McQuay TGZ 050A, TGZ 080A, TGZ 120A, TGZ 150A, TGZ 060A Operation And Maintenance Manual

...
Operation and Maintenance Manual
TGZ Scroll Compressor Templifiers
OMM TGZ-1
Group: Chiller
Part Number: 331975601
Effective: February 2011
Supercedes: June 2009
TGZ 040A to TGZ 190A, Packaged Water Heater
600 to 3100 MBH
R134a
Software: WGZDU0102E
Corrections 2/22/11 Changed/added setpoints pgs 62, 63,+
Table of Contents
Introduction ........................................... 3
General Description .......................................... 3
Nomenclature.................................................... 3
Water Pressure Drop............................. 3
TGZ Scroll........................................................ 4
TGZ Electrical Data.............................. 7
Field Wiring Diagram ......................... 16
Start-Up and Shutdown ...................... 18
Pre Start-up ..................................................... 18
Start-up ........................................................... 18
Weekend or Temporary Shutdown.................. 19
Start-up after Temporary Shutdown................ 19
Extended Shutdown ........................................ 19
Start-up after Extended Shutdown .................. 19
Sequence of Operation ........................ 20
MicroTech II Controller...................... 23
TGZ Controller Software Version................... 23
General Description ........................................ 23
Inputs and Outputs ............................. 25
Large PCO2/PCO3 Controller ........................ 25
Expansion I/O Controller................................ 27
Setpoints ......................................................... 27
Events & Alarms.................................. 30
Protection (Shutdown) Alarms........................ 30
Alarms and Events .............................. 30
Unit Stop Alarms............................................. 30
Limit Events.................................................... 34
Controller Operation ........................... 37
EXV Control ................................................... 52
Using the Controller.............................53
Menu Screens.................................................. 55
Menu Descriptions .......................................... 55
BAS Interface ................................................. 72
Optional Controls................................. 74
Part Winding Start........................................... 74
Phase/Voltage Monitor (Optional) .................. 74
Hot Gas Bypass (Optional) ............................. 74
System Maintenance ............................ 76
General............................................................ 76
Electrical Terminals ........................................ 77
Operating Limits ............................................. 77
Compressor Oil ............................................... 77
Oil Equalization .............................................. 78
Sightglass and Moisture Indicator................... 78
Crankcase Heaters........................................... 78
System Service......................................79
Filter-Driers..................................................... 79
Liquid Line Solenoid Valve ............................ 79
Troubleshooting Chart ........................80
©2007 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve
the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONM managed, granted and used by LONM Corporation; Modbus from Schneider Electric; MicroTech II and Open Choices from McQuay International
Manufactured in an ISO Certified facility
ARK
ARK
International under a license granted by Echelon Corporation; Compliant Scroll from Copeland
, LonTalk, LONW
ORKS
, and the LONM
ARK
logo are
2 TGZ 040A through TGZ 190A OMM TGZ-1
Introduction
General Description
McQuay Type TGZ water heaters are scroll compressor refrigeration units that recover heat from warm fluid streams in the evaporator and deliver hot water, at a useful temperature, from the condenser to a heating load. They are designed for indoor installations only and are completely assembled, wired, charged and tested. Each unit consists of four or six (depending on unit size) scroll compressors, brazed-plate evaporators on models 040 to 120 and shell-and-tube evaporators on models 150 to 190, shell-and-tube condenser/heater, and complete refrigerant piping.
There are two refrigerant circuits, each with manual liquid line shutoff valves, charging valves, filter­driers, liquid line solenoid valves, sightglass/moisture indicators, and expansion valves (thermal on TGZ 040-120, electronic on TGZ 150-190.
The electrical control center includes a MicroTech II control system and other components necessary for dependable automatic operation.
NOTE: Additional information not included in this manual, such as unit dimensions and weights, physical data, and performance data can be found in Catalog Templifier-1.
Nomenclature
T G Z 100 A
Templifier
Vintage
Global
Scroll Compressor
Nominal Evaporator Capacity in Tons
Water Pressure Drop
The vessel flow rates must fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves on pages 4 through 6. Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency, cause erratic operation of the expansion valve and could cause low temperature cutoffs. On the other hand, flow rates exceeding the maximum values shown can cause erosion on the evaporator water connections and tubes.
Measure the water pressure drop through the vessels at field installed pressure taps. It is important not to include valves or strainers in these readings.
The condenser flow rate will determine whether 2-pass or 4-pass condensers are used, according to the following table:
CONDENSER DELTA-T PASSES FLOW
10- to 20 Degrees F 2-Pass High Flow Rate
20 to 40 Degrees F 4-Pass Low Flow Rate
The entering water should be piped to the bottom connection of the condenser and out the top.
OMM TGZ-1 TGZ 040A through TGZ 190A 3
TGZ Scroll
Figure 1, Evaporator Pressure Drop
TGZ Evaporator Water Pressure Drop
100
10
Dp (ft)
TGZ040
TGZ050
TGZ060
TGZ080
TGZ100
TGZ110
TGZ120
TGZ150
TGZ170
TGZ190
TGZ040
TGZ060
TGZ110
TGZ100
TGZ120
TGZ170
TGZ150
TGZ190
TGZ050
TGZ080
1
10 100 1000
Flow Rate (gpm)
TGZ UNIT
MODEL
040A
050A
060A
080A
100A
110A
120A
150A
170A
190A EV34191212/7 192 4.5 12.1 13.4 369 15.5 23.3 46.3 615 40.9 38.8 122.3
Note: Nominal Flow Rate is gpm for 10ºF Delta-T at unit operating conditions of evaporator at 75/65ºF water temp and condenser at
110/30º F water temp.
EVAPORATOR
MODEL
AC250-70DQ 34 1.1 2.1 3.2 72 4.4 4.5 13.2 120 11.6 7.6 34.7
AC250-94DQ 45 1.0 2.8 3.1 100 4.7 6.3 14.0 167 12.5 10.5 37.2
AC250-94DQ 55 1.5 3.5 4.5 121 6.7 7.6 20.0 202 17.7 12.7 53.0
AC350-162DQ 83 1.4 5.2 4.3 162 5.1 10.2 15.2 270 13.5 17.0 40.2
AC350-162DQ 98 2.0 6.2 5.8 189 6.8 11.9 20.3 315 17.9 19.9 53.6
AC350-182DQ 113 2.2 7.1 6.4 218 7.5 13.8 22.4 363 19.8 22.9 59.1
AC350-182DQ 128 2.7 8.1 8.2 246 9.5 15.5 28.4 410 25.1 25.9 74.9
EV34191111/9 147 2.4 9.3 7.3 283 8.5 17.9 25.4 472 22.5 29.8 67.1
EV34191212/7 169 3.5 10.7 10.5 326 12.2 20.6 36.5 543 32.2 34.3 96.1
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
INCH-POUND S.I. INCH-POUND
GPM FT. L/S KPA GPM FT. LPS KPA GPM FT. LPS KPA
S.I. INCH-POUND
S.I.
