McQuay TGZ 040A Installation Manual

Installation Manual
Group: Chiller Part Number: 331975501 Effective: October 2008 Supersedes: New
TGZ 040A to TGZ 190A, Packaged Water Heater 600 to 3100 MBH R134a
50/60 Hz
IM TGZ
TABLE OF CONTENTS
Introduction .........................................2
General Description...............................
Nomenclature.........................................
2 2
Inspection ..............................................2
Installation............................................
Handling ................................................
3
3
Moving the Unit ....................................3
Location.................................................4
Vibration Isolators.................................5
Water Piping........................................7
General ..................................................7
Source Water Piping..............................8
Source/Hot Water Thermostat...............
Flow Switch...........................................
8
9
Glycol Solutions..................................10
Condenser Water Piping......................10
Heating and Cooling Units..................11
Water Pressure Drop............................11
TGZ Scroll...........................................12
Dimensional Data...........................16
Weights............................................24
Physical Data..................................25
TGZ Scroll.......................................25
Unit Components ...........................29
Wiring.............................................31
Electrical Data................................33
Start-Up and Shutdown.................41
Pre Start-up ......................................41
Start-up.............................................41
Extended Shutdown.........................42
Start-up after Extended Shutdown...42
General............................................42
Electrical Terminals.........................43
Operating Limits..............................43
Compressor Oil................................44
Sightglass and Moisture Indicator ...44
Troubleshooting Chart..................45
HAZARD IDENTIFICATION INFORMATION
!
DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
!
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage,
severe personal injury, or death if not avoided.
!
CAUTION
Cautions indicate potentially hazardous situations that can result in personal injury or equipment
damage if not avoided.
Manufactured in an ISO Certified facility
©2008 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make
changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; license granted by Echelon Corporation; Modbus from Schneider Electric; MicroTech II and Open Choices from McQuay International
LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a
1 TGZ 040A through TGZ 190A IM TGZ

Introduction

General Description

McQuay TGZ water heaters are scroll compressor refrigeration units that recover heat from warm fluid streams in the evaporator and deliver hot water, at a useful temperature, from the condenser to a heating load. They are designed for indoor installations only and are completely assembled, wired, charged and tested. Each unit consists of four or six (depending on unit size) scroll compressors, brazed-plate evaporators on models 040 through 120 and shell-and-tube evaporators on models 150 to 190, shell-and-tube condenser/heater, and complete refrigerant piping.
There are two refrigerant circuits, each with manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sightglass/moisture indicators, and thermal expansion valves.
®
The electrical control center includes a MicroTech II dependable automatic operation.

Nomenclature

T G Z 100 A
Templifier
Global
control system and other components necessary for
Vintage
Scroll Compressor
Nominal Evaporator Tons

Inspection

When the equipment is received, all items should be carefully checked against the bill of lading to provide a complete shipment. All units must be carefully inspected for damage upon arrival. All shipping damage must be reported to the carrier and a claim must be filed with the carrier. The unit serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available. Physical damage to unit after acceptance is not the responsibility of McQuay.
Note: Unit shipping and operating weights are given in the Physical Data Tables beginning on page
24.
IM TGZ TGZ 040A through TGZ 190A 2

Installation

TGZ040-190A / WGZ030-200C
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.
!
WARNING
Avoid contact with sharp edges. Personal injury can result.

Handling

Every model TGZ water heater is shipped with a full refrigerant charge that is isolated in the condenser by the manual condenser liquid valve and the compressor discharge service valve.
If the unit has been damaged, allowing the refrigerant to escape, there can be danger of suffocation in the equipment area since the refrigerant will displace the air. Be sure to review Environmental Protection Agency (EPA) requirements if damage has occurred. Avoid exposing an open flame to the refrigerant.

