McQuay RCS-15E Installation Manual

10 & 12.5 TON
15 & 20 TON
Installat
ion and Ma
intenance Manual
IM 910
roup: Applied Systems
G
Part Number: 92-102421-10
Air-Cooled Split-System Condensing Units for Rooftop Systems and Air Handlers
Models RCS 10E to 20E 10, 12.5, 15 & 20 Tons
Date: February 2008
© 2008 McQuay International
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
nstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
I
Crankcase Heaters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Order Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standard Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Corrosive Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rooftop Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Slab Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation of Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Typical Piping Recommendations . . . . . . . . . . . . . . . 9
Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wire Routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Evacuation and Charging . . . . . . . . . . . . . . . . . . . . . 13
Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
re-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
P
ccessories Installation . . . . . . . . . . . . . . . . . . . . . . 15
A
Service Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Louvers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance and Operation . . . . . . . . . . . . . . . . . . . 15
Crankcase Heaters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Low Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Charge Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . 23
Service and Warranty Procedure . . . . . . . . . . . . . . . 24
RCS Condensing Unit Equipment Warranty
Registration Form. . . . . . . . . . . . . . . . . . . . . . . 25-26
Quality Assurance Survey Report . . . . . . . . . . . . . . 27
Nomenclature
R C S — 15 –E
Design vintageRooftop Condensing Unit
Nominal capacity (tons) 10, 12, 15, 20
2 IM 910
Recognize this symbol as an indication of
!
Important Safety Information!
ANGER
D
!
The use of unauthorized components, accessories or devices may adversely affect the operation of the condens­ing unit and may also endanger life and property.
The manufacturer disclaims any responsibility for such loss or injury and the manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto or in conjunction with the condensing unit.
Introduction
This manual contains the installation and operating instruc­tions for your split condensing unit. There are a few precau­tions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory oper­ation or dangerous conditions.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
Checking Product Received
Upon receiving the unit, inspect it for any damage from ship­ment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, electrical characteristics, and accessories to determine if they are correct.
Standard Unit Features
CABINET — Galvanized steel with a durable powder paint finish. Stamped louvered panels offer 100% protection for the condenser coil.
COMPRESSOR — Tandem scrolls are utilized with com­pressors mounted and piped as a set. Replacement must be by complete set, not individual compressors. The compressor set is mounted on isolators, and features inherent protection with crankcase heaters as standard. By staging compressors, 50% and 100% loading is allowed.
CONDENSER COIL — Constructed with copper tubes and
luminum fins mechanically bonded to the tubes for maximum
a heat transfer capabilities. All coil assemblies are leak tested at 450 psig internal pressure.
REFRIGERANT CONNECTIONS — Field piping connec­tions are made through a fixed panel. This allows complete access or removal of access panels after piping connections
ave been made.
h
CRANKCASE HEATER — Standard, all models.
LOW AMBIENT CONTROL — A pressure sensitive fan
cycling control to allow unit operation to 0°F is standard.
SERVICE VALVES — Standard on liquid lines, optional on vapor lines.
SERVICE ACCESS — The control box, as well as the com­pressor and other refrigerant controls, is accessible through access panels. It may be opened without affecting the normal operation of the unit.
Condenser fan motors are accessible by removing wire grilles.
FILTER DRIER — Field supplied.
SIGHT GLASS — Optional, field supplied.
TRANSFORMER — Step down type, line to 24 volts.
CONTACTOR — The contactor is an electrical switch which
operates the compressor and condenser fans.
HIGH PRESSURE CONTROL — Opens the contactor cir­cuit on high refrigerant pressure; manual reset.
LOW PRESSURE CONTROL — Stops compressor opera­tion in the event of loss of refrigerant.
CONDENSER FAN MOTOR (Direct Drive) — Ball bearing 1075 RPM motors are mounted to minimize vibration and noise problems.These are permanent split capacitor types and require the same capacitance for both run and start.
TESTING — All units are run tested at the factory prior to shipment. Units are shipped with a holding pressure of nitro­gen.
IM 910
3
Figure 1: Dimensions – 10 Ton Units
ST-A0890-11
ST-A0890-12
ST-A0890-11
ST-A0890-12
ST-A0890-11
ST-A0890-11
Figure 2 : Dimensions – 12.5 Ton Units
4
IM 910
Gauge (nominal)
Top (frame)
CONDENSER FANS:
Quantity
CONDENSER COIL:
Quantity
REFRIGERANT CONNECTION:
Vapor, O.D.F. (inches), Sweat Type (1 ea.)
