McQuay OAC 003G, OAH 003G, OAH 090G, OAC 090G Maintenance Manual

Installation and Maintenance Manual IM 777-7
Skyline™ Air Handler
Models OAC/OAH 003G – 090G
Group: Applied Air Systems
Part Number: IM 777
Date: November 2011
© 2011 McQuay International
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . 5
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Curb Mounting and Unit Leveling . . . . . . . . . . . . . . . 5
Assembling Sections . . . . . . . . . . . . . . . . . . . . . . . . . 6
Shipping Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Panels, Frame Channels, and Doors . . . . . . . . . . . . . 8
Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Frame Channel Removal . . . . . . . . . . . . . . . . . . . . . . 8
Access Doors and Panels . . . . . . . . . . . . . . . . . . . . . 8
Fan Section Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Injected-Foam Insulated Panels . . . . . . . . . . . . . . . . . 9
Field Mounting Junction Boxes and
Other Components . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dampers and Hoods . . . . . . . . . . . . . . . . . . . . . . . . . 10
Mounting Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Face and Bypass Section Mounting . . . . . . . . . . . . 11
Isolation Dampers for Multiple Fans . . . . . . . . . . . . 11
Piping Vestibules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Piping and Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Water Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . 11
Direct Expansion Coils . . . . . . . . . . . . . . . . . . . . . . . 12
Steam Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Heating Coils . . . . . . . . . . . . . . . . . . . . . . . . . 14
Drain Pan Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Internal Isolation Assembly Adjustment . . . . . . . . . 15
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . 19
Startup Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Before Starting the Unit . . . . . . . . . . . . . . . . . . . . . . 19
VFD Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Wheel Alignment . . . . . . . . . . . . . . . . . . . . . . . 20
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fan Vibration Levels . . . . . . . . . . . . . . . . . . . . . . . . 24
Vibration Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Service and Maintenance . . . . . . . . . . . . . . . . . . . . 25
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . 25
Ball Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . 25
Motor Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
VM and VP Variable Pitch Key Type Sheaves . . . . 26
LVP Variable Speed Sheaves . . . . . . . . . . . . . . . . . 27
MVP Variable Speed Sheaves . . . . . . . . . . . . . . . . 28
Fan Drive Belt Adjustment . . . . . . . . . . . . . . . . . . . 30
Front Load Filter Option . . . . . . . . . . . . . . . . . . . . . 31
Filter Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Winterizing Water Coils . . . . . . . . . . . . . . . . . . . . . . 32
Removing and Replacing Components . . . . . . . . . 32
Removing the Fan Section . . . . . . . . . . . . . . . . . . . 32
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Service and Warranty Procedure . . . . . . . . . . . . . . 36
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Warranty Return Material Procedure . . . . . . . . . . . 36
Check, Test, and Start Procedure Form . . . . . . . . . 37
Quality Assurance Survey Report . . . . . . . . . . . . . 39
Introduction
General Information
Introduction
Receiving and Handling
The system design and installation must follow accepted industry practice as described in the ASHRAE Handbook, the National Electric Code, and other applicable s t a n d ar d s . Install this equipment in accordance with regulations of authorities having jurisdiction and all applicable codes.
Installation and maintenance must be performed by qualified personnel familiar with applicable codes and regulations and experienced with this type of equipment. Sheet metal parts, self-tapping screws, fins, clips, and such items inherently have sharp edges; the installer should exercise caution.
CAUTION
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
Nomenclature
2AH 003 G D A C
1 Carefully check items against the bills of lading to verify
all crates and cartons have been received. Carefully inspect all units for shipping damage. Report damage immediately to the carrier and file a claim.
2 Skyline air handler units are constructed of galvanized or
painted steel and are inspected thoroughly before leaving the factory. Take care during installation to prevent damage to units.
3 Take special care when handling the blower section. All
fans are dynamically balanced before leaving the factory . Rough handling can cause misalignment or a damaged bearings or shaft. Carefully inspect fans and shaft before unit installation to verify this has not happened.
