McQuay CCH Installation Manual

Page 1
Operation & Maintenance Data
Group: WSHP Part Number: 910134617 Date: August 2012
MicroTech® III Unit Controller for Water Source Heat Pump Units
©2012 McQuay International • 800.432.1342 • www.daikinmcquay.com
Page 2
Page 3
Contents
Introduction ..........................................................................3
Replacing a MicroTech III circuit board: Initial Power-Up General Use and Information
Occupied Operation Thermostat Inputs (G, Y1, Y2, W1 and W2) Control Inputs (HP, LP, SLTS, COF, U, E, O)
Control Outputs {A and IV/PR (H8)}..................................8
Fan Operation Unoccupied Operation – Stand Alone Thermostat Control
Thermostat Inputs (G, Y1, Y2, W1, and W2) Control Inputs (HP, LP, SLTS, COF, U, E, O)
Control Outputs {A and IV/PR (H8)}..................................9
Additional Operating Modes
High / Low Pressure Faults (HP/LP)
Fan Operation during most Modes, Faults and Shutdowns
Troubleshooting the MicroTech III Unit Controller Troubleshooting the Water Source Heat Pump Unit Microtech® III Unit Controller Interface to External
Equipment Appendix A
Operation and Maintenance of I/O Expansion Module Introduction
Features..........................................................................15
Initial Power up
...................................................................6
.............................................7
..........................................................7
...................................................................8
...........................................................8
...............................................9
.........................................................................12
..........................................................................15
.........................................................................15
.....................................................................15
..................................................................16
............................6
.....................7
....................7
....................8
....................9
...............................10
.........12
......14
...15
Operation
Dual Circuit Units
Thermostat Inputs (Y2, W2)............................................17
Electric Heat Controls
Boilerless Heat Coil Control
Multiple Speed Fan Control
Three-Speed Fan Operations
Circuit Two, Additional Operating Modes
Second Circuit Faults......................................................18
Appendix B
MicroTech III Unit Controller with Communication Module MicroTech III Controller with BACnet® Communication Module
Appendix C – Typical Wiring Diagrams
MicroTech III Unit Controller (Standalone) – 208/230/460/575/60Hz/3-Phase MicroTech III Unit Controller with Optional ECM Motor, Desuperheater and I/O Expansion Module – 208/230/265/277/60 Hz/1-Phase MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, Electric Heat Coil and I/O Expansion Module – 208/230/460/60 Hz/3-Phase MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, and I/O Expansion Module 208/230/460/60/3-Phase MicroTech III Unit Controller with PSC Motor, Desuperheater and I/O Expansion Module for Hot Gas Reheat Control (Unit Sizes 019-070) 208/230/60/1-Phase
Controller Comparison
............................................................................17
............................................................17
.......................................................17
............................................17
..............................................17
.........................................17
.......................17
........................................................................19
LonWorks®
..................................................19
............................................................................20
...........................21
.....................................21
....................................22
...........................23
................................................24
.......................................................25
....................................................26