CABINET:
Finish
Liquid O.D.F. (inches), Sweat Type (1ea.)
MODEL RCS­NOMINAL CAPACITY (TONS)
Operating Weight (lbs.) Shipping Weight (approximate, lbs.)
Type RPM
CFM (total) Diameter (inches) Drive Motor Horsepower (ea.) Type RPM
Rows Fins per inch Square Feet Fins/Tubes Tube Size, O.D. (inches)
Sheet Metal
Sides (posts) Base rails (frame)
COMPRESSOR:
Quantity
10 12.5
569 640 609 680
11
Tandem Scroll Tandem Scroll
3500 3500
Capacity Steps
22
Percent from full load 50 50
23
6,800 6,800
24 24
Direct Direct
PSC PSC
1075
1075
22 22
18
22
27.0 32.875
Al/Cu Al/Cu
Powder Paint Powder Paint
Galvanized Galvanized
20 20 20 20 14 14
20
945 985
1
Tandem Scroll
3500
2
50
3
10,200
24
Direct
PSC 1075
2
3
18
40.375 Al/Cu
Powder Paint
Galvanized
20 20 14
15
818 858
1
Tandem Scroll
3500
2
50
3
10,200
24
Direct
PSC 1075
2
2
18
40.375 Al/Cu
Powder Paint
Galvanized
20 20 14
10E
12E
15E
20E
1/3 1/3
1/3
1/3
3/8 3/8
3/8
3/8
1-3/8
1-3/8
1-5/8
1-5/8
5/8
5/8
5/8
7/8
Figure 3 : Dimensions – 15 to 20 Ton Units
ST-A0890-11
ST-A0890-12
ST-A0890-11
S
T-A0890-12
ST-A0890-13
Table 1 – Physical Data
IM 910
5
CONDENSING UNIT
Gauge (nominal)
Top (frame)
CONDENSER FANS:
Quantity
CONDENSER COIL:
Quantity
REFRIGERANT CONNECTION:
Vapor, O.D.F. (inches), Sweat Type (1 ea.)
CABINET:
Finish
Liquid O.D.F. (inches), Sweat Type (1ea.)
MODEL NO. NOMINAL CAPACITY (TONS)
Operating Weight (lbs.) Shipping Weight (approximate, lbs.)
T
ype
RPM
C
FM (total) Diameter (inches) Drive Motor Horsepower (ea.) Type RPM
Rows Fins per inch Square Feet Fins/Tubes Tube Size, O.D. (inches)
Sheet Metal
Sides (posts) Base rails (frame)
COMPRESSOR:
Quantity
10 12.5
569 640 609 680
11
T
andem Scroll Tandem Scroll
3500 3500
Capacity Steps
22
P
ercent from full load 50 50
23
6
,800 6,800
24 24
D
irect Direct
1
/3
1
/3
PSC PSC
1075
1075
2
2
22
18
22
27.0 32.875
Al/Cu Al/Cu
3
/8
3
/8
13/8 13/8
5
/8
5
/8
Powder Paint Powder Paint
Galvanized Galvanized
20 20 20 20 14 14
20
945 985
1
Tandem Scroll
3500
2
5
0
3
10,200
24
Direct
1
/3 PSC 1075
2 3
18
40.375 Al/Cu
3
/8
15/8
7
/8
Powder Paint
G
alvanized
20 20 14
15
818 858
1
T
andem Scroll
3500
2
5
0
3
10,200
24
Direct
1
/3
PSC
1075
2
2
18
40.375 Al/Cu
3
/8
15/8
5
/8
Powder Paint
Galvanized
2
0 20 14
A0890-14
Table 2: Electrical Data
lectrical
E
odel
M
umber
N
CS
R
0ECAZ 3-60-208/230 17.3/17.3 137 4.8 44/44 50/50 60/60 27 [2.51] 1 6600 [3115] 309 [8760] 569 [258.1] 609 [276.2]
1
10EDAZ 3-60-460 9 62 2.8 24 30 30 27 [2.51] 1 6600 [3115] 309 [8760] 569 [258.1] 609 [276.2]
10EYAZ 3-60-575 7.1 50 2 18 20 25 27 [2.51] 1 6600 [3115] 309 [8760] 569 [258.1] 609 [276.2]
12ECAZ 3-60-208/230 18.6/18.6 156 4.8 47/47 60/60 60/60 32.88 [3.05] 2 6600 [3115] 413 [11709] 640 [290.3] 680 [308.4]
2EDAZ 3-60-460 9 75 2.8 24 30 35 32.88 [3.05] 2 6600 [3115] 413 [11709] 640 [290.3] 680 [308.4]
1
2EYAZ 3-60-575 7.4 54 2 19 25 25 32.88 [3.05] 2 6600 [3115] 413 [11709] 640 [290.3] 680 [308.4]
1
5ECAZ 3-60-208/230 28.8/28.8 195 7.2 72/72 80/80 100/100 40.38 [3.75] 2 9900 [4672] 573 [16245] 819 [371.5] 859 [389.6]
1
5EDAZ 3-60-460 14.7 95 4.2 38 40 50 40.38 [3.75] 2 9900 [4672] 573 [16245] 819 [371.5] 859 [389.6]
1
15EYAZ 3-60-575 10.8 80 3 28 30 35 40.38 [3.75] 2 9900 [4672] 573 [16245] 819 [371.5] 859 [389.6]
20ECAZ 3-60-208/230 37.2/37.2 239 7.2 91/91 110/110 125/125 40.38 [3.75] 3 9900 [4672] 778 [22056] 945 [428.7] 985 [446.8]
