This manual provides general information about the “C”
vintage McQuay RoofPak applied rooftop unit, models RPS,
RDT, RFS, and RCS. In addition to an overall description of
the unit, it includes mechanical and electrical installation
procedures, commissioning procedures, sequence of operation
information, and maintenance instructions. For further
information on the optional forced draft gas-fired furnace,
refer to Bulletin No. IM 684 or IM 685.
The MicroTech II applied rooftop unit controller is available
on “C” vintage applied rooftop units. For a detailed description
of the MicroTech II components, input/output configurations,
field wiring options, requirements, and service procedures, see
IM 696-3. For operation and information on using and
programming the MicroTech II unit controller, refer to the
appropriate operation manual (see Table 1).
For a description of operation and information on using the
keypad to view data and set parameters, refer to the
appropriate program-specific operation manual (see Table 1).
Table 1: Program specific rooftop unit operation literature
Rooftop unit control configuration
VFDsVendor IM manuals
Discharge Air Control (VAV or CAV) OM 137-2
Space Comfort Control
(CAV-Zone temperature control)
Operation manual bulletin
number
OM 138-2
Unit Nameplate
The unit nameplate is located on the outside lower right corner
of the main control box door. It includes the unit model
number, serial number, unit part number, electrical
characteristics, and refrigerant charge.
On units that utilize the tandem compressor design, each
compressor includes an individual nameplate along with a
nameplate identifying the tandem compressors.
Gas Burner Nameplate
On units that include gas heat, the nameplate is located on the
lower right corner of the main control box door. It includes the
burner model number, minimum/maximum input, maximum
temperature rise, and minimum cfm.
On units that utilize the tandem scroll compressor design, each
compressor includes an individual nameplate along with a
nameplate identifying the tandem compressors.
On units that utilize the tandem reciprocating design, each
compressor includes an individual nameplate.
Hazard Identification Information
WARNING
Warnings indicate potentially hazardous situations, which can
result in property damage, severe personal injury, or death if
not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can
result in personal injury or equipment damage if not avoided.
Compressor Nameplate
On units with a single compressor on each circuit, the
compressor includes one compressor nameplate.
McQuay IM 738-23
Introduction
Figure 1: Nomenclature
R P S – 030 C S E
RoofPak
Unit configuration
P = Heating, mechanical cooling
F = Heating, future mechanical cooling
C = Condensing section only
D = Draw through cooling
C - Condenser coil †
D - Evaporator coil*
E - Manual shutoff valve†
F - Filter-drier*
G - Liquid line solenoid valve*
H - Sightglass*
I - Liquid line*†
J - Suction line
K - Thermal expansion valve*
L - Distributor*
M - Hot gas bypass and solenoid valve (optional)*†
N - Hot gas bypass lines (optional)* †
*Supplied on RFS units
†Supplied on RCS units
Compressor #1
Discharge lines
Circuit #1
Circuit #2
1
Compressor #3
2
Liquid lines
Circuit #1
Circuit #2
3
Compressor #4
Compressor #2
Optional
hot gas
bypass
lines
Circuit #1
Circuit #2
Suction
lines
Circuit #1
Circuit #2
4
McQuay IM 738-29
Introduction
Figure 7: Condenser piping, four reciprocating compressors (115 to 135C)
Legend
1 - Discharge Line Service Valve
2 - Discharge Muffler
3 - High Pressure Relief Valve
4 - Liquid Line Manual Shut-off Valve
5 - Suction Line Service Valve
10McQuay IM 738-2
Figure 8: Air handler piping (flat DX)
circu
Legend
1 - Filter-drier
2 - Liquid line solenoid valve
3 - Sightglass
4 - Hot gas bypass and solenoid valve (optional)
5 - Thermostatic expansion valve
6 - Distributor
Introduction
Figure 9: Air handler piping (staggered DX)
Legend
1 - Filter-drier
2 - Liquid line solenoid valve
3 - Sightglass
4 - Hot gas bypass and solenoid valve (optional)
5 - Thermostatic expansion valve
6 - Distributor
Liquid line
circuit #1
1
Optional
hot gas
bypass
line
circuit #1
circuit #2
Air handler
section
Condenser
section
Circuit #1
6
5
Circuit #2
2
1
Liquid line
circuit #2
4
6
5
Suction line
circuit #1
it #2
McQuay IM 738-211
Introduction
Control Locations
Figure 10 (RPS Units) and Figure 11 on page 13 (RDT Units)
show the locations of the various control components mounted
throughout the units. See “Control Panel” on page 14 for the
locations of control components mounted in control panels.
