle Protection & Random Start – Each time
the compressor stops, a new random compressor start-
delay time between 180 and 240 seconds is generated.
This prevents compressor short cycling and prevents units
from starting simultaneously after coming back from an
unoccupied cycle.
■ Unoccupied Mode – A simple “grounded” signal between
terminals U and C (no power source required), puts the
unit into the unoccupied mode for night setback operation.
■ Override Mode – A switch on the deluxe automatic
changeover thermostat can be activated during the unoccupied mode to put the unit back into the occupied mode
for two hours for after-hours heating or cooling.
■ Motorized Valve/Pump Restart – The IV/PR (H8) ter-
minals on the The MicroTech III unit controller are used
to energize (open) a motorized valve or start a water pump
to get water circulating prior to starting the compressor
on call for heating or cooling. The IV/PR (H8) terminal
may
be “daisy chained” between 200 units.
■ Brownout Protection – The MicroTech III unit controller
measures the input voltage and will suspend compressor
and fan operation if the voltage falls below 80% of the
unit nameplate rated value. A unique LED status is generated and an output is available to a “fault” LED at the
thermostat.
Unit Shutdown – A simple grounded signal puts the unit
■
into the shutdown mode. Compressor and fan operations
are suspended. A unique LED status is generated and an
output signal is made available for connection to a “fault”
LED at the thermostat.
■ Condensate Overow Protection – The
MicroTech III
unit controller incorporates a liquid sensor at the top of the
drain pan. Upon sensing water ow, cooling operation is
suspended. A unique LED status is generated and output
is available to a “fault” LED at the thermostat. Heating
operation is not suspended.
■ Remote Reset of Automatic Lockouts – The Remote Re-
set feature provides the means to remotely reset automatic
lockouts generated by high-pressure and/or low-temperature faults. When the MicroTech III unit controller is in
automatic lockout due to one of these faults, and the cause
of the fault condition has been alleviated, energizing the
O-terminal for 10 seconds or more will force the control
board to clear the lockout. A unit power cycle can also
be used to clear an automatic lockout if the conditions
causing the fault have been alleviated.
■ Intelligent Reset – The Fault Retry feature helps to
minimize nuisance trips of automatic lockouts caused by
high-pressure and/or low-temperature faults. This feature
clears faults the rst two times they occur within a 24-hour
period and triggers an automatic lockout on the 3rd fault.
The retry count is reset to zero every 24 hours.
■ Equipment Protection Control – The MicroTech III
unit controller receives separate input signals from the
refrigerant high-pressure switch and the low suction line
temperature sensor. In a high-pressure situation, compressor operation is suspended. In a low temperature situation,
the unit goes into a defrost cycle where the unit is put into
cooling operation for 60 seconds until the coaxial heat
exchanger is free of ice. Each switch generates its own
unique LED status and output is available to a “fault”
LED at the thermostat if either situation exists.
Note: Most unit fault conditions are the result of operating
the equipment outside the unit specications.
MicroTech III unit controller LED & fault outputs
Mode / Fault
Occupied, Bypass,
Standby
Override
Unoccupied On On Off Energized
Condensate Overow On Off Off De-energized
High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized
Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return
Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM
Corrupted
Network “Ofine”
Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’
, or Tenant Off On Off Energized
Air or Low
1
ellow Green Red Output-Terminal “A”
Y
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-energized
On On Off De-energized
On On On De-energized
Off Off Off De-energized
s
Thermostat Alarm Light
Catalog 1103-2McQuay Ennity Water Source Heat Pumps11
Control Features – I/O Expansion Module
I/O Expansion Module
The I/O Expansion Module is a factory installed option.
It is an extension of the MicroTech III unit controller and
provides extra functionality.
The I/O Expansion Module has 4 main purposes:
The Microtech III unit controller in combination with
the I/O Expansion Module will be the standard control
system for dual-circuit Water Source Heat Pump
equipment. For example: large vertical units.
The I/O Expansion Module has outputs to control
electric heat on a standard Water Source Heat Pump.
