The use of unauthorized components, accessories or
devices may adversely affect the operation of the condensing unit and may also endanger life and property.
The manufacturer disclaims any responsibility for such loss
or injury and the manufacturer’s warranty does not cover
any damage or defect to the air conditioner caused by the
attachment or use of any components, accessories or
devices (other than those authorized by the manufacturer)
into, onto or in conjunction with the condensing unit.
Introduction
This manual contains the installation and operating instructions for your split condensing unit. There are a few precautions that should be taken to derive maximum satisfaction
from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this manual and any instructions packaged with separate
equipment required to make up the system prior to installation.
Give this manual to the owner and explain its provisions. The
owner should retain this manual for future reference.
Checking Product Received
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should
be filed immediately with the shipping company. Check the
unit model number, electrical characteristics, and accessories
to determine if they are correct.
Standard Unit Features
CABINET — Galvanized steel with a durable powder paint
finish. Stamped louvered panels offer 100% protection for the
condenser coil.
COMPRESSOR — Tandem scrolls are utilized with compressors mounted and piped as a set. Replacement must be by
complete set, not individual compressors. The compressor set
is mounted on isolators, and features inherent protection with
crankcase heaters as standard. By staging compressors, 50%
and 100% loading is allowed.
CONDENSER COIL — Constructed with copper tubes and
luminum fins mechanically bonded to the tubes for maximum
a
heat transfer capabilities. All coil assemblies are leak tested at
450 psig internal pressure.
REFRIGERANT CONNECTIONS — Field piping connections are made through a fixed panel. This allows complete
access or removal of access panels after piping connections
ave been made.
h
CRANKCASE HEATER — Standard, all models.
LOW AMBIENT CONTROL — A pressure sensitive fan
cycling control to allow unit operation to 0°F is standard.
SERVICE VALVES — Standard on liquid lines, optional on
vapor lines.
SERVICE ACCESS — The control box, as well as the compressor and other refrigerant controls, is accessible through
access panels. It may be opened without affecting the normal
operation of the unit.
Condenser fan motors are accessible by removing wire grilles.
FILTER DRIER — Field supplied.
SIGHT GLASS — Optional, field supplied.
TRANSFORMER — Step down type, line to 24 volts.
CONTACTOR — The contactor is an electrical switch which
operates the compressor and condenser fans.
HIGH PRESSURE CONTROL — Opens the contactor circuit on high refrigerant pressure; manual reset.
LOW PRESSURE CONTROL — Stops compressor operation in the event of loss of refrigerant.
CONDENSER FAN MOTOR (Direct Drive) — Ball bearing
1075 RPM motors are mounted to minimize vibration and
noise problems.These are permanent split capacitor types and
require the same capacitance for both run and start.
TESTING — All units are run tested at the factory prior to
shipment. Units are shipped with a holding pressure of nitrogen.
These units are equipped with a crankcase heater that is facto-
The condensing unit consists of a completely assembled package which includes a compressor pack, condenser coils, fans,
fan motors, outdoor control box, factory wiring, factory tubing
and fittings.
ry wired to operate whenever the main power supply to the
unit is “on” and compressors are “off.” Before starting the
equipment after prolonged shut-down or at the time of initial
spring start-up, be sure that the circuits to the condensing units
are closed for at least 24 hours.
Order Parts
When reporting shortages or damaged parts, or when ordering
repair parts, give the complete unit model and serial numbers
which are stamped on the unit rating plate.
Standard Items
6IM 910
Corrosive Environment
The metal parts of this unit may be subject to rust or deteriora-
tion if exposed to a corrosive environment. This oxidation
could shorten the equipment’s useful life. Corrosive elements
include salt spray, fog or mist in seacoast areas, sulphur or
chlorine from lawn watering systems, and various chemical
contaminants from industries such as paper mills and petrole-
um refineries.
If the unit is to be installed in an area where contaminants are
likely to be a problem, special attention should be given to the
equipment location and exposure.
• Avoid having lawn sprinkler heads spray directly on the unit
INSTALLATION GENERAL
The condensingunit should be installed outdoors. It should belocated as near as possible to the evaporator section to keepconnecting refrigerant tubing lengths to a minimum. The unit must beinstalled to allow a free air flow to the condenser coils.
If several units are installed adjacent toeach other, care must betaken to avoid recirculation of air from one condenser to another.Inall installations,adequate space must be provided for installation andservicing.
cabinet.
• In coastal areas, locate the unit on the side of the building
away from the waterfront.
• Shielding provided by a fence or shrubs may give some protection, based on clearances recommended in this book.
Regular maintenance will reduce the build-up of contaminants
and help to protect the unit’s finish.
DANGER
!
▲▲
isconnect all power to unit before starting maintenance.