Figure 10: Control locations—RPS units
FS1
SD2
(optional)
Return air
economizer
C19
RAT
Filter
section
Supply
fan
section
LT11
(opt io nal )
OAT
S11,
REC11
(optional)
Heat
section
OAE
ACT3
ACT6 (optional)
RAE (optional)
section
LT10
S10, REC10
PC5
Additional information is included in Table 3 on page 22 and
the wiring diagram legend, which is included in “Wiring
Diagrams” on page 71.Components mounted in the blowthrough section are located in the same position within the
draw-through section.
The unit control panels and their locations are shown in the
following figures. These figures show a typical unit
Figure 12: Control panel locations
Prop exhaust
(optional)
not shown)
(
VFDs, line reactors, and
manual bypass
(optional)
Electric heat
control panel
(optional)
configuration. Specific unit configurations may differ slightly
from these figures depending on the particular unit options.
Supply fan
section
Condenser
section
Main control panel
14McQuay IM 738-2
Figure 13: Typical main control panel, 015 to 040, 460 volt
Introduction
See separate
detail, page 17.
McQuay IM 738-215
Introduction
Figure 14: Typical main control panel, 045 to 075, 460 volt
See separate
detail, page 17.
16McQuay IM 738-2
Figure 15: Typical main control panel, 080 to 135, 460 volt
Introduction
Figure 16:
McQuay IM 738-217
Introduction
e
A
Figure 17: Typical gas heat panel, 1000 MBHFigure 18: Typical propeller exhaust panel, 3 fans, 460 volt
IT
R22
TD10
R20
S
R23R21
LS2
LS1
Figure 19: VFD bypass panel, 40 HP, 460 volt)
S3
FSG
FSG Tim
18McQuay IM 738-2
Figure 20: RCS control panel with MicroTech II, 015 to 040C
Figure 21: RCS control panel with MicroTech II, RPS 045 to 075C
Introduction
Figure 22: RCS control panel with MicroTech II, RPS 080 to 135C
McQuay IM 738-219
Introduction
Figure 23: Electric heat panel, sizes 15 to 40C
FB33FB32FB31
M33M32M31
FB43FB42FB41
M41M42M41
SR2
SR3
SR1
TB11
Figure 25: Electric heat panel, sizes 80 to 135
FB31FB32FB33
M31M32M33
FB34FB44
M34M44
FB41FB42FB43
M41M42M43
H53
TB11
PB3
Figure 24: Electric heat panel, sizes 45 to 75C
FB31FB32FB33
M31M32M33
FB41FB42FB43
M42
M41M43
GLG3
DS3
H53
TB11
GLG3
DS3
20McQuay IM 738-2
Figure 26: Harness plug connector detail
RATSOATSDATS
FP1OPEN1EPTS
AFD10AFD20
SV12SV56
ACT3OPEN2
OAEPC7PC5
Introduction
HL22OPEN3
GSHT1GSHT2
SD1SD2
DFRH DFLHOPEN4
COMP1COMP2
COMP3COMP4
COMP6COMP5
LT11LT1 0
LT OP1LT OP2
McQuay IM 738-221
Introduction
Controls, Settings, and Functions
Table 3 below lists all of the unit control devices and
associated information.
Table 3: Controls, settings, and functions
Symb
ol
CS1 &
2
DAT
DHL
EFT
FP1, 2
FS1
HP1,
2,
3 & 4
LP1, 2
MCB
MP1–
6
OAE
OAT
PC5
DescriptionFunction
Switch (toggle),
refrigerant circuit
Discharge air
temperature
sensor
Duct high limit
switch
Entering fan air
temperature
sensor
Evaporator frost
protection
Freezestat
High pressure
control
Low pressure
control
Main control board Processes input information
Compressor motor
protector
Enthalpy control
(electromechanical)
Enthalpy control
(electronic)
Outside air
temperature
sensor
Dirty filter switchSenses filter pressure drop
Shuts off compressor control
circuits manually
Senses discharge air
temperature
Prevents excessive VAV duct
pressures; shuts off fan
Senses entering fan air
temperature
Senses low refrigerant
temperature
Shuts off fans, opens heating
valve, and closes outdoor
damper if low air temperature
at coil is detected
Stops compressor when
refrigerant discharge
pressure is too high
Stops compressor when
suction pressure is too low
(used for pumpdown)
Senses motor winding
temperature, shuts off
compressor on high
temperature.
Notes:
1.Unit size 018C compressors
include internal motor
protector.
