McQuay RCS015 Installation Manual

Installation and Maintenance Manual IM 738-2
RoofPak™ Singlezone Roof Mounted Heating and Cooling Units
RPS/RDT/RFS/RCS 015-135C
Group: Applied Systems
Date: June 2006
US
© 2006 McQuay International
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Compressor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Gas Burner Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Hazard Identification Information . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . 6
Condenser Fan Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigeration Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Control Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Controls, Settings, and Functions . . . . . . . . . . . . . . . . . . . . . 22
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ventilation Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Overhead Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
IBC Seismic Compliant Units . . . . . . . . . . . . . . . . . . . . . . . . 30
Roof Curb Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Post and Rail Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Post and Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Rigging and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Reassembly of Split Units . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
RPS/RDT Factory Split at Condensing Unit . . . . . . . . . . . . . 42
RFS/RCS Permanent Split Systems . . . . . . . . . . . . . . . . . . . 47
Unit Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Steam Coil Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Steam Piping Recommendations . . . . . . . . . . . . . . . . . . . . . 54
Steam Trap Recommendations . . . . . . . . . . . . . . . . . . . . . . . 55
Damper Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Cabinet Weather Protection . . . . . . . . . . . . . . . . . . . . . . . . . 58
Installing Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Installing Duct Static Pressure Sensor Taps . . . . . . . . . . . . . 59
Installing Building Static Pressure Sensor Taps . . . . . . . . . . 60
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Field Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Preparing Unit for Operation . . . . . . . . . . . . . . . . . . . . . 65
Spring Isolated Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Relief Damper Tie-Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Adjusting Scroll Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Adjusting Supply Fan Thrust Restraints . . . . . . . . . . . . . . . . 66
Sequences of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Economizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Mechanical Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . 68
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Enthalpy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Hot Gas Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
SpeedTrol™ (N/A Unit Sizes 015C to 030C) . . . . . . . . . . . . 99
External Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Smoke and Fire Protection . . . . . . . . . . . . . . . . . . . . . . . . . 100
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Entering Fan Temperature Sensor . . . . . . . . . . . . . . . . . . . 102
Duct High Pressure Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
MicroTech II™ Remote User Interface (UI) . . . . . . . . . . . . . 102
Variable Frequency Drive Operation . . . . . . . . . . . . . . . . . . 104
Convenience Receptacle/Section Lights . . . . . . . . . . . . . . . 104
DesignFlow™ Outdoor Air Damper Option . . . . . . . . . . . . . 104
Propeller Exhaust Fan Option . . . . . . . . . . . . . . . . . . . . . . . 107
Exhaust Fan On/Off Control . . . . . . . . . . . . . . . . . . . . . . . . . 109
Ultraviolet Lights Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Ultraviolet Light Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Check, Test, and Start Procedures . . . . . . . . . . . . . . 112
Servicing Control Panel Components . . . . . . . . . . . . . . . . . 112
Before Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Fan Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Economizer Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Compressor Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Scroll Compressor Rotational Direction (sizes 15 to 105) . . 114
Oil Pressure (sizes 115 to 135C only) . . . . . . . . . . . . . . . . . 115
Heating System Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Air Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Sheave Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Drive Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Mounting and Adjusting Motor Sheaves . . . . . . . . . . . . . . . 119
Final Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Servicing Control Panel Components . . . . . . . . . . . . . . . . . 126
Planned Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Setscrews . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Supply Fan Wheel-to-Funnel Alignment . . . . . . . . . . . . . . . 130
Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Servicing Refrigerant Sensors or Switches . . . . . . . . . . . . . 131
Winterizing Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . 132
Replacement Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Service and Warranty Procedure . . . . . . . . . . . . . . . . 137
Scroll Compressor (sizes 15 to 105C) . . . . . . . . . . . . . . . . . 137
Reciprocating Compressors (sizes 115 to 135C) . . . . . . . . 137
All Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Limited Product Warranty (North America) . . . . . . 139
Exceptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Sole Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Rooftop Equipment Warranty Regist. Form . . . . . 140