20EDAZ 3-60-460 17.2 125 3.3 42 50 50 40.38 [3.75] 3 9900 [4672] 778 [22056] 945 [428.7] 985 [446.8]
20EYAZ 3-60-575 12.4 80 2.4 31 35 40 40.38 [3.75] 3 9900 [4672] 778 [22056] 945 [428.7] 985 [446.8]
Figure 4: Control Box Configuration
hase
P
requency (Hz)
F
oltage (Volts)
V
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
ull Load
F A
mperes
FLA)
(
Minimum
ircuit
C mpacity
A
mperes
A
Fuse or HACR
Circuit Breaker
inimum
M A
M
mperes
A
aximum mperes
ace Area
F
q. Ft. [m2]
S
Outdoor Coil
o.
N
ows
R
FM
C
L/s]
[
Refrig.
er
P ircuit
C
z. [g]
O
N
bs. [kg]
L
Weight
et
hipping
S
bs. [kg]
L
Installation
Crankcase Heaters
These units are equipped with a crankcase heater that is facto-
The condensing unit consists of a completely assembled pack­age which includes a compressor pack, condenser coils, fans, fan motors, outdoor control box, factory wiring, factory tubing
and fittings. ry wired to operate whenever the main power supply to the unit is “on” and compressors are “off.” Before starting the equipment after prolonged shut-down or at the time of initial spring start-up, be sure that the circuits to the condensing units are closed for at least 24 hours.
Order Parts
When reporting shortages or damaged parts, or when ordering repair parts, give the complete unit model and serial numbers which are stamped on the unit rating plate.
Standard Items
6 IM 910
Corrosive Environment
The metal parts of this unit may be subject to rust or deteriora-
tion if exposed to a corrosive environment. This oxidation
could shorten the equipment’s useful life. Corrosive elements
include salt spray, fog or mist in seacoast areas, sulphur or
chlorine from lawn watering systems, and various chemical
contaminants from industries such as paper mills and petrole-
um refineries.
If the unit is to be installed in an area where contaminants are
likely to be a problem, special attention should be given to the
equipment location and exposure.
• Avoid having lawn sprinkler heads spray directly on the unit
INSTALLATION GENERAL
The condensing unit should be installed outdoors. It should be located as near as possible to the evaporator section to keep connecting refrigerant tubing lengths to a minimum. The unit must be installed to allow a free air flow to the condenser coils.
If several units are installed adjacent to each other, care must be taken to avoid recirculation of air from one condenser to another. In all installations, adequate space must be provided for installation and servicing.
cabinet.
• In coastal areas, locate the unit on the side of the building away from the waterfront.
• Shielding provided by a fence or shrubs may give some pro­tection, based on clearances recommended in this book.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
DANGER
!
isconnect all power to unit before starting maintenance.
D Failure to do so can cause electrical shock resulting in severe personal injury or death.
• Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contami­nants that build up on the unit.
• Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
• A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
Installation General
The condensing unit should be installed outdoors. It should be located as near as possible to the evaporator section to keep connecting refrigerant tubing lengths to a minimum. The unit must be installed to allow a free air flow to the condenser coils.