Note: Screws, bolts, etc., for assembling sections are supplied
in a bag attached to each section. All necessary gasketing is applied in the factory for section-to-section mounting, unless the unit has a curb ready base. Units require caulk sealant between sections.
Model
OAH = Custom modular air handler OAC = Custom modular component
Nominal unit size (cataloged size—nominal square foot of coil)
003, 004, 006, 008, 010, 012, 014, 017, 021, 025, 030, 035, 040, 050, 065, 080, 085, 090
Vintage of McQuay air handling unit
Unit cross section
C = Standard unit cross section M = Custom size cross section
Motor location
A = Motor along side of fan housing D = Motor down stream of belt drive
plenum fan
F = Motor on inline fan
G = Motor downstream of direct drive
plenum fan
H = Motor downstream of fan array
T = Motor behind twin fan housing
Unit type/coil position
B = Blow-through cooling coil location D = Draw-through cooling coil location H = Heating only V = Vent only M = Multizone
McQuay IM 777-7 3
Introduction
Unit Storage
Store on a level surface in a clean, dry location where
temperature can be controlled if possible.
Pack fan and motor bearings (unless motor bearings are
sealed) with compatible grease with the shaft stationary. After grease has been installed, rotate shaft about 10 rotations.
Isolate unit from shock and vibration.
Once a month, rotate shaft a minimum of 10 revolutions.
Insure the stopped position is different than the original position.
Coat shafts with lubricant as needed to prevent corrosion.
A descant bag may be hung in the interior of the unit to
minimize corrosion in humid storage environments.
Do not clean galvanized steel surfaces with oil dissolving
chemicals. This may remove the protective coating and accelerate corrosion.
Do not allow coverings to trap moisture on galvanized
surfaces.
Belt driven fans:
Reduce belt tension by at least 50% or remove the belts.
Remove belts if they will be subjected to temperatures exceeding 85° F to avoid deterioration.
• Remove belt guard when adjusting belts
• Reduce belt tension prior to removing or installing belts. Removing or installing tensioned belts may cause per­sonal injury and damage to the sheaves, belts, bearings or shafts.
Adjustable sheaves should be opened as wide as possible
and the adjustment threads lubricated so they do not corrode. Be careful not to put lubricant on the belt running surface
Prior to start up:
Set screws on bearings, fan wheels, and sheaves need to be
checked for proper torque. Also check bolt torque for any taper lock hubs either on the wheel or sheaves.
Check sheaves for corrosion. Significant corrosion can cause
belt or sheave failure.
Purge old grease from fan bearings while rotating the shaft
to distribute the new grease evenly and prevent bearing seal failure.
Correctly align and tension belts. See General Rules of
T ensioning‚ page 30.
Mechanical Installation
4 . 0 0 " b a s e r a i l e x t e n s i o n
W i d t h
3 0 . 0 0 "
4 . 0 0 "
W i d t h o f c o i l s e c t i o n
W i d t h o f
f a n s e c t i o n
3 0 . 0 0 "
H e i g h t
5 4 "
1 2 "
Service Clearances
Mechanical Installation
Rigging
In addition to providing adequate space around the unit for piping coils and drains, access to at least one side of the unit is always required to allow for regular service and routine maintenance, which includes filter replacement, drain pan inspection and cleaning, fan bearing lubrication, and belt adjustment. Provide sufficient space—at least equal to the length of the coil—on the side of the unit for coil removal. See
Figure 1 for servicing space requirements.
Maintain at least 54" of clearance in front of electrical power devices. Electrical power devices that are mounted on the side of the unit typically are up to 12" deep (Figure 2). Fan sections with multiple fans have motor control boxes up to 16” deep when supplied with VFDs.