2.Unit sizes 020C–036C,
circuit #1 compressors
include internal motor
protector (refer to unit wiring
diagram).
Returns outside air dampers
to minimum position when
enthalpy is too high
Returns outside air dampers
to minimum position when
outside air enthalpy is higher
than return air empalthy (use
RAE)
Senses outside air
temperature
Rese
t
N/A
N/A
Auto
N/A
N/A
Auto
Manu
al
(relay
latche
d)
AutoCompressor
N/A
Auto
at
3400
ohms
Auto
Auto
N/AN/AN/A
Auto
LocationSettingRangeDifferentialPart no.
Main control
panel
Discharge air
section
Main control
panel
Inlet of supply
fan
Return bends
of evaporative
coil
Heating
section
Compressor
Main control
box
Compressor
junction box
Economizer
section
Economizer
section
First filter
section
N/AN/AN/A01355000
N/AN/A
3.5" w.c
(871.8 Pa)
N/AN/A
Opens at
30°F
Closes at
45°F
38°F (3°C)
or as
required
See page
131.
See page
131.
N/AN/AN/A
9 K–18 K
ohms
“B” or as
required
Fully CW
past “D”
(when used
with RAE)
As required
0.05–5.0" wc
(12.5–1245.4
Pa)
N/AN/A
35°F–45°F
(2°C–7°C)
N/A
N/A
700 ohms coldN/A
A–D
A–DN/A
.05-5" wc
(12.5–1245.4
Pa)
.05" wc
(12.5 Pa),
fixed
12°F (7°C),
fixed
100 psi
(689 kPa)
25 psi
(172 kPa)
Temperature:
3.5°F (2°C)
Humidity:
5% fixed
.05" wc
(12.5 Pa)
06000470
5
06549380
1
06000470
5
07250190
1
06583000
1
04735612
0
047356111
06000610
1
04469150
9
03070670
2
04926220
1
06000470
5
06549380
1
22McQuay IM 738-2
Table 3: Controls, settings, and functions (continued)
Symb
ol
PC6
PC7
PS1,
2
RAE
RAT
SD1
SD2
SPS1
SPS2
SV1,
2
SV5,
6
S1
S7
DescriptionFunction
Dirty filter switchSenses filter pressure drop
Airflow proving
switch
Pumpdown switch Used to manually pump down
Return air enthalpy
sensor
Return air
temperature
sensor
Smoke detector,
supply air
Smoke detector,
return air
Static pressure
sensor duct #1
Static pressure
sensor duct #2
Static pressure
sensor: building
(space) pressure
Solenoid valve
(liquid line)
Solenoid valve
(hot gas bypass)
System switch
ON-OFF-AUTO
switch
Senses supply fan pressure
to prove airflow
compressor
Used to compare return air
enthalpy to outside air
enthalpy (used with OAE)
Senses return air temperature
Initiates unit shutdown if
smoke is detected
Initiates unit shutdown if
smoke is detected
Converts static pressure
signals to voltage signals
Converts static pressure
signals to voltage signals and
sends them to MicroTech II
controller
Converts static pressure
signals to voltage signals.
Closes liquid line for
pumpdown
Closes hot gas bypass line for
pump-down
Shuts off entire control circuit
(except crankcase heaters)
Used to manually switch unit
Rese
Auto
Auto
N/A
N/A
N/A
ManualDischarge air
ManualReturn air
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LocationSettingRangeDifferentialPart no.
t
Final filter
section
Supply fan
section
Condenser
control box
Economizer
section
Return air
section
section
section
Main control
box
Main control
box
Main control
box
Condenser
section
Condenser
section
Main control
box
Main control
box
Introduction
As required
.10" wc (25
Pa)
N/AN/AN/A01355000
N/AN/AN/A
N/AN/A
N/AN/AN/A04925001
N/AN/AN/A04925001
N/A
N/A
N/A
N/AN/AN/A
N/AN/AN/A111011001
N/AN/AN/A
N/AN/AN/A
.05-5" wc
(12.5–1245.4
Pa)
.03-1.40" wc
(7.5–348 Pa)
0–5" wc
(0–1245.4 Pa)
1–6 V (dc) out
0–5" wc
(0–1245.4 Pa)
1–6 V (dc) out
-025–0.25" wc
(-62.3–62.3 Pa)
1–5 V (dc) out
.05" wc
(12.5 Pa)
.03" wc
(7.5 Pa),
fixed
N/A
N/A
N/A
06549380
06001580
04926220
06000470
04954500
04954500
04954500
00135500
1
1
2
5
7
7
6
See parts
catalog
0
FanTrol
The FanTrol, provided on all units, is a method of head
pressure control that automatically cycles the condenser fans
in response to ambient air temperature. This feature maintains
head pressure and allows the unit to run at low ambient air
temperatures.