Introduction

Introduction
This manual provides general information about the “C” vintage McQuay RoofPak applied rooftop unit, models RPS, RDT, RFS, and RCS. In addition to an overall description of the unit, it includes mechanical and electrical installation procedures, commissioning procedures, sequence of operation information, and maintenance instructions. For further information on the optional forced draft gas-fired furnace, refer to Bulletin No. IM 684 or IM 685.
The MicroTech II applied rooftop unit controller is available on “C” vintage applied rooftop units. For a detailed description of the MicroTech II components, input/output configurations, field wiring options, requirements, and service procedures, see IM 696-3. For operation and information on using and programming the MicroTech II unit controller, refer to the appropriate operation manual (see Table 1).
For a description of operation and information on using the keypad to view data and set parameters, refer to the appropriate program-specific operation manual (see Table 1).
Table 1: Program specific rooftop unit operation literature
Rooftop unit control configuration
VFDs Vendor IM manuals
Discharge Air Control (VAV or CAV) OM 137-2
Space Comfort Control
(CAV-Zone temperature control)
Operation manual bulletin
number
OM 138-2

Unit Nameplate

The unit nameplate is located on the outside lower right corner of the main control box door. It includes the unit model number, serial number, unit part number, electrical characteristics, and refrigerant charge.
On units that utilize the tandem compressor design, each compressor includes an individual nameplate along with a nameplate identifying the tandem compressors.

Gas Burner Nameplate

On units that include gas heat, the nameplate is located on the lower right corner of the main control box door. It includes the burner model number, minimum/maximum input, maximum temperature rise, and minimum cfm.
On units that utilize the tandem scroll compressor design, each compressor includes an individual nameplate along with a nameplate identifying the tandem compressors.
On units that utilize the tandem reciprocating design, each compressor includes an individual nameplate.

Hazard Identification Information

WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.

Compressor Nameplate

On units with a single compressor on each circuit, the compressor includes one compressor nameplate.
McQuay IM 738-2 3
Introduction
Figure 1: Nomenclature
R P S – 030 C S E
RoofPak
Unit configuration P = Heating, mechanical cooling F = Heating, future mechanical cooling C = Condensing section only D = Draw through cooling
Blow through cooling = S Draw through cooling = T
Nominal capacity (tons) RPS, RFS, RCS, RDT: 015, 018, 020, 025, 030, 036, 040, 045, 050, 060, 070, 075, 080, 090, 105, 115, 125, 135
Heat medium A = Natural gas E = Electric S = Steam W = Hot water Y = None (cooling only)
Cooling coil size S=Standard (low airflow) L =Large (high airflow)
Design vintage
4 McQuay IM 738-2

Unit Description

Figure 2: RPS/RDT/RFS/RCS unit
Introduction
R P S / R D T
R F S
R C S
McQuay IM 738-2 5
Introduction

Typical Component Locations

Figure 2 shows an RPS/RDT/RFS/RCS unit. Figure 3 shows a typical RPS unit with the locations of the major components.
Figure 3: Typical component locations—RPS units
Top View
Outside and return air dampersa
Side View
Exhaust hood
Bottom return air opening
Filter section
Supply air fan
Figure 4 on page 7 shows a typical RDT unit with the locations of the major components.
These figures are for general information only. See the project’s certified submittals for actual specific dimensions and locations.
Bottom discharge air opening
Power and control entrances
Evaporator coil
Discharge plenum (main control panel)
Optional back return opening
Return air
Return airReturn air fan
Outside air louvers
Heat section (natural gas, oil, steam, hot water, electric
Air cooled condenser
6 McQuay IM 738-2
Figure 4: Component locations—RDT units
Top View
Introduction
Bottom supply air opening
1.50 MPT drain
Bottom return opening
Side View
Return air plenum
Exhaust dampers
Optional back return air opening
Return air fan
Optional outside & return air dampers
Filter section
Outside air louvers (both sides)
Control entrances 7/8" dia K.O.
DX coil section
Evaporator coils
Power entrances 3" dia K.O.
Supply fan section
McQuay IM 738-2 7
Introduction

Condenser Fan Arrangement

Table 2 shows the condenser fan numbering conventions and locations for each unit size.
Table 2: Condenser fan arrangement
Unit size Refrigerant circuit Arrangement Unit size Refrigerant circuit Arrangement
COND
015C 018C 020C
1 or 2
12
11
AHU
075C 080C 090C
1
2
11
24
21
12
22
13
14
23
025C 030C 1 or 2
036C 040C
045C 050C
060C 070C
1
2
1
2
1
2
11
13
12
11
21
11
23
21
21
11
12
22
12
13
22
12
22
1
105C
2
1
115 C
2
1 125C 135C
2
8 McQuay IM 738-2
Introduction

