MicroTech® III Controllers for Open Choices™ Integration
For Daikin McQuay Water Source Heat Pump Products
Daikin McQuay SmartSource
™
and Ennity
™
water source
heat pumps are equipped with factory-mounted MicroTech®
III unit controls for optimized performance. Optional Open
Choices communication modules provide easy integration
with your building automation system using BACnet® or
LonWorks
®
networks.
Open Choices Advantages
• Easy, low cost integration into building automation
systems without expensive gateway panels
• Comprehensive unit control and status information
available with either BACnet or LonWorks. See typical
points list on reverse
• Easy conguration and simplied addressing to reduce
installation time
SmartSource
1 or 2-stage
horizontal unit
Advanced Control Strategies and Troubleshooting for
Optimized Performance
The MicroTech III unit controller with a LonWorks or
BACnet communication module coordinates the following
operations for advanced control and easy troubleshooting.
• Enable heating and cooling to maintain setpoint
• Monitor discharge air temperature
• Space temperature control
• Monitor leaving water temperature
• Enable fan cycling and compressor operation
• Relay status of all vital unit functions
• Monitor all equipment protection controls
• On-board status LEDs aid in diagnostics by indicating
the water source heat pump communication conditions
• Remotely reset alarms and adjust setpoints
SmartSource
1 or 2-stage
vertical unit
Daikin McQuay water
source heat pumps
are available with
MicroTech III controls
and the Open Choices
feature.
Ennity console
in-room unit
Ennity vertical oor
mounted unit
Engineered for flexibility and performance
™
Comprehensive Data Available
The MicroTech III unit controller provides water source heat
pump unit status information and noties your BAS of alarm
conditions, regardless of the communication protocol.
• BACnet MS/TP
• LonTaLk SCC (FTT-10A) designed in accordance
with the LonM a rk® Space Comfort Control (SCC)
Functional Prole
Units are
LonMark 3.4 certied with the appropriate
communications module for LonWorks® networks.
Open Choices Feature Components
The BACnet or LonWorks communication module can be
factory or eld installed and is tested with all logic required
to monitor and control the water source heat pump unit.
The MicroTech III controller with communication module
includes unit-mounted return air, discharge air and leaving
water temperature sensors. Options include a tenant setpoint
adjustment knob and tenant override button and the ability
to substitute the return air sensor with wall-mounted room
sensor.
Typical Data Points
1
■ LonWorks only ■ BACnet only ■ SmartSource models only ■ Ennity models only
Inputs (read/write only)
Application Mode
Auxiliary Heat Enable
Clear Alarm
Compressor Enable
Energy Hold Off
Fan On/Auto Remote Input
Humidistat Remote Input
Occupancy Override
Occupancy Scheduler
Occupancy Sensor
Space Temperature
■
■
Conguration Properties
Brownout Reference Setpoint
Occupied differential
Cooling Interstage Timer Setpoint
Cooling Setpoint High/Low Limit
Heating Interstage Timer Setpoint
Heating Setpoint High/Low Limit
HVAC Unit-Type Identier
Hydronic Cooling On Setpoint
Hydronic Heating On Setpoint
Hydronic Setpoint Differential
Interstage Off Timer Setpoint
Interstage On Timer Setpoint
Local Bypass Time Setpoint
Location Label
Long Range Setpoint Adjust Min/Max
Low Entering Water Temp for Glycol
Low Entering Water Temp for Water
Low Leaving Water Temp Differential
Low Pressure Alarm Delay
Low Temperature Protection Setpoint
Low Temp Protection Setpoint for Glycol
Low Temperature Protection Differential
Minimum Compressor Off Timer Setpoint
Minimum Compressor On Timer Setpoint
Minimum Send Time
Occupancy Temperature Setpoints
Receive Heartbeat
Room Sensor Setpoint Enable/Disable
Send Heartbeat
Setpoint Control Adjustment
Software Identication
Unit Application
Unoccupied Differential
2nd – 4th Stage Setpoint Differential
■
2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Outputs (read only)
Binary Input Status
Binary Output Status
Brownout (Shutdown)
Condensate Overow
Current Alarm
Previous Alarm
Discharge Air Temperature
Effective Occupancy
Effective Setpoint
Entering Water Temperature
Fan On/Auto Status
Fan Running Output
Fan Speed
Heat/Cool/Auto Status
Humidistat Status
Leaving Water Temperature
Local Setpoint
Local Setpoint Shift
Local Space Temperature
Daikin McQuay WSHP Status
Pump Request
Space Temperature
■
Status
Suction Temperature Compressor #1
Suction Temperature Compressor #2
Unit Status
NOTE: 1. Due to our policy of continuous product improvement, data
■
■
■
points may change. For the most current information, refer to
publication ED 15103 available on www.DaikinMc Quay.com.
2. Conguration proper ties reside in EEPRO M that
has a write cycle limit of approximately 10000 writes. Do not
unnecessarily write to conguration properties as this can
limit the life of the device.
Alarms
Condensate Overow
Entering Water Temp Sensor Fail
Low Voltage Brownout
Room Temp Sensor Fail
Serial EEPROM Corrupted
Comp #1 High Pressure
Comp #2 High Pressure
Comp #1 Low Pressure
Comp #2 Low Pressure
Comp #1 Low Suction Temp Sensor Fail
Comp #2 Low Suction Temp Sensor Fail
Comp #1 Low Suction Temp
Comp #2 Low Suction Temp
Invalid Jumper Congu ration
Comp High Pressure ■
Comp Low Pressure
Comp Suction Temp Sensor Fail
Comp Low Suction Temp
Freeze Fault Detect
IO Exp Communication Fail
Invalid Conguration
Leaving Water Temp Sensor Fail
Low Entering Water Temp
WSE Low Temp Cutout
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
The following are tradenames or registered trademarks of their respective companies: BACnet from ASHR AE; Ennity,
MicroTech III, Open Choices and SmartSource from Daikin McQuay.
are managed, granted and used by LonMark International under a license granted by Echelon Corporation.
©2012 McQuay International • (80 0) 432-1342 • www.DaikinMcQuay.com A/SP 31-264 (06/12)