McQuay RCS 040C Installation Manual

Installation and Maintenance Manual IM 787
Field Installed SpeedTrol™ for RoofPak™ Singlezone Rooftop Units
RPS/RDT/RCS 036C-135C
Group: Aftermarket Products
Part Number: 300040599
Date: December 2003
© 2003 McQuay International
Table of Contents
Typical Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 1 Typical Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Condenser Fan Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2 Condenser Fan Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Field Installation of SpeedTrol Option to “C” Vintage Rooftop Units: RPS/RDT/RCS (Sizes 036-135) . . . . . . . . . . . . . . . 5
Figure 3 Typical Schematic for RPS/RDT Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 4 Typical Schematic for RCS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Remove Panel V04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 6 SpeedTrol Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 7 Typical Condenser Box Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 8 Typical Condenser Box Power Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
WARNING
Moisture in control panel can cause severe personal injury and damage equipment.
When servicing this equipment during rainy weather, protect electrical components in main control panel from rain.
™ ® The following are trademarks or registered trademarks of McQuay International: FanTrol, MicroTech, MicroTech II, RoofPak and SpeedTrol.
Typical Component Locations
Figure 1 shows a typical RPS unit with the location of the major components and also lists some major dimensions. These figures are for reference only.
Figure 1: Typical Component Locations
IM 787 3
Condenser Fan Arrangement
Figure 2 shows the condenser fan numbering conventions and locations for each unit size with SpeedTrol application.
Figure 2: Condenser Fan Arrangement
Unit Size Refrig.Circuit Arrangement
12
11
036C
040C
May be a Singular or Dual Circuit Unit
22
21
100" (2540 mm)
12
1
2
100" (2540 mm)
11
22
21
83”
COND. AHU
045C
1
11 12
050C
060C
2
1
2
21 22
11 12
23
21 22
83”
13
Low Ambient (SpeedTrol)
Fan No.
11 21
11 21
11 21
11 21
070C
075C 080C 090C
105C
115C
125C 135C
1
2
1
2
1
2
1
2
1
2
11
21
11
24
21
11
24
21
11
25
21
11
251526
21
12
22
12
22
12
25
22
12
22 23
12
22 23
119”
13
23
119”
13
14
23
119”
13
14
23
139”
13 14
139”
13 14
16
11 21
11 21
11 21
11
15
24
21
11 21
24
Field Installation of SpeedTrol Option to “C” Vintage Rooftop Units: RPS/RDT/RCS (Sizes 036-135)
McQuay's SpeedTrol system of head pressure control oper­ates in conjunction with FanTrol™ by modulating the motor speed of the last condenser fan of each refrigeration circuit in response to condenser pressure. By varying the speed of the last condenser fan of each refrigeration circuit, the SpeedTrol option allows mechanical cooling operation in ambient temperatures down to 0°F (-18°C). SpeedTrol con­trollers SC11 and SC21 sense refrigerant head pressure and vary the fan speed accordingly. When the pressure rises, SpeedTrol increases the fan speed; when the pressure falls, SpeedTrol decreases the fan speed. The SpeedTrol control­ler's throttling range is 140 to 200 psig (965-1379 kPa) fixed.
The SpeedTrol fan motor is a single phase, 208/240 volt, thermally protected motor specially designed for variable speed application. Units with 460-volt power have a trans­former mounted inside the condenser fan compartment to step the voltage down to 230 volts for the SpeedTrol motor. A portion of a typical SpeedTrol power circuit schematic is shown in Figure 3 on page 6 and Figure 4 on page 7.
1. Before proceeding, confirm all electrical power has been terminated to the entire unit.
2. Using Figure 2 on page 4, (Condenser fan arrange­ments) identify the correct fan arrangement according to the unit size being worked on and locate condenser fans 11 and 21.
3. Make note of the fan blade position in relation to the fan deck panel so the fan blade is installed in the exact same position during reassembly on the motor shaft to assure maximum efficiency.
4. Remove condenser motor assemblies 11 and 21. Do not discard the motor mount or mounting hardware, and make sure not to damage the existing motor wire har­ness. These items will be needed during reassembly.
Note: The three phase motors and fan blades that were
removed will no longer be needed.
WARNING
Electric shock hazard. Before proceeding, lock and tag out all power sources to unit.
IM 787 5
5. Install the new single phase motor, motor slinger (6-3/4" diameter plastic disc), and fan blade into fan positions 11 and 21 using the existing motor mount and hardware
Figure 3: Typical Schematic for RPS/RDT Units
mentioned in step 4. Position fan blade in the same location that was noted in step 3.
