McQuay RDE076C Installation Manual

Installation and Mainenance Manual IM791-2
Applied Packaged Rooftop System Heating and Cooling with Evaporative Condenser
Gas/Electric Models RPE/RDE 076C-150C 76 to 150 Tons
Date: September 2010
© 2010 McQuay International
®
Contents
Unit Nameplate............................................................ 3
Gas Burner Nameplate....... .......................................... 3
Hazard Identification Information............................... 3
Nomenclature....... ..................................................... ... 3
Unit Description........................................................... 4
Condenser Fan Arrangement ....................................... 5
Refrigerant Circuit Schematic ..................................... 5
Refrigeration Piping..................................................... 6
Spray System Plumbing with Optional Non-Chemical
Water Treatment .......................................................... 9
Bleed Off and Water Consumption ........................... 10
Control Locations ...................................................... 10
Walk-In Service Compartment.................................. 14
Receiving Inspection.................................................. 17
Unit Clearances.......................................................... 17
Ventilation Clearance ................................................ 18
Overhead clearance.................................................... 18
Roof Curb Assembly and Installation........................ 19
Reassembly of Split Units.......................................... 24
Condensate Drain Connection ................................... 26
Unit Piping................................................................. 26
Steam Coil Piping...................................................... 28
Steam Piping Recommendations ............................... 28
Steam Trap Recommendations.................................. 28
Damper Assemblies................................................... 30
Cabinet Weatherproofing........................................... 31
Installing Ductwork ................................................... 32
Installing Duct Static Pressure Sensor Taps.............. 33
Electrical Installation ........................................................ 34
Field Power Wiring.................................................... 34
Field Control Wiring.................................................. 37
Relief Damper Tie-Down .......................................... 38
Spring Isolated Fans....................................... ............ 38
Adjusting Spring Mounts........................................... 38
Spring Isolated Compressors..................................... 40
Power-up.................................................................... 41
Fan Operation ............................................................ 41
Economizer Operation............................................... 41
Heating....................................................................... 46
Legend ....................................................................... 47
Typical Control Schematic: Discharge Air Control
(DAC) ........................................................................ 50
Typical Control Schematic: Zone or Space Comfort Con-
trol (SCC).................................................... ............... 52
Typical Output Schematic: Actuator Control ............ 54
Typical Schematic: Condenser Fan, Anti-Corrosion Elec-
tric Heaters ................................................................ 55
Typical Output Schematic: VFD Control (SAF/RAF) 56 Typical Output Schematic: VFD Control Continued
(SAF/RAF)................................................................. 57
Typical Power Circuit Wiring - 4 Compressor - VFD 58 Typical Condensing Unit Control - MicroTech II - 4
Compressor................................................................. 60
Typical Super Mod Gas Furnace Control (1000 MBh) 64
Non-Chemical Water Treatment ................................ 66
Enthalpy Control ........................................................ 66
Hot Gas Bypass .......................................................... 68
External Time Clock................................................... 68
Smoke Detectors......................................................... 68
Freeze Protection........................................................ 68
Low Airflow Alarm.................................................... 69
Duct High Pressure Limit........................................... 69
Condensing Unit VFD Operation.... ........................... 69
Variable Frequency Drive Operation ......................... 69
Convenience Receptacle/Section Lights .................... 69
DesignFlow™ Outdoor Air Damper Option.............. 69
Propeller Exhaust Fan Option .................................... 72
Propeller Exhaust Fan Control ................................... 74
Ultraviolet Lights Option ........................................... 76
Ultraviolet Light Operation........................................ 76
Before Start-Up........................................................... 78
Power-Up.................................................................... 79
Fan Start-Up ............................................................... 79
Economizer Start-Up.................................................. 79
Evaporative Condenser Start-Up................................ 79
Compressor Start-Up.................................................. 80
Oil Pressure ................................................................ 81
Heating System Start-Up............................................ 81
Air Balancing.............................................................. 82
Sheave Alignment ...................................................... 82
Drive Belt Adjustment................................................ 83
Mounting and Adjusting Motor Sheaves.................... 83
Rooftop Equipment Warranty Regist. Form...................... 86
Planned Maintenance.............................................. .... 93
Sump Cleaning ............................. .............................. 95
Unit Storage................................................................ 95
Gas Furnace................................................................ 96
Bearing Lubrication.................................................... 96
Setscrews.................................................................... 98
Supply Fan Wheel-to-Funnel Alignment ................... 99
Refrigerant Charge ................................... .................. 99
Replacing Failed Refrigerant Sensors
or Switches ............................................................... 100
Evaporative Condenser Section................................ 100
Control Panel Components....................................... 101
Limited Product Warranty............................................... 104
Service and Warranty Procedure ..................... ................ 104
Replacement Parts .................................................... 104
Compressor....................................................... ........ 105
In-Warranty Return Material Procedure................... 105

Introduction

This manual provides general information about the “C” vintage McQuay RoofPak applied rooftop unit, models RDE and RPE. In addition to an overall description of the unit, it includes mechanical and electrical installation procedures, commissioning procedures, sequence of operation information, and maintenance instructions. For further information on the optional forced draft gas-fired furnace, refer to Bulletin No. IM 684 or IM 685.
The MicroTech II applied rooftop unit controller is available on “C” vintage applied rooftop units. For a detailed description of the MicroTech II components, input/output configurations, field wiring options and requirements, and service procedures, refer to IM696 for a description of operation and information on using and programming the MicroTech II unit controller, refer to the appropriate operation manual (see Figure 1).
For a description of operation and information on using the keypad to view data and set parameters, refer to the
appropriate program-specific operation manual (see Figure 1).
Table 1: Operation Manuals
Unit Manual
VFD’s Vendor IM Manuals
Discharge Air Control (VAV or CAV) OM 137
Space Comfort Control
(CAV-Zone Temperature Control)
Non-Chemical Water Treatment Option IM 827
OM 138
Introduction

Unit Nameplate

The unit nameplate is located on the outside lower right corner on the main control box door. It includes the unit model number, serial number, unit part number, electrical characteristics, and refrigerant charge.

Gas Burner Nameplate

On units which include gas heat, the nameplate is located on the lower right corner on the main control box door. It includes the burner model number, minimum/maximum input, maximum temperature rise and minimum CFM.

Hazard Identification Information

WARNING
Warnings are provided throughout this manual to indicate to installing contractors, operators, and service personnel potentially hazardous situatio n s wh i c h, if no t avo i d ed , ca n result in severe personal injury or property damage.
CAUTION
Cautions are provided throughout this manual to indicate to installing contractors, operators, and service personnel potentially hazardous situatio n s wh i c h, if no t avo i d ed , ca n result in personal injury or equipment damage.

