This manual provides information on the MicroTech II® control system used in the AAF®-
®
HermanNelson
Unit Ventilator product line. It describes the MicroTech II components, input/
output configurations, field wiring options and requirements, and service procedures.
For installation and general information on the MicroTech II Unit Ventilator Controller, refer
to IM 747, MicroTech II Unit Ventilator Controller.
For installation, commissioning instructions, and general information on a particular unit
ventilator model, refer to the appropriate manual (Table 1), as well as accompanying software
operating instruction manual (T able 4), and possible accessory manuals that may pertain to the
unit (Table 3).
For installation and maintenance instructions on a plug-in communications card, refer to the
appropriate protocol-specific installation and maintenance manual (Table 2). For a description
of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED
15065.
Copies of the latest version of these manuals are available for download on our website at
www. mcquay.com or from your local McQuay Representative.
Table 1: Model-spe c ific unit ventilator installation literature
DescriptionManual #
VerticalIM 817X X X X
HorizontalIM 830X X X X
Vertical Self-ContainedIM 789X X X X X X
AHF
AHB
AHV
AHR
AVS
AVB
AVV
AVR
AZB
AZR
AZS
AZU
AZV
AZQ
Table 2: Protocol-specific communication card installation literature and protocol data
DescriptionManual #
Unit Ventilator Unit Controller LonWorks® Communications ModuleIM 729
Unit Ventilator Unit Controller JCI N2 Open® Communications ModuleIM 730
Unit Ventilator Unit Controller BACnet® Communications ModuleIM 731
Protocol Data PacketED-15065
Table 3: Accessory-specific installation literature
DescriptionManual #
MTII Unit Ventilator Controls InstallationIM 747
Room Temperature Sensors InstallationIM 629
ATS Service Cable Installation for Unit VentilatorsIM 762
McQuay OM 7523
Introduction
Table 4: Software program literature
DescriptionManual #
Air Source Heat Pump with Electric Heat (Software Model 00)OM 748
Water Source Heat Pump with Electric Heat (Software Model 02)
Water Source Heat Pump without Electric Heat (Software Model 03)
DX Cooling with Electric Heat (Software Model 04)OM 750
DX Cooling Only (Software Model 05)OM 751
Electric Heat Only (Software Model 06)OM 752
DX Cooling with Hydronic Heat - Valve Control (Software Model 07)
DX Cooling with Hydronic Heat - F&BP Damper Control (Software Model 08)
2-Pipe Hydronic Heat Only - Valve Control (Software Model 09)
2-Pipe Hydronic Heat Only - F&BP Damper Control (Software Model 10)
2-Pipe Chilled Water Cooling and Hot Water Heat - Valve Control (Software Model 11)
2-Pipe Chilled Water Cooling and Hot Water Heat - F&BP Damper Control (Software
Model 12)
4-Pipe Chilled Water Cooling and Hydronic Heat - Valve Control (Software Model 13)
4-Pipe Chilled Water Cooling and Hydronic Heat - F&BP Damper Control (Software
Model 14)
2-Pipe Chilled Water Cooling Only - Valve Control (Software Model 15)
2-Pipe Chilled Water Cooling Only - F&BP Damper Control (Software Model 16)
2-Pipe Chilled Water Cooling with Electric Heat - Valve Control (Software Model 17)
2-Pipe Chilled Water Cooling with Electric Heat - F&BP Damper Control (Software
Model 18)
OM 749
OM 753
OM 754
OM 755
OM 756
OM 757
OM 758
NOTICE
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with this instruction manual, may cause interference to radio
communications. It has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against detrimental interference when the equipment is operated in a
commercial environment. Operation of this equipment in a residential area is likely to cause
detrimental interference in which case users are required to correct the interference at their
own expense. McQuay International disclaims any liability resulting from any
interference or for the correction thereof.
WARNING
Electric shock hazard. Can cause personal injury or equipment damage.
This equipment must be properly grounded. Connections and service to the MicroTech II
control panel must be performed only by personnel that are knowledgeable in the operation
of the equipment being controlled.
CAUTION
Extreme temperature can damage system components.
The MicroTech II controller is designed to operate in ambient temperatures from -20°F to
125°F. It can be stored in ambient temperatures from -40°F to 140°F. It is designed to be
stored and operated in relative humidity up to 95% (non-condensing).
CAUTION
Static sensitive components. A static discharge while handling electronic circuit
boards can damage components.
Discharge any static electrical charge by touching the bare metal inside the main control
panel before performing any service work. Never unplug any cables, circuit board terminal
blocks, relay modules, or power plugs while power is applied to the panel.
4McQuay OM 752
Introduction
Acronyms/Abbreviations
The following table list acronyms and abbreviations that may or may not be used within this
manual. Other abbreviations for keypad displays and parameters can be found in Table 7 on
page 10 and Table 25 on page 44.
Table 5: Acronyms and abbre v iations
Description
Air FanAF
Auxiliary Heat End DifferentialAHED
Auxiliary Heat Start DifferentialAHSD
American Standard Code for Information InterchangeASCII
American Society of Heating, Refrigerating, and Air
Conditioning Engineers, Inc
Compressorized Cooling LockoutCCLO
Spac e CO
Chilled WaterCW
Chilled Water Valve PositionCWVP
Discharge AirDA
Discharge Air High Limit DAHL
Discharge Air TemperatureDAT
Discharge Air Temperature SetpointDATS
Demand Controlled Ventilation
DX Cooling Discharge Air Low LimitDXLL
Economizer Compare DifferentialECD
Economizer IA/OA Enthalpy Differential EED
Economizer OA Enthalpy Setpoint EES
Emergency Heat SetpointEHS
Exhaust Interlock OAD Min Position Setpoint EOAD
Outdoor Air Temperature SetpointEOAT
End-of-CycleEOC
EOC OAT Low Setpoint EOCS
Outdoor Air Humidity OutputEORH
Space Humidity SetpointERH
Economizer IA/OA Temp Differential ETD
Economizer OA Temp Setpoint ETS
Source (water in) TemperatureEWIT
Face and Bypass Damper PositionFBDP
Federal Communications CommissionFCC
Face and BypassF & BP
Heating, Ventilating, Air Conditioning RefrigerationHVACR
Heating EOC Valve SetpointHEOC
Hot WaterHW
Indoor AirIA
Indoor Air FanIAF
Indoor Air TemperatureIAT
Light Emitting DiodeLED
Local User InterfaceLUI
Mixed Air Low LimitMALL
Mechanical Cooling Low Limit Setpoint MCLL
National Electric CodeNEC
Outside AirOA
Outside Air DampersOAD
Energize Exhaust Fan OAD Setpoint OADE
OAD Min Position High-Speed Setpoint OADH
OAD Min Position Low-Speed Setpoint OADL
OAD Min Position Med-Speed Setpoint OADM
Outdoor Air Damper PositionOADP
OAD Lockout Setpoint OALS
OAD Max Position Setpoint OAMX
Outside Air TemperatureOAT
The MicroTech II U nit Vent Controller (UVC) is a self-contained device that is capable of
complete, stand-alone operation. Information in the controller can be displayed and modified
by using the keypad/display (local user interface). The following sections describe how to use
the keypad/display.
Note – Many UVC parameters are accessible both through the keypad/display and the network
interface. The shared keypad/display and the network interface variables have a “lastchange-wins” relationship.
Using the Keypad/Display
The keypad/display shown in Figure 1 is provided with all MicroTech II Applied Unit
Ventilator unit controllers. With the keypad/display, operating conditions, system alarms, and
control parameters can be monitored. Set points and other parameters also can be modified.
Figure 1: Keypad/display
MicroTechTMII
FAN ONLY
COOL
HEAT
AUTO
MODEFAN
HIGH
MED
LOW
AUTO
FUNC
ON /
STOP
Display Format
The keypad/display’s 2-digit, 7-segment display normally shows the effective heating or
cooling temperature set point (Effective Set Point Output). The display also is used to view
and modify UVC parameters as explained in the following sections.
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.
All other LEDs are switched off.
Keypad Functions
Security Levels
The keypad/display provides a 4-level password security feature that can be used to restrict
access. The available security levels are shown in Table 6.
Note – All unit ventilator controllers ship with the lowest security (level 0) enabled. To change
security levels, see Figure 2. Once a security level is changed, the keypad/display
remains at that security level until the next time it is changed.
Why can’t I use the MODE or FAN key or adjust Set Point Offset?
Most likely this is due to the security feature being used. If the security feature is set higher
than level 0, then some keypad/display functionality is locked out. To ensure this is not the
problem, enter the level 0 password then try to use the keypad/display again.
McQuay OM 7527
Getting Started
Table 6: Keypad/display security levels
Level DisplayWhat is restricted?Password
0
1
2
3
Default level (access all)10
Does not allow set point offset changes;
also locks out keypad/display menu
access.
Does not allow set point offset changes
nor MODE key changes; also locks out
keypad/display menu access.
Does not allow set point offset changes
nor MODE and FAN key changes; also
locks out keypad/display menu access.
21
32
43
Figure 2: Changing keypad/display security levels
ON/STOP Key and LED
Use the ON/STOP key to toggle the UVC between OFF mode and running (Application Mode
Input). The ON/STOP LED is off when the UVC is in the OFF mode.
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.
All other LEDs are switched off.
– The UVC archives each change to the keypad/display FAN and MODE keys. When the
ON/STOP key is used to bring the unit out of OFF mode, the UVC implements the last
active fan and unit modes.
– Each time the UVC power cycles, the UVC is in the auto fan and auto unit modes when
power is returned.
WARNING
Off mode is a “stop” state for the unit ventilator. It is not a “power
off” state. Power may still be provided to the unit.
FAN Key
Use the F AN key to toggle through each of the fan speeds (Fan Speed Command Input): Auto,
Low, Medium, and High.
MODE Key
Use the MODE key to toggle through the keypad/display accessible unit modes (Heat/Cool
Mode Input): Auto, Heat, Cool, and Fan Only.
Arrow Keys
Use the arrow keys to scroll between parameters and to adjust parameters.
FUNC Key
Use the Func key to view the actual space temperature or to confirm selection and changes to
user-adjustable parameters.
8McQuay OM 752
Getting Started
Using the Keypad/Display
Viewing Actual Indoor Air Temperature (IAT)
Normally, the effective set point temperature appears on the keypad/display. You also can use
the keypad/display to view the indoor air temperature (IAT). See Figure 3.
Note – When the actual indoor air temperature (Effective Space Temp Output) equals the
effective set point temperature (Effective Set Point Output), you there is no change to the
keypad/display when you view space temperature.
Figure 3: Viewing indoor air temperature
707170
Effective
set point
Changing Set Points
The keypad/display can be used to make a +/–5°F (+/–3°C) offset adjustment to the effective
temperature set point. See Figure 4. Also see “Space Temperature Set Points” on page 24 to
learn more about temperature set points.
Figure 4: Adjusting the set point offset
FUNC
Enter
(5-sec)
Actual space
temperature
Effective
set point
-1
Flash
value
FUNC
Enter
0
0
Current
offset
So69
Effective
set point
70
Effective
set point
-1
Adjusted
offset
FUNC
Save
change
So
Set point
offset
Note – The set point offset clears whenever UVC power is cycled. When you change the set point
offset after a power cycle, or for the very first time, this cleared value shows as the highest
allowed value (5°F/3°C) but is not an actual offset value.
– When using the +/–3°F (+/–1.7°C) remote wall sensor, any set point offset adjustment
made at the keypad/display causes the UVC to override and ignore the remote wall
sensor set point adjustment knob. To use the remote wall sensor set point adjustment
knob after you changed the set point offset on the keypad/display, clear the keypad/
display set point offset by cycling UVC power.
– When using the 55°F to 85°F remote wall sensor, the UVC ignores any LUI set point offset
adjustments.
Menu Reference
The keypad/display menu eases troubleshooting and simplifies UVC configuration. The user
can access the most common parameters and system status values without a PC or network
interface.
The keypad/display menu is accessed via an unmarked, hidden key. This hidden key is located
approximately behind the letter “h” in the MicroTech II logo on the keypad/display face.
The keypad/display menu consists of two levels. The first level is the keypad/display Menu
Item List containing alphanumeric characters representing each parameter. The second level is
where the parameter’s value is viewed and adjusted if the parameter is adjustable. After 15seconds, an inactivity timer automatically causes the display to back out of the menu levels,
returning to the effective set point display.