Figure 1: Servicing Space Requirements
Skyline air assembled, or in modules of assembled sections.
handlers ship as separate sections, completely
The unit must be rigged as it ships from the factory. Do not rig units after assembly.
and
Units are
can be lifted using the 2" diameter lifting holes located in
the corners of each shipping section.
provided with a factory-installed base rail
To prevent damage to the unit cabinetry, use spreader bars. Position spreader bars to prevent cables from rubbing the frame or panels. Before hoisting into position, test lift for stability and balance. Avoid twisting or uneven lifting of unit.
Figure 3: Unit and Section Rigging
Figure 2: Service Clearance for Electrical Power Devices
Curb Mounting and Unit Leveling
Do not place a Skyline unit over an open curb unless it is equipped with a curb-ready base. Installation instructions for mounting units on a roof curb are provided in IM 770. For a copy, contact your local McQuay representative or visit www.mcquay.com. Make provisions under the unit to divert any moisture from entering the building below.
For units without roof curb mounting, place the equipment on a flat and level surface. Where surface irregularities exist, shim the base of the unit at one or more points along the length of the rails to prevent distortion or sagging of the support rails. Uneven or distorted sections cause misfit or binding of the doors and panels and improper draining of drain pans (Figure 4).
McQuay IM 777-7 5
Mechanical Installation
S h i m t o p r e v e n t d i s t o r t i o n i f w i d t h i s o v e r 1 0 8 "
S h i m s e c t i o n s u n t i l t h e y a r e s t r a i g h t a n d l e v e l
1 / 4 " d i a m e t e r b e a d c e n t e r e d i n f a c e o f c l e a r a n c e
U s e S p l i c e J o i n t a s a g u i d e
R e m o v a b l e L i f t i n g B r a c k e t
3/8" x 1" Bolt and Nut
“D”
Gasket
If the unit is supported on rails they must be placed around the entire perimeter. Additional Supports must be placed perpendicular to airflow spanning the full width of the unit at all shipping splits. If the unit is over 107” wide these supports must also be placed at the entering and leaving edges of fan and cooling coil sections. The perimeter rails must be at least 2” wide at the top and capable of carrying the entire weight of the unit. The cross supports must be 4” wide at the top and capable of carrying the weight of the two sections it spans. The cross supports shall be placed such that 2” of the top is supporting each section. The perimeter rails shall be placed so that they are fully supporting the outer 2” of the unit. If shims are required they must be placed such that the unit is fully supported.
Figure 4: Leveling the Unit
2
Pull sections together to fasten. Use straps and a ratchet to help pull the sections together securely. Apply sealant to any gaps that may admit moisture.
3 Fasten base rails together first using the 3/8"-16 × 5"
bolts located in the splice kit provided with the unit (Figure 7).
a To fasten two shipping sections together, four bolts
are needed (two on each side of the unit). The bolts are run from one base rail into the other and fastened with a nut. Complete each section bottom and top before attaching additional sections.
b If desired, shipping sections for non curb-ready units
can be fastened together internally. To fasten internally, run field-provided #10 sheet metal screws or drill screws (4" long, maximum) through the interior frame channel of one unit into the splice joint of the neighboring section.
c Handle units with curb-ready bases and vestibules so
the lifting bracket can be removed after the unit is placed on the curbing.
Note: Remove the lifting bracket that projects inward over
the curbing. Save the self tapping screws. When the adjacent section is placed in position, use self tapping screw to secure the bases together.
Assembling Sections
If the unit is shipped in more than one shipping section, rig each section into position separately. Shipping sections are provided with a connection splice joint attached on the leaving air side of the shipping section that seals against the frame channel on the entering-air side of the adjoining. The splice joint is insulated and provides an air-tight seal between two sections once they are assembled together. Align the splice joint to seat into the mating gasket to provide an air seal. If the splice joint was bent during shipping or rigging, restore it to its original position (Figure 9). For Skyline Plus units, ensure that the D-gasket is attached to the entering air side frame channel (Figure 7 and Figure 10).If it dislodged during shipping, restore it to its designed position.