Refrigeration Piping

This section presents the unit refrigeration piping diagrams for the various available configurations.
Figure 5: Circuit schematic
A - Compressor (1, 2, or 3 per circuit)† B - Discharge line †
B
A
M
C
J
N
L
K
G
H
I
F
E
D
Figure 6: Condenser piping, scroll compressors, one to three compressors per circuit are provided (015 to 105C)
Legend
1 - Discharge shut-off valve—Circuit #1 2 - Liquid shut-off valve—Circuit #1 3 - Liquid shut-off valve—Circuit #2 4 - Discharge shut-off valve—Circuit #2
C - Condenser coil † D - Evaporator coil* E - Manual shutoff valve† F - Filter-drier* G - Liquid line solenoid valve* H - Sightglass* I - Liquid line*† J - Suction line K - Thermal expansion valve* L - Distributor* M - Hot gas bypass and solenoid valve (optional)*† N - Hot gas bypass lines (optional)* †
*Supplied on RFS units †Supplied on RCS units
Compressor #1
Discharge lines Circuit #1 Circuit #2
1
Compressor #3
2
Liquid lines Circuit #1 Circuit #2
3
Compressor #4
Compressor #2
Optional hot gas bypass lines Circuit #1 Circuit #2
Suction lines Circuit #1 Circuit #2
4
McQuay IM 738-2 9
Introduction
Figure 7: Condenser piping, four reciprocating compressors (115 to 135C)
Legend
1 - Discharge Line Service Valve 2 - Discharge Muffler 3 - High Pressure Relief Valve 4 - Liquid Line Manual Shut-off Valve 5 - Suction Line Service Valve
10 McQuay IM 738-2
Figure 8: Air handler piping (flat DX)
circu
Legend
1 - Filter-drier 2 - Liquid line solenoid valve 3 - Sightglass 4 - Hot gas bypass and solenoid valve (optional) 5 - Thermostatic expansion valve 6 - Distributor
Introduction
Figure 9: Air handler piping (staggered DX)
Legend
1 - Filter-drier 2 - Liquid line solenoid valve 3 - Sightglass 4 - Hot gas bypass and solenoid valve (optional) 5 - Thermostatic expansion valve 6 - Distributor
Liquid line circuit #1
1
Optional hot gas bypass line circuit #1 circuit #2
Air handler section
Condenser section
Circuit #1
6
5
Circuit #2
2
1
Liquid line circuit #2
4
6
5
Suction line circuit #1
it #2
McQuay IM 738-2 11
Introduction

Control Locations

Figure 10 (RPS Units) and Figure 11 on page 13 (RDT Units) show the locations of the various control components mounted throughout the units. See “Control Panel” on page 14 for the locations of control components mounted in control panels.
Figure 10: Control locations—RPS units
FS1
SD2
(optional)
Return air
economizer
C19
RAT
Filter
section
Supply
fan
section
LT11
(opt io nal )
OAT
S11, REC11
(optional)
Heat
section
OAE
ACT3
ACT6 (optional)
RAE (optional)
section
LT10
S10, REC10
PC5
Additional information is included in Table 3 on page 22 and the wiring diagram legend, which is included in “Wiring Diagrams” on page 71.Components mounted in the blow­through section are located in the same position within the draw-through section.
SC11, 12 (optional)
C11, 12 (optional)
SV1
SV5 (optional)
SV6 (optional)
ACT5 (optional)
HP1-2, HP3-4 (optional)
LP1-2
HTR1-2, HTR3-4 (optional)
SV2
Disc harge
DX
HL22
plenum section
EFT
(optional)
(optional)
(optional)
Condensor
section
SD1
PC7
DAT (optional)
VM1
(optional)
12 McQuay IM 738-2
Figure 11: Control locations—RDT units
DX
section
Filter
section
Economizer
return air
Heat
section
Supply fan
discharge
plenum
section
C9
Condenser
section
SC11, 21 (optional)
SV1, 2
Introduction
C11, 21 (optional)
HP1-2, LP1-2 HTR1-2, U1/U2 HP3-4 (optional) HTR3-4 (optional)
C19, 20
(optional)
RAT
LT11 (optional)
S11, REC11
SD2
(optional)
(optional)
RAE
(optional)
ACT3
ACT6
PC5
OAE
OAT
VM1
(optional)
FS1
(optional)
DAT
LT10 (optional)
S10, REC10 (optional)
SD1 (optional)
SV5, 6 (optional)
McQuay IM 738-2 13
Introduction