D
Failure to do so can cause electrical shock resulting in
severe personal injury or death.
• Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other contaminants that build up on the unit.
• Regular cleaning and waxing of the cabinet with a good
automobile polish will provide some protection.
• A good liquid cleaner may be used several times a year to
remove matter that will not wash off with water.
Several different types of protective coatings are offered in
some areas. These coatings may provide some benefit, but the
effectiveness of such coating materials cannot be verified by
the equipment manufacturer.
Installation General
The condensing unit should be installed outdoors. It should be
located as near as possible to the evaporator section to keep
connecting refrigerant tubing lengths to a minimum. The unit
must be installed to allow a free air flow to the condenser
coils.
If several units are installed adjacent to each other, take care to
void recirculation of air from one condenser to another. In all
a
installations, adequate space must be provided for installation
and servicing.
The unit must not be connected to any duct work. Do not
locate unit under a roof drip; if necessary, install gutters, etc.,
to prevent water run-off onto the unit. To prevent air recircula-
ion, it is recommended that the unit not be installed under an
t
overhang. However, if this is necessary, allow a minimum of
60 inches above the unit for air discharge.
Rooftop Installation
If rooftop installation is required, make certain that the building construction is adequate for the weight of the unit. (Refer
to physical data chart.) Before placing the unit on the roof,
make certain that the nylon rigging slings are of sufficient
length to maintain equilibrium of the unit when lifting. Under
no circumstances should the unit be lifted by only one corner
for rooftop installation.
Slab Installation
Condensing units should be set on a solid level foundation.
When installed at ground level, the unit should be placed on a
6 inch cement slab. If the pad is formed at the installation site,
do not pour the pad tight against the structure, otherwise vibration will be transmitted from the unit through the pad.
Figure 5: Clearances
IM 910
7
DETAIL
CORNER WEIGHTS (Pounds)
MODEL
10 TON140150135144
12.5 TON167163140170
15 TON211198211198
20 TON238246235227
ABCD
15 & 20
TON
10 & 12.5
TON
ST-A0890-17
ST-A0890-18
Figure 6: Rigging
B
D
A
B
C
A
D
C
8IM 910
Installation of Piping
INSTALLATION OF PIPING
IMPORTANT:CONDENSING UNITS ARE SHIPPED WITH A NITROGENHOLDING CHARGE. EVACUATE CONDENSINGUNITBEFORECHARGINGWITH REFRIGERANT.
Once located, the condensing unit is ready to be interconnected withthe evaporator using ONLY refrigeration grade dehydrated tubing.T
he following should be considered when connecting the tubing.
1.Pitch the vapor line toward the compressor approximately 1/2 inchevery 10 feet to facilitate oil return.
2.Itis recommended that the sight glass, filterdrier and liquid linesolenoid valve be installed in the liquid line just prior to theevaporator.
3.Silver solder (such as silfos,Easy Flow, etc.) should be used for allrefrigerant joints.
4.Thoroughly clean all joints before fluxing. DO NOT USE ACIDFLUX.
5.When fluxing, limit the application of paste to the minimum andalways apply flux to the male portion of the connection.
6.vapor lines should be insulated to prevent condensate drip. Useinsulation of at least 3/8 inch wall thickness. The insulation shouldbe installed on the tubing prior to making the sweat connections.
7.Insulate the liquid line whenever the heat pick-up or transfer canaffect the sub-cooling.
8.Careshould be taken to avoid transmission of noise or vibration tobuilding structure.
!
WARNING
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURESYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLYWITH OIL,WHICH CAN CAUSE AN EXPLOSION RESULTINGI
N SEVERE PERSONAL INJURY OR DEATH.
TABLE 2REFRIGERANT PIPING DATA
21/8
15/8
13/8
11/8
7
/8
3
/4
TUBE SIZE
(IN.) O.D.
5
/8
1
/2
SOLE-
NOID
VALVE
ANGLE
VALVE
SHORT
RADIUS
ELL
LONG
RADIUS
ELL
TEE LINE
FLOW
TEE
BRANCH
FLOW
70
72
75
78
87
102
115
141
24
25
25
28
29
33
34
39
4.7
5.7
6.5
7.8
2.7
3.2
3.8
5.2
3.2
3.9
4.5
5.3
1.9
2.2
2.6
3.4
1.7
2.3
2.9
3.7
5.2
6.9
8.7
12.0
6.6
8.2
9.7
12.0
8.0
10.0
12.0
16.0
FOR NON-FERROUS VALVES & FITTINGS (BRAZED)
EQUIVALENT LENGTH (FT.) [m] OF STRAIGHT TYPE "L" TUBING
a
pproximately 3 PSIG pressure drop.
approximately 3 PSIG pressure drop.
adjacent to evaporator. Filter drier should bebetween thecondensing unit and sight glass.