If several units are installed adjacent to each other, take care to
void recirculation of air from one condenser to another. In all
a installations, adequate space must be provided for installation and servicing.
The unit must not be connected to any duct work. Do not locate unit under a roof drip; if necessary, install gutters, etc., to prevent water run-off onto the unit. To prevent air recircula-
ion, it is recommended that the unit not be installed under an
t overhang. However, if this is necessary, allow a minimum of 60 inches above the unit for air discharge.
Rooftop Installation
If rooftop installation is required, make certain that the build­ing construction is adequate for the weight of the unit. (Refer to physical data chart.) Before placing the unit on the roof, make certain that the nylon rigging slings are of sufficient length to maintain equilibrium of the unit when lifting. Under no circumstances should the unit be lifted by only one corner for rooftop installation.
Slab Installation
Condensing units should be set on a solid level foundation. When installed at ground level, the unit should be placed on a 6 inch cement slab. If the pad is formed at the installation site, do not pour the pad tight against the structure, otherwise vibra­tion will be transmitted from the unit through the pad.
Figure 5: Clearances
IM 910
7
DETAIL
CORNER WEIGHTS (Pounds)
MODEL
10 TON 140 150 135 144
12.5 TON 167 163 140 170
15 TON 211 198 211 198
20 TON 238 246 235 227
ABCD
15 & 20
TON
10 & 12.5
TON
ST-A0890-17
ST-A0890-18
Figure 6: Rigging
B
D
A
B
C
A
D
C
8 IM 910
Installation of Piping
INSTALLATION OF PIPING
IMPORTANT: CONDENSING UNITS ARE SHIPPED WITH A NITROGEN HOLDING CHARGE. EVACUATE CONDENSING UNIT BEFORE CHARGING WITH REFRIGERANT.
Once located, the condensing unit is ready to be interconnected with the evaporator using ONLY refrigeration grade dehydrated tubing. T
he following should be considered when connecting the tubing.
1. Pitch the vapor line toward the compressor approximately 1/2 inch every 10 feet to facilitate oil return.
2. It is recommended that the sight glass, filter drier and liquid line solenoid valve be installed in the liquid line just prior to the evaporator.
3. Silver solder (such as silfos, Easy Flow, etc.) should be used for all refrigerant joints.
4. Thoroughly clean all joints before fluxing. DO NOT USE ACID FLUX.
5. When fluxing, limit the application of paste to the minimum and always apply flux to the male portion of the connection.
6. vapor lines should be insulated to prevent condensate drip. Use insulation of at least 3/8 inch wall thickness. The insulation should be installed on the tubing prior to making the sweat connections.
7. Insulate the liquid line whenever the heat pick-up or transfer can affect the sub-cooling.
8. Care should be taken to avoid transmission of noise or vibration to building structure.
!
WARNING
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURE SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN CAUSE AN EXPLOSION RESULTING I
N SEVERE PERSONAL INJURY OR DEATH.
TABLE 2 REFRIGERANT PIPING DATA
21/8
15/8
13/8
11/8
7
/8
3
/4
TUBE SIZE
(IN.) O.D.
5
/8
1
/2
SOLE-
NOID
VALVE
ANGLE
VALVE
SHORT
RADIUS
ELL
LONG
RADIUS
ELL
TEE LINE
FLOW
TEE
BRANCH
FLOW
70
72
75
78
87
102
115
141
24
25
25
28
29
33
34
39
4.7
5.7
6.5
7.8
2.7
3.2
3.8
5.2
3.2
3.9
4.5
5.3
1.9
2.2
2.6
3.4
1.7
2.3
2.9
3.7
5.2
6.9
8.7
12.0
6.6
8.2
9.7
12.0
8.0
10.0
12.0
16.0
FOR NON-FERROUS VALVES & FITTINGS (BRAZED)
EQUIVALENT LENGTH (FT.) [m] OF STRAIGHT TYPE "L" TUBING
a
pproximately 3 PSIG pressure drop.
approximately 3 PSIG pressure drop.
adjacent to evaporator. Filter drier should be between the condensing unit and sight glass.
. Pitch all horizontal vapor lines downward in the direction of flow
prevent dirt and moisture from entering the piping.
possible to minimize piping runs.
tubing noise transmission into the conditioned space, the suction clamp must be installed after tubing is brazed as illustrated in figure 7.