Control Panel

The unit control panels and their locations are shown in the following figures. These figures show a typical unit
Figure 12: Control panel locations
Prop exhaust (optional)
not shown)
(
VFDs, line reactors, and
manual bypass (optional)
Electric heat control panel (optional)
configuration. Specific unit configurations may differ slightly from these figures depending on the particular unit options.
Supply fan section
Condenser section
Main control panel
14 McQuay IM 738-2
Figure 13: Typical main control panel, 015 to 040, 460 volt
Introduction
See separate
detail, page 17.
McQuay IM 738-2 15
Introduction
Figure 14: Typical main control panel, 045 to 075, 460 volt
See separate
detail, page 17.
16 McQuay IM 738-2
Figure 15: Typical main control panel, 080 to 135, 460 volt
Introduction
Figure 16:
McQuay IM 738-2 17
Introduction
e
A
Figure 17: Typical gas heat panel, 1000 MBH Figure 18: Typical propeller exhaust panel, 3 fans, 460 volt
IT
R22
TD10
R20
S
R23 R21
LS2
LS1
Figure 19: VFD bypass panel, 40 HP, 460 volt)
S3
FSG
FSG Tim
18 McQuay IM 738-2
Figure 20: RCS control panel with MicroTech II, 015 to 040C
Figure 21: RCS control panel with MicroTech II, RPS 045 to 075C
Introduction
Figure 22: RCS control panel with MicroTech II, RPS 080 to 135C
McQuay IM 738-2 19
Introduction
Figure 23: Electric heat panel, sizes 15 to 40C
FB33 FB32 FB31
M33 M32 M31
FB43 FB42 FB41
M41 M42 M41
SR2
SR3
SR1
TB11
Figure 25: Electric heat panel, sizes 80 to 135
FB31FB32FB33
M31M32M33
FB34FB44
M34M44
FB41FB42FB43
M41M42M43
H53
TB11
PB3
Figure 24: Electric heat panel, sizes 45 to 75C
FB31FB32FB33 M31M32M33
FB41FB42FB43
M42
M41M43
GLG3
DS3
H53
TB11
GLG3
DS3
20 McQuay IM 738-2
Figure 26: Harness plug connector detail
RATS OATSDATS
FP1 OPEN1EPTS
AFD10 AFD20
SV12 SV56
ACT3 OPEN2
OAE PC7PC5
Introduction
HL22 OPEN3
GSHT1 GSHT2
SD1 SD2
DFRH DFLH OPEN4
COMP1 COMP2
COMP3 COMP4
COMP6COMP5
LT11LT1 0
LT OP1 LT OP2
McQuay IM 738-2 21
Introduction

