the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered
trademarks of their respective companies: BACnet from ASHRAE; LONM
managed, granted and used by LONM
Corporation; Modbus from Schneider Electric; MicroTech II and Open Choices from McQuay International
Manufactured in an ISO Certified facility
ARK
ARK
International under a license granted by Echelon Corporation; Compliant Scroll from Copeland
, LonTalk, LONW
ORKS
, and the LONM
ARK
logo are
2 TGZ 040A through TGZ 190A OMM TGZ-1
Introduction
General Description
McQuay Type TGZ water heaters are scroll compressor refrigeration units that recover heat from warm
fluid streams in the evaporator and deliver hot water, at a useful temperature, from the condenser to a
heating load. They are designed for indoor installations only and are completely assembled, wired,
charged and tested. Each unit consists of four or six (depending on unit size) scroll compressors,
brazed-plate evaporators on models 040 to 120 and shell-and-tube evaporators on models 150 to 190,
shell-and-tube condenser/heater, and complete refrigerant piping.
There are two refrigerant circuits, each with manual liquid line shutoff valves, charging valves, filterdriers, liquid line solenoid valves, sightglass/moisture indicators, and expansion valves (thermal on
TGZ 040-120, electronic on TGZ 150-190.
The electrical control center includes a MicroTech II control system and other components necessary
for dependable automatic operation.
NOTE: Additional information not included in this manual, such as unit dimensions and weights,
physical data, and performance data can be found in Catalog Templifier-1.
Nomenclature
T G Z 100 A
Templifier
Vintage
Global
Scroll Compressor
Nominal Evaporator
Capacity in Tons
Water Pressure Drop
The vessel flow rates must fall between the minimum and maximum values shown on the appropriate
evaporator and condenser curves on pages 4 through 6. Flow rates below the minimum values shown will
result in laminar flow that will reduce efficiency, cause erratic operation of the expansion valve and could
cause low temperature cutoffs. On the other hand, flow rates exceeding the maximum values shown can cause
erosion on the evaporator water connections and tubes.
Measure the water pressure drop through the vessels at field installed pressure taps. It is important not to
include valves or strainers in these readings.
The condenser flow rate will determine whether 2-pass or 4-pass condensers are used, according to the
following table:
CONDENSER DELTA-T PASSES FLOW
10- to 20 Degrees F 2-Pass High Flow Rate
20 to 40 Degrees F 4-Pass Low Flow Rate
The entering water should be piped to the bottom connection of the condenser and out the top.
1. External overloads only available on Templifier units with 140°F maximum condenser leaving water temperature.
2. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including control
transformer.
3. Single point power supply requires a single fused disconnect to supply electrical power to the unit.
4. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.
The TGZ units are supplied standard with compressor contactors and power terminal block, designed for multipoint power supply to the unit, no compressor circuit breakers. Available options are:
• Single-point connection to power block with compressor circuit breakers
• Single-point connection to disconnect switch with compressor circuit breakers
• High short circuit current rating with single-point disconnect switch
• Multi-point connection to disconnect switch, no compressor circuit breakers
A factory installed control circuit transformer is standard. Optionally, a field-installed control power source
can be wired to the unit.
Wiring and conduit selections must comply with the National Electrical Code and/or local requirements.
An open fuse indicates a short, ground, or overload. Before replacing a fuse or restarting a compressor,
the trouble must be found and corrected. Tables in the Electrical Data section (page 4) give specific
information on recommended wire sizes.
Unit power inlet wiring must enter the control box through the right side. A 7/8-inch pilot knockout is provided.
Refer to the unit dimension drawings for the location of power and control connections.
!
CAUTION
To avoid equipment damage, use only copper conductors in main terminal block.
Control Power
A factory mounted control transformer is provided to supply the correct control circuit voltage.
OMM TGZ-1 TGZ 040A through TGZ 190A 15
Field Wiring Diagram
DWG. 330538901 REV.0D (MOD)
WITH MICROTECH CONTROLLER
DISCONNECT
UNIT MAIN
120 VAC
TB1
TB1-20
(BY OTHERS)
2
1
N
120 VAC
GND
10
15
TB2
51
52
42
60
40
53
43
55
49
50
ALARM BELL
ALARM BELL OPTION
BELL
COM
MANUAL
AUTO
MANUAL
IF REMOTE STOP
CONTROL IS USED,
FROM TERM. 40 TO 53.
