McQuay Type THR Templifier heat pump water heaters are
designed for indoor installations.Each unit is completely
assembled and factory wired before evacuation, charging and
testing. Each unit consists of multiple accessible hermetic
compressors,replaceabletube dual circuit shell-and-tube
evaporator, water cooled condenser, and complete refrigerant
piping.
Liquid line components that are included are manual liquid
line shutoff valves, charging valves, filter-driers,liquid line
solenoidvalves, sightglass/moistureindicators,and diaphragm element thermal expansion valves. Other features
NOMENCLATURE
THR-040D-1
D;::+J
(Accessible Hermetic)
Nominal Capacity (Tons)
DESCRIPTION
includecompressordischargecheck valves, crankcase
heaters, recycling pumpdown during “on” or “off” seasons,
compressor lead-lag switch to alternate the compressor starting sequence, and sequenced starting of compressors.
The electricalcontrol centerincludesall safety and
operatingcontrolsnecessaryfor dependableautomatic
operation.
Compressors are not fused, but may be protected by op-
tional circuit breakers, or may rely on the field installed
fused disconnect for protection.
Basic Unit With Single Water Cooled
Condenser Per Refrigerant Circuit
L
‘1
1 = R-22 Refrigerant,130” F Max.
Leaving Water Temp.
INSPECTION
When the equipment is received, all items should be careful-be checked before unloading the unit to be sure that it agrees
Iy checked against the bill of lading to insure a complete shipment. All units should be carefully inspected for damage upon
arrival. All shipping damage should be reported to the carrier and a claim should be filed. The unit serial plate should
with the power supply available. Physical damage to unit after
acceptance is not the responsibility of McQuay International.
Note: Unit shipping and operating weights are available in
the physical data table (pages 17 and 18).
INSTALLATION
Note: Installation and maintenanceare to be performedonly by qualifiedpersonnelwho are familiar with local codes
and regulations,and experiencedwith this type of equipment.Caution: Sharp edges are a potentialinjury hazard. Avoid
contact.
HANDLING
Every model THR Templifier heat pump is supplied with a fullarea since the refrigerant will displace the air. Avoid exposrefrigerant charge. For shipment the charge is contained ining an open flame to refrigerant when moving the unit. Care
the condenser and is isolated by the manual condenser li-should be taken to avoid rough handling or shock due to dropquid valve and the compressor discharge service valve.ping the unit.
Should the unit be damaged, allowing the refrigerant toother than the unit base, unit skid, or rigging holes in the
escape, there may be danger of suffocation in the equipment,
area since the refrigerant will displace the air. Avoid exposure
evaporatoror condenservessels.
Never lift, push or pull unit from anything
IM 377 I Page 3
MOVINGTHE UNIT
The McQuay Templifierheat pump is mounted on heavy
wooden skids to protect the unit from accidental damage and
to permit easy handling and moving.
It is recommendedthat all moving and handling be performed with the skids under the unit when possible and that
the skids not be removed until the unit is in the final location.
When moving the unit, dollies or simple rollers can be
used under the skids.
Never put the weight of the unit against the control box.
In moving, always apply pressure to the base on skids only and not to the piping or shells, A long bar helps move the
unit easily. Avoid dropping the unit at the end of the roll.
If the unit must be hoisted, it is necessary to lift the unit
by attachingcables or chains at the lifting holes in the
evaporator tube sheets. Spreader bars must be used to protect the control cabinet and other areas of the chiller (see
Figure 1).
Do not attach slings to piping or equipment.Move unit in
the upright horizontal position at all times. Set unit down gently
when lowering from the trucks or rollers.
Note: On unit sizes 120 through 170D, ordered with the op-
tional acoustical enclosure, there will be extension brackets
attached to the evaporator tube sheets. These brackets will
be used for hoisting the unit and should be removed when
unit is in place.
Figure 1.
I
Unit is designed for indoor application and must be located
in an area where the surrounding ambient temperatures are
40For above,
Because of the electrical control devices, the units should
not be exposed to the weather. A plastic cover over the control box is supplied as temporary ’protection during transfer.
SPACE REQUIREMENTSFOR CONNECTIONSAND SERVICING
The chilled water piping for all units enters and leaves the
evaporator from the rear, with the control box side being the
front side of the unit. (A clearance of 3 to 4 feet should be provided for this piping and for replacing the filter-driers, for servicing the solenoid valves, or for changing the compressors,
should it ever become necessary). Recommendedservice
clearances are shown in Figure 2.