Controls, Settings, and Functions

Table 3 below lists all of the unit control devices and associated information.
Table 3: Controls, settings, and functions
Symb
ol
CS1 &
2
DAT
DHL
EFT
FP1, 2
FS1
HP1,
2,
3 & 4
LP1, 2
MCB
MP1–
6
OAE
OAT
PC5
Description Function
Switch (toggle), refrigerant circuit
Discharge air temperature sensor
Duct high limit switch
Entering fan air temperature sensor
Evaporator frost protection
Freezestat
High pressure control
Low pressure control
Main control board Processes input information
Compressor motor protector
Enthalpy control (electro­mechanical)
Enthalpy control (electronic)
Outside air temperature sensor
Dirty filter switch Senses filter pressure drop
Shuts off compressor control circuits manually
Senses discharge air temperature
Prevents excessive VAV duct pressures; shuts off fan
Senses entering fan air temperature
Senses low refrigerant temperature
Shuts off fans, opens heating valve, and closes outdoor damper if low air temperature at coil is detected Stops compressor when refrigerant discharge pressure is too high
Stops compressor when suction pressure is too low (used for pumpdown)
Senses motor winding temperature, shuts off compressor on high temperature. Notes:
1.Unit size 018C compressors include internal motor protector.
2.Unit sizes 020C–036C, circuit #1 compressors include internal motor protector (refer to unit wiring diagram).
Returns outside air dampers to minimum position when enthalpy is too high
Returns outside air dampers to minimum position when outside air enthalpy is higher than return air empalthy (use RAE)
Senses outside air temperature
Rese
t
N/A
N/A
Auto
N/A
N/A
Auto
Manu
al (relay latche
d)
Auto Compressor
N/A
Auto
at
3400
ohms
Auto
Auto
N/A N/A N/A
Auto
Location Setting Range Differential Part no.
Main control
panel
Discharge air
section
Main control
panel
Inlet of supply
fan
Return bends
of evaporative
coil
Heating
section
Compressor
Main control
box
Compressor
junction box
Economizer
section
Economizer
section
First filter
section
N/A N/A N/A 01355000
N/A N/A
3.5" w.c
(871.8 Pa)
N/A N/A
Opens at
30°F
Closes at
45°F
38°F (3°C)
or as
required
See page
131.
See page
131.
N/A N/A N/A
9 K–18 K
ohms
“B” or as required
Fully CW
past “D”
(when used
with RAE)
As required
0.05–5.0" wc (12.5–1245.4
Pa)
N/A N/A
35°F–45°F (2°C–7°C)
N/A
N/A
700 ohms cold N/A
A–D
A–D N/A
.05-5" wc
(12.5–1245.4
Pa)
.05" wc
(12.5 Pa),
fixed
12°F (7°C),
fixed
100 psi
(689 kPa)
25 psi
(172 kPa)
Temperature:
3.5°F (2°C) Humidity:
5% fixed
.05" wc
(12.5 Pa)
06000470
5
06549380
1
06000470
5
07250190
1
06583000
1
04735612
0
047356111
06000610
1
04469150
9
03070670
2
04926220
1
06000470
5
06549380
1
22 McQuay IM 738-2
Table 3: Controls, settings, and functions (continued)
Symb
ol
PC6
PC7
PS1,
2
RAE
RAT
SD1
SD2
SPS1
SPS2
SV1,
2
SV5,
6
S1
S7
Description Function
Dirty filter switch Senses filter pressure drop
Airflow proving switch
Pumpdown switch Used to manually pump down
Return air enthalpy sensor
Return air temperature sensor
Smoke detector, supply air
Smoke detector, return air
Static pressure sensor duct #1
Static pressure sensor duct #2
Static pressure sensor: building (space) pressure
Solenoid valve (liquid line)
Solenoid valve (hot gas bypass)
System switch
ON-OFF-AUTO switch
Senses supply fan pressure to prove airflow
compressor
Used to compare return air enthalpy to outside air enthalpy (used with OAE)
Senses return air temperature
Initiates unit shutdown if smoke is detected
Initiates unit shutdown if smoke is detected
Converts static pressure signals to voltage signals
Converts static pressure signals to voltage signals and sends them to MicroTech II controller
Converts static pressure signals to voltage signals.
Closes liquid line for pumpdown
Closes hot gas bypass line for pump-down
Shuts off entire control circuit (except crankcase heaters)
Used to manually switch unit
Rese
Auto
Auto
N/A
N/A
N/A
ManualDischarge air
ManualReturn air
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Location Setting Range Differential Part no.
t
Final filter
section
Supply fan
section
Condenser control box
Economizer
section
Return air
section
section
section
Main control
box
Main control
box
Main control
box
Condenser
section
Condenser
section
Main control
box
Main control
box
Introduction
As required
.10" wc (25
Pa)
N/A N/A N/A 01355000
N/A N/A N/A
N/A N/A
N/A N/A N/A 04925001
N/A N/A N/A 04925001
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A 111011001
N/A N/A N/A
N/A N/A N/A
.05-5" wc
(12.5–1245.4
Pa)
.03-1.40" wc
(7.5–348 Pa)
0–5" wc (0–1245.4 Pa) 1–6 V (dc) out
0–5" wc (0–1245.4 Pa) 1–6 V (dc) out
-025–0.25" wc
(-62.3–62.3 Pa)
1–5 V (dc) out
.05" wc
(12.5 Pa)
.03" wc
(7.5 Pa),
fixed
N/A
N/A
N/A
06549380
06001580
04926220
06000470
04954500
04954500
04954500
00135500
1
1
2
5
7
7
6
See parts
catalog
0
FanTrol
The FanTrol, provided on all units, is a method of head pressure control that automatically cycles the condenser fans in response to ambient air temperature. This feature maintains
head pressure and allows the unit to run at low ambient air temperatures.
RPS/RDT and RCS units have two independent refrigerant circuits with one to four condenser fans being controlled independently by the ambient air temperature of each circuit.
Table 4: R-22 FanTrol setpoints in °F with MicroTech II controls
RPS RCS RDT RPR
015 to 020C0 5 60 5 ———— 025 to 030C0 5 65 5 ————
0360 5 70 5 ————
045 to 045C0 5 65 5 ————
0500 5 60 5 ———— 0600 5255705—— 0700 5405705——
075 to 090C 0 5 65 5 75 5 0 5
1050505585705 1150505555755 1250 5655355805 1350 5555255655
Setpoint Differential Setpoint Differential Setpoint Differential Setpoint Differential
B05 B06 B07 B08
McQuay IM 738-2 23
Degrees Farenheit
Introduction
Table 5: R-407C FanTrol setpoints in °F with MicroTech II controls
RPS, RCS, RDT
Setpoint Differential Setpoint Differential Setpoint Differential Setpoint Differential
015 0 5 60 5 018 to 020C0505———— 025 to 036C0 5 65 5 ————
040 0 5 60 6
0450 5 55 5 ————
050 0 5 50 5
0600 5155705——
0700 5305705——
0750 5655755 0 5 080 to 090C 0 5 65 5 75 5 0 5
1050505525705
1150505455755
1250 5555305805
1350 5455205655
B05 B06 B07 B08
Degrees Farenheit
24 McQuay IM 738-2