Introduction

This installation and operation manual covers the Micro­Tech® III unit controller for Daikin McQuay Water Source Heat Pumps. For information on LonWorks® or BACnet® communication modules and other ancillary components, see:
■ IM 927 - MicroTech III Water Source Heat Pump
LonWorks Communication Module.
■ IM 928 - MicroTech III Water Source Heat Pump Unit
Controller BACnet MS/TP Communication Module.
■ IM 933 - LonWorks Plug-In Software for use with MicroTech III Unitary Controller - LonWorks
Communication Module.
■ IM 952 - Multiple Unit Control Panel (MUCP) for use with MicroTech III Unit Controller and Mark IV Unit
Controller.
■ IM 955 - MicroTech III Water Source Heat Pump Wall-
Mounted Room Temperature Sensors.
■ IM 956 - Temperature Sensors for Units with MicroTech
III Unit Controller and LonWorks Communication
Module.
OM 931-4 / Page 3 of 28
Page 4
Table 1: MicroTech III Unit Controller Terminals & Descriptions
H1 - 1 24 24 VAC Power Input
H1 - 2 C 24 VAC Common
H2 - 1 SL1 Fan Output - Switched L1
H2 - 2 Blank Terminal
H2 - 3 N Fan Neutral
H3 - 1 HP1-1 High Pressure Switch 1 Input Terminal 1
H3 -2 HP1-2 High Pressure Switch 1 Input Terminal 2
H4 - 1 Discharge Air Temp Common
H4 - 2 Discharge Air Temp Signal
H4 - 3 Leaving Water Temp Common
H4 - 4 Leaving Water Temp Signal
H5 - 1 1 I/O Expansion Board Common (Gnd)
H5 - 2 I/O Expansion Board Common (Gnd)
H5 - 3 I/O Exp Board +5 VDC
H5 - 4 I/O Expansion Board SPI CE1
H5 - 5 I/O Expansion Board SPI CLK
H5 - 6 I/O Expansion Board SPI OUT
H5 - 7 I/O Expansion Board SPI IN
H5 - 8 I/O Expansion Board +12 VDC
H5 - 9 I/O Expansion Board 24 VAC
H5 - 10 I/O Expansion Board 24 VAC
H5 - 11 Spare
H5 - 12 Spare
H6 - 1 1 Condensate Overow Signal Input
H6 - 2 Low Temp 1 Sensor Common
H6 - 3 Low Temp 1 Sensor Signal
H6 - 4 Low Pressure Switch 1 Source Voltage
H6 - 5 Low Pressure Switch 1 Signal
H6 - 6 Reversing Valve 1 Common
H6 - 7 Reversing Valve 1 Output
H7 - 1 1 Dummy Terminal
H7 - 2 Dummy Terminal
H7 - 3 Red LED Output
H7 - 4 Green LED Output
H7 - 5 Yellow LED Output
H7 - 6 Red-Green-Yellow LED Common
H8 - 1 1 Isolation Valve/Pump Request Relay N/O
H8 - 2 Isolation Valve/Pump Request Relay N/C
H8 - 3 24 VAC Common
H9 - 1 1 Return Air Temperature Signal
H9 - 2 Return Air Temperature Common
TB1 - 1 1 Room Sensor LED Output
TB1 - 2 2 Fan Mode / Heat-Cool-Auto Input
TB1 - 3 3 Setpoint Adjust Input
TB1 - 4 4 Room Temperature Sensor / Tenant Override
TB1 - 5 5 DC Signal Common
Test-1 R 24 VAC
Test-2 W2 Heat Stage 2 Input
Test-3 W1 Heat Stage 1 Input
Test-4 Y2 Cool Stage 2 Input
Test-5 Y1 Cool Stage 1 Input
Test-6 G Fan
TB2 - 1 R 24 VAC
TB2 - 2 A Alarm Output
TB2 - 3 W2 Heat Stage 2 Input
TB2 - 4 W1 Heat Stage 1 Input
TB2 - 5 Y2 Cool Stage 2 Input
TB2 - 6 Y1 Cool Stage 1 Input
TB2 - 7 G Fan Input
TB2 - 8 O Tenant Override Input
TB2 - 9 C 24 VAC Common
TB3 - 1 E Mark IV Emergency Shutdown Input
TB3 - 2 U Mark IV Unoccupied/Occupied Input
L1 - 1 L1 - 1 Line Voltage Terminal 1
L1 - 2 L1 - 2 Line Voltage Terminal 2
L1 - 3 L1 - 3 Line Voltage Terminal 3
N1 N1 Neutral T erminal 1 N2 N2 Neutral T erminal 2
N3 N3 Neutral Terminal 3
Page 4 of 28 / OM 931-4
Page 5
Figure 1: MicroTech III Unit Controller Terminal Locations
OM 931-4 / Page 5 of 28
Page 6
CAUTION

Initial Power-Up

The MicroTech III circuit board incorporates static sensitive de-
vices. A static charge from touching the device can damage the electronic components. To help prevent damage during service, use static discharge wrist straps.Static discharge wrist straps are grounded to the heat pump chassis through a 1 Mohm resistor.
Pre start check list:
A random start delay time between 180 and 240 seconds is
generated at power up.
Figure 2: Location of Configuration Jumpers on the Base Board Controller

Replacing a MicroTech III circuit board:

1. Connect wrist strap to unit.
2. Remove faulty board and place on static protected surface.
3. Remove replacement board from static protected bag.
Do not touch circuit board; hold by edges.
4. Holding board in grounded hand, install board in unit.
5. Insert faulty board in empty static bag for return.
Table 2: Configuration Jumper Settings
Jumper Description Options
JP1 Mode
Shorted for service/test operation mode JP2 Fan operation only applies to Open for continuous fan operation network controls Shorted for cycling fan operation
JP3 Freeze protection
Shorted for antifreeze protection JP4 Future spare Future spare JP5 Set point adjustment range only Open for adjustment range of -3.0° to +3.0° F applies to network controls with a Shorted for 50° to 90° F adjustment range
room temperature sensor
JP6 Room control type
Shorted for room temperature sensor control, MicroTech III only
JP7 Future spare Future spare
JP8 Future spare Future spare
Open for normal operation mode
Open for water freeze protection
Open for thermostatic room control
Page 6 of 28 / OM 931-4
Page 7

General Use and Information

The MicroTech III unit controller is provided with two drive
terminals, R (24VAC), and C (0VAC) that can be used to drive the thermostat inputs (G, Y1, Y2, W1, and W2) and control inputs (U, E and O). Any combination of or single
board drive terminal (R, or C) may be used to operate the Mi-
croTech III’s unit controller or thermostat inputs. Some of the control inputs are used within the Water Source Heat Pump
and not accessible to the end user without a eld service tool (laptop with appropriate software).
Typically the MicroTech III unit controller's R (24VAC)
terminal is used to drive the board’s thermostat inputs and control inputs by connecting it to the R terminal of an indus­try standard thermostat. The control outputs of the standard thermostat are then connected to the MicroTech III unit controller's thermostat inputs and control inputs as needed.
Any remaining board input(s) may be operated by additional thermostat outputs or remote relays (dry contacts only).
All MicroTech III unit controller inputs must be operated by dry contacts powered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate Micro­Tech III unit controller inputs. No outside power sources may be used to operate MicroTech III. All units must be properly grounded per local code requirements. See the Installation
and Maintenance bulletin specic to your Water Source Heat
Pump.

Occupied Operation

ellow
Y
Of
The board will be in occupied mode if the unoccupied
terminal (U) is de-energized.

Thermostat Inputs (G, Y1, Y2, W1 and W2)

Thermostat inputs used during occupied operation are G, Y1, and W1, which when energized will activate the Fan Only, Cooling Mode, and Heating Mode respectively. Input W2 and Y2 work the same as W1 and Y2 respectively for single circuit units in occupied mode. For information on W2 and Y2 for dual circuit units, refer to "Dual Circuit Units" on page
17.
Board LED Status – Occupied
f
Green
On
Red
Of
f
The MicroTech III unit controller is congured so that when either the Y1 or W1 input is energized the unit fan is also
activated with Cooling or Heating Modes. In other words,
energizing Y1 and G together will have the same effect as en-
ergizing just Y1. The W1 input has priority over the Y1 input. In situations when both inputs W1 and Y1 become energized (unlikely) in any order the unit will go into the Heating Mode
as described below:
1. If the unit is in Cooling Mode, Y1 is energized. If W1
becomes energized and remains energized, the following
will occur:
• The compressor de-energizes.
• The compressor restarts at 180 seconds (powerup delay timer).
• The reversing valve output energizes within 5 to 20 seconds of the compressor being energized (Heating Mode position), depending on the conguration of jumpers JP7 and JP8.
2. If the unit is in Cooling Mode, Y1 is energized. If W1
becomes energized momentarily, the controller de­energizes the compressor for 180 seconds (shortcycle timer) and then returns to the cooling mode.
3. However, if the unit is in Heating Mode, W1 is energized.
If Y1 becomes energized the unit remains in Heating
Mode.
4. Y2 is the second stage cooling, and applies to dual
compressor units.

Control Inputs (HP, LP, SLTS, COF, U, E, O)

The control inputs are High Pressure (HP), Low Pressure (LP), Suction Line Temperature Sensor (SLTS), Condensate Overow (COF), Unoccupied (U), and Remote Shutdown (E). The control inputs are in normal states during occupied
mode. The state of each control in occupied mode during normal operation is as follows:
• High / Low Pressure (HP, LP): energizes, switch is closed
(no fault).
• Suction Line Temperature Sensor (SLTS): temperature
sensor on the suction line which provides low temperature
protection. Condensate Overow(COF):sensing no condensate water (no fault).
• Unoccupied (U): de-energized (no signal).
• Remote Shutdown (E): de-energized (no signal).
• Tenant Override (O): has no effect in occupied mode.
OM 931-4 / Page 7 of 28
Page 8

Control Outputs {A and IV/PR (H8)}

The control outputs are Alarm Fault (A) and Isolation Valve / Pump Request {IV/PR (H8)}. The operation of the control
outputs during occupied mode is as follows:
• Alarm Fault (A): energized (no fault).
• Isolation Valve / Pump Request {IV/PR (H8)}: is selectable to be energized when the compressor is off (normally closed), or when the compressor is on (normally open), by moving the wire lead to the appropriate
terminal.
Figure 3: H8 Terminals on MicroTech III Board

Fan Operation

The G terminal controls continuous fan operation. The fan runs continuously when the G terminal is energized. When the G terminal is de-energized, the fan cycles with the compressor.
Cooling Mode
The Y1 terminal controls the Cooling Mode of operation. When the Y1 terminal is energized (24VAC), the following
occurs:
1. The fan energizes.
2. The IV/PR (H8) control output de-energizes or energizes
depending on the H8 terminal wiring (refer to Table 1 on
page 4 & Figure 1 on page 5).
3. The compressor energizes after 30 seconds.
4. If the reversing valve output is energized, the reversing valve out put will be de-energize within 5 to 20 seconds of the compressor being energized, depending on the conguration of jumpers JP7 and JP8.
When the Y1 terminal is de-energized, the following occurs:
1. The compressor de-energizes.
2. The fan de-energizes, unless the G terminal is energized (24VAC).
3. The IV/PR (H8) control output energizes or deenergizes
depending on the H8 terminal wiring (refer to Table 1 on
page 4 & Figure 1 on page 5).
4. The reversing valve output remains de-energized.
Note: To prevent compressor cycling, the required minimum
on/off time default is 180 seconds. This may cause the compressor time delay to be longer than indicated above.
Heating Mode
The W1 terminal controls the occupied Heating Mode of
operation. When the W1 terminal is energized, the following
occurs:
1. The fan energizes
2. The IV/PR (H8) control output de-energizes or energizes
depending on the H8 terminal wiring (refer to Table 1 on
page 4 & Figure 1 on page 5).
3. The compressor energizes after 30 seconds.
4. If the reversing valve output is de-energized, the reversing valve output will be energize within 5 to 20 seconds of the compressor being energized, depending on the conguration of jumpers JP7 and JP8.
When the W1 terminal is de-energized, the following occurs:
1. The compressor de-energizes.
2.The fan de-energizes, unless the G terminal is energized.
3. The IV/PR (H8) control output energizes or deenergizes
depending on H8 terminal wiring (refer to Table 1 on page
4 & Figure 1 on page 5).
4. The reversing valve output remains energized.
Note: To prevent compressor cycling, the required minimum
on/off time default is 180 seconds. This may cause the compressor time delay to be longer than indicated above.

Unoccupied Operation – Stand Alone Thermostat Control

The board will be in unoccupied mode if the unoccupied
terminal (U) is grounded.
ellow
Y
On
Board LED Status – Unoccupied
Green
On
Red
Of
f

Thermostat Inputs (G, Y1, Y2, W1, and W2)

The only thermostat input used during unoccupied operation
is W2, which when energized will activate Heating Mode. Inputs G, Y1, Y2 and W1 have no effect during unoccupied
mode.
Figure 4: Terminal "U" - Grounded for Unoccupied
Page 8 of 28 / OM 931-4
Page 9

Control Inputs (HP, LP, SLTS, COF, U, E, O)

The control inputs are High Pressure (HP), Low Pressure (LP), Suction Line Temperature Sensor (SLTS), Condensate Overow (COF), Unoccupied (U), and Remote Shutdown (E). The state of each control input during unoccupied mode
during normal operation is as follows:
■ High / Low Pressure (HP, LP): energizes, switch is closed (no fault).
■ Suction Line Temperature Sensor (SLTS): greater than setpoint unit operates (no fault).
■ Condensate Overow (COF): sensing no condensate water (no fault).
■ Unoccupied (U): energizes (signal provided).
■ Remote Shutdown (E): de-energizes (no signal).
■ Tenant Override (O): see "Tenant Override" on page 11.