.Pitch allhorizontal vapor lines downward in the direction of flow
prevent dirt and moisture from entering the piping.
possible to minimize piping runs.
tubing noise transmission into the conditioned space, the suctionclamp must be installed after tubing is brazed as illustrated infigure 7.
92-22205-38
.Size liquid line for no more than 10
o
F
loss which corresponds to
o
(
1/2" to 10 ft. run).
TYPICAL PIPING RECOMMENDATIONS
The following will be of help in accomplishing a successfuli
nstallation.
approximately 3 PSIG pressure drop.
2.Size vapor lines for no more than 2F loss which corresponds to
approximately 3 PSIG pressure drop.
3.Install sight glass, filter drier and solenoid valve in liquid line
adjacent to evaporator. Filter drier should bebetween thecondensing unit andsight glass.
4.Pitch all horizontal vapor lines downward in the direction of flow
5.When making up refrigerant piping, take every precaution to
prevent dirt and moisture from entering the piping.
6.Locate the condensing unit andevaporator(s) as close together as
possible to minimize piping runs.
7.Liquid or vapor lifts not to exceed 60 ft.
8.To prevent suction line breakage due to vibration and to prevent
tubing noise transmission into the conditioned space,the suctionclamp must be installed after tubing is brazed as illustrated infigure 7.
92-22205-38
RECOMMENDED VAPOR AND LIQUID LINE
SIZES FOR VARIOUS LENGTHS OF RUN
200
EQUIVALENT
LENGTH TO
EVAPORATOR
(FEET)
200
LIQUID LINE O.D.
SIZES (INCHES)
VAPOR LINE O.D.
SIZES (INCHES)
150
150
1
5
/8
15/8
15/8
21/821/8
21/8
15/8
15/8
7
/8
7
/8
7
/8
7
/8
3
/4
3
/4
5
/8
5
/8
NOTE: Line length between condenser and evaporator (suction and liquid) not
to exceed 150’ equivalent length.
1.Size liquid line for no more than 10oF loss which corresponds to
o
(1/2" to 10 ft. run).
0” to 15”
16” to 50”
51” to 100”
101” to 150”
WARNING
!
▲▲
Do not use oxygen to purge lines or pressure system for
leak test. Oxygen reacts violently with oil, which can cause
n explosion resulting in severe personal injury or death.
a
NOTE – The condensing unit is shipped with a holding charge of
dry nitrogen which must be purged from the unit before evacuation.
Once located, the condensing unit is ready to be interconnected with the evaporator using ONLY refrigeration grade dehydrated tubing.The following should be considered when connecting the tubing.
1 Pitch the vapor line toward the compressor approximately
1/2 inch every 10 feet to facilitate oil return.
2 It is recommended that the sight glass, filter drier and liq-
uid line solenoid valve be installed in the liquid line just
prior to the evaporator.
3 Silver solder (such as silfos, Easy Flow, etc.) should be
used for all refrigerant joints.
4 Thoroughly clean all joints before fluxing. DO NOT USE
ACID FLUX.
5 When fluxing, limit the application of paste to the mini-
mum and always apply flux to the male portion of the
connection.
6 Vapor lines should be insulated to prevent condensate
drip. Use insulation of at least 3/8 inch wall thickness.
The insulation should be installed on the tubing prior to
making the sweat connections.
7 Insulate the liquid line whenever the heat pick-up or
transfer can affect the sub-cooling.
8 Care should be taken to avoid transmission of noise or
vibration to building structure.
Table 3: Refrigerant Piping Data
Typical Piping Recommendations
The following will be of help in accomplishing a successful
installation.
1 Size liquid line for no more than 10°F loss which corre-
sponds to approximately 3 psig pressure drop.
2 Size vapor lines for no more than 2°F loss which corre-
sponds to approximately 3 psig pressure drop.
3 Install sight glass, filter drier and solenoid valve in liquid
line adjacent to evaporator. Filter drier should be between
the condensing unit and sight glass.
4 Pitch all horizontal vapor lines downward in the direction
of flow (1/2” to 10 ft. run).
5 When making up refrigerant piping, take every precaution
to prevent dirt and moisture from entering the piping.
6 Locate the condensing unit and evaporator(s) as close
together as possible to minimize piping runs.
7 Liquid or vapor lifts not to exceed 60 ft.
8 To prevent suction line breakage due to vibration and to
prevent tubing noise transmission into the conditioned
space, the suction clamp must be installed after tubing is
brazed as illustrated in figure 7.
Figure 7: Suction Clamp
Table 4: Recommended Vapor and Liquid Line Sizes for
Various Lengths of Run
IM 910
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.