Nomenclature

RoofPak
Unit Configuration
P = Blow through Cooling D = Draw through Cooling
Evaporative Condensers
Nominal Capacity (Tons)
RPE, RDE: 076, 089, 100, 110, 130, 140, 150
R P E - 150 C S E
Heat Medium
A = Natural Gas E = Electric S = Steam W = Hot Water Y = None (Cooling Only)
Cooling Coil Size
S = Standard (Low Airflow) L = Large (High Airflow)
Design Vintage
McQuay IM 791-2 3
Introduction

Unit Description

Typical Component Lo ca tio ns
Figure 1 shows a typical RPE unit with the locations of the
major components. Figure 2, page 4 shows a typical RDE unit
Figure 1: Typical Component Locations - RPE Units
with the locations of the major components. These figures are for reference only. See the certified submittals for actual specific dimensions.
Figure 2: Component Locations - RDE Units
4 McQuay IM 791-2

Condenser Fan Arrangement

Table 2 shows the condenser fan numbering conventions and
locations for each unit size.
Table 2: Condenser Fan Arrangement
Introduction
Unit Size
076C 089C 100C
110C 130C 140C 150C
Refrig. Circuit
1
2
1
2
Arrangement
11
21

Refrigerant Circuit Schematic

Figure 3: Circuit Schematic
11
21
12
22
12
22
13
23
Fan Control With VFD Without VFD
11, 21 - Digital 12 - CCB1 - B06 22 - CCB2 - B06
11, 21 - Digital 12 - CCB1 - B06 22 - CCB2 - B06 31 - CCB1 - B07 32 - CCB1 - B07
11, 21 - Digital 21 - CCB2 - B05 12 - CCB1 - B06 22 - CCB2 - B06
11 - CCB1 - B05 21 - CCB2 - B05 12 - CCB1 - B06 22 - CCB2 - B06 13 - CCB1 - B07 23 - CCB2 - B07
Legend
A Compressor A1 Second Compressor (4 Compressor Units) B Discharge Line C Condenser Coil D Evaporator Coil
E Manual Shut-off Valve
F Filter-Drier G Liquid Line Solenoid Valve H Sightglass I Liquid Line
J Suction Line K Thermostatic Expansion Valve L Distributor
M Combination Hot Gas Bypass Control and Solenoid Valve
N Hot Gas Bypass Lines (Optional)
McQuay IM 791-2 5
Introduction

Refrigeration Piping

This section presents the unit refrigeration piping diagrams for the various available configurations. Component numbering conventions are also shown.
Figure 4: Condenser Piping - 2 Compressors - 2 Circuits (076C - 100C)
1. Discharge Line Service Valve
2. Discharge Muffler
3. Liquid Line Manual Shut-off Valve
4. Suction Line Service Valve
5. Vibration Eliminator
Suction LIne Circuit 2 Circuit 1
Compressor 2
4
Discharge Line Circuit 2
Hot Gas Bypass Circuit 2 Circuit 1
Liquid Line Circuit 1
Liquid Line Circuit 2
With Vibration Eliminators
Compressor 1
Discharge Line Circuit 1
Suction LIne Circuit 2 Circuit 1
5
5
3
2
4
Compressor 2
4
3
1
Discharge Line Circuit 2
2
Hot Gas Bypass Circuit 2 Circuit 1
Liquid Line Circuit 1
Liquid Line Circuit 2
Compressor 1
3
2
1
3
Without Vibration Eliminators
Discharge Line Circuit 1
4
6 McQuay IM 791-2
2
Figure 4. Condenser Piping - 4 Compressors - 4 Circuits (110C - 150C)
4
1. Discharge Line Service Valve
2. Discharge Muffler
3. Liquid Line Manual Shut-off Valve
4. Suction Line Service Valve
5. Vibration Eliminator
Hot Gas Bypass Circuit 2 Circuit 1
Liquid Line Circuit 2
Liquid Line Circuit 1
Suction LIne Circuit 2 Circuit 1
Compressor 4
5
Compressor 2
4
Introduction
Discharge Line Circuit 2
3
2
Compressor 3
With Vibration Eliminators
Hot Gas Bypass Circuit 2 Circuit 1
Liquid Line Circuit 2
Liquid Line Circuit 1
4
Compressor 1
Suction LIne Circuit 2 Circuit 1
Discharge Line Circuit 1
1
3
2
4
Compressor 4
4
Compressor 2
Discharge Line Circuit 2
3
2
Compressor 3
Without Vibration Eliminators
4
Compressor 1
Discharge Line Circuit 1
2
1
3
McQuay IM 791-2 7
Introduction
Figure 5: Service Compartment Piping
Solid Core Filters
1. Liquid Line Solid Core Filter/Drier
2. Liquid Solenoid Valves
3. Hot Gas Bypass Valve and Solenoids
To Evaporator Coil
Liquid Line Circuit # 1 Circuit # 2
Suction Line Circuit # 2 Circuit # 1
Hot Gas Bypass Circuit # 1
Hot Gas Bypass Circuit # 2
2
1
To Compressors
3
Replaceable Filters
1. Liquid Line Replaceable Core Filter/Drier
2. Liquid Solenoid Valves
3. Hot Gas Control and Solenoid Valve
To Compressors
To Evaporator Coil
Liquid Line Circuit # 1 Circuit # 2
Suction Line Circuit # 2 Circuit # 1
Hot Gas Bypass Circuit # 1
Hot Gas Bypass Circuit # 2
2
1
3
8 McQuay IM 791-2

Spray System Plumbing with Optional Non-Chemical Water Treatment

WARNING
Failure to maintain and continually provide water treatment may result in severe equipment damage and may create biologically hazardous conditions. See
Figure 26 for water connection sizes and locations.
Figure 6: Spray System Piping
NOTE: The cyclone separator is on a side stream. A hand
valve controls water flow. The hand valve should be opened until the inlet pressure to the separator is about 12 psi as determined by the factory-installed gauge. This will yield about 20 gpm of blowdown whenever the blowdown solenoid opens.
Dolphin makeup water
Dolphin sump water treatment module
Dolphin sump water transformer
To Spraybar
transformer
Introduction
To Spraybar
Conductivity sensor
Conductivity controller
Makeup water control valve
Auto purge controller
Flowmeter
Cyclone seperator
Sump overflow
Ball valve actuators
Heat-tape all components from customer connection point to makeup water control valve
Dolphin makeup water treatment module
Makeup water connection point to sump tank.
Cleanout
Customer makeup water connection point
Manual shutoff
Sump Pump
McQuay IM 791-2 9
Freeze protection valve and actuator
Blow down and drain
Introduction