Mechanical Installation

Mechanical Installation
Note – The installation of this equipment shall be in accordance
with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes. Low head pressure may lead to poor, erratic refrigerant feed control at the thermostatic expansion valve. The units have automatic control of the condenser fans which should provide adequate head pressure control down to 50°F (10°C) provided the unit is not exposed to windy conditions. The system designer is responsible for assuring the condensing section is not exposed to excessive wind or air recirculation.
CAUTION
Sharp edges on sheet metal and fasteners can cause personal injury. This equipment must be installed, operated, and serviced only by an experienced installation company and fully trained personnel.
Receiving Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and
Figure 27: Service clearances
72"
(1829 mm)
cartons have been received. If the unit has become dirty during shipment (winter road chemicals are of particular concern), clean it when received.
All units should be inspected carefully for damage when received. Report all shipping damage to the carrier and file a claim. In most cases, equipment ships F.O.B. factory and claims for freight damage should be filed by the consignee.
Before unloading the unit, check the unit nameplate to make sure the voltage complies with the power supply available.

Unit Clearances

Service Clearance
Allow an approximate service clearance as indicated in Figure 27. Also, McQuay recommends providing a roof walkway to the rooftop unit as well as along two sides of the unit that provide access to most controls and serviceable components.
60"
(1524 mm)
Roof walkway
To roof access
location
A
60"
(1524 mm)
BC
DE
96"
(2438 mm)
Varies with unit arrangement
Refer to certified drawing & note.

Ventilation Clearance

Below are minimum ventilation clearance recommendations. The system designer must consider each application and provide adequate ventilation. If this is not done, the unit will not perform properly.
Unit(s) surrounded by a screen or a fence:
C
F
60"
(1524 mm)
Legend:
A = Return air section B = Filter section C = Cooling section D = Cooling/supply fan section E = Heat section F = Discharge plenum section
1
The bottom of the screen or fence should be at least 1 ft. (305 mm) above the roof surface.
2 The distance between the unit and a screen or fence should
be as described in Figure 27.
3 The distance between any two units within a screen or
fence should be at least 120" (3048 mm).
McQuay IM 738-2 25
Mechanical Installation
Unit(s) surrounded by solid walls:
1 If there are walls on one or two adjacent sides of the unit,
the walls may be any height. If there are walls on more than two adjacent sides of the unit, the walls should not be higher than the unit.
2 The distance between the unit and the wall should be at
least 96" (2438 mm) on all sides of the unit.
3 The distance between any two units within the walls should
be at least 120" (3048 mm).
Do not locate outside air intakes near exhaust vents or other sources of contaminated air.
If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified (see Figure 28). This is particularly important to prevent blowing snow from entering the outside air intake and to maintain adequate head pressure control when
Figure 28: Overhead clearance
Overhead canopy
mechanical cooling is required at low outdoor air temperatures.