4 TGZ 040A through TGZ 190A OMM TGZ-1
Figure 2, Standard Four-pass Condenser Pressure Drop
TGZ 4-Pass Condenser Water Pressure Drop
100
TGZ040
TGZ050
TGZ060
TGZ080
TGZ100
TGZ110
TGZ120
TGZ150
TGZ170
TGZ190
TGZ060
TGZ100
10
Dp (ft)
TGZ170
TGZ120
TGZ080
TGZ050
TGZ040
TGZ110
TGZ150
TGZ190
1
TGZ UNIT
MODEL
TGZ040
TGZ050
TGZ060
TGZ080
TGZ100
TGZ110
TGZ120
TGZ150
TGZ170
TGZ190
10 100 1000
Flow Rate (gpm)
COND.
MODEL
C1010-62 23 1.93 1.45 5.77 47 7.5 3.0 22.4 63 13.1 4.0 39.1
C1010-62 32 2.44 2.02 7.29 64 9.1 4.0 27.2 86 16.0 5.4 47.7
C1010-76 38 3.40 2.40 10.16 77 13.0 4.9 38.9 103 22.6 6.5 67.5
C1410-112 51 2.84 3.22 8.49 103 10.8 6.5 32.3 138 18.8 8.7 56.3
C1410-128 60 3.00 3.79 8.97 120 11.2 7.6 33.5 160 19.3 10.1 57.8
C1610-164 69 2.44 4.35 7.29 138 9.1 8.7 27.2 184 15.7 11.6 47.0
C1610-164 78 3.08 4.92 9.21 156 11.5 9.8 34.4 208 19.9 13.1 59.4
C1612-164 90 4.85 5.68 14.50 180 18.1 11.4 54.1 240 31.3 15.1 93.4
C1612-184 103 4.89 6.50 14.60 207 18.4 13.1 55.0 276 31.8 17.4 95.0
C1612-184 117 6.24 7.38 18.66 234 23.3 14.8 69.6 312 40.2 19.7 120.3
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
INCH-POUND
GPM FT L/S KPA GPM FT L/S KPA GPM FT L/S KPA
S.I. INCH-POUND
S.I. INCH-POUND
S.I.
OMM TGZ-1 TGZ 040A through TGZ 190A 5
100
10
Dp (ft)
Figure 3, Optional Two-pass Condenser
TGZ 2-Pass Condenser Water Pressure Drop
TGZ040
TGZ050
TGZ060
TGZ080
TGZ100
TGZ110
TGZ120
TGZ150
TGZ170
TGZ190
TGZ060
TGZ190
TGZ150
TGZ100
TGZ170
TGZ080
TGZ050
TGZ040
TGZ120
TGZ110
1
10 100 1000
Flow Rate (gpm)
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
TGZ UNIT
MODEL
TGZ040
TGZ050
TGZ060
TGZ080
TGZ100
TGZ110
TGZ120
TGZ150
TGZ170
TGZ190
COND.
MODEL.
C1010-62 59 1.6 3.7 4.9 94 4.0 5.9 12.0 150 9.8 9.5 29.3
C1010-62 80 2.0 5.0 6.0 128 4.9 8.1 14.6 205 12.0 12.9 35.8
C1010-76 96 2.9 6.1 8.5 154 7.0 9.7 20.9 246 17.0 15.5 51.0
C1410-112 129 2.4 8.1 7.1 206 5.8 13.0 17.3 330 14.2 20.8 42.3
C1410-128 150 2.5 9.5 7.3 240 6.0 15.1 17.9 384 14.7 24.2 43.8
C1610-164 173 2.0 10.9 6.0 276 4.9 17.4 14.6 442 12.0 27.9 35.8
C1610-164 195 2.5 12.3 7.6 312 6.2 19.7 18.5 499 15.1 31.5 45.3
C1612-164 225 3.3 14.2 9.9 360 8.1 22.7 24.2 576 19.8 36.3 59.1
C1612-184 259 3.5 16.3 10.4 414 8.5 26.1 25.4 662 20.8 41.8 62.1
C1612-184 293 4.4 18.5 13.2 468 10.8 29.5 32.3 749 26.4 47.2 78.8
INCH-POUND S.I.
GPM FT L/S KPA GPM FT L/S KPA GPM FT LPS KPA
INCH-
POUND
S.I. INCH-POUND S.I.
6 TGZ 040A through TGZ 190A OMM TGZ-1
TGZ Electrical Data
Table 1, Compressor Amp Draw
TGZ
UNIT
VOLTS
SIZE
040
050
060
080
100
110
120
150
170
190
NOTES:
1. External overloads only available on Templifier units with 140°F maximum condenser leaving water temperature.
2. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control transformer.
3. Single point power supply requires a single fused disconnect to supply electrical power to the unit.
4. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.
FREQ.
(HERTZ)
208 35.3 35.3 - 35.3 35.3 - 30.8 30.8 - 30.8 30.8 - 239 239 - 239 239 -
230 35.3 35.3 - 35.3 35.3 - 28.0 28.0 - 28.0 28.0 - 239 239 - 239 239 -
460 17.9 17.9 - 17.9 17.9 - 14.0 14.0 - 14.0 14.0 - 125 125 - 125 125 -
575
208 48.1 48.1 - 48.1 48.1 - 42.0 42.0 - 42.0 42.0 - 300 300 - 300 300 -
230 48.1 48.1 - 48.1 48.1 - 38.4 38.4 - 38.4 38.4 - 300 300 - 300 300 -
460 21.8 21.8 - 21.8 21.8 - 19.2 19.2 - 19.2 19.2 - 150 150 - 150 150 -
575
208 54.0 54.0 - 54.0 54.0 - 54.0 54.0 - 54.0 54.0 - 340 340 - 340 340 -
230 52.6 52.6 - 52.6 52.6 - 48.8 48.8 - 48.8 48.8 - 340 340 - 340 340 -
460 25.6 25.6 - 25.6 25.6 - 24.4 24.4 - 24.4 24.4 - 173 173 - 173 173 -
575
208 73.1 73.1 - 73.1 73.1 - 58.0 58.0 - 58.0 58.0 - 505 505 - 505 505 -
230 73.1 73.1 - 73.1 73.1 - 52.8 52.8 - 52.8 52.8 - 505 505 - 505 505 -
460 30.1 30.1 - 30.1 30.1 - 26.4 26.4 - 26.4 26.4 - 225 225 - 225 225 -
575
208 73.1 73.1 - 73.1 73.1 - 69.2 69.2 - 69.2 69.2 - 500 500 - 500 500 -
230 73.1 73.1 - 73.1 73.1 - 62.4 62.4 - 62.4 62.4 - 500 500 - 500 500 -
460 35.3 35.3 - 35.3 35.3 - 31.2 31.2 - 31.2 31.2 - 250 250 - 250 250 -
575
208 73.1 73.1 - 93.6 93.6 - 69.2 69.2 - 88.8 88.8 - 500 500 - 599 599 -
230 73.1 73.1 - 93.6 93.6 - 62.4 62.4 - 80.0 80.0 - 500 500 - 599 599 -
460 35.3 35.3 - 45.5 45.5 - 31.2 31.2 - 40.0 40.0 - 250 250 - 310 310 -
575
208 93.6 93.6 - 93.6 93.6 - 88.8 88.8 - 88.8 88.8 - 599 599 - 599 599 -
230 93.6 93.6 - 93.6 93.6 - 80.0 80.0 - 80.0 80.0 - 599 599 - 599 599 -
460 45.5 45.5 - 45.5 45.5 - 40.0 40.0 - 40.0 40.0 - 310 310 - 310 310 -
575
208 73.1 73.1 73.1 73.1 73.1 73.1 69.2 69.2 69.2 69.2 69.2 69.2 500 500 500 500 500 500