92-22205-38
. Size liquid line for no more than 10
o
F
loss which corresponds to
o
(
1/2" to 10 ft. run).
TYPICAL PIPING RECOMMENDATIONS
The following will be of help in accomplishing a successful i
nstallation.
approximately 3 PSIG pressure drop.
2. Size vapor lines for no more than 2F loss which corresponds to
approximately 3 PSIG pressure drop.
3. Install sight glass, filter drier and solenoid valve in liquid line
adjacent to evaporator. Filter drier should be between the condensing unit and sight glass.
4. Pitch all horizontal vapor lines downward in the direction of flow
5. When making up refrigerant piping, take every precaution to
prevent dirt and moisture from entering the piping.
6. Locate the condensing unit and evaporator(s) as close together as
possible to minimize piping runs.
7. Liquid or vapor lifts not to exceed 60 ft.
8. To prevent suction line breakage due to vibration and to prevent
tubing noise transmission into the conditioned space, the suction clamp must be installed after tubing is brazed as illustrated in figure 7.
92-22205-38
RECOMMENDED VAPOR AND LIQUID LINE
SIZES FOR VARIOUS LENGTHS OF RUN
200
EQUIVALENT
LENGTH TO
EVAPORATOR
(FEET)
200
LIQUID LINE O.D.
SIZES (INCHES)
VAPOR LINE O.D.
SIZES (INCHES)
150
150
1
5
/8
15/8
15/8
21/8 21/8
21/8
15/8
15/8
7
/8
7
/8
7
/8
7
/8
3
/4
3
/4
5
/8
5
/8
NOTE: Line length between condenser and evaporator (suction and liquid) not to exceed 150’ equivalent length.
1. Size liquid line for no more than 10oF loss which corresponds to
o
(1/2" to 10 ft. run).
0” to 15”
16” to 50”
51” to 100”
101” to 150”
WARNING
!
Do not use oxygen to purge lines or pressure system for leak test. Oxygen reacts violently with oil, which can cause
n explosion resulting in severe personal injury or death.
a
NOTE – The condensing unit is shipped with a holding charge of dry nitrogen which must be purged from the unit before evacua­tion.
Once located, the condensing unit is ready to be interconnect­ed with the evaporator using ONLY refrigeration grade dehy­drated tubing.The following should be considered when con­necting the tubing.
1 Pitch the vapor line toward the compressor approximately
1/2 inch every 10 feet to facilitate oil return.
2 It is recommended that the sight glass, filter drier and liq-
uid line solenoid valve be installed in the liquid line just prior to the evaporator.
3 Silver solder (such as silfos, Easy Flow, etc.) should be
used for all refrigerant joints.
4 Thoroughly clean all joints before fluxing. DO NOT USE
ACID FLUX.
5 When fluxing, limit the application of paste to the mini-
mum and always apply flux to the male portion of the connection.
6 Vapor lines should be insulated to prevent condensate
drip. Use insulation of at least 3/8 inch wall thickness. The insulation should be installed on the tubing prior to making the sweat connections.
7 Insulate the liquid line whenever the heat pick-up or
transfer can affect the sub-cooling.
8 Care should be taken to avoid transmission of noise or
vibration to building structure.
Table 3: Refrigerant Piping Data
Typical Piping Recommendations
The following will be of help in accomplishing a successful installation.
1 Size liquid line for no more than 10°F loss which corre-
sponds to approximately 3 psig pressure drop.
2 Size vapor lines for no more than 2°F loss which corre-
sponds to approximately 3 psig pressure drop.
3 Install sight glass, filter drier and solenoid valve in liquid
line adjacent to evaporator. Filter drier should be between the condensing unit and sight glass.
4 Pitch all horizontal vapor lines downward in the direction
of flow (1/2” to 10 ft. run).
5 When making up refrigerant piping, take every precaution
to prevent dirt and moisture from entering the piping.
6 Locate the condensing unit and evaporator(s) as close
together as possible to minimize piping runs.
7 Liquid or vapor lifts not to exceed 60 ft.
8 To prevent suction line breakage due to vibration and to
prevent tubing noise transmission into the conditioned space, the suction clamp must be installed after tubing is brazed as illustrated in figure 7.
Figure 7: Suction Clamp
Table 4: Recommended Vapor and Liquid Line Sizes for Various Lengths of Run
IM 910
9
Loading...
+ 19 hidden pages