Shipping Sections
1 Caulk all assembly joints of the unit—Before joining the
sections, apply at least 1/4 inch diameter bead of sealant to the mating faces of the cabinet. Use the splice joint as a guide for applying the sealant (Figure 5).
Figure 5: Apply Sealant to Mating Faces
Figure 6: Remove Vestibule Lifting Bracket
Figure 7: Fasten Bottom of Section
Mechanical Installation
V i e w A
A
S p l i c e C o l l a r m u s t b e a l i g n e d t o s e a l t o g a s k e t .
5 / 1 6 - 1 8 N u t
S p l i c e P l a t e
5 / 1 6 - 1 8 B o l t
S l i d e S p l i c e C a p o n a n d b e n d e n d s d o w n
d A length of “D” gasket is attached to each section
(Figure 7). This gasket MUST be installed to the unit base section.
IMPORTANT
The gasket is to be installed in an arc shape with the ends lower than the center, so that any moisture that may reach the gasket will be drained to the outside of the unit.
e Handle units with curb-ready bases and vestibules so
the lifting bracket can be removed after the unit is placed on the curbing.
Note: Remove the lifting bracket that projects inward over
the curbing. Save the self tapping screws. When the adjacent section is placed in position, use self tapping screw to secure the bases together.
f For certain Skyline Plus units, use the provided
section joining plates to fasten sections together. Space them as shown in Figure 8. Using the provided ¼"-14 x 1" self tapping screws, drill screw the joining plates into the frame channel on each section, keeping unit sections tight together. Follow instruction drawing included in the assembly kit.
Figure 8: Frame Channel Stiffener Plates (Skyline Plus Units Only)
Figure 10: D-Gasket Placement Detail (Skyline Plus Units Only)
1
Check that the sealant is compressed between the mating
channels when the unit sections are joined. T ouch up any places where gaps are noted.
2 After sections are seated tightly together, slip the splice
cap over the top panel flanges. Bend the ends of the splice cap down to secure in place (Figure 11).
3 Assemble the small splice plate at the top rail to secure
the sections together at the top. Use 5/16" bolts (Figure 11).
Figure 11: Splice Cap and Splice Plate
Figure 9: Internal Fastening
McQuay IM 777-7 7
Mechanical Installation
Remove panel to remove frame
Remove any panel screws that engage frame
Panels, Frame Channels, and Doors
Panel Removal
To remove a side or top panel, remove the flat head Torx 30 fasteners along the sides of the panel. Lift off the panel after removing all fasteners.
Frame Channel Removal
Frame channels that run the length of the unit along the top can be removed to allow access to both the side and top of the unit. To remove the frame channel, first remove the side panel(s). Once the side panel is off, remove the flat head Torx 30 fasteners in the corner of the frame channels. Then pull the frame channel out the side. Remove any panel screws that are within one inch of the of the frame since they are engaged into the gasketed flange of the frame (Figure 12).
Figure 12: Removing Panel Screws
Fan Section Doors
Note: Opening fan section doors requires using a 1/2" socket
wrench (Figure 13), which satisfies ANSI standards and other codes that require the “use of tools” to access compartments containing moving parts or electrical
wiring.
CAUTION
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
1
Insert 1/2" socket and rotate 1/4 turn clockwise as shown in
Figure 13. If the handle is on the left side of the door, rotate
1/4 turn counterclockwise.
2 Rotate the door handle 1/4 turn clockwise and then 1/4 turn
counterclockwise to release any internal pressure or vacuum and open the door. If the handle is on the left side of the door, rotate the door handle 1/4 turn counterclockwise and then 1/4 turn clockwise.
3 To prevent air leakage, tighten the door panels by adjusting
the jam nuts.
Access Doors and Panels
For routine maintenance, access normally is obtained through access doors or by removing side panels. Removing all flat head fasteners along the sides of a panel allow it to be removed.