230 73.1 73.1 73.1 73.1 73.1 73.1 62.4 62.4 62.4 62.4 62.4 62.4 500 500 500 500 500 500
460 35.3 35.3 35.3 35.3 35.3 35.3 31.2 31.2 31.2 31.2 31.2 31.2 250 250 250 250 250 250
575
208 73.1 73.1 73.1 93.6 93.6 93.6 69.2 69.2 69.2 88.8 88.8 88.8 500 500 500 599 599 599
230 73.1 73.1 73.1 93.6 93.6 93.6 62.4 62.4 62.4 80.0 80.0 80.0 500 500 500 599 599 599
460 35.3 35.3 35.3 45.5 45.5 45.5 31.2 31.2 31.2 40.0 40.0 40.0 250 250 250 310 310 310
575
208 93.6 93.6 93.6 93.6 93.6 93.6 88.8 88.8 88.8 88.8 88.8 88.8 599 599 599 599 599 599
230 93.6 93.6 93.6 93.6 93.6 93.6 80.0 80.0 80.0 80.0 80.0 80.0 599 599 599 599 599 599
460 45.5 45.5 45.5 45.5 45.5 45.5 40.0 40.0 40.0 40.0 40.0 40.0 310 310 310 310 310 310
575
STANDARD UNIT W/O EXT. OL'S
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
No.1 No.3 No.5 No.2 No.4 No.6 No.1 No.3 No.5 No.2 No.4 No.6 No.1 No.3 No.5 No.2 No.4 No.6
60
11.5 11.5 - 11.5 11.5 - 11.2 11.2 - 11.2 11.2 - 80 80 - 80 80 -
60
19.9 19.9 - 19.9 19.9 - 15.2 15.2 - 15.2 15.2 - 109 109 - 109 109 -
60
21.2 21.2 - 21.2 21.2 - 19.6 19.6 - 19.6 19.6 - 132 132 - 132 132 -
60
24.4 24.4 - 24.4 24.4 - 21.2 21.2 - 21.2 21.2 - 180 180 - 180 180 -
60
28.2 28.2 - 28.2 28.2 - 25.2 25.2 - 25.2 25.2 - 198 198 - 198 198 -
60
28.2 28.2 - 36.5 36.5 - 25.2 25.2 - 32.0 32.0 - 198 198 - 239 239 -
60
36.5 36.5 - 36.5 36.5 - 32.0 32.0 - 32.0 32.0 - 239 239 - 239 239 -
60
28.2 28.2 28.2 28.2 28.2 28.2 25.2 25.2 25.2 25.2 25.2 25.2 198 198 198 198 198 198
60
28.2 28.2 28.2 36.5 36.5 36.5 25.2 25.2 25.2 32.0 32.0 32.0 198 198 198 239 239 239
60
36.5 36.5 36.5 36.5 36.5 36.5 32.0 32.0 32.0 32.0 32.0 32.0 239 239 239 239 239 239
OPTIONAL UNIT WITH EXT. OL'S
LOCKED ROTOR AMPS
OMM TGZ-1 TGZ 040A through TGZ 190A 7
Table 2, Wire Sizing Amps, Standard Multi-Point Power Supply
CIRCUIT
CIRCUIT
CIRCUIT
TGZ
UNIT
VOLTS
SIZE
040
050
060
080
100
110
120
150
170
190
NOTES:
1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of the other compressor RLA's.
2. Multiple point power supply requires a separate fused disconnect for each circuit to supply electrical power to the unit.
3. External compressor overload option is only available for units with 140° F maximum leaving condenser water temperature.
4. Wire sizes shown above are for standard ambient temperature and short runs of wire.
FREQ.
(HERTZ)
208 79 79 69 69 3 #4 #4 3 #4 #4
230 79 79 63 63 3 #4 #4 3 #6 #6
460 40 40 32 32 3 #8 #8 3 #10 #10
575
208 108 108 95 95 3 #2 #2 3 #3 #3
230 108 108 86 86 3 #2 #2 3 #3 #3
460 49 49 43 43 3 #8 #8 3 #8 #8
575
208 122 122 122 122 3 #1 #1 3 #1 #1
230 118 118 110 110 3 #1 #1 3 #2 #2
460 58 58 55 55 3 #6 #6 3 #6 #6
575
208 165 165 131 131 3 2/0 2/0 3 1/0 1/0
230 165 165 119 119 3 2/0 2/0 3 #1 #1
460 68 68 59 59 3 #4 #4 3 #6 #6
575
208 165 165 156 156 3 2/0 2/0 3 2/0 2/0
230 165 165 140 140 3 2/0 2/0 3 1/0 1/0
460 79 79 70 70 3 #4 #4 3 #4 #4
575
208 165 211 156 200 3 2/0 4/0 3 2/0 3/0
230 165 211 140 180 3 2/0 4/0 3 1/0 3/0
460 79 102 70 90 3 #4 #2 3 #4 #3
575
208 211 211 200 200 3 4/0 4/0 3 3/0 3/0
230 211 211 180 180 3 4/0 4/0 3 3/0 3/0
460 102 102 90 90 3 #2 #2 3 #3 #3
575
208 238 238 225 225 3 250 250 3 4/0 4/0
230 238 238 203 203 3 250 250 3 4/0 4/0
460 115 115 101 101 3 #2 #2 3 #2 #2
575
208 238 304 225 289 3 250 350 3 4/0 350
230 238 304 203 260 3 250 350 3 4/0 300
460 115 148 101 130 3 #2 1/0 3 #2 #1
575
208 304 304 289 289 3 350 350 3 350 350
230 304 304 260 260 3 350 350 3 300 300
460 148 148 130 130 3 1/0 1/0 3 #1 #1
575
60
60
60
60
60
60
60
60
60
60
MINIMUM CIRCUIT AMPACITY (MCA) POWER SUPPLY
WITHOUT EXTTERNAL
MULTIPLE POINT POWER SUPPLY
CIRCUIT
26 26 25 25 3 #10 #10 3 #10 #10
45 45 34 34 3 #8 #8 3 #10 #10
48 48 44 44 3 #8 #8 3 #8 #8
55 55 48 48 3 #6 #6 3 #8 #8
64 64 57 57 3 #6 #6 3 #6 #6
64 82 57 72 3 #6 #4 3 #6 #4
82 82 72 72 3 #4 #4 3 #4 #4
92 92 82 82 3 #3 #3 3 #4 #4
92 119 82 104 3 #3 #1 3 #4 #2
119 119 104 104 3 #1 #1 3 #2 #2
CIRCUIT
WITH EXTERNAL
CIRCUIT
CIRCUIT
WITHOUT EXTERNAL
FIELD
WIRE
WIRE GAUGE
WITH EXTERNAL
FIELD
WIRE
WIRE GAUGE
CIRCUIT
8 TGZ 040A through TGZ 190A OMM TGZ-1
Table 3, Wire Sizing Amps, Optional Single Point Power Supply
WIRE GAUGE
208 150 131 3 1/0 3 1/0
TGZ
UNIT
SIZE
NOTES:.
1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of the other compressor RLA's.
2. Single point power supply requires a single fused disconnect to supply electrical power to the unit.
3. External compressor overload option is only available for units with 140° F maximum leaving condenser water temperature.