The condenser water piping enters and leaves the shell
from the ends. Work space must be provided in case water
regulating valves are being used and for general servicing.
Clearance should be provided for cleaning condenser tubes
or for removing evaporator tubes on one end of the unit as
specified in Table 1. It is also necessary to leave a work area
on the end opposite that used for replacement of a cooler tube.
Table 1. Minimumrecommendedclearancerequirements
B
A
961<
41“
I Minimum clearance required for removal and replacement of cooler tubes
(either end).
flJ36,,
c
I 96” 0!46 “
D
AB
120” @36 “120“ (u
LOCATION
A reasonably level and sufficiently strong floor is all that
is required for the Templifier heat pump. If necessary, additional structural members should be provided to transfer the
weight of the unit to the nearest beams.
Note: Unit shippinq and operating weights are available in
the physical data’ table, pages 17 and I8
Figure 2. Clearancerequirements
01
FRONT
cONTROL BOX
20
1
f
The small amount of vibration normally encountered with the
Templifier makes this unit particularly desirable for basement
or ground floor installationswhere the unit can be bolted
directly to the floor. The floor construction should be such that
the unit will not affect the building structure, or transmit noise
and vibrationinto the structure,See vibrationisolator
Page 4 I IM 337
PLACING
THE UNIT
section for additionalmountina information.
Note: On the THR 120D thru 170D, shipping bolts are used
to secure the compressor rails to the evaporator brackets.
Remove these and discard after unit is mounted and before
unit is started.
VIBRATIONISOLATORS
Rubber-in-shear or spring isolators can be furnished and field
placed under each corner of the package,It is recommended that a rubber-in-shearpad be used as the minimum
isolation on all upper level installations or areas in which vibra-
tion transmissionis a consideration.
Transfer the unit as indicated under “Moving the Unit.” In
all cases, set the unit in place and level with a spirit level.
When spring type isolators are required, install springs running under the main unit supports. Adjust spring type mountings so that upper housing clears lower housing by at least
1/4” and not more than 1/2”.A rubber anti-skid pad should be
used under isolators if hold-down bolts are not used.
Vibration eliminators in all water piping connected to the
Templifier are recommended to avoid straining the piping and
transmittingvibration and noise.
Table 2.
-----
Figure 3. Isolator Locations
REAR
= oQ
K 0
FRONT
CONTROL BOX
!5
Q
Table 3. SpringFlex Isolators
CP-1-25Gray WI 1 Red Stripe
CP-1-26Gray WI 2 White Stripes
CP-1-27Gray WI 1 Orange Stripe
CP-1-28Gray WI 1 Green Stripe
CP-1-31Gray WI 2 Yellow Stripes11000.637%
CP-2-26Gray WI 2 White Stripes
CP-2-27Gray WI 1 Orange Stripe15001.06 1
CP-2-28Gray WI 1 Green Stripe
CP-2-31 I Gray w/ 2 Yellow Stripes I 2200 I 0.83 IIOV. I 9Vz I 6
CP-4-27 I Gray w/ 1 orange Stripe I 3000 I 1.06 II ol/4 [ 9’/2 I 7’/2 I 5] 6% ]886-58051 3A-27
Since regional piping practices vary considerably,local ordinances and practices will govern the selection and installation of piping. In all cases local building and safety codes and
ordinances should be studied and complied with.
All piping should be installed and supported to prevent the
unit connectionsfrom bearing any strain or weight of the
system piping.
Vibration eliminatorsin all water piping connected to the
unit are recommendedto avoid straining the piping and
transmittingpump noise and vibrationto the building
structure.
It is recommended that temperature and pressure indicators
be installed within 3 feet of the inlet and outlet of the shells
to aid in the normal checking and servicing of the unit.
A strainer or some means of removing foreign matter from
EVAPORATORPIPING
The water flow entering the evaporator must always be on the
end nearest the expansion valves and evaporator refrigerant
piping connections to assure proper expansion valve opera-
tion and unit capacity (see pages 14 thru 16).
Design the piping so that it has a minimumnumber of
changes in elevation. Include manual or automatic vent valves
at the high points of the chilled water piping, so that air can
be vented from the water circuit, System pressures can be
GENERAL
the water before it enters the unit or the pump is recom-
mended. It should be placed far enough upstream to prevent
cavitation at the pump inlet (consult pump manufacturer for
recommendations).The use of a strainer will prolong pump
and unit life and thus keep system performanceup.