Overhead Clearance

1 Unit(s) surrounded by screens or solid walls must have no
overhead obstructions over any part of the unit.
2 The area above the condenser must be installed
unobstructed to allow vertical air discharge.
3 The following restrictions must be observed for overhead
obstructions above the air handler section (see Figure 28):
a There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b Overhead obstructions must be no less than 96"
(2438 mm) above the top of the unit.
c There must be no overhead obstructions in the areas
above the outside air and exhaust dampers that are farther than 24" (610 mm) from the side of the unit.
24" (610 mm) maximum
96" (2438 mm)
minimum,
top of unit to
permanent
overhead
obstruction
9" (229 mm) minimum to flue box, typical all sides
Flue box
24" (610 mm) maximum
26 McQuay IM 738-2
Mechanical Installation
Roof Curb Assembly and Installation
Locate the roof curb and unit on a portion of the roof that can support the weight of the unit. The unit must be supported to prevent bending or twisting of the machine.
If building construction allows sound and vibration into the occupied space, locate the unit over a non-critical area. It is
the responsibility of the system designer to make adequate provisions for noise and vibration in the occupied space.
WARNING
Mold can cause personal injury. Some materials such as gypsum wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation.
Install the curb and unit level to allow the condensate drain to flow properly and allow service access doors to open and close without binding.
Figure 29: RCS roof curb assembly
6 "
" Z Z "
6 "
1 . U n i t B a s e
B
A
A
2 . G a l v a n i z e d C u r b 3 . G a l v a n i z e d C u i r b C o v e r 4 . 2 x 4 N a i l e r S t r i p 5 . R i g i d I n s u l a t i o
6 "
6 . C a n t S t r i p ( n o t f u r n i s h e d ) 7 . F l a s h i n g ( n o t f u r n i s h e d ) 8 . C u r b G a s k e t i n g 9 . I n s u G a l v a n i z e d C u r b ( n o t f u r n i s h e d ) 1 0 . R o o f i n g M a t e r i a l ( n o t f u r n i s h e d )
B
A
A
n ( n o t f u r n i s h e d )
l a t i o n b e t w e e n
Integral supply and return air duct flanges are provided with the RPS/RFS roof curb, allowing connection of duct work to the curb before the unit is set. The gasketed top surface of the duct flanges seals against the unit when it is set on the curb. These flanges must not support the total weight of the duct work. See “Installing Ductwork” on page 58for details on duct connections. It is critical that the condensate drain side of the unit be no higher than the opposite side.
Assembly of a typical RPS/RDT roof curb is shown in Figure 30 on page 28. Parts A through K are common to all units having bottom return openings. Depending on the unit length, Parts L and M may be included with the roof curb kit to create the correct overall curb length.
Figure 29 shows the assembly of the RCS roof curb.
RCS unit size
015C–030C 31.0 787
6 "
D e t a i l C
1
5
6
8
4
7
9
3
4
5
1 0
2
036C & 040C 94.0 2057
045C–060C 62.0 1575 070C–105C 100.0 2540 115C–135C 120.0 3048
in. mm
“ZZ”
RCS Assembly instructions
1 Set curbing parts “A” (Figure 29) in place making sure that
the orientation complies with the assembly instructions. Check alignment of all mating bolt holes.
2 Bolt curbing parts together using fasteners provided.
3 Curb must be level from side to side and over its length.
4 Weld curbing in place. Caulk all seams watertight and
insulate between channels.
5 Flash curbing into roof as shown in Detail C.
RPS/RDT Assembly instructions
1 Set curbing parts A through K per dimensions shown over
roof opening or on a level surface (see Figure 30 on page 28). Note location of return and supply air openings.
2 If applicable, set other curbing parts (D, L, M, etc.) in place
making sure that the orientation complies with the assembly instructions (see Detail A). Check alignment of
3 Bolt curbing parts together using fasteners provided.
Tighten all bolts finger tight.
4 Square entire curbing assembly and securely tighten all
bolts.
5 Position curb assembly over roof openings. Curb must be
level from side to side and over its length. Check that top surface of the curb is flat with no bowing or sagging.
6 Weld curbing in place. Caulk all seams watertight. Remove
backing from 0.25" (6 mm) thick × 1.50" (38 mm) wide gasketing and apply to surfaces shown by cross-hatching.
7 Flash curbing into roof as shown in Detail B.
8 Parts E and F are not required on units with no return shaft
within the curb perimeter.
9 Parts G and H are not required on units with no supply shaft
within the curb perimeter.
10 Be sure that electrical connections are coordinated (see
Figure 36).
all mating bolt holes.
McQuay IM 738-2 27
Mechanical Installation
Figure 30: RPS/RFS roof curb assembly
28 McQuay IM 738-2
Mechanical Installation
Table 6: Roof curb assembly dimensions
Unit size Fan
None 24.0 610 82.0 2083 6.8 173 1.5 38 015C–030C 45.9 1165 20.0 508
015–040C
045C–075C All units 38.0 965 87.0 2210 8.8 222 3.5 89 105C—135C 113 2870 46.0 1168
80C–135C All units 62.0 1575 87.0 2210 8.8 222 3.5 89
Note: These dimensions do not apply to units with energy recovery wheels.
(2) 15” FC 24.0 610 82.0 2083 6.8 173 1.5 38
30" AF 30.0 762 76.0 1930 6.8 173 4.5 114 045C–075C 77.0 1956 28.0 712 40" AF 36.0 914 78.0 1981 14.8 376 3.5 89 80C–90C 113 2870 38.0 965
“X” “Y” “XX” “YY”
in mm in mm in mm in mm in mm in mm
Unit size
036C and
040C
“Z” “W”
94.0 2388 20.0 508
McQuay IM 738-2 29
Mechanical Installation