4. Wire Sizes shown above are for standard ambient temperature and short runs of wire.
040
050
060
080
100
110
120
150
170
190
VOLTS
230 150 119 3 1/0 3 #1
460 76 60 3 #4 3 #6
575
208 204 179 3 4/0 3 3/0
230 204 163 3 4/0 3 2/0
460 93 82 3 #3 3 #4
575
208 230 230 3 4/0 3 4/0
230 224 207 3 4/0 3 4/0
460 109 104 3 #2 3 #2
575
208 311 247 3 400 3 250
230 311 224 3 400 3 4/0
460 128 112 3 #1 3 #2
575
208 311 294 3 400 3 350
230 311 265 3 400 3 300
460 150 133 3 1/0 3 1/0
575
208 357 338 6 (2) 3/0 6 (2) 2/0
230 357 305 6 (2) 3/0 3 350
460 173 152 3 2/0 3 2/0
575
208 398 377 6 (2) 3/0 6 (2) 3/0
230 398 340 6 (2) 3/0 6 (2) 2/0
460 193 170 3 3/0 3 2/0
575
208 457 433 6 (2) 4/0 6 (2) 4/0
230 457 390 6 (2) 4/0 6 (2) 3/0
460 221 195 3 4/0 3 3/0
575
208 524 496 6 (2) 300 6 (2) 250
230 524 447 6 (2) 300 6 (2) 4/0
460 254 224 3 250 3 4/0
575
208 585 555 6 (2) 350 6 (2) 300
230 585 500 6 (2) 350 6 (2) 250
460 284 250 3 300 3 250
575
FREQ.
(HERTZ)
60
60
60
60
60
60
60
60
60
60
MINIMUM CIRCUIT AMPACITY (MCA) POWER SUPPLY
SINGLE POINT
POWER SUPPLY )
WITHOUT EXT OL'S
49 48 3 #8 3 #8
85 65 3 #4 3 #6
90 83 3 #3 3 #4
104 90 3 #2 3 #3
120 107 3 #1 3 #2
139 122 3 1/0 3 #1
155 136 3 2/0 3 1/0
176 158 3 3/0 3 2/0
203 180 3 4/0 3 3/0
228 200 3 4/0 3 3/0
SINGLE POINT
POWER SUPPLY
WITH EXT OL'S
WITHOUT EXTERNAL OL'S WITH EXTERNAL OL’S
FIELD WIRE
QUANTITY
WIRE GAUGE
75°°°°C
FIELD WIRE
QUANTITY
75°°°°C
OMM TGZ-1 TGZ 040A through TGZ 190A 9
Table 4, Maximum Fuse Sizing
TGZ
VOLTAGE
UNIT
SIZE
040
050
060
080
100
110
120
150
170
190
NOTE:
1. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA plus 100% of other compressor RLA values.
PHASE
208 175 150 110 110 100 100
230 175 125 110 110 90 90
460 90 70 50 50 45 45
575
208 250 200 150 150 125 125
230 250 200 150 150 110 110
460 110 100 70 70 60 60
575
208 250 250 175 175 175 175
230 250 250 150 150 150 150
460 125 125 80 80 70 70
575
208 350 300 225 225 175 175
230 350 250 225 225 150 150
460 150 125 90 90 80 80
575
208 350 350 225 225 200 200
230 350 300 225 225 200 200
460 175 150 110 110 100 100
575
208 450 400 225 300 200 250
230 450 350 225 300 200 250
460 200 175 110 125 100 125
575
208 450 450 300 300 250 250
230 450 400 300 300 250 250
460 225 200 125 125 125 125
575
208 500 500 300 300 250 250
230 500 450 300 300 250 250
460 250 225 150 150 125 125
575
208 600 500 300 350 250 350
230 600 500 300 350 250 300
460 250 250 150 175 125 150
575
208 600 600 350 350 350 350
230 600 500 350 350 300 300
460 300 250 175 175 150 150
575
FREQ.
(HERTZ)
60
60
60
60
60
60
60
60
60
60
SINGLE POINT POWER SUPPLY MULTIPLE POINT POWER SUPPLY
WITHOUT
EXTERNAL OL'S
TOTAL UNIT
60 50 35 35 35 35
100 70 60 60 45 45
110 100 60 60 60 60
125 110 70 70 60 60
125 125 90 90 80 80
175 150 90 110 80 100
175 150 110 110 100 100
200 175 110 110 100 100
225 200 110 150 100 125
350 225 150 150 125 125
WITH
EXTERNAL OL'S
TOTAL UNIT
WITHOUT EXTERNAL OL'S WITH EXTERNAL OL'S
CIRC.#1 CIRC.#2 CIRC.#1 CIRC.#2
10 TGZ 040A through TGZ 190A OMM TGZ-1
Table 5, Connection Sizes, Single Point Power Supply, Without External Overloads
Power Block Terminal Factory Installed Disconnect Factory Installed HSCCR
TGZ
Unit
Size
040
050
060
080
100
110
120
150
170
190
Volts
208 380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 100 #10 - 1/0 150 #6 - 350 kcmil
575
208 380 #4 - 500 kcmil 250 #6 - 350 kcmil 350 (2) 3/0 - 500 kcmil
230 380 #4 - 500 kcmil 250 #6 - 350 kcmil 350 (2) 3/0 - 500 kcmil
460 175 #14 - 2/0 125 #3 - 3/0 175 #6 - 350 kcmil
575
208 380 #4 - 500 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
230 380 #4 - 500 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
460 175 #14 - 2/0 125 #3 - 3/0 200 #6 - 350 kcmil
575
208 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
230 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
460 175 #14 - 2/0 250 #6 - 350 kcmil 225 #6 - 350 kcmil
575
208 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 600 (2) 3/0 - 500 kcmil
230 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 600 (2) 3/0 - 500 kcmil
460 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575
208 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 600 (2) 3/0 - 500 kcmil
230 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 600 (2) 3/0 - 500 kcmil
460 380 #4 - 500 kcmil 250 #6 - 350 kcmil 300 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 700 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 700 (2) 3/0 - 500 kcmil
460 380 #4 - 500 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 800 (3) 1/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 800 (3) 1/0 - 500 kcmil
460 380 #4 - 500 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 1000 (3) 1/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil 1000 (3) 1/0 - 500 kcmil
460 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 450 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil 1000 (3) 1/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil 1000 (3) 1/0 - 500 kcmil
460 380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 500 (2) 3/0 - 500 kcmil
575
Freq.
(Hertz)
60
60
60
60
60
60
60
60
60
60
NOTES:.
1. "Size" is the maximum amperage rating for the terminals or the main electrical device...
2. "Connection" is the range of wire sizes that the terminals on the electrical device will accept.
Power Block or
Bus Bar Lugs
Size (1)
175 #14 - 2/0 100 #10 - 1/0 90 #10 - 1/0
175 #14 - 2/0 100 #10 - 1/0 150 #6 - 350 kcmil
175 #14 - 2/0 100 #10 - 1/0 150 #6 - 350 kcmil
175 #14 - 2/0 125 #3 - 3/0 175 #6 - 350 kcmil
175 #14 - 2/0 250 #6 - 350 kcmil 200 #6 - 350 kcmil
175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
175 #14 - 2/0 250 #6 - 350 kcmil 300 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 300 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 350 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
Connection (2)
Wire Range - CU
Disconnect Switch
Molded Case
Switch
Size (1)
Connection (2)
Wire Range - CU
Disconnect Switch
(Circuit Breaker )
Circ. Brkr Connection (2)
Size (1) Wire Range - CU
OMM TGZ-1 TGZ 040A through TGZ 190A 11
Table 6, Connection Sizes, Single Point Power Supply with External Overloads
Power Block Terminal Factory Installed Disconnect Factory Installed HSCCR
TGZ
Unit
Size
040
050
060
080
100
110
120
150
170
190
Volts
208 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 100 #3 - 3/0 150 #4 - 350 kcmil
575
208 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575
208 335 #6 - 400 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
230 335 #6 - 400 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
460 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575
208 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
460 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575
208 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
460 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575
208 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 400 (2) 3/0 - 500 kcmil
460 335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575
208 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil
460 335 #6 - 400 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 600 (2) 3/0 - 500 kcmil
460 335 #6 - 400 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil
460 335 #6 - 400 kcmil 400 (2) 3/0 - 500 kcmil
575
208 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil
230 760 (2) #2 - 500 kcmil 800 (3) 1/0 - 500 kcmil
460 335 #6 - 400 kcmil 400 (2) 3/0 - 500 kcmil
575
Freq.
(Hertz)
60
60
60
60
60
60
60
60
60
60
Power Block or
Bus Bar Lugs
Size (1)
175 #14 - 2/0 100 #3 - 3/0 150 #4 - 350 kcmil
175 #14 - 2/0 100 #3 - 3/0 100 #3 - 3/0
175 #14 - 2/0 100 #3 - 3/0 125 #3 - 3/0
335 #6 - 400 kcmil 125 #3 - 3/0 125 #3 - 3/0
335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
335 #6 - 400 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
335 #6 - 400 kcmil 250 #6 - 350 kcmil 400 (2) 3/0 - 500 kcmil
335 #6 - 400 kcmil 400 (2) 3/0 - 500 kcmil
Connection (2)
Wire Range - CU
Disconnect Switch
Molded Case
Switch
Size (1)
Connection (2)
Wire Range - CU
Disconnect Switch
(Circuit Breaker )
Circ. Brkr
Size (1)
400 (2) 3/0 - 500 kcmil
400 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
600 (2) 3/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
400 (2) 3/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
800 (3) 1/0 - 500 kcmil
400 (2) 3/0 - 500 kcmil
400 (2) 3/0 - 500 kcmil
NOTES:
1. "Size" is the maximum amperage rating for the terminals or the main electrical device.
2. "Connection" is the range of wire sizes that the terminals on the electrical device will accept.
Connection (2)
Wire Range - CU
12 TGZ 040A through TGZ 190A OMM TGZ-1
Table 7, Connection Sizes, Multi-Point Power Connection, without External Overloads
Power Terminal Block Factory Installed Disconnect
TGZ
Unit
Volts
Size
040
050
060
080
100
110
120
150
170
190
Power Block or
Bus Bar Lugs
208 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
230 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
230 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
230 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 250 #6 - 350 kcmil
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
Circuit #1 Circuit #2 Circ.#1 Circ.#2
Molded Case
Switch
Size (1)
Size (1)
Connection
Wire Range
(2)
Power Block/
Bus Bar Lugs
Size (1)
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
Connection (2)
Wire Range
Switch
Size (1)
Connection (2)
Wire Range
Connection (2)
Wire Range U
OMM TGZ-1 TGZ 040A through TGZ 190A 13
Table 8, Connection Sizes, Multi-Point Power Connection, with External Overloads
Power Block or
Power Terminal Block Factory Installed Disconnect
TGZ
Unit
Volts
Size
040
050
060
080
100
110
120
150
170
190
Power Block or
Bus Bar Lugs
208 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
230 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
230 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
230 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
230 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 100 #10 - 1/0 100 #10 - 1/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
575 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 125 #3 - 3/0
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575 175 #14 - 2/0 175 #14 - 2/0 125 #3 - 3/0 250 #6 - 350 kcmil
208 380 #4 - 500 kcmil
230 380 #4 - 500 kcmil
460 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
575 175 #14 - 2/0 175 #14 - 2/0 250 #6 - 350 kcmil 250 #6 - 350 kcmil
Circuit #1 Circuit #2 Circ.#1 Circ.#2
Molded Case
Switch
Size
Size
Connection)
Wire Range
Bus Bar Lugs
Size
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 250 #6 - 350 kcmil 250 #6 - 350 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
380 #4 - 500 kcmil 400 (2) 3/0 - 500 kcmil 400 (2) 3/0 - 500 kcmil
Connection
Wire Range
Switch
Size
Connection
Wire Range
Connection
Wire Range -
14 TGZ 040A through TGZ 190A OMM TGZ-1
Field Wiring, Power
The TGZ units are supplied standard with compressor contactors and power terminal block, designed for multi­point power supply to the unit, no compressor circuit breakers. Available options are:
Single-point connection to power block with compressor circuit breakers
Single-point connection to disconnect switch with compressor circuit breakers
High short circuit current rating with single-point disconnect switch
Multi-point connection to disconnect switch, no compressor circuit breakers
A factory installed control circuit transformer is standard. Optionally, a field-installed control power source
can be wired to the unit.
Wiring and conduit selections must comply with the National Electrical Code and/or local requirements.
An open fuse indicates a short, ground, or overload. Before replacing a fuse or restarting a compressor,
the trouble must be found and corrected. Tables in the Electrical Data section (page 4) give specific
information on recommended wire sizes.
Unit power inlet wiring must enter the control box through the right side. A 7/8-inch pilot knockout is provided.
Refer to the unit dimension drawings for the location of power and control connections.
!
CAUTION
To avoid equipment damage, use only copper conductors in main terminal block.
Control Power
A factory mounted control transformer is provided to supply the correct control circuit voltage.
OMM TGZ-1 TGZ 040A through TGZ 190A 15
Field Wiring Diagram
DWG. 330538901 REV.0D (MOD)
WITH MICROTECH CONTROLLER
DISCONNECT
UNIT MAIN
120 VAC
TB1
TB1-20
(BY OTHERS)
2
1
N
120 VAC
GND
10
15
TB2
51
52
42
60
40
53
43
55
49
50
ALARM BELL
ALARM BELL OPTION
BELL
COM
MANUAL
AUTO
MANUAL
IF REMOTE STOP
CONTROL IS USED,
FROM TERM. 40 TO 53.