A preliminaryleak check of the water piping should be
made before filling the system.
Shutoff valves should be provided at the unit so that normal servicing can be accomplishedwithout draining the
system.
A water flow switch or pressure differentialswitch must
be mountedin the water lines to the evaporatorand the
condenserto verify water flow before unit is permittedto
start.
maintainedby using an expansion tank or a combination
pressure relief and reducing valve.
All chilled water piping should be insulated to prevent con-
densation on the lines. If insulation is not of the self-contained
vapor barrier type, it should be covered with a vapor seal.
Piping should not be insulated until completely leak tested.
Vent and drain connectionsmust extend beyond pro-
posed insulation thickness
for accessibility.
Page 6 I IM 377
EVAPORATORTEMPERATURELIMITS
EVAPORATORFLOW RATE LIMITS–GPM*
Table 6.
THR
UNIT
SIZE
040D
0500
0600
0700
080D
0900
1000
1100
1200
t30D
1400
1500
1600
1700
‘ Water flows are basedon 10 FPS for max. flow and3 FPS formin, flow.
NOTE: Maximum allowable evaporator water pressure is 175 psig
WATER FLOW –GPM
lM3771Page7
CONDENSERWATER PIPING
THR condensers have factory manifolds for single inlet and
outlet connections. Water flow may be 2-pass parallel, 4-pass
parallel or 8-pass series/parallel to suit the application, Refer
to Figure 6 to determine condenser water circuiting arrangement. For proper performance,the condenser water must
enter the bottom connection of the condenser on all circuiting
arrangements.
Condenserwater pressure drop for the unit should be
measured at the common inlet and outlet pipe, through a port
provided by the installing contractor. All pressure drop measurements should be made with the same gauge to insure
an accurate reading, Before the pressure drop curves can be
read, the pressure drop values on the curve must be corrected
based on the average hot condenser water temperature. The
correction factor can be obtained from page 9, and then
multiplied by the values on the pressure drop curves to adjust them according to the average water temperature in the
system.
CONDENSERTEMPERATURELIMITS
Table 7. Condenser temperature limits, operating and maximum ( 0F)
!,
UNIT SERIES
REFRIGERANT
TW%
OPERATINGMAX. ALLOWABLE
MAX. LEAVING
WATERTEMP.
WATERTEMP,IN CONDENSER
(“F)(“F)
I
Note: Water flowlng through the condenser should never exceed the maximum allowable
temperature in the table above even when the urmt IS not operating.
1
R-22
I
I
130
I
145
I
CONDENSERTEMPERATURERISE
Table 8. Allowable condenser temperature rise applicable to refrige
!rant 22
Note: Temperature rise for various water circuit arrangements may for a given
load be limited by the maximum or minimum flow hsted in the unit condenser
and evaporator flow Iimlt tables. The flow Iimlts for a given unit should be used
to calculate the temperature rise limit before a water circuiting arrangement
and temperature rise are established.
CONDENSERFLOW RATE LIMITS
Table 9. Unit CondenserWater Flow Limits (GPM)*
060D
070D
080D
090D
100D
I1OD508
120044056
130D5066426032
\
140D5066426032
150D61080
1600610
170D610
‘Values shown are total unit flow AdJust flow per condenser to meet flow requirement for flow arrangement being used
2523212616638
316
360
44456
444
40
44
56
62
80
80
158
1802290
222
222
254
224
305
305
305
207910
2811114
2811114
31130
2811214
40150
4015020
40150
13016
13016
11
16
20
20
Page 8 I IM 377
Figure 6. Condenser Water Arrangements.
2-Pass Parallel
m
OUT
IN
NOTE: When parallel circuitingis used, design leaving condenserwater temperaturemay not be obtainableunless both condensercircuits
NOTES: Valves, drains, vents, expansion tanks and instrumentation must be added in accordance with good piping practice.
Temperatures, where shown, are for illustration only.
These are typical Templifier application possibilities shown in schematic way. Each specific application will vary in the use of storage, supplemental heat, etc.,
to suit the job characteristics
WASTE HEATCONVERSIONUNIT
#
I
4
150°F
170”F *
L----------
-------.~
TEMPLIFIER
FROM PARTIAL SOURCE FLUIO FLOW
HEAT RECOVERY
-------
!~~
—EVAPORATOR-
I
I
CONDENSER!