Moving the Unit

Moving the Unit The skid option is strongly recommended for ease of handling and to help prevent damage
if a crane is not available for rigging at site.
Figure 1, Lifting the Unit
RIGGING INSTRUCTIONS
SPREADER BARS MUST
BE USED FOR STABILITY
DURING LIFTING OF
ALL SIZE UNITS
WGZ150-200C UNIT SHOWN
3 TGZ 040A through TGZ 190A IM TGZ
331926901 REV. 0A
It is recommended that all moving and handling be performed with skids under the unit when possible and that the skids not be removed until the unit is in the final location. When moving the unit, dollies or simple rollers can be used under the skids. Never put the weight of the unit against the control box.
In moving, always apply pressure to the base on the skids only and not to the piping or shells. A long bar will help move the unit easily. Avoid dropping the unit at the end of the roll.
If the unit must be hoisted, it is necessary to lift the unit by attaching cables or chains at the lifting holes located on the disposable lifting bars. Spreader bars must be used to protect the control cabinet and other areas of the unit (see
Figure 1)
Do not attach slings to piping or equipment. Move unit in the upright horizontal position at all times. Set unit down gently when lowering from the trucks or rollers.

Location

The unit is designed for indoor application and must be located in an area where the ambient temperature is above 40°F (4°C) minimum.
Because of the electronic control devices, the units should not be exposed to the weather. A plastic cover over the control box is supplied as temporary protection during shipment. A reasonably level and sufficiently strong floor is required for the unit. If necessary, additional structural members should be provided to transfer the weight of the unit to the nearest beams.
Note: Unit shipping and operating weights are available in the Weights section beginning on page
24.

Space Requirements for Connections and Servicing

Allow a minimum of 4-foot clearance in front of the control panel. The source water and hot water piping enters and leaves the unit from the right side when looking at the control panel. Left-hand condenser connections are an option. A clearance of at least 3 feet (1219 mm), or more if codes require, should be provided beyond this piping and on all other sides and ends of the unit for general servicing or for changing the compressors, if it ever becomes necessary.
Clearance should also be provided for cleaning or removal of condenser tubes, and evaporator tubes on models 150 to 190, on one end of the unit. The clearance for cleaning depends on the type of apparatus used, but can be as much as the length of the largest condenser (12 feet, 3660 mm). Tube replacement requires the tube length plus one to two feet of workspace. This space can often be provided through a doorway or other opening.

Placing the Unit

The small amount of vibration normally encountered with the water chiller makes this unit particularly desirable for basement or ground floor installations where the unit can be mounted directly to the floor. The floor construction should be such that the unit will not affect the building structure, or transmit noise and vibration into the structure.
IM TGZ TGZ 040A through TGZ 190A 4