897
4-20MA FOR
4-20MA FOR
DEMAND LIMIT
GND
33
44
NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL)
41
54
NOR. OPEN PUMP AUX. CONTACTS (OPTIONAL)
N
N
120 VAC
120 VAC
120 VAC
120 VAC
CDW PUMP RELAY (BY OTHERS)
TB1-12
J15-NO8
TB1-12
J16-NO9
J16-NO10
TB3-91
TB3-92
79
80
N
0-10 VDC
77
78
N
0-10 VDC
COOLING TOWER BYPASS
COOLING TOWER BYPASS
TB3
Figure 4, Field Wiring Diagram
(BY OTHERS)
3 PHASE
POWER
SUPPLY
TERMINAL BLOCK
FUSED CONTROL
CIRCUIT TRANSFORMER
OPTION
GND LUG
TO COMPRESSOR(S)
AND FAN MOTORS
FIELD
SUPPLIED
OPTION
120VAC
CONTROL POWER
NOTE: ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1
WIRING SYSTEM WITH CONDUCTOR
RATED 600 VOLTS
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL RELAY
TIME
CLOCK
AUTO
ON
ON
REMOTE STOP
SWITCH
(BY OTHERS)
ICE MODE SWITCH
(BY OTHERS)
ALARM
BELL
OPTION
DISCONNECT
N
FUSE
(BY OTHERS)
CHW PUMP RELAY (BY OTHERS)
120 VAC 1.0 AMP MAX
120 VAC 1.0 AMP MAX
TOWER FAN #1 COIL (BY OTHERS)
120 VAC 1.0 AMP MAX
TOWER FAN #2 COIL (BY OTHERS)
120 VAC 1.0 AMP MAX
OFF
OFF
10A
CONTROLLER
TB3-90
CONTROL
CIRCUIT
FUSE
11
14
REMOVE LEAD 897
12
RELAY
NO
CHW FLOW SWITCH
---MANDATORY–(BY OTHERS)
CDW FLOW SWITCH
---MANDATORY–(BY OTHERS)
LEAVING WAT ER RESET
(BY OTHERS)
(BY OTHERS)
16TGZ 040A through TGZ 190A OMM TGZ-1
+
-
+
-
(BY OTHERS)
(BY OTHERS)
FIELD WIRING FOR TGZ
KDL 09-04-08
Figure 5, Control Center Layout
Fuses, Primary
Microtech II
Controller
(2) Circuit
Mechanical
Hi-Pressure Switch
Relays
Switches
On Side
(3) 120V/24V
Transformers
LineV/120V
Control
Transformer
Control
Transformer
7/8-in. KO for
control wiring
(4) Compressor
Contactors
Location for
Optional External
Overloads
Control
Transformer
Fuse, Secondary
Optional Disconnect
Switch
KO for Power
Wiring
Grounding Lug
OMM TGZ-1 TGZ 040A through TGZ 190A 17
Start-Up and Shutdown
Pre Start-up
1. With main disconnect open, check all electrical connections in control panel and starter to be sure
they are tight and provide good electrical contact. Although connections are tightened at the factory,
they can have loosened enough in shipment to cause a malfunction.
2. Check and inspect all water piping. Make sure flow direction is correct and piping is made to
correct connection on evaporator and condenser.
3. Open all water flow valves to the condenser and evaporator.
4. Flush the cooling tower (if one is in the system) and system piping to be sure the system is clean.
Start source water pump and manually start hot water pump. Check all piping for leaks. Vent the air
from the evaporator and condenser water circuit as well as from the entire water system. The cooler
circuits should contain clean, non-corrosive water.
5. Check to see that the water temperature thermostat sensor is installed in the correct water line.
6. Making sure control stop switch S1 is open (off) and pumpdown switches PS1 and PS2 are on
“manual pumpdown”, move the main power and control disconnect switches to “on.” This will
energize crankcase heaters. Wait a minimum of 12 hours before starting up unit.
7. Check compressor oil level. The oil level should be at least one-third of the oil sightglass.
8. Check pressure drop across evaporator and condenser, and see that water flow is correct per the
design flow rates and data on pages 4 through 6.
9. Check the actual line voltage to the unit to make sure it is the same as called for on the compressor
nameplate within + 10% and that phase voltage unbalance does not exceed 2%. Verify that adequate
power supply and capacity is available to handle load.
10. Make sure all wiring and fuses are of the proper size. Also make sure all interlock wiring is
completed per McQuay diagrams.
11. Verify that all mechanical and electrical inspections by code authorities have been completed.
12. Make sure all auxiliary load and control equipment is operative and that an adequate cooling load is
available for initial start-up.
Start-up
1. Open the compressor suction and discharge shutoff valves until backseated. Replace valve caps.
2. Open the manual liquid line shutoff valve.
3. Check to see that the unit circuit breakers are in the “off” position.
4. Check to see that the pumpdown switches PS1 and PS2 are in the “manual pumpdown” position and
the control system switch S1 is in the “off” position.
5. Place the main power and control circuit disconnects to the “on” position.
6. Verify crankcase heaters have operated for at least 12 hours prior to start-up. Crankcase should be
warm.
7. Adjust the setpoint on the MicroTech controller to the desired hot water temperature.
8. Start the auxiliary equipment for the installation by turning on the time clock, ambient thermostat
and/or remote on/off switch and chilled water pump.
9. Check resets of all equipment protection controls.
10. Switch the unit circuit breakers to on.
11. Place pumpdown switch(es) PS1 and PS2 to “auto” for restart and normal operation.
12. Start the system by pushing the system switch S1 to on.
13. After running the unit for a short time, check the oil level in each compressor crankcase and check
for flashing in the refrigerant sightglass.
14. After system performance has stabilized, it is necessary that the “Compressorized Equipment
Warranty Form” (Form No. 206036A) be completed to obtain full warranty benefits. Be sure to list
the pressure drop across both vessels. This form is shipped with the unit and after completion
should be returned to the McQuay Service Department through your sales representative.
18 TGZ 040A through TGZ 190A OMM TGZ-1
Weekend or Temporary Shutdown
Move pumpdown switch(es) PS1 and PS2 to the “manual pumpdown” position.
Note: With the unit in this condition, it is capable of limited pumpdown. To defeat this mode of
operation, simply move control system switch S1 to the “off” position.
!
CAUTION
The compressors must complete pump down before the water flow to the unit is interrupted to
avoid freeze-up damage in the evaporator.
Start-up after Temporary Shutdown
1. Start the source water and hot water flow through the unit.
2. With the control system switch S1 in the “on” position, move the pumpdown switch(es) PS1
and PS2 to the “auto pumpdown” position.
3. Observe the unit operation for a short time, noting unusual sounds or cycling of compressors.
Extended Shutdown
1. Close the manual liquid line shutoff valves.
2. After the compressors have pumped down, stop or bypass the source water and hot water flow.
3. Turn off all power to the unit.
4. Move the control service switch S1 to the “off” position.
5. Close the suction and discharge shutoff valves on the compressor(s) and the liquid outlet
valves at the condenser(s) or receiver(s).
6. Tag all opened disconnect switches to warn against start-up before opening the compressor
suction and discharge valves.
7. Drain all water from the unit evaporator and chilled water piping if the unit is to be shut down
during the winter and exposed to below freezing temperatures. Do not leave the vessels or
piping open to the atmosphere over the shutdown period.
Start-up after Extended Shutdown
1. Inspect all equipment to see that it is in satisfactory operating condition.
2. Backseat the compressor suction and discharge valves. Always replace valve seal caps.
3. Open the manual liquid line shutoff valves.
4. Check circuit breakers. They must be in the “off” position.
5. Check to see that the pumpdown switches PS1 and PS2 are in the “manual shutdown” position
and the control system switch S1 is in the “off” position.
6. Throw the main power and control circuit disconnects to the “on” position.
7. Allow the crankcase heaters to operate for at least 12 hours prior to start-up.
8. Start the source water flow and purge the water piping as well as the evaporator in the unit.
9. Start the auxiliary equipment for the installation by turning on the time clock, ambient
thermostat and/or remote on/off switch.
10. Adjust the setpoint on the MicroTech controller to the desired hot water temperature.
11. Check resets of all equipment protection controls.
12. Switch the unit circuit breakers to “on.”
13. Start the system by pushing the system switch S1 to “on.”
!
CAUTION
Most relays and terminals in the control center are powered when S1 is closed and the
control circuit disconnect is on. Do not close S1 until ready for start-up or serious
equipment damage can occur.
14. Place pumpdown switch(es) PS1 and PS2 to the “auto pumpdown” position for restart and
normal operation.
15. After running the unit for a short time, check the oil level in each compressor crankcase
and for flashing in the refrigerant sightglass (see Maintenance section).
OMM TGZ-1 TGZ 040A through TGZ 190A 19
Sequence of Operation
The following sequence of operation is typical for TGZ Templifier models when in the
heating mode. The sequence can vary slightly depending upon options.
Start-up/Compressor Staging (when compressors start and stop)
Stage Up Temperature (displayed on ‘VIEW UNIT TEMP (3)’ screen) is the Condenser
Leaving Water Temperature by which the next compressor to start will stage up (start) after at
least one compressor on the unit has started and is running.
Start Up Temperature (displayed on ‘VIEW UNIT TEMP (3)’ screen) is the Condenser
Leaving Water Temperature by which the first compressor starts. The start up temperature
equals the Stage Up Temperature minus the Start Delta Temperature set point. A higher Start
Delta Temperature set point value will keep the unit off longer and reduce unit cycling at low
loads. However, this high Start Delta Temperature set point will cause a larger excursion from
the Active Heat Leaving Water Temperature set point before the unit starts. Stated another
way, the Start Delta Temperature set point is the number of degrees below the Active Heat
Leaving Water Temperature set point, minus ½ the Control Band, that determines when the
first compressor starts. The Start Delta is in effect for only the first start after all compressors
have been off. Additional compressor starts and stops are determined by the Condenser
Leaving Water Temperature (LWT) with respect to the Control Band only. The Control Band
is automatically set based upon the number of stages (compressors) for the unit. A four (4)
compressor unit will have a Control Band that is 30% of the CondDeltaT set point. A six (6)
compressor unit will have a Control Band that is 20% of the CondDeltaT set point.
The following sequence would occur for the settings shown below for a four compressor unit:
CondDelta T set point = 10.0°F
StartDelta set point = 5.0°F
StopDelta set point = 2.0°F
Heat LWT set point = 140.0°F
The calculated Control Band will be 30% of 10ºF (Cond Delta T) which is 3ºF.
For a cold start-up (no compressors running), the first compressor will start at any temperature
below 133.5°F. Each subsequent compressor will start after the Stage Up Timer has timed out and if
the temperature is below the Control Band, 138.5°F in this case.
20 TGZ 040A through TGZ 190A OMM TGZ-1
Figure 1, Staging/Starting Temperatures
Leaving Water Temperature
Set Point
Condenser Delta Temperature
Set Point
140º F
10º F
Stop Delta T
½ Control Band
½ Control Band
Start Delta T
143.5º F
141.5º F
138.5º F
133.5º F
Entering Water Temperature
130º F
If the Condenser Leaving Water Temperature stays below 138.5°F, all three (or five)
remaining compressors will eventually stage on after the Stage Up Timer times out between
each stage. At some point, the Condenser Leaving Water Temperature will be rising and begin
to approach the point when compressors should begin staging off, which is the Active Heat
Leaving Water Temperature set point plus ½ of the Control Band, 141.5°F in this case.
If the Condenser Leaving Water Temperature remains above the Active Heat Leaving Water
Temperature set point plus ½ Control Band and the Stage Down Timer times out, additional
compressors will stage off. The last compressor will stage off when the Condenser Leaving
Water Temperature raises above the Active Leaving Water Temperature set point plus ½ the
Control Band plus the Stop Delta T. The Stop Delta T is in effect for only the last compressor
running.
If the condenser leaving water temperature falls below 141.5°F, all running compressors will
remain on. No compressor staging occurs within the Control Band. The next-on compressor
will start when the condenser leaving water temperature drops below 138.5°F and the Stage
Up Timer times out. In the example shown in Figure 7, the Shutdown Temp (last compressor
off) would be 143.5°F.
Manual Compressor Disable Logic
Logic is available that allows the operator to manually enable and disable compressors. When a
compressor is disabled, it is considered unavailable to start in the staging logic. This allows a
damaged compressor to be taken offline while the remaining compressor can still provide some
cooling
•The Compressor Disable set points are found on Compressor Set Points screens three and
four.
• A running compressor cannot be disabled until it has been shutdown.
• If all of the compressors on a circuit are disabled, then the circuit will be disabled.
• If both circuits have all of their compressors disabled, the Unit State will remain Off
OMM TGZ-1 TGZ 040A through TGZ 190A 21
Automatic Pumpdown
TGZ units are equipped with single pumpdown control. When the last compressor running
on either circuit is ready to shut off, the liquid line solenoid valve (LLSV) is closed first
and the compressor continues to run until the pumpdown pressure is reached, at which time
the compressor shuts off. The shut off pressure is set at 15 psi below the Low Evaporator
pressure Unload setpoint.
When the first compressor on a circuit starts, the LLSV opens simultaneously.
Manual Pumpdown
When the Pumpdown Switch is in the pumpdown position, all compressors except #1 and
#2 will shut off. Then the Liquid Line and Hot Gas Bypass Valves will close. The
operating compressor will pump out the refrigerant. When the Suction Pressure is at 40
psig, the compressors will stop.
Evaporator and Condenser Water Pumps
Most TGZ Templifier unit applications are not arranged to controll the pumps from the
TGZ MicroTech II control system. But if desired, the chiller MicroTech II controller can be
programmed to start and stop the system evaporator and condenser water pumps. They may
also be controlled by the BAS or manually . Programming directions and the sequence of
operation can be found beginning on page 42.
22 TGZ 040A through TGZ 190A OMM TGZ-1
MicroTech II Controller
TGZ Controller Software Version
This manual is based on software version WGZDU0102E. The “02E” is the version
descriptor. The version installed in a unit can be viewed by pressing the MENU and
ENTER keys simultaneously, then pressing MENU to return to the regular menu screen.
General Description
The MicroTech II controller’s design will not only permit the chiller to run more efficiently
but will also simplify troubleshooting if a system failure occurs. Every MicroTech II
controller is programmed and tested prior to shipment to assist in a trouble-free start-up.
Operator Friendly
The MicroTech II controller menu structure is separated into three distinct categories,
which provide the operator or service technician with a full description of
1) Current unit status
2) Control parameters (setpoints)
3) Alarms.
Security protection prevents unauthorized changing of the setpoints and control parameters
The MicroTech II controller continuously performs self-diagnostic checks, monitoring all
system temperatures, pressures and protection devices, and will automatically shutdown a
compressor, a refrigerant circuit or the entire unit should a fault occur. The cause of the
shutdown and date stamp is retained in memory and can be easily displayed in plain
English for operator review, which is an extremely useful feature for troubleshooting. In
addition to displaying alarm diagnostics, the MicroTech II chiller controller also provides
the operator with a warning of pre-alarm conditions.
Staging
The four scroll (or six) compressors are staged on and off as a function of leaving hot water
temperature in the Heating Mode or leaving evaporator water temperature in the Cooling
Mode, number of starts and number of run-hours. See Sequence of Operation on page 20.
Equipment Protection
The unit is protected by alarms that shut it down and require manual reset, and also by limit
alarms that limit unit operation in response to some out-of-limit condition. Shut down
alarms activate an alarm signal that can be wired to a remote device.
Unit Enable Selection
Enables unit operation from local keypad or digital input.
Unit Mode Selection
Selects standard cooling, ice, glycol, or test operation mode.
OMM TGZ-1 TGZ 040A through TGZ 190A 23
Keypad/Display
ALARM
Key to Screen Pathway
Arrow Keys
A 4-line by 20-character/line liquid crystal display and 6-key keypad is mounted on the unit
controller. Its layout is shown below.
Figure 6, Keypad and Display in MENU Mode
Air Conditioning
Menu Key
<
VIEW
<
<
SET
"Enter" Key
The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.
1. Scroll between data screens as indicated by the arrows (default mode).
2. Select a specific data screen in a hierarchical fashion using dynamic labels on the right
side of the display (this mode is entered by pressing the MENU key).
3. Change field values in edit mode according to the following table:
LEFT Default
RIGHT Cancel
UP Increment
DOWN Decrement
These four edit functions are indicated by one-character abbreviation on the right side of
the display (this mode is entered by pressing the ENTER key).
24 TGZ 040A through TGZ 190A OMM TGZ-1
Inputs and Outputs
The main controller used in the TGZ is either a Carel PCO2 or a PCO3. An expansion module is
also be required for additional outputs on some unit configurations. The software is designed for
use with R-410a water chillers as well as TGZ Templifier units. The selection of the type of
refrigerant (R-134a) is made at the factory and sets certain inputs and outputs.