L
--..-.-
1+=
TEMPLIFIER
USEFUL
1
TOWEROR CLOSEO
CIRCUITCOOLER
IM 377 I Page 11
WATER QUALITY
The water flowing through the condenser and evaporator must
be of suitable quality for use with standard materials of
construction:
Condenser:Steel heads and tube sheets,
rubber gaskets, copper tubes.
Evaporator:Steel shell, copper tubes,
polypropylenebaffles
Any additives that may be harmful should not be used.
quality may deteriorate later, an intermediate heat exchanger
is recommended, Plate type exchangers should be considered
for minimum temperatureapproach at economicalcost.
Note: If cooling”tower or other source water containing dirt,
sediment or other foreign matter is used, assure that take-offs
to the Templifier are at the top of horizontal pipelines to minimize foreign matter getting into the evaporator. Depending
on water conditions,dual strainers and/or a settling drum
should be considered.
Where water or other fluids of unsuitable quality, or where
CONDENSERWATER THERMOSTAT
On units THR-040D thru 170D units, the condenser water thermostat (CP1) is mounted inside the control console. The con-
ever be removed from the well for servicing, care should be
taken as not to wipe off the heat conducting compound suptrol sensor is mounted in a well, located in the condenserplied in the well.
water inlet manifold. Care should be taken not to damage the
sensor cable or leadwires when working around the unit. It
is also advisable to check the leadwire before running the
unit to be sure that it is firmly anchored and not rubbing on
the frame or any other component,Should the sensor
Figure 7. ThermostatWell Installation
Note: See page 51 for additional thermostat information.
Caution:The thermostat bulb should not be exposed to
water temperatures above those listed in the condenser water
temperaturelimit Table 7.
EVA
INLET
The water flow switchesmust be mountedin either the
entering or leaving water lines to insure that there will
INSTALLED
FLOW SWITCHES
be adequate water flow and load to the evaporator and condenser
before the unit can start. This will safeguard against liquid
refrigerant entering the compressors on startup. It also serves
to shut down the unit in the event that water flow is interrupted
to guard against evaporator freeze-up.
A flow switch is available from McQuay under ordering
number 175033 B-00. It is a “paddle”type switch and adaptable to any pipe size from 1“ to 6“ nominal. Certain minimum
flow rates are required to close the switch and are listed in
Table 10. Installation should be as shown in Figure 8. Electrical connections in the unit control center should be made
at terminals 5 and 6. The normally open contacts of the flow
switch should be wired between these two terminals. There
is also a set of normally closed contacts on the switch that
could be used for an indicator light or an alarm to indicate
when a “no flow” condition exists.
1. Apply pipe sealing compound to only the threads of the
switch and screw unit into D“x D“x1” reducing tee (see
Figure 8). The flow arrow must be pointed in the correct
direction.
2. Piping should provide a straight length before and after
R
the flow switch of at least five times the pipe diameter.
3. Trim flow switch paddle if needed to fit the pipe diameter.
Make sure paddle does not hang up in pipe.
Caution:Make sure the arrow on the side of the switch is
pointedin the proper directionof flow.
The flow switch is
designed to handle the control voltage and should be connected according to the wiring diagram (see wiring diagram
inside control box door).
Table 10. Flow Switch Minimum Flow Rates
NOMINAL PIPE SIZEMINIMUM REQUIRED FLOW TO
(INCHES)ACTIVATESWITCH (GPM)
16.00
11A
I 1/2
218.80
21/2
3
A
5
6
I
9.80
12.70
24.30
30.00
39.7C
-. .
58.70
79,20
Page 12 I IM 377
Figure 8.
FLOW SWITCH
PADDLE
FLOW SWITCH
*
1“2,,
VIEW FROM END OF EVAPORATOR/CONDENSER
--
m
PIPE
-EF;?’)
~ FLOW3
w
STRAIGHTPIPE
FOR AT LEAST 5D”
Y
The ANSI/ASHRAE Standard 15-1978 specifies that pressure
relief valves on vessels containing Group 1 refrigerants (R-22)
“shall discharge to the atmosphere at a location not less than
15 feet above the adjoining ground level and not less than
20 feet from any window, ventilation opening or exit in any
building.” The piping must be provided with a rain cap at the
outside terminating point and a drain at the low point on the
vent piping to prevent water buildup on the atmospheric side
of the relief valve. In addition, a flexible pipe section should
be installed in the line to eliminate any piping stress on the
relief valve(s).