Fan and filter sections are always provided with a service door on one side of the unit. If requested on order, doors can be provided on both sides of the unit. Optional service doors are available for most section types and are provided based on customer request.
Figure 13: Opening Fan Section Door
Mechanical Installation
D i s c h a r g e
P l e n u m
Injected-Foam Insulated Panels
Skyline air handlers now are furnished with double-wall, injected-foam insulated panels. Foam panels are stronger, more rigid, and lighter than panels with fiberglass insulation. The insulation R-value is improved to 13. However, foam insulation can burn when exposed to flame or other ignition sources and release toxic fumes. Take care in cutting and sealing all field-cut openings in these panels.
Panel Cutting Procedure
1 Determine the number and location of holes required for
electrical conduit, piping, and control wiring as follows:
a Check that adequate space is available inside the unit
for conduit or pipe routing.
b Do not locate holes in a panel that provides access to
key maintenance components such as filters and fan assemblies.
c Do not locate where the conduit or piping blocks
airflow or obstructs hinged access doors.
2 Once a proper location is determined, drill a small pilot
hole completely through the panel. Then use a sharp hole saw or a saber saw and cut from each side of the panel.
3 Seal the double-wall panel on each side with an
industrial/commercial grade silicone sealant or duct seal compound. It is extremely important to seal each panel hole or penetration securely so it is airtight, watertight, and so that there is no exposed insulation.
Figure 14: Cutting/Sealing Injected-Foam Insulated Pan els
Seal completely with silicone
Cut hole from both sides of panel
Prop 65—Substances in fuel or from fuel combustion can cause personal injury or death, and are known to the State of California to cause cancer, birth defects or other reproductive harm.
sealant or duct seal compound
Field Mounting Junction Boxes and Other Components
For field mounting 4" × 4" or smaller junction boxes to the standard panel exterior, use a minimum quantity of four, 3/16" diameter pop rivets. Do not use self-tapping drill screws.
They will not tighten nor secure properly and panel damage can occur.
If larger, heavier components require mounting on unit panels, use through-bolts with flat washers through both outer and inner panels. To maintain panel integrity, seal both ends with an industrial/commercial grade silicone sealant or duct seal compound.
WARNING
Flame and smoke can cause equipment damage, severe personal injury, or death.
Before operating unit, seal all piping and wiring holes on both inner and outer panels with an industrial grade silicone sealant or duct seal compound. Do not use a cutting
torch or expose panel to fire. Panel damage can occur.
WARNING
La fumée et les flammes peuvent endommager le matériel et causesr des blessures graves ou la mort. Avant d’utiliser le dispositif, obturer tous les trous de passage de tubulures et de fils ménagés dans les panneaux intérieurs et extérieurs au moyen d’une pâte à base de silicone ou d’un mastic d’étanchéite â conduits de qualité industrielle. Ne pas se servir d’un chalumeau coupeur ni exposer les pannequx à une flamme nue pour ne pas risquer de les endommager.
The unit frame channel is another excellent location for securing heavier components; self-tapping screws are not acceptable. Ensure that the location permits the full operation of all access doors and panels and does not interfere with other vital components.
Duct Connections
Use flexible connectors on the outlet and inlet duct connections of all units. Do not position down flow fans over air ducts that are routed down into the building. Use a discharge plenum when bottom connections are necessary (Figure 15).
Figure 15: Discharge Plenum
McQuay IM 777-7 9
Mechanical Installation
F l a s h i n g
D u c t
F l a s h i n g
U n i t t o p p a n e l
F l a s h i n g
D u c t
F l a s h i n g
Remove screws and panel to access damper control shaft.
Hood
E x h a u s t
I n t a k e
B a r r i e r
If the unit has a top mixing box or economizer damper or a top duct connection, field fabricate and install flashing to divert moisture from the connection. The flashing must lap over the standing seams of the top panels. The flashing also must lap over the side edges of the unit (Figure 16).