Large PCO2/PCO3 Controller
Table 9, Analog Inputs
The following parameters are analog inputs to this controller.
Type: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
# Description Type Signal Source Range
*1 Evaporator Refrigerant Pressure #1 C1 0.1 to 0.9 VDC
*2 Evaporator Refrigerant Pressure #2 C2 0.1 to 0.9 VDC
*3 Condenser Refrigerant Pressure #1 C1 0.1 to 0.9 VDC
4 Leaving Evaporator Water Temperature UT
5 Condenser Entering Water Temperature UT
*6 Condenser Refrigerant Pressure #2 C2 0.1 to 0.9 VDC
7 Reset of Leaving Water Temperature UT 4-20 mA Current 0-(10 to 80°F)
*8 Condenser Leaving Water Temperature UT
9 Compressor Suction Temperature #1 C1
10 Compressor Suction Temperature #2 C2
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
NTC Thermister
(10k@25°C)
0 to 132 psi
0 to 132 psi
3.6 to 410 psi
-58 to 212°F
-58 to 212°F
3.6 to 410 psi
-58 to 212°F
-58 to 212°F
-58 to 212°F
Table 10, Analog Outputs
The following parameters are analog outputs from this controller.
# Description Output Signal Range
1 Cooling Tower Bypass Valve Position 0 to 10 VDC 0 to 100% Open
2 Cooling Tower VFD Speed 0 to 10 VDC 0 to 100%
3 Circuit #1 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
4 Circuit #2 Electronic Expansion Valve 0 to 10 VDC 0 to 100%
Table 11, Digital Inputs
The following parameters are digital inputs to this controller.
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, & *n = Refrigerant
Dependent
1. See Safety Alarms Table for “Phase Voltage Protection”. Units with single point electrical
connection will have one PVM with Inputs 9 and 10 wired together. Units with multiple point
connection will have two PVM’s with Input 9 for Electrical Circuit #1 and Input 10 for
Electrical Circuit #2.
2. See Safety Alarms Table for “Ground Fault Protection”. Units with single point electrical
connection will have one GFP with Inputs 11 and 12 wired together. Units with multiple point
connection will have two GFP’s with Input 11 for Electrical Circuit #1 and Input 12 for
Electrical Circuit #2.
Table 12, Digital Outputs
The following parameters are digital outputs from this controller.
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, & *n = Refrigerant Dependent
# Description Type Load Output OFF Output ON
1 Alarm
2 Evaporator Water Pump UT Pump Contactor Pump OFF Pump ON
Condenser Water Pump – Water
3
Cooled = Y
4 Motor Control Relay #1 = Compr#1 C1 Starter Compressor OFF Compressor ON
5 Motor Control Relay #3 = Compr#3 C1 Starter Compressor OFF Compressor ON
*6 Motor Control Relay #5 = Compr#5 C1 Starter Compressor OFF Compressor ON
7 Liquid Line #1 C1 Solenoid Cooling OFF Cooling ON
8 Tower Fan #1-Water Cooled=Y C2 /UT Fan Contactor Fan OFF Fan ON
9 Motor Control Relay #2 = Compr#2 C2 Starter Compressor OFF Compressor ON
10 Motor Control Relay #4 = Compr#4 C2 Starter Compressor OFF Compressor ON
*11 Motor Control Relay #6 = Compr#6 C2 Starter Compressor OFF Compressor ON
12 Liquid Line #2 C2 Solenoid Cooling OFF Cooling ON
13 Condenser Fan #3 C1 Fan Contactor Fan OFF Fan ON
14 Hot Gas Bypass #1 C1 Solenoid Cooling OFF Cooling ON
15 Hot Gas Bypass #2 C2 Solenoid Cooling OFF Cooling ON
*16 Condenser Fan #4 (R134a) C2 Fan Contactor Fan OFF Fan ON
*17 Condenser Fan #5&7 (R134a) C1 Fan Contactor Fan OFF Fan ON
18 Condenser Fan #8 C2 Fan Contactor Fan OFF Fan ON
18 Condenser Fan #6&8 C2 Fan Contactor Fan OFF Fan ON
C1,C2,
UT
C1 / UT
Alarm Indicator Alarm OFF Alarm ON
Fan Contactor/
Pump Contactor
Fan OFF Fan ON
26TGZ 040A through TGZ 190A OMM TGZ-1
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.