897
4-20MA FOR
4-20MA FOR
DEMAND LIMIT
GND
33
44
NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL)
41
54
NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL)
N
N
120 VAC
120 VAC
120 VAC
120 VAC
CDW PUMP RELAY (BY OTHERS)
TB1-12
J15-NO8
TB1-12
J16-NO9
J16-NO10
TB3-91
TB3-92
79
80
N
0-10 VDC
77
78
N
0-10 VDC
COOLING TOWER BYPASS
COOLING TOWER BYPASS
TB3
Figure 4, Field Wiring Diagram
(BY OTHERS)
3 PHASE
POWER
SUPPLY
TERMINAL BLOCK
FUSED CONTROL
CIRCUIT TRANSFORMER
OPTION
GND LUG
TO COMPRESSOR(S)
AND FAN MOTORS
FIELD
SUPPLIED
OPTION
120VAC
CONTROL POWER
NOTE: ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1
WIRING SYSTEM WITH CONDUCTOR
RATED 600 VOLTS
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL RELAY
TIME
CLOCK
AUTO
ON
ON
REMOTE STOP
SWITCH
(BY OTHERS)
ICE MODE SWITCH
(BY OTHERS)
ALARM
BELL
OPTION
DISCONNECT
N
FUSE
(BY OTHERS)
CHW PUMP RELAY (BY OTHERS)
120 VAC 1.0 AMP MAX
120 VAC 1.0 AMP MAX
TOWER FAN #1 COIL (BY OTHERS)
120 VAC 1.0 AMP MAX
TOWER FAN #2 COIL (BY OTHERS)
120 VAC 1.0 AMP MAX
OFF
OFF
10A
CONTROLLER
TB3-90
CONTROL
CIRCUIT
FUSE
11
14
REMOVE LEAD 897
1 2
RELAY
NO
CHW FLOW SWITCH
---MANDATORY–­(BY OTHERS)
CDW FLOW SWITCH
---MANDATORY–­(BY OTHERS)
LEAVING WAT ER RESET
(BY OTHERS)
(BY OTHERS)
16 TGZ 040A through TGZ 190A OMM TGZ-1
+
-
+
-
(BY OTHERS)
(BY OTHERS)
FIELD WIRING FOR TGZ
KDL 09-04-08
Figure 5, Control Center Layout
Fuses, Primary
Microtech II
Controller
(2) Circuit
Mechanical
Hi-Pressure Switch
Relays
Switches
On Side
(3) 120V/24V Transformers
LineV/120V Control Transformer
Control Transformer
7/8-in. KO for
control wiring
(4) Compressor
Contactors
Location for
Optional External
Overloads
Control Transformer Fuse, Secondary
Optional Disconnect Switch
KO for Power Wiring
Grounding Lug
OMM TGZ-1 TGZ 040A through TGZ 190A 17
Start-Up and Shutdown
Pre Start-up
1. With main disconnect open, check all electrical connections in control panel and starter to be sure
they are tight and provide good electrical contact. Although connections are tightened at the factory, they can have loosened enough in shipment to cause a malfunction.
2. Check and inspect all water piping. Make sure flow direction is correct and piping is made to
correct connection on evaporator and condenser.
3. Open all water flow valves to the condenser and evaporator.
4. Flush the cooling tower (if one is in the system) and system piping to be sure the system is clean.
Start source water pump and manually start hot water pump. Check all piping for leaks. Vent the air from the evaporator and condenser water circuit as well as from the entire water system. The cooler circuits should contain clean, non-corrosive water.
5. Check to see that the water temperature thermostat sensor is installed in the correct water line.
6. Making sure control stop switch S1 is open (off) and pumpdown switches PS1 and PS2 are on
“manual pumpdown”, move the main power and control disconnect switches to “on.” This will energize crankcase heaters. Wait a minimum of 12 hours before starting up unit.
7. Check compressor oil level. The oil level should be at least one-third of the oil sightglass.
8. Check pressure drop across evaporator and condenser, and see that water flow is correct per the
design flow rates and data on pages 4 through 6.
9. Check the actual line voltage to the unit to make sure it is the same as called for on the compressor
nameplate within + 10% and that phase voltage unbalance does not exceed 2%. Verify that adequate power supply and capacity is available to handle load.
10. Make sure all wiring and fuses are of the proper size. Also make sure all interlock wiring is
completed per McQuay diagrams.
11. Verify that all mechanical and electrical inspections by code authorities have been completed.
12. Make sure all auxiliary load and control equipment is operative and that an adequate cooling load is
available for initial start-up.
Start-up
1. Open the compressor suction and discharge shutoff valves until backseated. Replace valve caps.
2. Open the manual liquid line shutoff valve.
3. Check to see that the unit circuit breakers are in the “off” position.
4. Check to see that the pumpdown switches PS1 and PS2 are in the “manual pumpdown” position and
the control system switch S1 is in the “off” position.
5. Place the main power and control circuit disconnects to the “on” position.
6. Verify crankcase heaters have operated for at least 12 hours prior to start-up. Crankcase should be
warm.
7. Adjust the setpoint on the MicroTech controller to the desired hot water temperature.
8. Start the auxiliary equipment for the installation by turning on the time clock, ambient thermostat
and/or remote on/off switch and chilled water pump.
9. Check resets of all equipment protection controls.
10. Switch the unit circuit breakers to on.
11. Place pumpdown switch(es) PS1 and PS2 to “auto” for restart and normal operation.
12. Start the system by pushing the system switch S1 to on.
13. After running the unit for a short time, check the oil level in each compressor crankcase and check
for flashing in the refrigerant sightglass.
14. After system performance has stabilized, it is necessary that the “Compressorized Equipment
Warranty Form” (Form No. 206036A) be completed to obtain full warranty benefits. Be sure to list the pressure drop across both vessels. This form is shipped with the unit and after completion should be returned to the McQuay Service Department through your sales representative.
18 TGZ 040A through TGZ 190A OMM TGZ-1
Weekend or Temporary Shutdown
Move pumpdown switch(es) PS1 and PS2 to the “manual pumpdown” position.
Note: With the unit in this condition, it is capable of limited pumpdown. To defeat this mode of operation, simply move control system switch S1 to the “off” position.
!
CAUTION
The compressors must complete pump down before the water flow to the unit is interrupted to avoid freeze-up damage in the evaporator.
Start-up after Temporary Shutdown
1. Start the source water and hot water flow through the unit.
2. With the control system switch S1 in the “on” position, move the pumpdown switch(es) PS1
and PS2 to the “auto pumpdown” position.
3. Observe the unit operation for a short time, noting unusual sounds or cycling of compressors.
Extended Shutdown
1. Close the manual liquid line shutoff valves.
2. After the compressors have pumped down, stop or bypass the source water and hot water flow.
3. Turn off all power to the unit.
4. Move the control service switch S1 to the “off” position.
5. Close the suction and discharge shutoff valves on the compressor(s) and the liquid outlet
valves at the condenser(s) or receiver(s).
6. Tag all opened disconnect switches to warn against start-up before opening the compressor
suction and discharge valves.
7. Drain all water from the unit evaporator and chilled water piping if the unit is to be shut down
during the winter and exposed to below freezing temperatures. Do not leave the vessels or piping open to the atmosphere over the shutdown period.
Start-up after Extended Shutdown
1. Inspect all equipment to see that it is in satisfactory operating condition.
2. Backseat the compressor suction and discharge valves. Always replace valve seal caps.
3. Open the manual liquid line shutoff valves.
4. Check circuit breakers. They must be in the “off” position.
5. Check to see that the pumpdown switches PS1 and PS2 are in the “manual shutdown” position
and the control system switch S1 is in the “off” position.
6. Throw the main power and control circuit disconnects to the “on” position.
7. Allow the crankcase heaters to operate for at least 12 hours prior to start-up.
8. Start the source water flow and purge the water piping as well as the evaporator in the unit.
9. Start the auxiliary equipment for the installation by turning on the time clock, ambient
thermostat and/or remote on/off switch.
10. Adjust the setpoint on the MicroTech controller to the desired hot water temperature.
11. Check resets of all equipment protection controls.
12. Switch the unit circuit breakers to “on.”
13. Start the system by pushing the system switch S1 to “on.”
!