Bleed Off and Water Consumption

Controlled bleed off [or blow down] is required on McQuay RPE/ RDE units as it should be with all evaporative condensing products. It involves draining off a portion of the highly concentrated water from the bottom of the sump and replacing it with lower concentration make-up water to inhibit scale. Scale protection is required because the evaporation process leaves behind solids (scale) that will coat the heat exchanger surfaces and sump. This reduces the capacity, efficiency, and life expectancy of the equipment.
Manual bleed off occurs whenever the spray pump operates. A manual valve adjusts flow and is provided as standard. Refer to Figure 6. This inevitably bleeds off too much [increased water costs] or too little [risking scale build up] water. Automatic bleed off control is superior and usually is provided with the water treatment system.
Theoretical water consumption required for proper heat rejection is 1.8 gallons per ton hour. All of this water evaporates and none goes into the sewer. An additional 0.6 to
0.9 gallons per ton hour (.03 to .05 with McQuay non­chemical water treatment) is also required for make up and bleed off. The exact amount should be determined by water
Figure 7: Control Locations - RPE Units
analysis. The RPE/ RDE includes a float valve and solenoid that automatically refills the sump as required.
Bleed off must be handled in accordance with local codes and normally is drained into the sanitary sewer. Normally, this water should not be drained onto the roof or into a storm drain. One possible exception to this is with the McQuay non­chemical water treatment option (consult local codes carefully). Because most water utilities charge for both intake and sewer water flows based on intake meter readings, sewer charges may be reduced if sewer flow is proven to be less than water intake. McQuay offers both intake and bleed off water meters to document reduced sewer flow [confirm details with your local utility]. These meters are not included in the basic water treatment option.

Control Locations

Figure 7 (RPE Units) and Figure 8, page 11 (RDE Units) show
the locations of the various control components mounted throughout the units. See Control Locations‚ page 10 for the locations of control components mounted in control panels. Additional information is included in Table 3, page 15 and the
Legend‚ page 47.
Return Air
Economizer
Heat
Section
Discharge
Plenum Section
HL22 (Optional)
LT10 (Optional)
S10, REC10 (Optional)
Service Section
SD1 (Optional)
Condensor
Section
VM1 (Optional)
Exhaust Fan
Water Treatment (Optional)
Oil Pressure Box
Water Pump
Control Box
Space Heater (Optional)
Water Level Switches (WL63, WL64)
Sump Heater (Optional)
Sump Water Temp Sensor
ACT5 (optional)
ACT6 (optional)
OAT
LT11
(Optional)
S11 REC11
OAE
RAE (optional)
10 McQuay IM 791-2
Figure 8: Control Locations - RDE Units
(
)
C
ondensor Section
Introduction
C19,20
(Optional)
Economizer
Return Air
Filter
Section
Heat
Section
SV1, 2
Supply Fan
Discharge
Plenum Section
OAE
OAT
Service Section
FS1
(Optional)
LT10 (Optional)
S10, REC10 (Optional)
SD1 (Optional)
Exhaust Fan
Water Treatment (Optional)
Water Pump
Control Box
Space Heater (Optional)
Sump Heater (Optional)
Sump Water Temp Sensor
Oil Pressure Box
Water Level Switches (WL63, WL64)
LT11 (Optional)
S11, REC11
SD2
Optional
McQuay IM 791-2 11
Introduction
Control Panel Locations
The unit control panels and their locations are shown in the following figures. These figures show a typical unit configuration. Specific unit configurations may differ slightly from these figures depending on the particular unit options. See Wiring Diagrams‚ page 47 for the Legend and component description.
Figure 9: Control Panel Locations - Service Compartment
WARNING
Electrical shock can cause severe personal injury or death.
The control panel must be serviced by trained, experienced technicians.
Oil Pressure Instruments
Control Panel
Power Disconnect
12 McQuay IM 791-2
Figure 10: Main Control Panel - 076C - 150C
Introduction
See page page 47 for Legend
UP
for Control
Connections
Terminal Block
2 Feet to Floor
Main Disconnect
or Power Block
McQuay IM 791-2 13
Introduction
Figure 11: Electric Heat Control Panel - Sizes 075C- 135C
FB31FB32FB33
M31M32M33
FB34FB44
M34M44
FB41FB42FB43
M41M42M43
GLG3
DS3
H53
TB11
The manual shutter is normally be closed but can be opened
to condition the compartment when service is needed.
Figure 12: Walk-In Service Compartment
Perform Most Refrigerant Service in Comfort, Away
From Compressor Noise
Marine Lights
Exhaust Fan
Optional Unit Heater

Walk-In Service Compartment

Each unit includes a walk-in service compartment containing the following:
Main control panel. See Figure 9, page 12.
Liquid Line components except the expansion valve.
Spray pumps, water control valves (except float valves in the
sump) and water supply and sanitary connections. See
Figure 6, page 9.
Water treatment system (optional).
Main access door opened from the inside and outside.
Raised service grate to help protect service personnel against
water and chemical spills.
Refrigerant Schrader ports are provided on the liquid and
suction lines to allow for easy refrigerant pressure readings, however, discharge pressure at the compressor must be measured outside the enclosure.
Refrigerant charge can be added at the Schrader connections
in the compartment.
Lights, ventilation fans, manual shutter that can be opened to
allow conditioned air into the plenum and optional unit heater provide more comfortable servicing.
An adjustable TC66 thermostat turns on the ventilation fan
when the compartment temperature exceeds 75°F.
An adjustable integral thermostat runs the unit heater when
the compartment temperature drops to 35°F.
Charging, Suction, Discharge & Liquid Schrader Connections
Hot Gas Bypass Valves
Solenoid, Sight Glass & Filter Drier
Raised Floor Grate and Drain Pan
Space for Water Treatment
WARNING
Moving parts and electrical connections in the service compartment can cause severe personal injury or death.
Cabinet access must be limited to trained, experienced technicians only.
14 McQuay IM 791-2
Controls, Settings, and Functions
Introduction
Table 3 presents a listing of all the unit control devices.
Included in the table are the device symbol, a description of the device, its function, and any reset information, its location,
Table 3: Controls, Settings , an d Fu nc tions
Symbol
CS1 & 2
DAT
DHL
EFT
FP1, 2
FS1 Freezestat
HP1, 2,
3 & 4
LP1, 2
MCB Main control board Processes input information N/A
MP1–6 Compressor motor
OAE
OAT
PC5 Dirty filter switch Senses filter pressure drop Auto
PC6 Dirty filter switch Senses filter pressure drop Auto
Description Function Reset Location Setting Range Differential Part no.
Switch (toggle), refrigerant circuit
Discharge air temperature sensor
Duct high limit switch
Entering fan air temperature sensor
Evaporator frost protection
High pressure control
Low pressure control
protector
Enthalpy control (electro­mechanical)
Enthalpy control (electronic)
Outside air temperature sensor
Shuts off compressor control circuits manually
Senses discharge air temperature
Prevents excessive VAV duct pressures; shuts off fan
Senses entering fan air temperature
Senses low refrigerant temperature
Shuts off fans, opens heating valve, and closes outdoor damper if low air temperature at coil is detected
Stops compressor when refrigerant discharge pressure is too high
Stops compressor when suction pressure is too low (used for pumpdown)
Senses motor winding temperature, shuts off compressor on high temperature.
Notes:
1.Unit size 018C compressors include internal motor protector.
2.Unit sizes 020C–036C, circuit #1 compressors include internal motor protector (refer to unit wiring diagram).
Returns outside air dampers to minimum position when enthalpy is too high
Returns outside air dampers to minimum position when outside air enthalpy is higher than return air empalthy (use RAE)
Senses outside air temperature N/A N/A N/A 060004705
N/A
N/A
Auto
N/A
N/A
Auto Heating section
Manual
(relay
latched)
Auto Compressor
Auto at
3400
ohms
Auto
Auto
any device setting, any setting ranges, differentials, and the device part number.
Main control
panel
Discharge air
section
Main control
panel
Inlet of supply
fan
Return bends of
evaporative coil
Compressor
Main control
box
Compressor junction box
Economizer
section
Economizer
section
First filter
section
Final filter
section
N/A N/A N/A 01355000
N/A N/A 060004705
3.5" w.c
(871.8 Pa)
N/A N/A 060004705
Opens at
30°F
Closes at
45°F
38°F (3°C)
or as required
See
page 105.
See
page 105.
N/A N/A N/A 060006101
9 K–18 K
ohms
“B” or as
required
Fully CW past
“D”
(when used
with RAE)
As required
As required
0.05–5.0" wc
(12.5–1245.4
Pa)
N/A N/A 072501901
35°F–45°F
(2°C–7°C)
N/A
N/A
700 ohms cold N/A 044691509
A–D
A–D N/A 049262201
.05-5" wc
(12.5–1245.4
Pa)
.05-5" wc
(12.5–1245.4
Pa)
.05" wc
(12.5 Pa),
fixed
12°F (7°C),
fixed
100 psi
(689 kPa)
25 psi
(172 kPa)
Temperature:
3.5°F (2°C) Humidity:
5% fixed
.05" wc
(12.5 Pa)
.05" wc
(12.5 Pa)
065493801
065830001
047356120
047356111
030706702
065493801
065493801
McQuay IM 791-2 15
Introduction
Table 3: Controls, Settings , an d Fu nc tions (continued)
Symbol
PC7
PS1, 2 Pumpdown switch
RAE
RAT
SD1
SD2
SPS1
SPS2
SUMP
HTR
SV1, 2
SV5, 6
SV61,
62
SV63 Solenoid Valve
SWT Sump Water Temp
S1 System switch
S7
TC66 Temperature
WL63 Switch, Water Level
WL64 Switch, Low Water Maintains proper water level N/A Sump Holding
Description Function Reset Location Setting Range Differential Part no.
Airflow proving switch
Return air enthalpy sensor
Return air temperature sensor
Smoke detector, supply air
Smoke detector, return air
Static pressure sensor duct #1
Static pressure sensor duct #2
Static pressure sensor: building (space) pressure
Sump Water Heater , Evap Condenser
Solenoid valve (liquid line)
Solenoid valve (hot gas bypass)
Solenoid Valve (Water Fill - Evap Cond)
(Sump Drain - Evap Cond)
Sensor
ON-OFF-AUTO switch
Control - Evap Cond Exhaust Fan
Sump Fill
Senses supply fan pressure to prove airflow
Used to manually pump down compressor
Used to compare return air enthalpy to outside air enthalpy (used with OAE)
Senses return air temperature N/A Initiates unit shutdown if smoke
is detected Initiates unit shutdown if smoke
is detected Converts static pressure
signals to voltage signals Converts static pressure
signals to voltage signals and sends them to MicroTech II controller
Converts static pressure signals to voltage signals.
Controls Wa ter Temp in the Evap Condenser Sump
Closes liquid line for pumpdown
Closes hot gas bypass line for pump-down
Open when sump water level is
low to add water
Opens to drain sump N/A Service
Sensor for freeze and head
pressure control
Shuts off entire control circuit (except crankcase heaters)
Used to manually switch unit N/A
Sequences the vestibule
exhaust fan
Maintains proper water level N/A Sump Holding
Auto
N/A
N/A
Manual
Manual
N/A
N/A
N/A
N/A
N/A N/A Service
N/A Sump Holding
N/A
N/A Service
Supply fan
section
Condenser control box
Economizer
section
Return air
section
Discharge air
section
Return air
section
Main control
box
Main control
box
Main control
box
Sump Holding
Tank
Condenser
section
Condenser
section
Compartment
Compartment
Tank
Main control
box
Main control
box
Compartment
Tank
Tank
.10" wc (25
Pa)
N/A N/A N/A 01355000
N/A N/A N/A 049262202
N/A N/A 060004705
N/A N/A N/A 04925001
N/A N/A N/A 04925001
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A 111011001 N/A N/A N/A
N/A N/A N/A
N/A N/A N/A See parts
N/A N/A N/A 001355000
N/A N/A N/A N/A N/A N/A
N/A N/A N/A See parts
N/A N/A N/A See parts
.05-5" wc
(12.5–1245.4
Pa)
0–5" wc
(0–1245.4 Pa)
1–6 VDC out
0–5" wc
(0–1245.4 Pa)
1–6 VDC out
-025–0.25" wc
(-62.3–62.3 Pa)
1–5 VDC out
.05" wc
(12.5 Pa),
fixed
N/A 049545007
N/A 049545007
N/A 049545006
060015801
See parts
See parts
See parts
See parts
See parts
See parts
catalog
catalog
catalog
catalog
catalog
catalog
catalog
catalog
catalog
16 McQuay IM 791-2

Mechanical Installation

S
d
p
The installation of this equipment must be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to
determine and follow the applicable codes.
WARNING
Improper installation, adjustment, alteration se r v ic e or maintenance can cause personal inju ry or death.
Read and understand this Installation and Maintenance manual thoroughly before installing or servicing this equipment.
Note: Low head pressure may lead to poor, erratic refrigerant
feed control at the thermostatic expansion valve. The units have automatic control of the condenser fans which should provide adequate head pressure control down to 50°F (10°C). The system designer is responsible for assuring the condensing section is not exposed to
excessive wind or air recirculation.
WARNING
Sharp edges and coil surfaces can cause personal injury. Avoid contact with them.
Installation and maintenance must be performed only by trained and experienced personnel familiar with local codes and regulations.
WARNING
Sharp edges on sheet metal, screws and clips can cause personal injury.
This equipment must be installed and operated only by experienced trained personnel.
Mechanical Installation

Receiving Inspection

When the equipment is received, check all items against the bill of lading to be sure all crates and cartons have been received. If the unit has become dirty during shipment
(winter road chemicals are of particular concern), clean it when received.
Inspect all units for damage when received. Report all shipping damage to the carrier and file a claim. In most cases, equipment is shipped F.O.B. factory and claims for freight damage should be filed by the receiver.
The unit nameplate should be checked before unloading the unit to make sure the voltage complies with the power supply available.

Unit Clearances

Service Clearance
Allow service clearance approximately as indicated in
Figure 13. Also, a roof walkway should be provided to the
rooftop unit and along at least the two sides of the unit that provide access to most controls and serviceable components.
NOTICE
On units with side discharge, access to plenum mounted components becomes difficult once ductwork is installed. Installer must provide access in the ductwork for plenum mounted controls.
Figure 13: Service Clearances Side Discharge
72" 4 sides except as indicated
ABCDEFG
24"
Roof Walkway
Adjacent to Cooling Coil, Heat, and Supply Fan Sections.
ervice Clearance on
Legend:
A = Return Air Section B = Filter Section C = Cooling Section D = Cooling/Supply Fan Section E = Heat Section F = Discharge Plenum Section G = Service Com
artment
72" Clearance to end of unit or en of outside hood
McQuay IM 791-2 17
Mechanical Installation
Maxi
All
Figure 14: Side Discharge

V entilation Clearance

Following are minimum ventilation clearance recommendations. The system designer must consider each application and provide adequate ventilation. If this is not done, the unit will not perform properly.
Unit(s) surrounded by a screen or a fence:
1 The bottom of the screen or fence should be at least 1 ft.
(305 mm) above the roof surface.
2 The distance between the unit and a screen or fence should
be as described in Service Clearance‚ page 17. See also
Figure 13, page 17.
3 The distance between any two units within a screen or
fence should be at least 120" (3048 mm).
Unit(s) surrounded by solid walls:
1 If there are walls on one or two adjacent sides of the unit,
the walls may be any height. If there are walls on more than two adjacent sides of the unit, the walls should not be higher than the unit.
2 The distance between the unit and the wall should be at
least 96" (2438 mm) on all sides of the unit.
3 The distance between any two units within the walls should
be at least 120" (3048 mm). Do not locate outside air intakes near exhaust vents or other sources of contaminated air.
If the unit is installed where windy conditions are common, wind screens should be installed around the unit, maintaining the clearances specified (see Figure 15). This is particularly important to prevent blowing snow from entering outside air intakes, and to maintain adequate head pressure control when mechanical cooling is required at low outdoor air temperatures.

Overhead clearance

1 Unit(s) surrounded by screens or solid walls must have no
overhead obstructions over any part of the unit.
2 The area above the condenser must be unobstructed in all
installations to allow vertical air discharge.
3 The following restrictions must be observed for overhead
obstructions above the air handler section (see Figure 15):
a There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b Overhead obstructions must be no less than 2" (51 mm)
above the top of the unit.
c There must be no overhead obstructions in the areas
above the outside air and exhaust dampers that are farther than 24" (610 mm) from the side of the unit.
Figure 15: Overhead Clearance
mum
owable
9" (229mm) Min to Flue Box Typical All Sides
24" (610 mm) Maximum
2" (51mm) Top of Unit To O verhead Obstruction
Overhead Canopy Area
Flue Box
18 McQuay IM 791-2
Mechanical Installation

Roof Curb Assembly and Installation

The roof curb and unit must be located on a portion of the roof that can support the weight of the unit. The unit must be supported to prevent bending or twisting of the machine.
If building construction could allow the transmission of sound and vibration into the occupied space, the unit should be
located over a non-critical area. It is the responsibility of the system designer to make adequate provisions for noise and vibration in the occupied space.
The curb and unit must be installed level to allow the condensate drain to flow properly.
Integral supply and return air duct flanges are provided with the RPE/RDE roof curb, allowing connection of ductwork to the curb before the unit is set. The gasketed top surface of the duct flanges seals against the unit when it is set on the curb. These flanges must not support the total weight of the ductwork. Refer to Installing Ductwork‚ page 32 for details on duct connections. It is critical that the condensate drain side of the unit be no higher than the opposite side.
Assembly of a typical RPE/RDE roof curb is shown in
Figure 17, page 21. Parts A through K are common to all units
having bottom return openings. Depending on the unit length, Parts L and M may be included with the roof curb kit to create the correct overall curb length.
RPE/RDE Assembly instructions
Refer to Figure 17, page 21.
1 Set curbing parts A through K per dimensions shown over
roof opening or on a level surface. Note location of return and supply air openings.
2 If applicable, set other curbing parts (D, L, M, etc.) in place
making sure that the orientation complies with the assembly instructions. Check alignment of all mating bolt holes.
3 Bolt curbing parts together using fasteners provided.
Tighten all bolts finger tight.
4 Square entire curbing assembly and securely tighten all
bolts.
5 Position curb assembly over roof openings. Curb must be
level from side to side and over its length. Check that top surface of the curb is flat with no bowing or sagging.
6 W eld curbing in place. Caulk all seams watertight. Remove
backing from 0.25" (6 mm) thick x 1.50" (38 mm) wide gasketing and apply to surfaces shown by notes.
7 Flash curbing into roof as shown in Detail “B”. 8 Parts E and F are not required on units with no return shaft
within the curb perimeter.
9 Parts G and H are not required on units with no supply shaft
within the curb perimeter.
McQuay IM 791-2 19
Mechanical Installation
Figure 16: RPE/RDE Roof Curb Assembly
RDE & RPE 076-100
D
SA
OPENING
OPENING
N
P
C
RA
SEE FIGURE "A"
G
F
E
F
R
Q
H
J
K
L
K
M
B
RDE & RPE 110-150
G
F
E
C
RA
OPENING
D
SA
OPENING
R
Q
H
K
L
L
K
F
N
P
SEE FIGURE "A"
J
M
B
B
M
Dim 076-100C 110-150C
J
100.00 100.00
84.00 60.00
62.00 62.00
38.00 46.00
87.00 87.00
1.50 1.50
6.80 6.80
81.00 81.00
7.50 7.50
5.00 5.00
8.00 8.00
2.00 2.00
4.00 4.00
1.50 1.50
78.80 78.80
B C D E F G H
K L M N P Q R
20 McQuay IM 791-2
Figure 17: RPE/RDE Roof Curb Assembly
Using remaining side supports in this area, align lengths on opposite sides of assembly and install a cross support at each side.
Equal Length Side Supports
See Detail "A"
B
Mechanical Installation
Condenser
Section Support
(1 of 2 shown)
A
A
38.8"
B
Return
Air
85"
62.8"
Section B-B
Section A-A
2
1
2
5
4
9
10
6
7
10
3
9
6
8
4
1. Unit Base
2. Curb Gasketing
3. 2 x 4 Nailer Strip
4. Galvanized Curb
5. Duct Support
6. Cant Strip (not furnished)
7. Roofing Material (not furnished)
8. Rigid Insulation (not furnished)
9. Counter flashing (not furnished)
10. Flashing (not furnished)
2
2
3
5
4
1
9
10
6
7
8
McQuay IM 791-2 21
Mechanical Installation
Post and Rail Mounting
When mounting by post and rail, the structural support should be run the full length of the unit. Locate the structural member at the base of the unit as shown in Figure 18 assuring the
shaded area is well supported by the structural member.
CAUTION
The unit must be level side to side and over the entire length. Equipment damage can result if the unit is not level.
If resilient material is placed between the unit and the rail, insert a heavy steel plate between the unit and the resilient material to distribute the load. Properly seal cabinet penetrations (electrical, piping, etc.) to protect against moisture and weather.
Figure 18: Post and Rail Mounting
max
4 Provide adequate protection from vandalism, mechanical
contact, etc.
5 Securely close the doors. 6 If there are isolation dampers, make sure they are properly
installed and fully closed to prevent the entry of animals and debris through the supply and return air openings.
7 Cover the supply and return air openings on units without
isolation dampers.
Figure 19 shows an example of the rigging instruction label
shipped with each unit.
WARNING
Use all lifting points. Severe personal injury and property damage can result from improp er lifting adjustment.
Figure 19: Rigging and Handling Instruction Label
Rigging and Handling Instructions
Unit has either four or six lifting points (four-point shown below).
Caution: All lifting points must be used.
Rigging cables must be at least as long as distance "A".
Note:
*Rail cannot extend beneath the unit more than 5" (127 mm) or it will interfere with duct and electrical connections.
Rigging and Handling
Lifting brackets with 2" (51 mm) diameter holes are provided on the sides of the unit.
Use spreader bars, 96" to 100" (2438 to 2540 mm) wide to prevent damage to the unit cabinet. Avoid twisting or uneven lifting of the unit. The cable length from the bracket to the hook should always be longer than the distance between the outer lifting points.
If the unit must be stored at the construction site for an intermediate period, these additional precautions should be taken:
1 Make sure to support the unit well along the length of the
base rail.
2 Make sure to level the unit
(no twists or uneven ground surface).
3 Provide proper drainage around the unit to prevent flooding
of the equipment.
Caution:
Lifting points may not be symmetrical to center of gravity of unit. Balast or unequal
Lift Only As Indicated
cable lengths may be required
Lifting Points
Refer to Figure 20 and the following calculations to determine whether a four or six point lift is required.
X= Distance from the entering air end of the unit (or shipping section) to the first lifting lug in the direction of air flow.
For all units or shipping sections with outdoor air/return air options, X= 48"
For shipping sections without outdoor air/return air options,
X= 0 Y= distance from condenser or leaving air end of unit to the
last lifting lug. For all units or shipping sections with condensers, Y= 21.5
(sizes 76-100) or Y= 60.2 (sizes 110-150). For all units or shipping sections without condensers, Y=0 Z= Total base rail length of the unit. Note: Z excludes hoods
and overhung parts extending past base rails of the unit.
22 McQuay IM 791-2
Mechanical Installation
A= Z-X-Y If A<288", 4-point lift is sufficient If A>288", 6-point lift is required B= Distance from first lifting lug to middle lifting lug on units
with 6-point lift. B= A/2 +/- 48" Note: Middle lifting lug may be installed on
either side of the midpoint to avoid interference with condensate drains.
Figure 20: Unit Type RPE/RDE Lifting Points
Figure 21: RPE/RDE Factory Split at Supply Fan Section
McQuay IM 791-2 23
Mechanical Installation