RPS/RDT and RCS units have two independent refrigerant
circuits with one to four condenser fans being controlled
independently by the ambient air temperature of each circuit.
Table 4: R-22 FanTrol setpoints in °F with MicroTech II controls
01505605
018 to 020C0505————
025 to 036C0 5 65 5 ————
04005606
0450 5 55 5 ————
05005505——
0600 5155705——
0700 5305705——
0750 5655755 0 5
080 to 090C0565575505
1050505525705
1150505455755
1250 5555305805
1350 5455205655
B05B06B07B08
Degrees Farenheit
24McQuay IM 738-2
Mechanical Installation
Mechanical Installation
Note – The installation of this equipment shall be in accordance
with the regulations of authorities having jurisdiction and
all applicable codes. It is the responsibility of the installer
to determine and follow the applicable codes. Low head
pressure may lead to poor, erratic refrigerant feed control
at the thermostatic expansion valve. The units have
automatic control of the condenser fans which should
provide adequate head pressure control down to 50°F
(10°C) provided the unit is not exposed to windy
conditions. The system designer is responsible for
assuring the condensing section is not exposed to
excessive wind or air recirculation.
CAUTION
Sharp edges on sheet metal and fasteners can cause personal
injury.
This equipment must be installed, operated, and serviced only
by an experienced installation company and fully trained
personnel.
Receiving Inspection
When the equipment is received, all items should be carefully
checked against the bill of lading to be sure all crates and
Figure 27: Service clearances
72"
(1829 mm)
cartons have been received. If the unit has become dirty
during shipment (winter road chemicals are of particular
concern), clean it when received.
All units should be inspected carefully for damage when
received. Report all shipping damage to the carrier and file a
claim. In most cases, equipment ships F.O.B. factory and
claims for freight damage should be filed by the consignee.
Before unloading the unit, check the unit nameplate to make
sure the voltage complies with the power supply available.
Unit Clearances
Service Clearance
Allow an approximate service clearance as indicated in
Figure 27. Also, McQuay recommends providing a roof
walkway to the rooftop unit as well as along two sides of the
unit that provide access to most controls and serviceable
components.
60"
(1524 mm)
Roof walkway
To roof
access
location
A
60"
(1524 mm)
BC
DE
96"
(2438 mm)
Varies with unit arrangement
Refer to certified drawing & note.
Ventilation Clearance
Below are minimum ventilation clearance recommendations.
The system designer must consider each application and
provide adequate ventilation. If this is not done, the unit will
not perform properly.
Unit(s) surrounded by a screen or a fence:
C
F
60"
(1524 mm)
Legend:
A = Return air section
B = Filter section
C = Cooling section
D = Cooling/supply fan section
E = Heat section
F = Discharge plenum section
1
The bottom of the screen or fence should be at least 1 ft.
(305 mm) above the roof surface.
2 The distance between the unit and a screen or fence should
be as described in Figure 27.
3 The distance between any two units within a screen or
fence should be at least 120" (3048 mm).
McQuay IM 738-225
Mechanical Installation
Unit(s) surrounded by solid walls:
1 If there are walls on one or two adjacent sides of the unit,
the walls may be any height. If there are walls on more than
two adjacent sides of the unit, the walls should not be
higher than the unit.
2 The distance between the unit and the wall should be at
least 96" (2438 mm) on all sides of the unit.
3 The distance between any two units within the walls should
be at least 120" (3048 mm).
Do not locate outside air intakes near exhaust vents or other
sources of contaminated air.
If the unit is installed where windy conditions are common,
install wind screens around the unit, maintaining the
clearances specified (see Figure 28). This is particularly
important to prevent blowing snow from entering the outside
air intake and to maintain adequate head pressure control when
Figure 28: Overhead clearance
Overhead
canopy
mechanical cooling is required at low outdoor air
temperatures.
Overhead Clearance
1 Unit(s) surrounded by screens or solid walls must have no
overhead obstructions over any part of the unit.
2 The area above the condenser must be installed
unobstructed to allow vertical air discharge.
3 The following restrictions must be observed for overhead
obstructions above the air handler section (see Figure 28):
a There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b Overhead obstructions must be no less than 96"
(2438 mm) above the top of the unit.
c There must be no overhead obstructions in the areas
above the outside air and exhaust dampers that are
farther than 24" (610 mm) from the side of the unit.