CAUTION
Most relays and terminals in the control center are powered when S1 is closed and the control circuit disconnect is on. Do not close S1 until ready for start-up or serious equipment damage can occur.
14. Place pumpdown switch(es) PS1 and PS2 to the “auto pumpdown” position for restart and
normal operation.
15. After running the unit for a short time, check the oil level in each compressor crankcase
and for flashing in the refrigerant sightglass (see Maintenance section).
OMM TGZ-1 TGZ 040A through TGZ 190A 19
Sequence of Operation
The following sequence of operation is typical for TGZ Templifier models when in the heating mode. The sequence can vary slightly depending upon options.
Start-up/Compressor Staging (when compressors start and stop)
Stage Up Temperature (displayed on ‘VIEW UNIT TEMP (3)’ screen) is the Condenser Leaving Water Temperature by which the next compressor to start will stage up (start) after at least one compressor on the unit has started and is running.
Start Up Temperature (displayed on ‘VIEW UNIT TEMP (3)’ screen) is the Condenser Leaving Water Temperature by which the first compressor starts. The start up temperature equals the Stage Up Temperature minus the Start Delta Temperature set point. A higher Start Delta Temperature set point value will keep the unit off longer and reduce unit cycling at low loads. However, this high Start Delta Temperature set point will cause a larger excursion from the Active Heat Leaving Water Temperature set point before the unit starts. Stated another way, the Start Delta Temperature set point is the number of degrees below the Active Heat Leaving Water Temperature set point, minus ½ the Control Band, that determines when the first compressor starts. The Start Delta is in effect for only the first start after all compressors have been off. Additional compressor starts and stops are determined by the Condenser Leaving Water Temperature (LWT) with respect to the Control Band only. The Control Band is automatically set based upon the number of stages (compressors) for the unit. A four (4) compressor unit will have a Control Band that is 30% of the CondDeltaT set point. A six (6) compressor unit will have a Control Band that is 20% of the CondDeltaT set point.
The following sequence would occur for the settings shown below for a four compressor unit:
CondDelta T set point = 10.0°F
StartDelta set point = 5.0°F
StopDelta set point = 2.0°F
Heat LWT set point = 140.0°F
The calculated Control Band will be 30% of 10ºF (Cond Delta T) which is 3ºF.
For a cold start-up (no compressors running), the first compressor will start at any temperature below 133.5°F. Each subsequent compressor will start after the Stage Up Timer has timed out and if the temperature is below the Control Band, 138.5°F in this case.
20 TGZ 040A through TGZ 190A OMM TGZ-1
Figure 1, Staging/Starting Temperatures
Leaving Water Temperature
Set Point
Condenser Delta Temperature
Set Point
140º F
10º F
Stop Delta T
½ Control Band
½ Control Band
Start Delta T
143.5º F
141.5º F
138.5º F
133.5º F
Entering Water Temperature
130º F
If the Condenser Leaving Water Temperature stays below 138.5°F, all three (or five) remaining compressors will eventually stage on after the Stage Up Timer times out between each stage. At some point, the Condenser Leaving Water Temperature will be rising and begin to approach the point when compressors should begin staging off, which is the Active Heat Leaving Water Temperature set point plus ½ of the Control Band, 141.5°F in this case.
If the Condenser Leaving Water Temperature remains above the Active Heat Leaving Water Temperature set point plus ½ Control Band and the Stage Down Timer times out, additional compressors will stage off. The last compressor will stage off when the Condenser Leaving Water Temperature raises above the Active Leaving Water Temperature set point plus ½ the Control Band plus the Stop Delta T. The Stop Delta T is in effect for only the last compressor running.
If the condenser leaving water temperature falls below 141.5°F, all running compressors will remain on. No compressor staging occurs within the Control Band. The next-on compressor will start when the condenser leaving water temperature drops below 138.5°F and the Stage Up Timer times out. In the example shown in Figure 7, the Shutdown Temp (last compressor off) would be 143.5°F.
Manual Compressor Disable Logic
Logic is available that allows the operator to manually enable and disable compressors. When a compressor is disabled, it is considered unavailable to start in the staging logic. This allows a damaged compressor to be taken offline while the remaining compressor can still provide some cooling
The Compressor Disable set points are found on Compressor Set Points screens three and
four.
A running compressor cannot be disabled until it has been shutdown.
If all of the compressors on a circuit are disabled, then the circuit will be disabled.
If both circuits have all of their compressors disabled, the Unit State will remain Off
OMM TGZ-1 TGZ 040A through TGZ 190A 21
Automatic Pumpdown
TGZ units are equipped with single pumpdown control. When the last compressor running on either circuit is ready to shut off, the liquid line solenoid valve (LLSV) is closed first and the compressor continues to run until the pumpdown pressure is reached, at which time the compressor shuts off. The shut off pressure is set at 15 psi below the Low Evaporator pressure Unload setpoint.
When the first compressor on a circuit starts, the LLSV opens simultaneously.
Manual Pumpdown
When the Pumpdown Switch is in the pumpdown position, all compressors except #1 and #2 will shut off. Then the Liquid Line and Hot Gas Bypass Valves will close. The operating compressor will pump out the refrigerant. When the Suction Pressure is at 40 psig, the compressors will stop.
Evaporator and Condenser Water Pumps
Most TGZ Templifier unit applications are not arranged to controll the pumps from the TGZ MicroTech II control system. But if desired, the chiller MicroTech II controller can be programmed to start and stop the system evaporator and condenser water pumps. They may also be controlled by the BAS or manually . Programming directions and the sequence of operation can be found beginning on page 42.
22 TGZ 040A through TGZ 190A OMM TGZ-1
MicroTech II Controller
TGZ Controller Software Version
This manual is based on software version WGZDU0102E. The “02E” is the version descriptor. The version installed in a unit can be viewed by pressing the MENU and ENTER keys simultaneously, then pressing MENU to return to the regular menu screen.
General Description
The MicroTech II controller’s design will not only permit the chiller to run more efficiently but will also simplify troubleshooting if a system failure occurs. Every MicroTech II controller is programmed and tested prior to shipment to assist in a trouble-free start-up.
Operator Friendly
The MicroTech II controller menu structure is separated into three distinct categories, which provide the operator or service technician with a full description of
1) Current unit status
2) Control parameters (setpoints)
3) Alarms.
Security protection prevents unauthorized changing of the setpoints and control parameters
The MicroTech II controller continuously performs self-diagnostic checks, monitoring all system temperatures, pressures and protection devices, and will automatically shutdown a compressor, a refrigerant circuit or the entire unit should a fault occur. The cause of the shutdown and date stamp is retained in memory and can be easily displayed in plain English for operator review, which is an extremely useful feature for troubleshooting. In addition to displaying alarm diagnostics, the MicroTech II chiller controller also provides the operator with a warning of pre-alarm conditions.
Staging
The four scroll (or six) compressors are staged on and off as a function of leaving hot water temperature in the Heating Mode or leaving evaporator water temperature in the Cooling Mode, number of starts and number of run-hours. See Sequence of Operation on page 20.
Equipment Protection
The unit is protected by alarms that shut it down and require manual reset, and also by limit alarms that limit unit operation in response to some out-of-limit condition. Shut down alarms activate an alarm signal that can be wired to a remote device.