Figure 16: Flashing Over To p Pan el s and Sid es of Units
Dampers and Hoods
Side dampers may be provided in the mixing box and economizer sections of units. When dampers are provided, a removable panel is located above the weather hood to provide access to the damper drive shaft. Other access may be available depending on the specific construction of the unit (Figure 17).
Figure 17: Filler Panel Over the Weather Hood
Figure 18: Field-Installed Barrier Between Hoods
Mounting Actuators
The installing contractor is responsible for the mounting of all field-installed actuators. No provisions are made for the location of these actuators due to the number of options and arrangements available and the variety of specific applications. Typically, actuators are mounted inside the cabinet. Provide proper support for the actuator to avoid excessive stress in the cabinet, linkage, or damper shafts.
Note: Damper blades are at full flow when open to 70 degrees.
Do not open blades further than 70 degrees.
Fresh air and return air dampers can be linked together and driven from the same actuator if the dampers are the same size. If the dampers are different sizes, they must be driven by separate actuators and controlled appropriately. Exhaust dampers are always driven by a separate actuator.
When units are ordered with exhaust hoods and intake hoods adjacent to each other, install a field-supplied barrier to prevent recirculation of exhaust air into the intake openings. (Figure 18).
A typical rotary electric actuator can handle up to 40 sq. ft. of damper. For pneumatic actuators, allow 5 in-lb per square foot of damper area.
CAUTION
Maximum damper rotation is 70°. Maximum shaft torque is 205 inches/pound. Greater rotation or torque can cause equipment damage.
ATTENTION
La rotation maximale des volets est de 70°. Le couple (torque) maximum de l’arbre est de 205po/lb. Une plus grande rotation (ou torque) peut endommager l’équipement.
Mechanical Installation
Seal holes cut for piping
Seal holes cut for piping
Face and Bypass Section Mounting
Internal and external face and bypass sections are mounted together using the instructions for horizontal components and do not require additional instruction. Skyline air handlers are provided with a bypass duct that is integral to the unit construction and requires no field assembly.
Face and bypass dampers may or may not be linked together. When dampers are placed before a single bank of coils, they always are linked together and require a single actuator. When dampers bypass a stacked or staggered coil, the dampers are not linked and require multiple actuators.
Face and bypass dampers have a torque requirement of 10 in-lbs per square foot of damper face area.
Isolation Dampers for Multiple Fans
Optional isolation dampers can be provided on multiple fans to prevent backflow through a fan that is turned off for service. These isolation dampers are not intended to be used to control flow through the fan. The isolation damper for a fan that is going to be started must be positioned in the full open position before the fan is started. Do not start a fan with the damper located at the inlet with the damper fully or partially closed. This can cause airflow, vibration, and sound problems that can lead to failure.
Isolation dampers can be provided with actuators that are mounted in the airstream. Actuator sizing for the isolation dampers should be based on 9 in-lb per square foot of damper.
Piping Vestibules
For units that include a piping vestibule, cut the openings for routing the field piping as required in the field. Carefully seal passages cut through the panels to prevent air leakage. A single metal thickness pan is provided in the bottom of the curb-mounted vestibule. The pan can be removed if necessary. If holes are cut into the pan for a piping passage, seal the holes to prevent moisture leakage (Figure 19).
Figure 19: Seal Holes for Piping—Curb Mounted Units
For units with standard base rails, the vestibule is open to the coil section; therefore, seal all holes to prevent air leakage.
Figure 20: Seal Holes for Piping—Standard Base Rail Units
Piping and Coils
When designing and installing piping:
Follow applicable piping design, sizing, and instal lation
information in ASHRAE handbooks.
Observe all local codes and industry standards.
Do not apply undue stress at the connection to coil headers;
always use a backup pipe wrench.
Support pipework independently of the coils.