Reassembly of Split Units

Although RoofPak units typically ship from the factory as complete units, they may be split at the factory.
The RPE/RDE unit may ship from the factory as two pieces, split at the supply fan bulkhead, to be recoupled together on the roof. This configuration would be ordered if shipping length or weight limitation prevented a packaged RPE/RDE from being ordered. Splitting at the fan has the advantage of leaving all factory refrigerant piping intact so field evacuation and charging is not required.
A single nameplate is attached to the air handler section and power is fed to both sections through the main control box, as it would be in a non-split RPE/RDE unit.
RPE/RDE Factory Split at Fan
Field reassembly of an RPE/RDE unit that has shipped split at the fan takes place in two phases:
Phase 1 - Setting the Sections and Cabinet Reassembly
The steps required to set the unit and reassemble the cabinet are shown in Figure 22, Figure 23, and Figure 24, page 25. The following items should be noted:
1 Top cap and plywood covers must be removed before the
sections are set together, but the steel retainer clips must be left in place to secure the bulkhead. Refer to Step 1 and
Figure 22.
2 Both sections must be carefully lowered into place to make
sure that the roof curb engages the recesses in the unit base.
3 All seams at the split must be caulked watertight after
recoupling the sections, as shown in Step 3 and Figure 23,
page 25.
WARNING
Improper installation can cause severe equipment damage, personal injury or death.
Connect the power block correctly and maintain proper phasing.
When reconnection of the power wires is complete, the inner raceway cover in the blank or heat section must be reinstalled.
Figure 24, page 25 shows a typical installation of the raceway
cover. If the unit is equipped with a fan diffuser, install as shown in Figure 24.
Control harnesses can be run by removing the external raceway covers on either side of the unit split. The excess harness length can be removed from the external raceway on the DX side of the split, routed along the raceway through the bushed hole in the fan section and into the junction box where control wiring terminal blocks are provided for reconnection. All electrical connections should be made per the unit's electrical schematics. Reinstall the external raceway covers after routing of the control wires is complete.
1 Prepare the units for reassembly as shown in Figure 22.
Figure 22: RPE/RDE Split at Fan Reassembly - Step 1
R e m o v e p l y w o o d a n d r e t a i n i n g
R e m o v e t o p c a p a n d s a v e f o r s t e p 3
a n g l e s f r o m u n i t a n d d i s c a r d
D i s c h a r g e e n
d o f U n i t
Phase 2 - Reconnecting Power and Control Wiring
The DX coil/condenser section contains power and control harnesses which have their excess length in the blank or heat section that is normally immediately downstream of the fan. Once the sections are physically reconnected, the ends of the
F a n e n d o f U n i t
power harness are fed back through the unit base into the junction box, per the unit’s electrical schematics.
24 McQuay IM 791-2
2
Set fan end of unit and discharge end of unit in place.
3 Caulk and install parts as shown in Figure 23.
R e m o v e s c r e w s o n f a n p a n e l , b u t l e a v e r e t a i n e r c l i p s i n p l a c e ; s a v e s c r e w s f o r
S t e p 3 .
Mechanical Installation
ovided
Figure 23: Split at Fan Reassembly - Step 3
Reinstall Top Cap Saved from Step 1
Caulk Ends of Splice Cap
Splice Cover Provided
Install #10 Screws Provided
Figure 24: RPE Split at Fan Reassembly - Step 4
Install Screws (.250-20 x .75) Saved from Step 1
Nut Clip-on Pr
4
Make electrical connections and reinstall Inner Raceway Cover as shown in Figure 24.
McQuay IM 791-2 25
Mechanical Installation

Condensate Drain Connection

The unit is provided with a 1.5" male NPT condensate drain connection. Refer to certified drawings for the exact location. The unit and drain pan must be level side to side and a P-trap must be installed for proper drainage.
RPE units may have positive or negative pressure sections. Traps should be used in both cases, with care given to negative pressure sections. In Figure 25, page 26, dimension “A” should be a minimum of 8" (203 mm). So the cabinet static pressure does not blow or draw the water out of the trap and cause air leakage, dimension A should be two times the maximum static pressure encountered in the coil section in inches w.c.
Drainage of condensate directly onto the roof may be acceptable; refer to local codes. A small drip pad of stone, mortar, wood or metal be should be provided to protect the roof against possible damage.
If condensate is to be piped into the building drainage system, the drain line should be pitched away from the unit at a minimum of 1/8" per foot. The drain line must penetrate the roof external to the unit. Refer to local codes for additional requirements. Sealed drain lines require venting to provide proper condensate flow.
Where the cooling coils have intermediate condensate pans on the face of the evaporator coil, copper tubes near both ends of the coil provide drainage to the main drain pan. Check that the copper tubes are in place and open before the unit is put into operation.
Because drain pans in any air conditioning unit will have some moisture in them, algae, etc. will grow. Periodic cleaning is necessary to prevent this buildup from plugging the drain and causing the drain pan to overflow. Also, the drain pans should be kept clean to prevent the spread of disease. Cleaning must
be performed by qualified personnel.
WARNING
Clean drain pans regularly. Growth in uncleaned drain pans can cause disease.
Cleaning must be done by trained, experienced personnel.
Figure 25: Condensate Drain Connection
S e e V i e w " A "
C o p p e r T u b e
( o n e e a c h e n d o f c o i l )
S t a t i c P r e s s u r e " P "
4 " ( 1 0 2 m m )
M i n i m u m
" A "
8 " ( 2 0 3 m m )
M i n . o r 2 x " P "
( i n . w . o . )
D r a i n P a n
N o t e : D r a i n l i n e m u s t
n o t b e r u n h i g h e r
t h a n t h i s l e v e l
M i n i m i z e T h i s
e n s i o n
D i m