Control Outputs {A and IV/PR (H8)}

The control outputs provided by the MicroTech III unit
controller are Alarm Fault (A) and Isolation Valve / Pump Request (IV/PR (H8)). The operation of the control outputs
during unoccupied mode is the same as in occupied mode
(see "Occupied Operation" on page 7).
Fan Operation
The G terminal has no effect during unoccupied mode.
Cooling Mode
Cooling operation is not available during unoccupied mode.
Heating Mode
The W2 terminal controls the unoccupied Heating Mode of operation. When the W2 terminal is energized the following
occurs:
1. The fan energizes.
2. The IV/PR (H8) control output energizes or deenergizes depending on H8 terminal wiring (refer to Table 1 on page 4 & Figure 1, page 5).
3. The compressor will start 30 seconds later.
4. If the reversing valve output is de-energized, the reversing valve output will energize within 5 to 20 seconds of the compressor being energized, depending on the conguration of jumpers JP7 and JP8.
When the W2 terminal is de-energized the following occurs:
1. The compressor de-energizes.
2. The IV/PR (H8) control output energizes or deenergizes depending on H8 terminal wiring (refer to Table 1 on page 4 & Figure 1, page 5).
3. The reversing valve remains energized.
Note: To prevent compressor cycling, the required
minimum on/off time default is 180 seconds. This may cause the compressor time delay to be longer than indicated above.

Additional Operating Modes

Brownout
ellow
Y
Of
Brownout condition is provided to protect the water source heat pump’s motor electrical damage due to low voltage conditions.
The MicroTech III unit controller is designed to monitor the
24VAC power supply to the board. If the line voltage supplied to the water source heat pump drops, the 24VAC supply to the
control board will also drop. When the line voltage supplied to the unit drops below approximately 80% of the unit name­plate rated value, the controller goes into brownout condition. The controller remains in brownout condition until line volt-
age returns to approximately 90% of the unit nameplate value.
When in brownout condition, thermostat and control inputs have no affect upon unit operation. No faults or modes have higher priority than a brownout fault condition. Remote shutdown and brownout conditions have the same level of priority. See "Priority of Faults and Modes" on page 12 and
Table 3 on page 12.
When the unit is in brownout condition the following occurs:
1. The compressor de-energizes.
2. The reversing valve de-energizes.
3. The fan de-energizes.
4. Fault terminal (A) de-energizes (fault). A to C will be used
to indicate an alarm signal.
When the line voltage supplied to the unit returns to accept-
able levels (~90% of nameplate) the controller returns to the
current mode.
Remote Shutdown
ellow
Y
Flash
When the E terminal is grounded, the MicroTech III unit
controller enters remote shutdown mode. Remote shutdown is provided so that when properly connected to a building
automation system, remote switch, etc., the E terminal can be
used to shut down the water source heat pump.
Figure 5: Terminal "E" - Grounded for Remote Shutdown
Board LED Status – Brownout
f Flash
Board LED Status – Remote Shutdown
Green
Green
f
Of
Red
Of
Red
Of
f
f
OM 931-4 / Page 9 of 28
Page 10
When in remote shutdown (E terminal grounded), thermostat
and control inputs have no affect upon unit operation. No faults or modes have higher priority than remote shutdown. Remote shutdown and brownout condition have the same level of priority. See "Priority of Faults and Modes" on page 12 and Table 3 on page 12.
When the unit is in remote shutdown mode, the following occurs:
1. The compressor de-energizes.
2. The reversing valve de-energizes.
3. The fan de-energizes.
4. Fault terminal (A) de-energizes (fault). A to C will be used
to indicate an alarm signal.
When the E terminal is no longer grounded the unit will auto­matically return to normal operation.
Note: The remote shutdown input (E) will suspend unit
operation. Disconnect power when servicing the unit/ controller.