Unit Enable Selection
Enables unit operation from local keypad or digital input.
Unit Mode Selection
Selects standard cooling, ice, glycol, or test operation mode.
OMM TGZ-1 TGZ 040A through TGZ 190A 23
Keypad/Display
ALARM
Key to Screen Pathway
Arrow Keys
A 4-line by 20-character/line liquid crystal display and 6-key keypad is mounted on the unit controller. Its layout is shown below.
Figure 6, Keypad and Display in MENU Mode
Air Conditioning
Menu Key
<
VIEW
< <
SET
"Enter" Key
The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.
1. Scroll between data screens as indicated by the arrows (default mode).
2. Select a specific data screen in a hierarchical fashion using dynamic labels on the right
side of the display (this mode is entered by pressing the MENU key).
3. Change field values in edit mode according to the following table: LEFT Default RIGHT Cancel UP Increment DOWN Decrement These four edit functions are indicated by one-character abbreviation on the right side of the display (this mode is entered by pressing the ENTER key).
24 TGZ 040A through TGZ 190A OMM TGZ-1
Inputs and Outputs
The main controller used in the TGZ is either a Carel PCO2 or a PCO3. An expansion module is also be required for additional outputs on some unit configurations. The software is designed for use with R-410a water chillers as well as TGZ Templifier units. The selection of the type of refrigerant (R-134a) is made at the factory and sets certain inputs and outputs.
Large PCO2/PCO3 Controller
Table 9, Analog Inputs
The following parameters are analog inputs to this controller. Type: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
# Description Type Signal Source Range
*1 Evaporator Refrigerant Pressure #1 C1 0.1 to 0.9 VDC
*2 Evaporator Refrigerant Pressure #2 C2 0.1 to 0.9 VDC
*3 Condenser Refrigerant Pressure #1 C1 0.1 to 0.9 VDC
4 Leaving Evaporator Water Temperature UT
5 Condenser Entering Water Temperature UT
*6 Condenser Refrigerant Pressure #2 C2 0.1 to 0.9 VDC
7 Reset of Leaving Water Temperature UT 4-20 mA Current 0-(10 to 80°F)
*8 Condenser Leaving Water Temperature UT
9 Compressor Suction Temperature #1 C1
10 Compressor Suction Temperature #2 C2
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
0 to 132 psi
0 to 132 psi
3.6 to 410 psi
-58 to 212°F
-58 to 212°F
3.6 to 410 psi
-58 to 212°F
-58 to 212°F
-58 to 212°F
Table 10, Analog Outputs
The following parameters are analog outputs from this controller.
# Description Output Signal Range
1 Cooling Tower Bypass Valve Position 0 to 10 VDC 0 to 100% Open
2 Cooling Tower VFD Speed 0 to 10 VDC 0 to 100%
3 Circuit #1 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
4 Circuit #2 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
Table 11, Digital Inputs
The following parameters are digital inputs to this controller. C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, & *n = Refrigerant Dependent
# Description Type Signal Signal
1 Unit OFF Switch UT 0 VAC (Stop) 24 VAC (Auto)
2 Pump Down Switch #1 C1 0 VAC (Stop) 24 VAC (Start)
3 Evaporator Water Flow Switch UT 0 VAC (No Flow) 24 VAC (Flow)
*4 Open
5 Open
6 Pump Down Switch #2 C2 0 VAC (Stop) 24 VAC (Start)
*7 Open
*8 Condenser Water Flow Switch UT 0 VAC (No Flow) 24 VAC (Flow)
Continued on next page.
OMM TGZ-1 TGZ 040A through TGZ 190A 25
Table 11, Digital Inputs, Continued
# Description Type Signal Signal
9 Phase Voltage Fault #1 (See Note 1 Below) C1 0 VAC (Fault) 24 VAC (No Fault)
10 Phase Voltage Fault #2 (See Note 1 Below) C2 0 VAC (Fault) 24 VAC (No Fault)
11 Ground Fault Prot. #1 (See Note 2 Below) C1 0 VAC (Fault) 24 VAC (No Fault)
12 Ground Fault Prot. #2 (See Note 2 Below) C2 0 VAC (Fault) 24 VAC (No Fault)
13 Remote Start/Stop UT 0 VAC (Stop) 24 VAC (Start)
*14 Open
*15 Motor Protection #1 C1 0 VAC (Fault) 24 VAC (No Fault)
*16 Motor Protection #2 C2 0 VAC (Fault) 24 VAC (No Fault)
17 Ice Mode Switch UT 0 VAC (Normal) 24 VAC (Ice)
18 Heat Mode Switch UT 0 VAC (Normal) 24 VAC (Heat)
Notes:
1. See Safety Alarms Table for “Phase Voltage Protection”. Units with single point electrical
connection will have one PVM with Inputs 9 and 10 wired together. Units with multiple point connection will have two PVM’s with Input 9 for Electrical Circuit #1 and Input 10 for Electrical Circuit #2.
2. See Safety Alarms Table for “Ground Fault Protection”. Units with single point electrical
connection will have one GFP with Inputs 11 and 12 wired together. Units with multiple point connection will have two GFP’s with Input 11 for Electrical Circuit #1 and Input 12 for Electrical Circuit #2.
Table 12, Digital Outputs
The following parameters are digital outputs from this controller. C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, & *n = Refrigerant Dependent
# Description Type Load Output OFF Output ON
1 Alarm
2 Evaporator Water Pump UT Pump Contactor Pump OFF Pump ON
Condenser Water Pump – Water
3
Cooled = Y
4 Motor Control Relay #1 = Compr#1 C1 Starter Compressor OFF Compressor ON
5 Motor Control Relay #3 = Compr#3 C1 Starter Compressor OFF Compressor ON
*6 Motor Control Relay #5 = Compr#5 C1 Starter Compressor OFF Compressor ON
7 Liquid Line #1 C1 Solenoid Cooling OFF Cooling ON
8 Tower Fan #1-Water Cooled=Y C2 /UT Fan Contactor Fan OFF Fan ON
9 Motor Control Relay #2 = Compr#2 C2 Starter Compressor OFF Compressor ON
10 Motor Control Relay #4 = Compr#4 C2 Starter Compressor OFF Compressor ON
*11 Motor Control Relay #6 = Compr#6 C2 Starter Compressor OFF Compressor ON
12 Liquid Line #2 C2 Solenoid Cooling OFF Cooling ON
13 Condenser Fan #3 C1 Fan Contactor Fan OFF Fan ON
14 Hot Gas Bypass #1 C1 Solenoid Cooling OFF Cooling ON
15 Hot Gas Bypass #2 C2 Solenoid Cooling OFF Cooling ON
*16 Condenser Fan #4 (R134a) C2 Fan Contactor Fan OFF Fan ON
*17 Condenser Fan #5&7 (R134a) C1 Fan Contactor Fan OFF Fan ON
18 Condenser Fan #8 C2 Fan Contactor Fan OFF Fan ON
18 Condenser Fan #6&8 C2 Fan Contactor Fan OFF Fan ON
C1,C2,
UT
C1 / UT
Alarm Indicator Alarm OFF Alarm ON
Fan Contactor/
Pump Contactor
Fan OFF Fan ON
26 TGZ 040A through TGZ 190A OMM TGZ-1
Loading...
+ 58 hidden pages