IBC Seismic Compliant Units

It is important to follow these installation instructions for all IBC Seismic compliant McQuay Rooftop units.
IBC Seismic compliant McQuay Rooftop units can be mounted to either a roof curb or a post and rail setup. If using a roof curb, it must be specifically designed for seismic restraint and be IBC seismic compliant (spring isolated or non-isolated type seismic roof curbs are available). Typical construction of a seismic rated roof curb is from structural steel framing and contains seismic hold down brackets for attachment of the rooftop unit (see Figure 31). Post and rail arrangements rated for seismic applications are also available (spring isolated or non-isolated).
IMPORTANT: An acceptable IBC seismic installation provides a direct positive attachment to both the building structure and the roof mounted equipment.
Refer to the roof curb manufacturer’s submittal drawings for actual roof curb assembly, attachment details and rigging instructions for both roof curb and post and rail arrangements.
Figure 31: Typical seismic roof curb (spring isolated)

Roof Curb Arrangement

1 Set the rooftop unit on the roof curb (McQuay Rooftop
units are designed to overhang from the roof curb).
2 Adjust the seismic hold down brackets so they come into
contact with the unit base per Figures 32 and 33 on page
31.
a The seismic hold down brackets should be adjustable
and accommodate the overhang of the rooftop unit.
b If the hold down bracket cannot reach the unit base, use
a shim spacer. See Figure 33 on page 31.
3 Weld each seismic hold down bracket (and shim spacer, if
required) to the unit base as shown in the acceptable weld zone detail in Figure 32 on page 31.
CAUTION
When welding unit to the curb, do not damage wiring (control panel side). Weld ONLY in the specified zone in the acceptable weld zone (see Figure 32 on page 31). Welding must comply with weld fillet size, etc. as indicated in Figure 32 on page 31.
Note – High temperature insulation is installed at the factory to
allow for field welding along the lower front edge region of the unit base.
Duct opening
Seismic hold down brackets
Structural steel frame
Seismic hold down brackets
Spring isolator
30 McQuay IM 738-2
Loading...
+ 114 hidden pages