24" (610 mm)
maximum
96" (2438 mm)
minimum,
top of unit to
permanent
overhead
obstruction
9" (229 mm)
minimum to flue box,
typical all sides
Flue box
24" (610 mm)
maximum
26McQuay IM 738-2
Mechanical Installation
Roof Curb Assembly and Installation
Locate the roof curb and unit on a portion of the roof that can
support the weight of the unit. The unit must be supported to
prevent bending or twisting of the machine.
If building construction allows sound and vibration into the
occupied space, locate the unit over a non-critical area. It is
the responsibility of the system designer to make adequate
provisions for noise and vibration in the occupied space.
WARNING
Mold can cause personal injury. Some materials such as
gypsum wall board can promote mold growth when damp.
Such materials must be protected from moisture that can enter
units during maintenance or normal operation.
Install the curb and unit level to allow the condensate drain to
flow properly and allow service access doors to open and close
without binding.
Figure 29: RCS roof curb assembly
6 "
" Z Z "
6 "
1 . U n i t B a s e
B
A
A
2 . G a l v a n i z e d C u r b
3 . G a l v a n i z e d C u i r b C o v e r
4 . 2 x 4 N a i l e r S t r i p
5 . R i g i d I n s u l a t i o
6 "
6 . C a n t S t r i p ( n o t f u r n i s h e d )
7 . F l a s h i n g ( n o t f u r n i s h e d )
8 . C u r b G a s k e t i n g
9 . I n s u
G a l v a n i z e d C u r b ( n o t f u r n i s h e d )
1 0 . R o o f i n g M a t e r i a l ( n o t f u r n i s h e d )
B
A
A
n ( n o t f u r n i s h e d )
l a t i o n b e t w e e n
Integral supply and return air duct flanges are provided with
the RPS/RFS roof curb, allowing connection of duct work to
the curb before the unit is set. The gasketed top surface of the
duct flanges seals against the unit when it is set on the curb.
These flanges must not support the total weight of the duct
work. See “Installing Ductwork” on page 58for details on duct
connections. It is critical that the condensate drain side of the
unit be no higher than the opposite side.
Assembly of a typical RPS/RDT roof curb is shown in
Figure 30 on page 28. Parts A through K are common to all
units having bottom return openings. Depending on the unit
length, Parts L and M may be included with the roof curb kit to
create the correct overall curb length.
Figure 29 shows the assembly of the RCS roof curb.
It is important to follow these installation instructions for all
IBC Seismic compliant McQuay Rooftop units.
IBC Seismic compliant McQuay Rooftop units can be
mounted to either a roof curb or a post and rail setup. If using a
roof curb, it must be specifically designed for seismic restraint
and be IBC seismic compliant (spring isolated or non-isolated
type seismic roof curbs are available). Typical construction of
a seismic rated roof curb is from structural steel framing and
contains seismic hold down brackets for attachment of the
rooftop unit (see Figure 31). Post and rail arrangements rated
for seismic applications are also available (spring isolated or
non-isolated).
IMPORTANT: An acceptable IBC seismic installation
provides a direct positive attachment to both the building
structure and the roof mounted equipment.
Refer to the roof curb manufacturer’s submittal drawings for
actual roof curb assembly, attachment details and rigging
instructions for both roof curb and post and rail arrangements.
1 Set the rooftop unit on the roof curb (McQuay Rooftop
units are designed to overhang from the roof curb).
2 Adjust the seismic hold down brackets so they come into
contact with the unit base per Figures 32 and 33 on page
31.
a The seismic hold down brackets should be adjustable
and accommodate the overhang of the rooftop unit.
b If the hold down bracket cannot reach the unit base, use
a shim spacer. See Figure 33 on page 31.
3 Weld each seismic hold down bracket (and shim spacer, if
required) to the unit base as shown in the acceptable weld
zone detail in Figure 32 on page 31.
CAUTION
When welding unit to the curb, do not damage wiring (control
panel side). Weld ONLY in the specified zone in the acceptable
weld zone (see Figure 32 on page 31). Welding must comply
with weld fillet size, etc. as indicated in Figure 32 on page 31.
Note – High temperature insulation is installed at the factory to
allow for field welding along the lower front edge region of
the unit base.
Duct opening
Seismic hold down brackets
Structural steel frame
Seismic hold down brackets
Spring
isolator
30McQuay IM 738-2
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.