Water Cooling Coils
Note: Use glycol in water coils for outdoor air handlers. Power
failures and other mechanical issues can expose coils to freezing temperatures.
Water supply, water return, drain, and vent connections
extend through the end panel of the coil section. All connections are labeled on the end panel.
Water supply and water return connections are typically
male NPT iron pipe.
When installing couplings, do not apply undue stress to the
connection extending through unit panel. Use a backup
pipe wrench to avoid breaking the weld between coil connection and header.
Follow recommendations of the control manufacturer
regarding types, sizing, and installation of controls.
McQuay IM 777-7 11
Mechanical Installation
Direct Expansion Coils
The coil distributor and suction connection extend through
the end panel of the coil section.
Check nozzle in distributor for proper tonnage.
When a (field supplied) thermostatic expansion valve is
located outside the unit and connected directly to the distributor (except on units with piping vestibules). Do not apply heat to the body of the expansion valve.
The thermostatic expansion valve must be the external
equalizer tube type. Connect the 1/4-inch diameter external equalizer tube provided on the coil to the connection on the expansion valve.
Use care when piping the system, making sure all joints are
tight and all lines are dry and free of foreign material. For typical refrigerant piping, see condensing unit product manual.
Steam Coils
Piping (see Figure 21)
Steam supply and steam return connections typically are
male NPT iron pipe and are labeled on the end panel of coil section. Connections extend through the coil section end panel.
When installing couplings, do not ap ply undue stress to the connection extending through unit panel. Use a backup
pipe wrench to avoid breaking the weld between coil connection and header.
Support piping independently of coils and provide adequate
piping flexibility. Stresses resulting from expansion of closely coupled piping can cause serious damage.
Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket, making the reduction at the branch leading to the trap.
Coils
Pitch all steam coils in units toward the return connection.
Do not drip supply mains through the coil.
Do not attempt to lift condensate when using modulating or
on/off control.
Install vacuum breakers on all applications to prevent retaining condensate in the coil. Generally, connect the vacuum breaker between the coil inlet and the return main. The vacuum breaker should be open to the atmosphere and the trap design should allow venting of large quantities of air.
Traps
Note: Do not place steam traps outdoors.
Size traps in accordance with the manufacturers’
recommendations. Make sure the required pressure differential is always available. Do not undersize.
Use float and thermostatic or bucket traps for low pressure
steam. On high pressure steam, use bucket traps. Use thermostatic traps only for air venting.
Use bucket traps for on/off control only.
Locate traps at least 12 inches below the coil return
connection.
Multiple coil installation—individually trap each coil or
group of coils.
Coils in series—use separate traps for each coil, or a bank of
coils.
Coils in parallel—a single trap can be used, but an individual
trap for each coil is preferred.
Do not attempt to lift condensate when using modul ating or
on/off control.
With coils arranged for series airflow, use a separate control
on each bank or coil in the direction of airflow.
Valves
Do not use modulating steam valves on high pressure
systems.
Properly size modulating valves. Do not undersize.
Avoid freezing conditions (entering air temperatures below
35°F).
McQuay strongly recommends 5JA, 8JA, 5RA and 8RA
coils.
Supply 5 psi steam to coils at all times.
Do not use modulating valves. Provide control by face and
bypass dampers.
Consider using two or three coils in series with two position
steam control valves on the coil or coils that handle 35°F or colder air. Use a modulating valve on the downstream coil to provide the desired degree of control.
Thoroughly mix fresh air and ret urn air before it enters the
coil. Also, to obtain true air mixture temperatures, properly locate temperature control elements.
As additional protection against freeze-up, install the trap
sufficiently below the coil to provide an adequate hydrostatic head to remove condensate during an interruption in the steam pressure. Estimate three feet for each 1 psi of trap differential required.
On startup, admit steam to coil ten minutes before admitting
outdoor air.
Close fresh air dampers if steam supply pressure falls below
the minimum specified.
Loading...
+ 28 hidden pages