6. Reconnect motor wire harness to motor as shown on schematics in Figures 3 or 4.
Figure 4: Typical Schematic for RCS Units
IM 787 7
7. Remove panel V04 . Locate and add a rectangular cut­out per dimensions shown on tabulated chart per unit
Figure 5: Remove Panel V04
size. Set panel V04 aside for the time being and keep panel mounting screws for later.
CABINET
SIZE
PANEL SIZE
(REF. ONLY)
A x B
CUTOUT SIZE
C x D
RPS 125 SHOWN FAN QTY. WILL VARY PER UNIT SIZE SEE FIGURE 2 FOR APPROPRIATE FAN LAYOUT
E
F
A
D
E
C
B
F
V04
CONDENSER END PANEL
CONDENSER BOX CONTROL DOOR
V04
CONDENSER BOX POWER DOOR
V14 SPEEDTROL COVER
#10 DRILL SCREW
8. With the condenser end panel V04 removed, the con­denser bulkhead will be accessible to mount (2) Speed­Trol panels. See Figure 6 to aid in positioning SpeedTrol panel for circuit 1 and circuit 2.
9. Locate the wire harness for condenser motors 11 and 21 in the condenser power box and disconnect the wire har­nesses from their respective contactors M11 and M21.
Reroute both motor wire harnesses to the SpeedTrol panels for circuit 1 and 2 as shown in Figure 6. Con­denser motor 11 to be assigned circuit 1 and motor 21 to be assigned circuit 2. Trim the motor harness wires to the appropriate length and crimp the 1/4 quick connects in place. Wire SpeedTrol panels as shown in Figures 3 or 4.
Figure 6: SpeedTrol Panels
NOTE:
1. ATTACH SPEEDTROL CAPILLARIES TO SCHRAEDER FITTINGS ON DISCHARGE TUBING AS SHOWN BELOW.
2. UNITS WITH VOLTAGES 380/460/415/575V HAVE A TRANSFORMER T11, 208/230 DO NOT.
SEE NOTE #1
SEE NOTE #1
FROM
MTR. #11
FROM
MTR. #21
SEE NOTE #2
TO CONDENSER
CONTROL BOX
SPEEDTROL PANEL #1
(CIRCUIT #1)
TO CONDENSER
CONTROL BOX
SPEEDTROL PANEL #2
(CIRCUIT #2)
IM 787 9
10. Mounting condenser control and power electrical com­ponents:
Figure 7 (Condenser Box Control Panel) shows loca­tions of the time delay relays TD11 & TD12 and relays R11 & R12. These components are required for units with MicroTech™ controls and units with no controls. RCS rooftop units require an additional transformer (T10), mount this transformer in upper left of control panel as shown. Refer to original condenser box control schematic for wiring instructions.
Figure 7: Typical Condenser Box Control Panel
Figure 8 (Condenser Box Power Panel) on page 11 shows the mounting location of fuse block FB11. Refer to Figure 3 or 4 for rewiring of existing fuse blocks, as well as fuse block FB11.
If the rooftop unit being worked on has MicroTech II™ controls, the software configuration string position 5 must be set to value 1 or (YES) as shown in Table 1 on page 11. Changing this requires an AAHU MicroTech II service tools.
CIRCUIT 1 RELAY
CIRCUIT 1 TIME DELAY
CIRCUIT 2 TIME DELAY
CIRCUIT 2 RELAY
Figure 8: Typical Condenser Box Power Panel
NOTE: QUANTITIES OF FUSE BLOCKS AND CONTACTORS WILL VARY PER UNIT SIZE.
NOTE DIRECTION OF L1 - L3 ON THIS DRAWING. FOR ALL COMPONENTS.
.
MOUNTING LOCATION OF FUSEBLOCK FB11
Table 1: Software Configuration String
Configuration
String Position
Description
5 Low Ambient
Values
(Default in bold)
0 FanTrol
1 SpeedTrol
11. Replace condenser end panel V04 using existing mount­ing screws and place SpeedTrol cover V14 over the opening created in V04 in step 7.
12. Add SpeedTrol Access label on SpeedTrol cover V14.
13. Please place this Instruction Manual in the Condenser Control Box.
14. Return electrical power to unit.
IM 787 11
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
www.mcquay.com • 800-432-1342
Loading...