Vibration Isolators

It is recommended that isolators be used on all upper level installations or in areas where vibration transmission is a consideration.
Figure 2, Isolator Locations
4
LB
RB
3
Water Connections
Transfer the unit as indicated under “Moving the Unit.” In all cases, set the unit in place and level with a spirit level. When spring-type isolators are required, install springs running under the main unit supports.
1
LF
FRF
2
The unit should be set initially on shims or blocks at the listed spring free height. When all piping, wiring, flushing,
Control Panel
charging, etc., is completed, the springs are adjusted upward
to loosen the blocks or shims that are then removed. A rubber anti-skid pad should be used under isolators if hold-down bolts are not used. Installation of spring isolators requires flexible piping connections and at least three feet of flexible electrical
conduit to avoid straining the piping and transmitting vibration and noise
.
Table 1, Vibration Mounting Location and Kit Number
TGZ
MODEL
040A
050A
060A
080A
M1
(LEFT-
FRONT)
RP-3
Gray-WR
RP-3
Gray-WR
RP-3
Gray-WR
RP-4
Brown-WR
R-I-S MOUNTING LOCATION SPRING-FLEX MOUNTING LOCATION
M2 (RIGHT­FRONT)
RP-3
Gray-WR
RP-3
Gray-WR
RP-3
Gray-WR
RP-4
Brown-WR
M3
(RIGHT-
REAR)
RP-3
Gray-WR
RP-3
Gray-WR
RP-3
Gray-WR
RP-4
Brown-WR
M4 (LEFT­REAR)
RP-3
Gray-WR
RP-3
Gray-WR
RP-3
Gray-WR
RP-4
Brown-WR
KIT PART
NUMBER
332325701
332325701
332325701
332325702
M1
(LEFT-
FRONT)
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP2E-
ID-1350
Dk. Purple
M2 (RIGHT­FRONT)
CP1E­ID-900
Dk. Green
CP1E­ID-900
Dk. Green
CP1E­ID-900
Dk. Green
CP2E-
ID-1350
Dk. Purple
M3
(RIGHT-
REAR)
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP2E-
ID-1350
Dk. Purple
M4 (LEFT­REAR)
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP1E-
ID-900
Dk. Green
CP2E-
ID-1350
Dk. Purple
KIT PART
NUMBER
332320701
332320701
332320701
332320702
100A
110A
120A
150A
170A
190A
RP-4
Brown-WR
RP-4
Red-WR
RP-4
Red-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Brown-WR
RP-4
Red-WR
RP-4
Red-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Brown-WR
RP-4
Red-WR
RP-4
Red-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Brown-WR
RP-4
Red-WR
RP-4
Red-WR
RP-4
Lime-WR
RP-4
Lime-WR
RP-4
Lime-WR
332325702
332325703
332325703
332325704
332325704
332325704
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-1800
Dk. Green
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
CP2E-
ID-2400
Gray
332320703
332320703
332703703
332320704
332320704
332320704
NOTE: For Spring-flex mountings, CP2E have two springs per isolator housing, CP1E have one spring per housing.
5 TGZ 040A through TGZ 190A IM TGZ
Figure 3, Isolator Dimensions
6
D
S
E
A
Spring Flex Mounting. CP-2 Spring Flex Mounting, CP-1
Rubber-in-Shear Mounting, RP-3
1/2-13 TAP
ø3.38
ø.5
2 HOL
Rubber-in-Shear, RP-4
6.25
5.00
3.75
3.00
R4
ø .500-13NC-2B
LOCA TING PIN TO BE INSTALLED HERE
MOUNTING MOLDED IN DURULENE. WEATHER RESISTANT (WR)
1.75 (R)
.25
4.13
5.50
DRAWING NUMBER 3319880
ALL DIMENSION
2.50
ARE IN DECIMAL INCH
3.87 .56 TYP.
DURULENE
MATERIAL
NOTES:
MOUNT MATERIAL TO BE DURULENE RUBBER.1. MOLDED STEEL AND ELASTOMER MOUNT FOR2.
OUTDOOR SERVICE CONDITIONS.
3. RP-4 MOUNT VERSION WITH STUD IN PLACE.
VM&C
RECESSED GRIP RIBS
VM&C
R4
1.13 ± .25 APPROX.
RAISED GRIP RIBS
DRAWING NUMBER 3314814
LL DIMENSIONS ARE IN DECIMAL INCHES
R.28 TYP.
R.250 TYP.
R.750 TYP.
.38
4.63
1.63
IM TGZ TGZ 040A through TGZ 190A 6

Water Piping

General

Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities. They can supply the installer with the proper building and safety codes required for a safe and proper installation.
Note: Since the Templifier evaporator and/or condenser may have to be valved off for cleaning or repair, it may be essential that a bypass be piped around them so that source and hot water flow is not interrupted.
The piping should be designed with a minimum number of bends and changes in elevation to keep system cost down and performance up. It should contain:
1. All piping should be installed and supported to prevent the unit connections from bearing any strain or
weight of the system piping.
2. Vibration eliminators to reduce vibration and noise transmission to the building.
3. Shutoff valves to isolate the unit from the piping system during unit servicing.
4. Manual or automatic air vent valves at the high points of the system. Drains should be placed at the
lowest points in the system.
5. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulating valve).
6. Temperature and pressure indicators located within 3 feet (0.9 meters) of the inlet and outlet of the
vessels to aid in unit servicing.
7. A strainer or some means of removing foreign matter from the water before it enters the pump is
recommended. It should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). The use of a strainer will prolong pump life and thus keep system performance up.
8. A cleanable strainer must
condenser, 40-mesh on models TGZ 040 to 120 evaporators and 20-mesh on all other vessels. This will aid in preventing foreign material from entering and decreasing the performance of the evaporator and condenser.
9. Any water piping to the unit must be protected to prevent freezing. Consult the ASHRAE handbook for
standard industry practice.
10. If the unit is used in an existing piping system, the system should be thoroughly flushed prior to unit
installation. When job conditions permit, regular water analysis and chemical water treatment on the evaporator and condenser is recommended commencing at equipment start-up.
11. The total quantity of water in the evaporator and condenser systems should be sufficient to prevent
frequent “on-off” cycling. For closed loop applications where the cooling load changes relatively slowly, a minimum system volume of two to three minutes times the flow recommended. For example, if the design chiller flow rate is 120 gpm, we recommend a system
volume of 240 to 360 gallons.
12. In the event glycol is added to the water system, as an afterthought for freeze protection, recognize that
the refrigerant suction pressure will be lower, cooling and heating performance lower, and water side pressure drop will be greater. If the percentage of glycol is large, or if propylene is employed instead of ethylene glycol, the added pressure drop and loss of performance could be substantial. Reset the freezestat and low leaving water alarm temperatures. The freezestat is factory set to default at 36°F (2.2°C). Reset the freezestat setting to approximately 4° to 5°F (2.3° to 2.8°C) below the leaving chilled water setpoint temperature. See the section titled “Glycol Solutions” on page information concerning glycol.
13. A preliminary leak check of the water piping should be made before filling the system.
A flow switch must be installed in the horizontal piping of the evaporator and condenser outlet
also be placed in the water lines just prior to the inlets of the evaporator and
rate (GPM) is
10 for additional
!
CAUTION
piping to prove water flow..
7 TGZ 040A through TGZ 190A IM TGZ

Source Water Piping

r
The system water piping must be flushed thoroughly prior to making connections to the unit evaporator. Lay out the water piping so the source water circulating pump discharges into the evaporator inlet.
!
CAUTION
A cleanable strainer must be placed in the water lines just prior to the inlets of the evaporator and
condenser, 40-mesh on models 040 to 120 evaporators and 20-mesh on all other vessels. Failure
to do so will cause damage to the equipment.
!
CAUTION
Templifier Models TGZ 040 through TGZ 120 must have clean source water from a closed and treated loop going to the brazed-plate evaporator. For open water loop applications, an intermediate heat exchanger between the source water and evaporator is required. Failure to provide a clean, closed water loop can cause equipment failure and possible revocation of the unit warranty.
Templifier evaporator water can come from various sources and care must be exercised to avoid sources that can cause corrosion, fouling, or accumulation of debris in the heat exchanger. Borderline cases will require a careful and rigorously performed maintenance schedule.
Extensive, detailed information on the suitability of source water for brazed-plate exchangers can be found in an Alfa Laval, June 2001 publication titled A Technical Reference for Plate Heat Exchangers in Refrigeration & Air- conditioning Applications
Table 2, Evaporator Characteristics
TGZ UNIT SIZE EVAPORATOR MATERIALS STRAINER CLEANING
040A – 120A Brazed Plate Stainless Steel, Coppe 150A – 190A Shell-and-Tube Carbon Steel, Copper 20-Mesh Chemical
40-Mesh Chemical
Inlet and outlet connections are clearly marked on the unit and also appear on the dimension drawings, beginning on page
16.
Drain connections should be provided at all low points in the system to permit complete drainage. Air vents should be located at the high points in the system to purge out air. A vent connection, located on top of the evaporator vessel, permits the purging of air out of the evaporator. Air purged from the water system prior to unit start-up provides adequate flow through the vessel and prevents safety cutouts on the freeze protection. System pressures can be maintained by using an expansion tank as a combination pressure relief and reducing valve.
Pressure gauges should be installed in the inlet and outlet water lines to the evaporator. Pressure drop through the evaporator should be measured to calculate proper gpm (L/s) as specified in the Physical Data section tables, beginning on page
25. Vibration eliminators are recommended in both the supply and return water lines.
Source water piping may have to be insulated (depending on its temperature) to reduce heat loss and prevent condensation if cold water is used. If cooling tower water is used, insulation is not necessary. Complete unit and system leak tests should be performed prior to insulating the water piping. Insulation with a vapor barrier is recommended. If the vessel is insulated, the vent and drain connections must extend beyond the proposed insulation thickness for accessibility. If the unit operates year-round, or if the system is not drained for the winter, the chilled water piping exposed to outdoor ambient should be protected against freezing by wrapping the lines with a heater cable.

Source/Hot Water Thermostat

The source water temperature sensor is factory installed in the leaving water connection on the evaporator. The controlling hot water sensor is in the leaving condenser connection. A sensor is also located in the entering
IM TGZ TGZ 040A through TGZ 190A 8
water connection in order to measure the condenser Delta-T. Care should be taken not to damage the sensor
V
cable or leadwires when working around the unit. It is also advisable to check the leadwire before running the unit to be sure that it is firmly anchored and not rubbing on the frame or any other component.
If the sensor is ever removed from the well for servicing, care must be taken as not to wipe off the heat conducting compound supplied in the well. The units can be switched from heating to cooling. In the cooling mode they are controlled by a thermostat in the leaving evaporator connection, in the heating mode by the condenser thermostat.

Flow Switch

A water flow switch must be mounted in the evaporator and condenser leaving water lines to prove adequate water flow to the vessels before the unit can start. This will safeguard against slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up.
A flow switch is available from McQuay under ordering number 01750330. It is a “paddle” type switch and adaptable to any pipe size from 1” (25mm) to 6” (152mm) nominal. Certain minimum flow rates are required to close the switch and are listed in Diagram on page
32 for terminal locations. The normally open contacts of the flow switch should be wired between these two terminals. There is also a set of normally closed contacts on the switch that could be used for an indicator light or an alarm to indicate when a “no flow” condition exists.
1. Apply pipe sealing compound to only the threads of the switch and screw unit into D” x D” x 1 (25mm)
reducing tee (see
Figure 4). The flow arrow must be pointed in the correct direction.
2. Provide a straight length of pipe before and after the flow switch of at least five times the pipe diameter.
3. Trim flow switch paddle if needed to fit the pipe diameter. Make sure paddle does not hang up in pipe.
Table 3. Installation should be as shown on page 9. See the Field Wiring
!
CAUTION
Make sure the arrow on the side of the switch is pointed in the direction of flow. Install per manufacturer’s instructions. Incorrect installation will cause improper operation and possible evaporator damage.
Table 3, Flow Switch Minimum Flow Rates
Nominal Pipe Size
Inches (mm)
2 (50.8) 18.8 (1.2)
2 1/2 (63.5) 24.3 (1.5)
3 (76.2) 30.0 (1.9) 4 (101.6) 39.7 (2.5) 5 (127.0) 58.7 (3.7) 6 (152.4) 79.2 (5.0)
Minimum Required Flow to Activate Switch – GPM (l/s)
Figure 4, Flow Switch
iew From End of CoolerFlow Switch
Flow Switch
Paddle
1
(25)
(51)
Pipe Section
D” x 5D”
2
3
(76)
From
Evaporator
Flow Direction
Flow
Straight Pipe for at Least 5D”
Tee D” x D” x 1”
9 TGZ 040A through TGZ 190A IM TGZ

Glycol Solutions

T
The use of glycol in Templifier systems is rare but if used, the system glycol capacity, glycol solution flow rate in gpm (lps), pressure drop through the cooler, and system pressure drop can be calculated using the following formulas and table.
1. Capacity — Capacity is reduced from that with plain water. To find the reduced value multiply the unit’s
water system capacity by the capacity correction factor C, as shown in capacity in the glycol system.
2. GPM —To determine evaporator gpm (or ΔT) knowing ΔT (or gpm) and capacity:
GPMGlycol
24
=
CapacityGlycolx
Δ
FromTablesGx
3. Pressure Drop — To determine glycol pressure drop through the cooler, enter the proper water pressure drop
curve, beginning on page
11, at the water flow. Multiply the water pressure drop found there by P to obtain
corrected glycol pressure drop.
4. To determine glycol system kW, multiply the water system kW by factor K.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service stations) to determine the freezing point. Obtain percent glycol from the freezing point table below.
McQuay encourages a minimum glycol concentration of 25% be provided on all glycol applications. Glycol concentrations below 25% have too little inhibitor content for long-term corrosion protection of ferrous metals.
Note: The effect of glycol in the condenser is negligible and there is no capacity derate. There is a significant increase in pressure drop.
Table 4 and Table 5, to find the unit’s
Table 4, Ethylene Glycol
Glycol
20 18 -8 0.982 0.992 1.040 1.129 30 7 -14 0.972 0.986 1.074 1.181 40 -7 -22 0.961 0.976 1.121 1.263 50 -28 -33 0.946 0.966 1.178 1.308
Freezing Point Percent
°F °C
C (Capacity) K (Power) G (Flow)
P (Pressure
Drop)
Table 5, Propylene Glycol
Percent
Glycol
20 19 -7 0.975 0.985 1.028 1.147 30 9 -13 0.962 0.978 1.050 1.248 40 -5 -21 0.946 0.971 1.078 1.366 50 -27 -33 0.929 0.965 1.116 1.481
Freezing Point C (Capacity) K (Power) G (Flow)
°F °C
P (Pressure
Drop)
!
CAUTION
Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors which all cause plating on the copper within the unit evaporator. The type and handling of glycol used must be consistent with local codes.

Condenser Water Piping

Arrange the condenser water so the water enters the bottom connection of the condenser. The condenser water will discharge the condenser from the top connection. Failing to arrange the condenser water as stated above will negatively affect the capacity and efficiency. Note that the condensers are shipped as either two-pass (10 to 20­degree Delta-T) or four-pass (20 to 40-degree Delta-T). For 2-pass, the connections are on the vertical centerline of the condenser. For 4-pass, they are off to one side.
Pressure gauges should be installed in the inlet and outlet water lines to the condenser. Pressure drop through the condenser should be measured to determine gpm (L/s) from pressure drop curves on page eliminators are recommended in both the supply and return water lines.
11. Vibration
IM TGZ TGZ 040A through TGZ 190A 10
Templifier hot water systems usually have a supplementary heater located after (downstream) of the Templifier condenser to either boost the hot water temperature or to function as a standby heater.
Care should be exercised to avoid overly warm water coming back to the Templifier from the system and causing a relief valve discharge. This is true whether the unit is running or off. Maximum temperature is 165°F
Some jurisdictions require double heat exchange walls between refrigerant and potable water. Potable water run directly through a condenser has only one heat exchange wall (the condenser tube) and these jurisdictions may require an intermediate heat exchanger.

Heating and Cooling Units

Templifiers can be arranged and controlled to act as either a water chiller or a water heater. These systems vary considerably in the specifics of the piping arrangement. Care must be exercised when changeover occurs to avoid mixing water streams that could possibly contaminate a water system. For example a unit can have chilled water in the evaporator and tower water in the condenser when in the cooling mode. Changeover to heating could put tower water through the evaporator and hot water (possibly potable water) through the condenser. This could introduce tower water into the chilled water system and into the hot water system and should be avoided.