Figure 9. Relief Valve Piping
rl
f“’”
I
‘EI %%’:,w%’on
I ;~;~bleto relief
~:
c:
‘;
c
66
3“
Wall
Rain Cap
“eeve&Vent
Pitch !O
Outside OUTSIDE
[r
WALL
15 Ft. Min.
Clearance
To Ground
Level (See
Adjacent
Information)
RELIEF VALVE PIPING
The size of the discharge pipe from the pressure relief valve
shall not be less than the size of the pressure relief outlet.
When two or more vessels are piped together, the common
header and piping to the atmosphere shall not be less than
the sum of the area of the relief valve outlets connected to
the header. Fittings should be provided to permit vent piping
to be easily disconnected for inspection or replacement of the
relief valve.
Note: Provide adequate fittings in piping to permit repair or
NOTES:
@ 60Vo Full refrigerant at90° F.
@ 8-Pass Series/Parallel Arrangement.
36553705
I
3655
I
40 I 50 I 50 I 50 150160I 60 I 60
36353665
I
363536953895
I
3735
40 I 50 I 50 ] 50 I 50 I 60 I 60 I 60
399540654240
3935
WEIGHTS-8-PASS
3955
21/221/221/221/221/2I21/2
22
1 z3~
lZ3~
22
1 z3~
96969696
25,624.324.330.5
225
225
175175
225225
175
566
3/8%=/8%
125%125%
3434
6? 3/4
633A
12434124%
34
&,3~
343434
Gs3~
1167/8
127127
34
655A
125%125%
65%
117%1171~
34343434
Gs3~ss3~
655/3
4675
40254185
4690
65 I 65 I 70 I 70 [ 60 I 60 I 60 I 60
4045
4200
39654045
4715
4630
5255
5115
65 I 6570 I 7060 I 80
14
175
34
~~l/d
sG1/4
GG1/4
5315
5175
2
14
96
27.6
225
175
%
127
34
fjfjlfi
125?4
34
&jl/4
117%
34
GG1/4
5465
5325
5405
5265
60 I 80
Table 18. WHR-120D thru 170D.
UNIT SIZE
120D
1
130D140D
COMPRESSORS
Nominal Horsepower
Number
Speed RPM (60 Hz/50 Hz)
No. of Cylinders
Oil Charge (Oz.)
Discharge Line Size (In.)
Number
Diameter (In,)
Tube Length (In.)
Design W.P, (PSIG):
Refrigerant Side
Water Side
Relief Flare
Purge Valve Flare
Liquid SubcoolerIntegral
No. Water Passes
PumpOut Capacity 0
Connections:
Water Inlet & Outlet (Victaulic)
No. Water Passes
Pump-Out Capacity @I 250.0
I
Connections:
Water Inlet & Outlet (Victaulic)
160/1 36 160/136 160/1 36 160/1 60 160/1 60
I
I
I
35/2535/2535/25
2222
1750/ 1450
6/46/4614
1%111A 1y*ll 1/3 12/8/11A
22
103~liJ3~lrJ3~1133~
120120120
450450450
250250250
%5/8
V4 & V2
222
250.0250.0
444
444
333
2-PASS ARRAN QEMENT
238.6238.6238.6236.6
4-PASS ARRANGEMENT
250,0238,6
351353513535/3535/3535/40
22
1750/1 450
6/6
1yJl 1A
CONDENSERS
120120
V4 & V2V4 & V2
Integral
22
444
44444
238,6236,6236.
333333
1750/ 14501750/ 1450
6/66/66/66/66/6
160/1 60 160/160 160/242
1%/1 ye
13/Jl Ya
2
1034103~f 03~I03/4
1133~
I
120120120
5/8
IntegralIntegralIntegral
2222
6219.2219.2
S-PASS ARRANGEMENT
No. Water Passes@
PumpOut Capacity @250.0250.0
Connections:
Water Inlet & Outlet (Victaulic)
No. Refrigerant Circuits
Diameter (In,)
Tube Length (In.)
Water Volume (Gallons)38.236.136.1
Refrigerant Side D.W.P. (PSIG)
Water Side D.W.P. (PSIG)
Water Connections: