
Installation Instructions 698
Solid-State Speed Controller 
Steam/Hot Water Unit Heaters
Application
For remote control of air delivery, solid-state speed controllers 
are available for McQuay steam/hot water unit heaters. Models 
UH-18 through 108 with 115/60/1 motors (Power Code A). 
A solid-state module in the controller controls motor input 
voltage to maintain steady-state speed regulation at any setting 
between “High” and “Low”. Controllers are packed separately 
and must be connected according to wiring diagram, Figure 1 
or 2.
NOTE: These controllers are not interchangeable with different 
motor sizes or motor manufacturers. Before installation, check 
unit heater model number, motor manufacturer and speed 
controller size (listed in Amps on back of controller), to verify 
compatibility. See chart below. If not matched correctly and 
failure occurs, warranty will be nullified.
➀ Speed control cannot be used to turn unit on/off for 3-lead motors. 
A thermostat or disconnect switch must be used.
Figure 1 
Wiring Diagram
Group: Fan Coil 
Date: February 2001
Installation
1. Controllers are furnished assembled and must be connected 
between the fan motor and the thermostat; see Figure 1 or 2.
2. Install thermostat at desired location, (see instructions 
packed with thermostat).
3. Install speed controller in a suitable location that will not 
invite tampering.
Wiring Connections
1. Disconnect line voltage supply from service at the main 
electrical panel. Bring power supply leads into junction box.
2. Remove speed controller cover and make wiring connections 
as per the appropriate wiring diagram. CAUTION: Failure to 
wire this device according to the appropriate diagram may 
result in failure of the equipment or injury to the installer or user.
Operation Check
Set thermostat to lowest possible position. Turn controller to 
minimum speed. Turn on power to the system. Adjust thermostat above room temperature. Motor will then start on lowest 
speed. Adjust the controller to select the desired fan speed.
If motor does not start on lowest setting, the minimum control 
speed may be adjusted. This can be accomplished on the 5 
amp model by removing the cover plate to the controller and 
turning the screw labeled MIN SPEED ADJ with a small screw 
driver. Turn as indicated to increase or decrease minimum set 
point. For the 2.5 amp model, the same procedure can be 
followed with exception of the screw being located on the left 
side of controller. If the motor still does not start, check power 
supply and wiring. On new motors, bearings may be slightly 
tight until motor is “broken-in”. Do not adjust speed controller 
below minimum speed level until motor has experienced some 
running time. Periodically repeat above procedure if lower 
speeds are desired.
Figure 2 
Wiring Diagram
®
4900 Technology Park Blvd., Auburn, NY 13021-9030 USA  (315) 253-2771
 Printed on recycled paper containing at least 10% post-consumer recycled material.
ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND 
ALL LOCAL CODES. ALL COMPONENTS MUST AGREE WITH THEIR 
RESPECTIVE POWER SOURCE.
©2001 AAF-McQuay Incorporated