The I/O Expansion Module has outputs for multi-speed
fans on a standard Water Source Heat Pump.
The I/O Expansion Module has an independent LED
annunciator to identify operational fault conditions on
dual-circuit equipment.
I/O Expansion Module Conguration Jumper Settings
Jumper Description Options
JP1 Number of
JP2
Water Reheat Shorted to enable reheat
JP3 and JP4 open for no
supplemental heat
JP3 Supplemental JP3 open, JP4 shorted for
& JP4 Heat Type boilerless electric heat
JP3 and JP4 shorted is an
invalid setting
JP5 and JP6 open for single-speed fan
JP5
& JP6 Selection JP5 shorted and JP6 open for
two-speed fan
JP 5 and JP6 shorted is an
invalid setting
Occupied, Bypass,
Standby, or Tenant
Override Modes
Mode / Fault
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction
Low Suction
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Normal Operation
Y
Temp #2, Flash Flash On De-energized
Off On Off De-energized
Status LED's
ellow Green Red
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Terminal “A”
Thermostat Alarm
Light Output
Note: Mode / Faults are listed in order of priority.
1
Boilerless electric heat only
2
Alarm/fault LED indications take precedence over service test mode LED
indication. The controller shall use service test mode if the service test mode
jumper is installed, even if the LED’s indicate an alarm/fault.
Jumper Terminals
Features
Standard Heat Pumps / Single Circuit Units
Monitors entering water temperature for boilerless
electric heat control
Outputs for medium and high speed fan controls.
Second Circuit Units
High pressure switch
Low pressure switch
Low suction line temperature sensor
Compressor output
Reversing valve
12 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Control Features – MicroTech III Controller with LonWorksModule
MicroTech III / unit control board LED & fault outputs
Mode / Fault
Occupied, Bypass,
Standby
Override
Unoccupied On On Off Energized
Condensate Overow On Off Off De-engergized
High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized
Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return
Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM
Corrupted
Network “Ofine”
Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’
, or Tenant Off On Off Energized
Air or Low
1
ellow Green Red Output-Terminal “A”
Y
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-engergized
On On Off De-energized
On On On De-energized
Off Off Off De-enegized
MicroTech III Unit Controller with LonWorks®
Communication Module
Each McQuay water source heat pump can be equipped
with a LonWorks communication module that is LonMark
3.4 certied. The controller is microprocessor-based and is
designed to communicate over a LonWorks communica-
tions network. It can be factory or eld-installed.
The unit controller is programmed and tested with
all the logic required to monitor and control the unit. An
optional wall sensor may be used with the communication module to provide limited local control of the Water
Source Heat Pump. The unit controller monitors water and
air temperatures and passes information to the communication module. The module communicates with the BAS, to
provide network control of the Water Source Heat Pump.
s
Thermostat Alarm Light
MicroTech III Unit Controller with LonWorks
Communication Module orchestrates the following unit
operations:
Enable heating and cooling to maintain setpoint
based on a room sensor
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
The MicroTech III unit controller with communication
module includes:
A unit-mounted return air sensor*
A unit-mounted discharge air sensor*
A leaving water temperature sensor
* Discharge air and return air sensors must be
eld-installed per IM 956.
communication module provides access to
The
setpoints for operational control
Available wall sensors include:
Room sensor with LED status and tenant override
button
Room
sensor with LED status, tenant override
button, and ±3°F setpoint adjustment
Room
sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
The MicroTech III unit controller with communication module includes a unit-mounted return air, discharge
air and leaving water temperature sensor. Wall mounted
temperature sensors include setpoint adjustment and tenant
override. The user has the capability of substituting the wall
sensor with a duct-mounted return air sensor.
Catalog 1103-2McQuay Ennity Water Source Heat Pumps13
Control Features – MicroTech III Controller with BACnet Module
MicroTech III Controller with BACnet
Communication Module
McQuay water source heat pumps are available with
McQuay BACnet MS/TP communication module that
is designed to communicate over a BACnet MS/TP
communications network to a building automation system
(BAS). It can be factory or eld-installed.