Unit Piping

Gas Piping
See the “Installation” section of the gas-fired furnace installation manual, Bulletin No. IM684 or IM685.
Supply Water
City water must be piped into the service section of the unit. Install a manual shutoff valve to facilitate service of the unit. Provisions have been made to pipe through the floor of the service section within the curb. If the unit will be exposed to low outdoor air conditions, care must be taken to prevent freeze damage to this piping.
The service section has an optional heater to minimize freeze problems during cold weather. Verify that this heater functions before filling the unit. A sump heater option is also offered that includes heat tape on the pressure side of the float controlled fill valve, plus an extra 8 feet of heat tape to protect field connections inside the service compartment.
If the unit is mounted on post and rail structure, pipe will be exposed to outdoor conditions and will need to be heat taped or drained manually during the winter season.
26 McQuay IM 791-2
Mechanical Installation
Drain Water
A drain and bleed off connection is also located in the service section of the unit. Since this water will contain water treatment chemicals, local codes may require connection to the sanitary sewer. The freeze warning for supply water also applies to drain water piping.
Figure 26: Unit Piping Knockout Locations
Discharge
Air
Opening
A
7.87
6.88
9.26
DETAIL A
SCALE 1 : 9
4.75
2.25
6.75
4.75
Note: Make sure that a service compartment heater and
especially a sump heater or some type of freeze protection have been provided if freezing conditions are expected.
Walk-in
Vestibule
CONTROL WIRING .88" KNOCKOUT (3)
B
C ondensing
SUPPLY WATER
3.0" KNOCKOUT (.75" COPPER CONN ECTION)
Unit
7.87
26.50
DETAIL B
SCALE 1 : 9
21.50
3.0" KNOCKOUT (2)
Water Treatment
WARNING
Failure to maintain and continually provide water treatment will result in severe equipment damage and may create biologically hazardous conditions.
Water treatment, whether ordered as an option on the unit or purchased separately, must be properly installed and started before starting the unit. Failure to do so will result in scale build up on the condenser tubes with a resulting loss in heat rejection capacity. In severe cases, it may become impossible to operate the compressors. In addition, untreated cooling tower water can be a source for airborne disease.
Proper water treatment must include the following minimum features:
Bleed Off
Scale and corrosion inhibitor chemical treatment
Biocide chemical treatment
See Catalog 219 for information on the optional McQuay supplied water treatment systems.
POWER WIRES
72.00
(REFERENCE)
DRAIN WATER
3.0" KNOCKOUT (2.0" PVC C ONNEC TION)
Hot Water Coil Piping
Hot water coils either are provided without valves for field piping or are piped with three-way valves and actuator motors. Note: If the unit is equipped with an iron valve, connecting to a copper piping system will likely cause galvanic corrosion to occur and the valve will not last. All coils have vents and drains factory installed.
Hot water coils are not normally recommended for use with entering air temperatures below 40°F (4°C). No control system can guarantee a 100% safeguard against coil freeze-up. Glycol solutions or brines are the only freeze-safe media for operation of water coils at low entering air temperature conditions.
When no factory piping or valve is included, the coil connections are 2-1/8" copper (two supply and two return). With the factory piping and valve package, field piping connections are the same NPT size as the valve with female threading (see Figure 27, page 28).
Refer to the certified drawings for the recommended piping entrance locations. All piping penetrations must be sealed to prevent air and water leakage.
Note: The valve actuator spring returns to a stem down
position upon power failure. This allows full flow through the coil.
McQuay IM 791-2 27
Mechanical Installation
CAUTION
Coil freeze possible. Possible equipment damage. Carefully read and follow instructions for mixing antifreeze solution. Some products will have higher freezing points in their natural state than when mixed with water. The freezing of coils is not the responsibility of McQuay International.
Figure 27: Hot Water Valve Package
R e t u r n
Figure 28: Hot Water Heat Section (Factory Valve/Piping)
B y p a s s
S u p p l y
Refer to the certified drawings for the recommended piping entrance locations. All piping penetrations must be sealed to prevent air and water leakage.
Note: The valve actuator spring returns to a stem up position
upon power failure. This allows full flow through the coil.

Steam Piping Recommendations

1 Be certain that adequate piping flexibility is provided.
Stresses resulting from expansion of closely coupled piping and coil arrangement can cause serious damage.
2 Do not reduce pipe size at the coil return connection. Carry
return connection size through the dirt pocket, making the reduction at the branch leading to the trap.
3 Install vacuum breakers on all applications to prevent
retaining condensate in the coil. Generally, connect the vacuum breaker between the coil inlet and the return main. However, if the system has a flooded return main, the vacuum breaker should be open to the atmosphere and the trap design should allow venting of large quantities of air.
4 Do not drain steam mains or takeoffs through coils. Drain
mains ahead of coils through a steam trap to the return line.
5 Do not attempt to lift condensate. 6 Pitch all supply and return steam piping down a minimum
of 1" (25 mm) per 10 feet (3 m) of direction of flow.

Steam Coil Piping

Steam coils either are provided without valves for field piping, or are piped with two-way valves and actuator motors.
The steam coil is pitched at 1/8" (3 mm) per foot (305 mm) to provide positive condensate removal. When no factory piping or valve is included, the coil connections are 2.5" male NPT iron pipe.
With the factory piping and valve package, the field supply connection is the same NPT size as the valve with female threading (see Figure 30, page 29).

Steam Trap Recommendations

1 Size traps in accordance with manufacturers'
recommendations. Be certain that the required pressure differential will always be available. Do not undersize.
2 Float and thermostatic or bucket traps are recommended for
low pressure steam. Use bucket traps on systems with on­off control only.
3 Locate traps at least 12" (305 mm) below the coil return
connection.
4 Always install strainers as closely as possible to the inlet
side of the trap.
5 A single tap may generally be used for coils piped in
parallel, but an individual trap for each coil is preferred.
Steam Coil Freeze Conditions
If the air entering the steam coil is below 35°F (2°C), note the following recommendations:
1 1.5 psi (34.5 kPa) steam must be supplied to coils at all
times.
2 Do not use modulating valves. Control should be by means
of face and bypass dampers.
3 As additional protection against freeze-up, the tap should
be installed sufficiently far below the coil to provide an adequate hydrostatic head to provide removal of condensate during an interruption on the steam pressure. Estimate 3 ft. (914 mm) for each 1 psi (7 kPa) of trap differential required.
28 McQuay IM 791-2
Mechanical Installation
4 If the unit is to be operated in environments with possible
freezing temperatures, an optional freezestat is recommended. See Freeze Protection‚ page 68 for additional information.
Figure 29: Valve Assembly
S t e m C l i p
S t e m
S e t s c r e w s
Figure 30: Steam Valve Package
Condensate
Figure 31: Steam Heat Section (Factory Valve/Piping)
McQuay IM 791-2 29
Mechanical Installation

Damper Assemblies

The optional damper assemblies described in this section are provided with manually adjustable linkages, or may be shipped with factory installed actuators and linkages.
Economizer Dampers
Outside air intake is provided on both sides of the unit, and the return air path is at the center of the damper set. As the single actuator modulates the outside air dampers open, the return air dampers close. Exhaust air exits the unit through the gravity relief dampers provided at the end of the economizer section.
The outside air return air damper assembly (economizer) comes with manually adjustable linkage. This adjustable linkage can also be used for connection of a damper operator.
The damper is set so that the crankarm moves through a 90­degree angle to bring the economizer dampers from full open to full close. Mechanical stops have been placed in the crankarm mounting bracket. Do not remove stops. If the crankarm is driven past the stops, damage to the linkage or damper will result. The unit will ship with a shipping bolt securing the linkage crankarm. Remove shipping bolt before use.
Figure 32: Damper Adjustment
O u t s i d e
O u t s i d e
O p t i o n a l R e t u r n A i r F a n
A i r
A i r
E c o n o m i z e r
S h a f t . 5 0 0 D i a .
x 1 . 5 0 L o n g
O A
O p e n
9 0 °
S t r o k e
. 7 5
. 2 5
3 . 0 0
O A
C l o s e d
Note: For good airflow control, adjust linkages so damper
blades do not open beyond 70 degrees. Opening a damper blade beyond 70 degrees has little effect on its airflow. Do not “overclose” low leak damper blades. The edge seal should just lightly contact the adjoining blade. The blades will lock up if they are closed so far the seal goes over center.
30 McQuay IM 791-2
Loading...
+ 76 hidden pages