McQuay CCH User Manual

MicroTech® III Controllers for Open Choices™ Integration
For Daikin McQuay Water Source Heat Pump Products
and Ennity
water source heat pumps are equipped with factory-mounted MicroTech® III unit controls for optimized performance. Optional Open Choices communication modules provide easy integration with your building automation system using BACnet® or
LonWorks
®
networks.
Open Choices Advantages
Easy, low cost integration into building automation systems without expensive gateway panels
Comprehensive unit control and status information available with either BACnet or LonWorks. See typical points list on reverse
• Easy conguration and simplied addressing to reduce
installation time
SmartSource
1 or 2-stage
horizontal unit
Advanced Control Strategies and Troubleshooting for Optimized Performance
The MicroTech III unit controller with a LonWorks or BACnet communication module coordinates the following operations for advanced control and easy troubleshooting.
Enable heating and cooling to maintain setpoint
Monitor discharge air temperature
Space temperature control
Monitor leaving water temperature
Enable fan cycling and compressor operation
Relay status of all vital unit functions
Monitor all equipment protection controls
On-board status LEDs aid in diagnostics by indicating
the water source heat pump communication conditions
Remotely reset alarms and adjust setpoints
SmartSource
1 or 2-stage vertical unit
Daikin McQuay water source heat pumps are available with MicroTech III controls and the Open Choices feature.
Ennity console
in-room unit
Ennity vertical oor
mounted unit
Engineered for flexibility and performance
Comprehensive Data Available
The MicroTech III unit controller provides water source heat
pump unit status information and noties your BAS of alarm
conditions, regardless of the communication protocol.
BACnet MS/TP
LonTaLk SCC (FTT-10A) designed in accordance
with the LonM a rk® Space Comfort Control (SCC)
Functional Prole
Units are
LonMark 3.4 certied with the appropriate
communications module for LonWorks® networks.
Open Choices Feature Components
The BACnet or LonWorks communication module can be
factory or eld installed and is tested with all logic required
to monitor and control the water source heat pump unit. The MicroTech III controller with communication module
includes unit-mounted return air, discharge air and leaving water temperature sensors. Options include a tenant setpoint adjustment knob and tenant override button and the ability to substitute the return air sensor with wall-mounted room sensor.
Typical Data Points
1
LonWorks only BACnet only SmartSource models only Ennity models only
Inputs (read/write only)
Application Mode Auxiliary Heat Enable Clear Alarm Compressor Enable Energy Hold Off Fan On/Auto Remote Input Humidistat Remote Input Occupancy Override Occupancy Scheduler Occupancy Sensor Space Temperature
Conguration Properties
Brownout Reference Setpoint Occupied differential Cooling Interstage Timer Setpoint Cooling Setpoint High/Low Limit Heating Interstage Timer Setpoint Heating Setpoint High/Low Limit
HVAC Unit-Type Identier
Hydronic Cooling On Setpoint Hydronic Heating On Setpoint Hydronic Setpoint Differential Interstage Off Timer Setpoint Interstage On Timer Setpoint Local Bypass Time Setpoint Location Label Long Range Setpoint Adjust Min/Max Low Entering Water Temp for Glycol Low Entering Water Temp for Water Low Leaving Water Temp Differential Low Pressure Alarm Delay Low Temperature Protection Setpoint Low Temp Protection Setpoint for Glycol Low Temperature Protection Differential Minimum Compressor Off Timer Setpoint Minimum Compressor On Timer Setpoint Minimum Send Time Occupancy Temperature Setpoints Receive Heartbeat Room Sensor Setpoint Enable/Disable Send Heartbeat Setpoint Control Adjustment Software Identication Unit Application Unoccupied Differential 2nd – 4th Stage Setpoint Differential
2
Outputs (read only)
Binary Input Status Binary Output Status Brownout (Shutdown) Condensate Overow Current Alarm Previous Alarm Discharge Air Temperature Effective Occupancy Effective Setpoint Entering Water Temperature Fan On/Auto Status Fan Running Output Fan Speed Heat/Cool/Auto Status Humidistat Status Leaving Water Temperature Local Setpoint Local Setpoint Shift Local Space Temperature Daikin McQuay WSHP Status Pump Request Space Temperature
Status Suction Temperature Compressor #1 Suction Temperature Compressor #2 Unit Status
NOTE: 1. Due to our policy of continuous product improvement, data
points may change. For the most current information, refer to
publication ED 15103 available on www.DaikinMc Quay.com.
2. Conguration proper ties reside in EEPRO M that
has a write cycle limit of approximately 10000 writes. Do not unnecessarily write to conguration properties as this can limit the life of the device.
Alarms
Condensate Overow Entering Water Temp Sensor Fail Low Voltage Brownout Room Temp Sensor Fail Serial EEPROM Corrupted
Comp #1 High Pressure Comp #2 High Pressure Comp #1 Low Pressure Comp #2 Low Pressure Comp #1 Low Suction Temp Sensor Fail Comp #2 Low Suction Temp Sensor Fail Comp #1 Low Suction Temp Comp #2 Low Suction Temp
Invalid Jumper Congu ration
Comp High Pressure Comp Low Pressure Comp Suction Temp Sensor Fail Comp Low Suction Temp Freeze Fault Detect IO Exp Communication Fail
Invalid Conguration
Leaving Water Temp Sensor Fail Low Entering Water Temp WSE Low Temp Cutout
The following are tradenames or registered trademarks of their respective companies: BACnet from ASHR AE; Ennity, MicroTech III, Open Choices and SmartSource from Daikin McQuay.
are managed, granted and used by LonMark International under a license granted by Echelon Corporation.
©2012 McQuay International • (80 0) 432-1342 • www.DaikinMcQuay.com A/SP 31-264 (06/12)