The unit controller is programmed and tested with all the
logic required to monitor and control the unit. An optional
wall sensor may be used with the communication module to
provide limited local control of the water source heat pump.
The unit controller monitors water and air temperatures
and passes information to the communication module. The
module communicates with the BAS, to provide network
control of the water source heat pump.
The module makes operational data and commands
available on a communications network using BACnet
objects and properties:
The network cable is a shielded twisted-pair cable
Network communications run up to 76.8 Kbps
DIP switches on the controller enable the MS/TP MAC
address to be set in the range 0-127
Four green status LEDs on the communication module
indicate communication activity on the MS/TP communication network and with the unit controller
MicroTech III Unit Controller with BACnet MS/TP
Communication Module orchestrates the following
unit operations:
Enable heating and cooling to maintain setpoint
based on a room sensor
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
The MicroTech III unit controller with communication
module includes:
A unit-mounted return air sensor*
A unit-mounted discharge air sensor*
A leaving water temperature sensor
* Discharge air and return air sensors must be
eld-installed per IM 956.
communication module provides access to
The
setpoints for operational control
Available wall sensors include:
Figure 13. MicroTech III BACnet Water Source Heat Pump
Snap-in Communication Module
Room sensor with LED status and tenant override
button
Room
sensor with LED status, tenant override
button, and ±3°F setpoint adjustment
Room
sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
14 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications – Systems
Typical Cooling and Heating Refrigeration Cycles
Note: For standard heat pump operation only
Cooling Refrigeration Cycle
When the wall thermostat calls
for COOLING, the reversing valve
directs the ow of the refrigerant, a
hot gas, from the compressor to the
water-to-refrigerant heat exchanger.
There, the heat is removed by the
water, and the hot gas condenses
to become a liquid. The liquid then
ows through a thermal expansion
valve to the air-to-refrigerant heat
exchanger coil. The liquid then
evaporates and becomes a gas, at the
same time absorbing heat and cooling
the air passing over the surfaces of
the coil. The refrigerant then ows as
a low pressure gas through the reversing valve and back to the suction side
of the compressor to complete the
cycle.
Heating Refrigeration Cycle
When the wall thermostat calls
for HEATING, the reversing valve
directs the ow of the refrigerant, a
hot gas, from the compressor to the
air-to-refrigerant heat exchanger coil.
There, the heat is removed by the
air passing over the surfaces of the
coil and the hot gas condenses and
becomes a liquid. The liquid then
ows through a thermal expansion
valve to the water-to-refrigerant heat
exchanger. The liquid then evaporates
and becomes a gas, at the same time
absorbing heat and cooling the water.
The refrigerant then ows as a low
pressure
valve and back to the suction side of
the compressor to complete the cycle.
gas through the reversing
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Return Air
Conditioned Air
(Cooling)
Return Air
Conditioned Air
(Heating)
Thermal
Expansion Valve
Reversing Valve
Thermal
Expansion Valve
Reversing Valve
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing
Bulb and
Capillary
Tube
Compressor
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing
Bulb and
Capillary
Tube
Compressor
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 15
Applications – Systems
Water source heat pump systems are one of the most ef-
cient, environmentally friendly systems available for heating
and cooling buildings. High-efciency, self contained units
(sizes 7,000 btuh to 420,000 btuh) can be placed in virtually
any location within a building. Each unit responds only to
the heating or cooling load of the individual zone it serves.
This permits an excellent comfort level for occupants, better
control of energy use for building owners and lower seasonal
operating costs. The Air-Conditioning Refrigeration Institute
(ARI) and the International Standards Organization (ISO)
publish standards so that water source heat pumps are rated
for specic applications. The ARI/ISO loop options shown in
this catalog are typical water source heat pump loop choices
available in today’s market. These systems offer benets rang-
ing from low cost installation to the highest energy efciency
available in the market today.
Boiler / Tower Applications: ARI 320 / ISO
13256-1
A “Boiler/Tower” application uses a simple two-pipe
water circulating system that adds heat, removes heat or
transfers rejected heat to other units throughout the building. The water temperature for heating is generally maintained between 65ºF – 70ºF and is usually provided by a
natural gas or electric boiler located in a mechanical room.
The condensing water temperature, during cooling months,
is maintained between 85ºF and 95ºF and requires the use
of a cooling tower to dissipate waste heat. Cooling towers can be located on the roof, or inside or adjacent to the
building. This application can be the lowest cost of the loop
options available.
Note: ASHRAE 90.1 standards require that circulating
pumps over 10 HP will require use of “variable frequency
drive” equipment and pipe insulation to be used whenever
water temperatures are below 60 degrees and above 105
degrees. See ASHRAE 90.1 Standards for details.
Open Loop Well Water Applications: ARI
325 / ISO 13256-1
“Open Loop” well water systems use ground water
to remove or add heat to the interior water loop. The
key benet of an open loop system is the constant water
temperature, usually 50ºF to 60ºF, which provides efcient
operation at a low rst cost. Most commercial designers
incorporate a heat exchanger to isolate the building loop
from the well water. Using heat exchangers can reduce
maintenance issues while still allowing the transfer of heat
from unit to unit as with the “Boiler/Tower System”. A successful design provides an ample amount of groundwater
(approximately 2 GPM per ton) and adequate provisions
for discharging water back to the aquifer or surface. Open
Loop applications are commonly used in coastal areas
where soil characteristics allow reinjection wells to return
the water back to the aquifer. Note that some states have requirements on the depths of return water reinjection wells,
and such wells must be approved by the United States Environmental Protection Agency. Also, bad water quality can
increase problems with heat exchanger scaling. Suspended
solids can erode the heat exchanger. Strainers can be used
to contain suspended solids.
Open Loop Well Application
Boiler/Tower Application
16 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications – Systems
Closed Loop Geothermal Applications ARI
330/ISO 13256-1
“Vertical Closed Loop” applications are installed by
drilling vertical bore holes into the earth and inserting
a plastic polyethylene supply/return pipe into the holes.
The vertical wells are connected in parallel reverse return
fashion to allow the water from the building to circulate
evenly throughout the boreeld. The circulating uid dissipates heat to the ground in a similar manner as a “tower”
and adds heat back to the loop like a boiler. If properly
designed, the loop eld can maintain the loop temperatures
necessary to condition the building without the use of a
boiler or a tower. Loop temperatures usually range from
37ºF to 95ºF in Northern climates. Southern applications
can see temperatures ranging from 40ºF to 100ºF. The
number of bore holes and their depth should be determined
by using commercial software that is specically designed
for vertical geothermal applications. Typical bore depths
of a vertical loop range from 150 to 400 feet and generally
require about 250 feet of surface area per ton of cooling.
Vertical Loop Application
Horizontal Loop Application
“Surface Water” or “Lake” closed loop system is a
A
geothermal loop that is directly installed in a lake or body
of water that is near the building. In many cases, the body
of water is constructed on the building site to meet drainage or aesthetic requirements. Surface loops use bundled
polyethylene coils that are connected in the same manner
as a vertical or horizontal loop using a parallel reverse
return design. The size and the depth of the lake is critical.
Commercial design services should be used to certify that a
given body of water is sufcient to withstand the building
loads. Loop temperatures usually range from 35ºF to 90ºF
and prove to be the best cooling performer and lowest cost
loop option of the three geothermal loops. Some applications may not be good candidates due to public access or
debris problems from ooding.
Surface Water Loop Application
A closed loop “Horizontal” geothermal application
is similar to a vertical loop application with the exception
that the loops are installed in trenches approximately 5
feet below the ground surface. The piping may be installed
using a “four-pipe” or “six-pipe” design and could require
1,500 to 2,000 square feet of surface area per ton of
cooling. Loop temperatures for a commercial application
can range from 35ºF to 95ºF in Northern climates. Southern
climates can see temperatures ranging from 40ºF to
100ºF. Horizontal loops are generally not applied in urban
areas because land use and costs can be prohibitive. New
advances in installation procedures have improved the
assembly time of horizontal loops while keeping the rst
cost lower than a vertical loop.
Catalog 1103-2McQuay Ennity Water Source Heat Pumps17
Applications Considerations
Typical Vertical Installation
Unit Location
The VFC, VFW water source heat pump can be
installed “free standing” in an equipment room; however,
closet installations are more common for the small vertical
type units. Generally, the unit is located in the corner of a
closet with the non-ducted return air facing 90º to the door
and the major access panels facing the door as shown in
the illustration at right. Alternatively, the unit can have a
ducted return air with the opening facing the door and the
major access panels facing 90º to the door.
Locate a vertical unit to allow for easy removal of
the lter and access panels. Allow a minimum of 18" (46
cm) clearance on each side of the unit for service and
maintenance access. Always be sure to leave at least one
side of the lter rack unobstructed so that the service
personnel will be able to slide the lter out.
Install a eld supplied line voltage disconnect for
branch circuit protection.
To reduce noise emissions, install a eld-provided 1/2
inch thick, isolator pad below the entire base of the vertical
unit. The pad should be equal to the overall foot-print size
of the unit to provide sound dampening of the unit while in
operation.
A - Condensate
B- Desuperheater Water Return (Optional)
C
- Desuperheater Water Supply (Optional)
D
- Water Return
E
- Water Supply
F
- Low Voltage Control Wiring (Electric Entrance)
Right-Hand Return Air
Arrangement
Return
Air
Return Air Thru
Louvered Door
1. Discharge air
2. Acoustic thermal duct lining - 10 feet
3. Line voltage disconnect
4. Low voltage wiring to unit control box
5. Flexible duct collar
6. Louvered closet door
7. Condensate drain
8. Flexible, braided, stainless steel return hose with ow
controller/ball valve with port
9. Flexible, braided, stainless steel supply hose with Y-
strainer/ball valve with port
10. Access to unit control box
11. LED annunciator lights indicate unit operation status
and faults
12. Full vibration isolation pad between unit and oor
13. Minimum distance between return air duct collar and
wall for non-ducted return applications
• Size 007-012 – 5 inches
• Size 015-024 – 5 inches
• Size 030-036 – 6 inches
• Size 042-048 – 8 inches
• Size 060-070 – 10 inches
18 McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Applications Considerations
Ductwork and Attenuation
All ductwork should conform to industry standards of
good practice as described in ASHRAE Systems Guide.
The discharge duct system will normally consist of a
exible connector at the unit, a non-insulated transition
piece to the full duct size, a short run of duct, an elbow
without vanes, and a trunk duct teeing into a branch circuit
with discharge diffusers as illustrated below.
Return air ducts can be brought in through a wall grille
and then to the unit. The return duct system will normally
consist of a exible connector at the unit and a trunk duct to
the return air grille. With metal duct material, the return air
duct should be internally lined with acoustic insulation for
sound attenuation.
Return air ductwork to the unit requires the optional
return air duct collar/2" (51mm) lter rack kit.
Suggested Discharge Air Ducting
Trunk Duct
Square Elbow
(Both Sides
Internally Lined
With Acoustic
Insulation)
Branch Duct
Flexible
Duct Collar
Duct
Transition
(Internally Lined)
2 ft. x 2 ft. Diffuser
Discharge Collar
devices are commercially available and can be installed to
eliminate the need for memory stop shut off valves. Include
Pressure / Temperature ports to allow the service technician
to measure water ow and unit operation.
Control Access Panel
A - Condensate
B- Desuperheater Water Return (Optional)
C
- Desuperheater Water Supply (Optional)
D
- Water Return
E
- Water Supply
F
- Low Voltage Control Wiring (Electric Entrance)
G
- Line Voltage Unit Power (Electric Entrance)
McQuay has available optional hose kit combinations
to better facilitate system ow balancing. These exible
hoses reduce vibration between the unit and the rigid piping
system.
Fire Rated Supply or Return Hoses
Heat Pump
Piping
The water source heat pump unit is typically connected
to the supply / return piping using a “reverse return” piping
system which includes a ow control device so that ow
requirements are met for each zone. A short, high pressure
“exible hose” is used to connect the unit to the building’s
hard piping and acts as a sound attenuator for both the unit
operating noise and hydronic pumping noise. One end of
the hose has a swivel tting to facilitate removal of the
unit for replacement or service. Include supply and return
shutoff valves in the design to allow removal of a unit
without the need to shut down the entire heat pump system.
The return valve may be used for balancing and will
typically have a “memory stop” so that it can be reopened
to the proper position for the ow required. Fixed ow
Catalog 1103-2McQuay Ennity Water Source Heat Pumps19
Condensate Drain
The factory provided condensate drain trap on the
vertical unit is located inside the cabinet. Condensate
removal piping must be pitched away from the unit not
less than 1/4" per foot. A vent is required after the trap so
that the condensate will drain away from the unit. The vent
can also act as a clean out if the trap becomes clogged.
To avoid having waste gases entering the building, the
condensate drain should not be directly piped to a drain/
waste/vent stack. See local codes for the correct application
of condensate piping to drains.
Applications – Unit Selection
Achieving optimal performance with water source heat
pump systems requires both accurate system design and
proper equipment selection. Use a building load program to
determine the heating and cooling loads of each zone prior
to making equipment selections. With this information,
the McQuay SelectTools™ software selection program for
Water Source Heat Pumps can be used to provide fast, accurate and complete selections of all McQuay water source
heat pump products. SelectTools software is available by
contacting your local McQuay Representative.
While we recommend that you use McQuay SelectTools
software for all unit selections, manual selections can be
accomplished using the same zone load information and the
capacity tables available in this catalog.
Boiler / Tower Application Manual Selections:
The following example illustrates a typical selection for
a zone in a boiler/tower system for a commercial building.
A building load program determines that this zone needs
38,255 BTUH of total cooling, 31,832 BTUH of sensible
cooling and 36,988 BTUH of total heating. The water tem-
peratures for the boiler/tower system are 90ºF for cooling
and 70ºF for heating. The return air temperature is 80ºF dry
bulb with 67ºF wet bulb for cooling and 70ºF for heating.
Zone requirements:
Total Cooling Load = 38,255 BTUH
Sensible Cooling Load = 31,832 BTUH
Total Heating Load = 36,988 BTUH
Air Flow Required = 1510 CFM
Return Air Cooling = 80ºFDB/ 67ºFWB
Return Air - Heating = 70ºFDB
Since a McQuay Model VFC 036 produces approxi-
mately 36,000 BTUH of cooling, it is not sufcient for
this zone and a model VFC 042 should be considered.
Model VFC is chosen because it is specically designed
for a boiler/tower application. Typical water ow rates for
boiler/tower applications are 2.0 to 2.5 GPM per ton and in
this example no antifreeze is used.
Selection:
Model .............................VFC 042 (Boiler / Tower model)
Final Selection ....................................................VFC 042
Geothermal Applications:
The following example illustrates the same zone in a
geothermal application.
The load requirements for the zone are the same as the
above example – 38,255 BTUH of total cooling and 31,832
BTUH of sensible cooling and 36,988 BTUH of heating.
Geothermal loop software programs are available to help
determine the size of the loop eld based on:
Desired entering water temperatures for the system.
Specic acreage available for the loop which produces
specic min./max loop temps for the unit selection.
Entering water temperatures for geothermal systems can
be as high as 90º to 100ºF and as low as 30ºF based on the
geographical location of the building. Water ow rates are
typically 2.5 to 3 GPM per ton and the use of antifreeze is
required in most northern applications.