Water Pressure Drop

The vessel flow rates must fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves on pages laminar flow that will reduce efficiency, cause erratic operation of the expansion valve and could cause low temperature cutoffs. On the other hand, flow rates exceeding the maximum values shown can cause erosion on the evaporator water connections and tubes.
Measure the water pressure drop through the vessels at field installed pressure taps. It is important not to include valves or strainers in these readings.
The condenser flow rate will determine whether 2-pass or 4-pass condensers are used, according to the following table:
12 to 14. Flow rates below the minimum values shown will result in
CONDENSER DELTA-T PASSES FLOW
10- to 20 Degrees F 2-Pass High Flow Rate
20 to 40 Degrees F 4-Pass Low Flow Rate
The entering water should be piped to the bottom connection of the condenser and out the top.
11 TGZ 040A through TGZ 190A IM TGZ

TGZ Scroll

Figure 5, Evaporator Pressure Drop
TGZ Evaporator Wat er Pressur e Dr op
100
10
Dp (ft)
TGZ040 TGZ050 TGZ060 TGZ080 TGZ100 TGZ110 TGZ120 TGZ150 TGZ170 TGZ190
TGZ040
TGZ060
TGZ110
TGZ100
TGZ170
TGZ190
TGZ120
TGZ150
TGZ080
TGZ050
1
10 100 1000
Flow Rate (gpm)
TGZ UNIT
MODEL
040A 050A 060A 080A 100A 110A 120A 150A 170A 190A
Note: Nominal Flow Rate is gpm for 10 F Delta-T at unit operating conditions of evaporator at 75/65 F water temp and condenser at 110/30 F water temp.
EVAPORATOR
MODEL
AC250-70DQ 34 1.1 2.1 3.2 72 4.4 4.5 13.2 120 11.6 7.6 34.7 AC250-94DQ 45 1.0 2.8 3.1 100 4.7 6.3 14.0 167 12.5 10.5 37.2
AC250-94DQ 55 1.5 3.5 4.5 121 6.7 7.6 20.0 202 17.7 12.7 53.0 AC350-162DQ 83 1.4 5.2 4.3 162 5.1 10.2 15.2 270 13.5 17.0 40.2 AC350-162DQ 98 2.0 6.2 5.8 189 6.8 11.9 20.3 315 17.9 19.9 53.6 AC350-182DQ 113 2.2 7.1 6.4 218 7.5 13.8 22.4 363 19.8 22.9 59.1 AC350-182DQ 128 2.7 8.1 8.2 246 9.5 15.5 28.4 410 25.1 25.9 74.9
EV34191111/9 147 2.4 9.3 7.3 283 8.5 17.9 25.4 472 22.5 29.8 67.1 EV34191212/7 169 3.5 10.7 10.5 326 12.2 20.6 36.5 543 32.2 34.3 96.1 EV34191212/7 192 4.5 12.1 13.4 369 15.5 23.3 46.3 615 40.9 38.8 122.3
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
INCH-POUND S.I. INCH-POUND S.I. INCH-POUND S.I.
gpm ft. L/S kpa gpm ft. lps kpa gpm ft. lps kpa
IM TGZ TGZ 040A through TGZ 190A 12
Figure 6, Standard Four-pass Condenser Pressure Drop
TGZ 4-Pa ss Conde nse r Wa t er Pressur e Dr op
100
TGZ040 TGZ050 TGZ060 TGZ080 TGZ100 TGZ110 TGZ120 TGZ150
TGZ060
TGZ170 TGZ190
10
Dp (ft)
TGZ170
TGZ150
TGZ100
TGZ190
TGZ120
TGZ050
TGZ040
TGZ080
TGZ110
1
10 100 1000
Flow Rate (gpm)
UNIT
MODEL
TGZ040 TGZ050 TGZ060 TGZ080 TGZ100 TGZ110 TGZ120 TGZ150 TGZ170 TGZ190
COND.
MODEL
C1010-62 23 1.93 1.45 5.77 47 7.5 3.0 22.4 63 13.1 4.0 39.1 C1010-62 32 2.44 2.02 7.29 64 9.1 4.0 27.2 86 16.0 5.4 47.7
C1010-76 38 3.40 2.40 10.16 77 13.0 4.9 38.9 103 22.6 6.5 67.5 C1410-112 51 2.84 3.22 8.49 103 10.8 6.5 32.3 138 18.8 8.7 56.3 C1410-128 60 3.00 3.79 8.97 120 11.2 7.6 33.5 160 19.3 10.1 57.8 C1610-164 69 2.44 4.35 7.29 138 9.1 8.7 27.2 184 15.7 11.6 47.0 C1610-164 78 3.08 4.92 9.21 156 11.5 9.8 34.4 208 19.9 13.1 59.4 C1612-164 90 4.85 5.68 14.50 180 18.1 11.4 54.1 240 31.3 15.1 93.4 C1612-184 103 4.89 6.50 14.60 207 18.4 13.1 55.0 276 31.8 17.4 95.0 C1612-184 117 6.24 7.38 18.66 234 23.3 14.8 69.6 312 40.2 19.7 120.3
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
INCH-POUND S.I. INCH-POUND S.I. INCH-POUND S.I.
gpm ft L/S kpa gpm ft L/S kpa gpm ft L/S kpa
13 TGZ 040A through TGZ 190A IM TGZ
Figure 7, Optional Two-pass Condenser
TGZ 2- Pass Condenser Water Pressur e Drop
100
TGZ040 TGZ050 TGZ060 TGZ080 TGZ100 TGZ110 TGZ120 TGZ150 TGZ170 TGZ190
10
Dp (ft)
TGZ060
TGZ190
TGZ150
TGZ100
TGZ170
TGZ080
TGZ050
TGZ040
TGZ120
TGZ110
1
10 100 1000
Flow Rate (gpm)
MINIMUM FLOW RATE NOMINAL FLOW RATE MAXIMUM FLOW RATE
TGZ UNIT
MODEL
TGZ040 TGZ050 TGZ060 TGZ080 TGZ100 TGZ110 TGZ120 TGZ150 TGZ170 TGZ190
COND.
MODEL.
C1010-62 59 1.6 3.7 4.9 94 4.0 5.9 12.0 150 9.8 9.5 29.3 C1010-62 80 2.0 5.0 6.0 128 4.9 8.1 14.6 205 12.0 12.9 35.8
C1010-76 96 2.9 6.1 8.5 154 7.0 9.7 20.9 246 17.0 15.5 51.0 C1410-112 129 2.4 8.1 7.1 206 5.8 13.0 17.3 330 14.2 20.8 42.3 C1410-128 150 2.5 9.5 7.3 240 6.0 15.1 17.9 384 14.7 24.2 43.8 C1610-164 173 2.0 10.9 6.0 276 4.9 17.4 14.6 442 12.0 27.9 35.8 C1610-164 195 2.5 12.3 7.6 312 6.2 19.7 18.5 499 15.1 31.5 45.3 C1612-164 225 3.3 14.2 9.9 360 8.1 22.7 24.2 576 19.8 36.3 59.1 C1612-184 259 3.5 16.3 10.4 414 8.5 26.1 25.4 662 20.8 41.8 62.1 C1612-184 293 4.4 18.5 13.2 468 10.8 29.5 32.3 749 26.4 47.2 78.8
INCH-POUND S.I.
gpm ft L/S kpa gpm ft L/S kpa gpm ft lps kpa
INCH-
POUND
S.I. INCH-POUND S.I.
IM TGZ TGZ 040A through TGZ 190A 14
Loading...
+ 34 hidden pages