McQuay OM 7529
Getting Started
Figure 5: Changing a keypad/display menu item
Table 7: Keypad/display menu item list
Display Keypad menu item list Abr.Description
Reset Alarm InputEnter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable
UVC (Heat/Cool) Mode
Output
UVC State Output
Discharge Air Temp Set
point Output
Discharge Air Temp
Output
Ventilation Cooling Low
Limit set point
Mechanical Cooling Low
Limit set point
Slave Type ConfigurationSet slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave
Effective Occupancy
Output
Occupancy Override
Input
Occupied Cooling set
point
Standby Cooling Set
point
Unoccupied Cooling Set
point
Occupied Heating Set
point
Standby Heating Set
point
Unoccupied Heating Set
point
Wall Sensor Type
Outside Air Damper
Position Output
OAD Min Position High-
Speed Set point
OAD Min Position MedSpeed Set pointOADM
OAD Min Position LowSpeed Set pointOADL
the alarm again, enter 0.
Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.
UVCM
Heat, 9 = Fan Only
Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 =
Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11
VCLL Adjust economizer cooling DA temperature low limit.RWx
MCLL Adjust mechanical cooling DA temperature low limit.RWx
follows master). This feature requires a network over which the master and slave
UVCs can communicate.
Display current occupancy.ROx
Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting
this variable is intended only for troubleshooting. Once you are done, cycle unit
power to clear this variable and return the UVC to normal operation.
OCS Adjust occupied cooling set point.RWx
SCS Adjust standby cooling set point.RWx
UCS Adjust unoccupied cooling set point.RWx
OHS Adjust occupied heating set point.RWx
SHS Adjust standby heating set point.RWx
UHS Adjust unoccupied heating set point.RWx
Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F.RWx0
OADP Display OA damper position.ROx
Adjust OA damper minimum position with IAF at high speed. (This variable is
OADH
factory set to 5% open when the unit is ordered with optional
Adjust OA damper minimum position with IAF at medium speed. (This variable is
not used when the optional
damper minimum regardless of fan speed.)
Adjust OA damper minimum position with IAF at low speed. (This variable is not
used when the optional
damper minimum regardless of fan speed.)
Reset Filter Alarm InputEnter 1 to clear filter alarm.RWx
Space Temp Sensor
Offset
Keypad/display
Temperature Units
1. RW = read and write capable, RO = read only.
2. If a menu value is greater than 2-digits (higher than 99), then
Adjust OA damper position above which the exhaust fan output will be energized.
EOAD
There is a fixed –5% differential associated with this set point.
Adjust OA damper minimum position when the exhaust interlock input is
OADE
energized.
OAMX Adjust OA damper maximum position.RWx99%
Set OA damper lockout feature status: 0 = disable, 1 = enable. (This variable is
factory set to 1 when the unit is ordered as a recirc unit with no OAD.)
Adjust OA temperature below which the OA damper closes if the OA damper
lockout is enabled. (This variable is factory set to –99°C when the unit is ordered
as a recirc unit with no OAD.)
Adjust economizer OA temperature set point. DO NOT lower this set point below
ETS
CCLO or you risk creating a deadband where no cooling occurs.
ETD Adjust economizer IA/OA temperature differential.RWx 1.8°F (1°C)
EORH Display OA humidity (optional). 00 = No sensor connected.ROx
EHS Adjust emergency heat set point.RWx
Set emergency heat operation during shutdown, 0 = no emergency heat during
shutdown: 1 = allow emergency heat during shutdown.
Set the function external binary Input 3: 0 = ventilation lockout, 1 = exhaust
interlock.
Set space fan cycles (switches off) during occupied, bypass, and standby mode: 2
= continuous, 3 = cycling.
Adjust this setting to bias the UVC measured space temperature.RWx0
Set keypad/display temperature units in English or SI. This set point also effects
which unit types displayed over Metasys N2 and BACnet MS/TP networks using
the appropriate optional communications modules.
will be displayed on the keypad/display.
Getting Started
RO
06
1
RW
RWx99%
RWx12%
RWx0
RWx
RWx
RWx0
RWx0
RWx2
Default
35.6°F
(2°C)
68°F
(20°C)
25 Btu/lb
(58 kJ/kg)
1.3 Btu/lb
(3 kJ/kg)
53.6°F
(12°C)
RWxF
2
McQuay OM 75211
Description of Operation
Description of Operation
State Programming
The MicroTech II UVC takes advantage of “state” machine programming to define and
control unit ventilator operation. “State” defines specific states or modes of operation for each
process within the unit ventilator (e.g., heating, cooling, etc.) and contain the specific logic for
each state. This eliminates some of the most common problems associated with control
sequences such as the possibility of simultaneous heating and cooling, rapid cycling, etc.
State machine programming, and the unique nature of state diagrams, can be easily used to
describe operation. It can simplify sequence verification during unit commissioning, as well as
simplify troubleshooting. With the unique combination of state machine programming and the
keypad/display’s ability to allow a technician to easily determine the active UVC state,
troubleshooting the UVC can be very simple.
The state diagrams presented in the following sections consist of several “elements” including
super states, states, conditional jumps (also called transitions) and transition points. Super
states are used as a means to group two or more related states into a single control function
such as cooling, or heating, etc. States are where all the actual work takes place, within each
state the UVC enables PI-loops and other logic sequences required to control unit ventilator
operation within that particular state, while other functions and PI-loops not needed durin g
that state may be disabled. Conditional jumps, or transitions, are the logic paths used by the
UVC to determine which state should be made active, these are the “questions” the UVC
continually considers. The transition point is simply a point through which a number of
conditional jumps meet. Think of it as a point where a number of questions must be
considered from which the UVC then determines which path is followed and which state is
then made active.
The UVC states and super states are used to define the “normal” unit modes, such as Off,
Night Purge, Fan Only, Emergency Heat, Auto, Cool, and Heat. The UVC also supports
several “special purpose” unit modes such as Purge, Pressurize, De-pressurize, and Shutdown,
which can be forced via a network connection and override typical UVC operation.
Note – Not all states or modes are available for all UV configurations, and some states (such as
Active Dehum) are optional.
– In the state descriptions below the terms, saturated high and saturated low, indicate that
the heating or cooling function being described has reached 100% or 0%, respectively.
12McQuay OM 752
Figure 6: Complete UVC—state diagram
EmergencyHeat
ModeSuperState
FullHeat
CantHeat
Heat
LowLimit
7
D
5
E
FanOnly
A
NightPurge
8
Off
9
HeatMode
SuperState
AutoMode
Econ
3
CantCool
C
DAHeat
LowLimit
4
F
CoolMode
SuperState
CantHeat
B
Description of Operation
UVC Unit Modes
The UVC provides several “normal” modes of unit operation. These include: Off, Night
Purge, Fan Only, Cool, Emergency Heat, Auto, Heat, and Cool.
Normal UVC modes can contain a single state or several states depending upon the
functionality required for each particular mode. Each UVC state is assigned a number, which
can be very helpful when trying to understand which state is currently active within the UVC.
To view the current UVC state number, use the keypad/display.
McQuay OM 75213
Description of Operation
OFF
9
F
Table 8: UVC st a t e na mes and numbers
Normal UVC modesState names
OFFOFF9957
Night purgeNight Purge8856
Fan onlyFan Only10A65
Emergency heat
Heat
Auto
Cool
Full Heat7755
Cant Heat13D68
Heat5553
Cant Heat11B66
Low Limit14E69
EconMech1149
Mech2250
Econ3351
DA Heat4452
Cant Cool12C67
Low Limit15F70
DecimalASCIIHex
State numbers
WARNING
Off mode is a “stop” state for the unit ventilator. It is not a “power
off” state. Power may still be provided to the unit.
OFF Mode (State 9)
Off mode is provided so that the UVC can be forced into a powered OFF condition. OFF mode
is a “stop” state for the unit ventilator; it is not a power off state. OFF mode consists of a
single UVC state: OFF [9].
When OFF mode becomes active, the UVC stops all normal heating, cooling, and ventilatio n
(OA damper is closed), and fan operation ends. The UVC continues to monitor space
conditions, indicate faults, and provide network communications (if connected to a network)
in the OFF mode while power is maintained to the unit.
While in OFF mode, the UVC does not maintain DA temperatures. If the space temperature
drops below EHS while in the OFF mode, the UVC is forced into the Emergency Heat mode
(see “Emergency Heat Mode (Super State)” on page 16).
The space lighting output continues to operate based upon the current occupancy mode.
Note – Special purpose unit modes such as Purge, Pressurize, and De-pressurize can force the
UVC to perform “special” functions during which the display appears to be in the OFF
mode.
Figure 7: Off state diagram
UVC Mode
UVC Mode OFF
OF
Transition
point
14McQuay OM 752
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.