Zone requirements:
Total Cooling Load = 38,255 BTUH
Sensible Cooling Load = 31,832 BTUH
Total Heating Load = 36,988 BTUH
Air Flow Required = 1510 CFM
Return Air Cooling = 80 DB / 67 WB
Return Air - Heating = 70 DB
A McQuay Model VFW is chosen for this geothermal
application. Model VFW offers insulated water piping for
condensation considerations and a different freezestat setting to allow entering water temperatures lower than 40ºF
(with antifreeze). Output capacities should be recalculated
using the antifreeze reduction tables that are shown on page
49. The Model VFW 042 is rst considered but may not
meet the heating load because of the reduced entering water
temperatures (35ºF) and an antifreeze solution of 21 %
propylene (see page 49).
Selection:
Model ..................................VFW 042 (Geothermal model)
Total cooling capacity @ 100 EWT = 40,434 BTUH x
.980 = 39,625
Sensible cooling capacity @ 100 EWT = 32,164 BTUH x
.980 = 31,520
Total heating capacity @ 35 EWT = 38,335 BTUH x
.975 = 37,377 CFM = 1510 @ .6 ESP (Dry Coil)
Water Flow required to meet capacity = 10.8 GPM
Water Pressure drop = 12.7 x 1.5 = 14.61 (FT. H2O)
Final Selection ....................................................VFW 042
Note:
In applications where the zone may be a corner ofce or have
excessive glass area, the heating load could be greater than the
heating output capacity of the VFW 042 model (say 41,985 BTUH).
The choices are to upsize the unit to the next model available (048),
or add an electric duct heater to supplement the output of the 042
unit.
20McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Ennity Vertical ISO Performance Data – Water Loop
Water Loop Performance Data – Rated in Accordance with ISO Standard 13256-1 Boiler/Tower
Standard Unit ECM at High Static
*007
009
012
042
* Not available at time of publication. Please consult your McQuay Representative for specific availability
n/a = ECM not available in unit sizes 007, 009, 012.
Notes:
EER = Energy Efciency Ratio COP = Coefcient of Performance L/s = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature.
Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature.
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 21
Ennity Vertical ISO Performance Data – Ground Loop
Ground Loop Performance Data Rated in Accordance with ISO Standard 13256-1 Ground Coupled
Standard Unit ECM at High Static
*007
009
012
* Not available at time of publication. Please consult your McQuay Representative for specific availability
n/a = ECM not available in unit sizes 007, 009, 012.
Notes:
EER = Energy Efciency Ratio COP = Coefcient of Performance L/S = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 77°F (25°C) entering water temperature.
Heating capacity is based on 68°F (20°C) entering air temperature and 32°F (0°C) entering water temperature.
22McQuay Ennity Water Source Heat Pumps Catalog 1103-2
Ennity Vertical ISO Performance Data – Ground Water
Ground Water Performance Data Rated in Accordance with ISO Standard 13256-1.
Standard Unit ECM at High Static
*007
009
012
* Not available at time of publication. Please consult your McQuay Representative for specific availability
n/a = ECM not available in unit sizes 007, 009, 012.
Notes:
EER = Energy Efciency Ratio COP = Coefcient of Performance L/S = Liters per second
Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 59°F (15°C) entering water temperature.
Heating capacity is based on 68°F (20°C) entering air temperature and 50°F (10°C) entering water temperature.
Capacity Tables Notes:
EWT = Entering Water Temperature (ºF) L/sec. = Airow in Liters per second WPD = Water Pressure Drop (Ft. Hd) EA = Entering Air Temperature (ºF)
LWT = Leaving Water Temperature (ºF) TOT = Total Heat (Btu) SEN = Sensible Heat (Btu) kW = Kilowatts
COP = Coefcient of Performance THA = Total Heat of Absorption (Btu) THR = Total Heat of Rejection (Btu) GPM = Gallons Per Minute
Catalog 1103-2 McQuay Ennity Water Source Heat Pumps 23