High / Low Pressure Faults (HP/LP)

Normally closed high and low refrigerant pressure switches help protect the water source heat pump from excessively high or low refrigerant pressures. The MicroTech III unit con­troller monitors these switches individually. If the compressor is running and the HP circuit is open, the controller enters a
pressure fault mode. If the compressor is running and the LP
circuit is open after a time delay (default of 30 seconds, ad-
justable if a communication module is present) the controller
enters a low pressure fault mode. The fan operates normally during a pressure fault condition.
HP
LP
Only brownout and remote shutdown modes have higher pri­ority than the pressure fault mode. See "Priority of Faults and
Modes" on page 12 and Table 3 on page 12.
When the unit is in high pressure fault mode the following occurs:
1. The compressor de-energizes.
2. The fault terminal (A) de-energizes (fault). A to C will be
used to indicate an alarm signal.
3. After the shutdown is complete the IV/PR(H8) output will change state. (On to Off / Off to On).
High Pressure Reset
After the HP circuit is closed, the unit does not return to normal operation until the control board is reset. The unit is locked out in this manner until the unit can be serviced.
The control board is reset by a short interruption of unit pow­er, by holding down the tenant override button for more than
10 seconds, or via the Building Automation System (BAS).
Board LED Status – High/Low Pressure Faults
ellow Green
Y
f
Of Of
f f
Of Of
f
Red
Flash
Solid
Low Pressure Reset
The low pressure switch fault is subject to intelligent reset. If the pressure recovers, it resets three times within a 24-hour time period. If further faults are detected within the 24 hours,
the controller must be manually reset as described in the High Pressure Reset section above.
Low Suction Line Temperature Fault
Board LED Status – Low Suction Line T
ellow
Y
Flash
Green
Of
f
emperature Fault
Red
Of
f
Heating Mode
When the suction line temperature falls below 28°F on stan-
dard equipment (6.5°F on Geothermal) the low temperature
fault generates the following:
■ The reversing valve de-energizes. The compressor and fan continue to operate in cooling mode for 60 seconds, which
results in a defrost mode. This defrosts any ice that may have accumulated in the water-to-refrigerant coil, because
of a lack of condenser water ow in heat mode.
■ In heat mode the low temperature fault is subject to
Intelligent Reset.
■ The fault terminal A de-energizes while the unit is in defrost mode. It will stay de-energized until the temperature recovers to 38°F for standard equipment (18°F for geothermal). A to C will be used to indicate an
alarm signal.
Cooling Mode
When the suction line temperature falls below 28°F standard equipment (6.5°F geothermal) in cool mode the:
■ Compressor de-energizes.
■ The fan continues to run for 60 seconds.
■ Alarm output de-energizes.
■ When the suction line temperature recovers to 38°F standard equipment (18°F on geothermal) the low
temperature fault continues and the unit will be locked out.
Fan Only Mode
When the suction line temperature falls below 28°F standard equipment (6.5°F geothermal) in cool mode the:
■ Fan de-energizes.
■ Alarm output de-energizes.
■ In Fan Only mode, the low temperature fault is subject to
Intelligent Reset.
Page 10 of 28 / OM 931-4
Page 11
Condensate Overow
Board LED Status – Condensate Overow
ellow
Y
On
Green
f
Of
Red
Of
f
The MicroTech III unit controller's condensate sensor is designed to detect excessively high condensate water levels in the drain pan. When high condensate water levels are detected during cooling mode, the controller enters into condensate fault mode. The fan operates normally during the
condensate overow fault mode.
Some faults and modes have higher priority than condensate
overow mode. See "Priority of Faults and Modes" on page
12 and Table 3 on page 12.
When the unit senses a condensate overow fault while in
cooling mode the following occurs:
1. The compressor de-energizes.
2. The fault terminal (A) de-energizes (fault). A to C will be
used to indicate an alarm signal.
When condensate levels return to normal, the controller will automatically return to normal operation.
Remote Reset of Automatic Lockouts
The Remote Reset feature provides the means to remotely reset some lockouts generated by high-pressure and/or low­temperature faults. When the MicroTech III unit controller is locked out due to one of these faults, and the cause of the
fault condition has been cleared, energizing the O-terminal
for 10 seconds or more forces the MicroTech III unit control-
ler to clear the lockout. Cycling unit power also clears a lock­out if the conditions causing the fault have been alleviated.
Tenant Override
Note: It is recommended that the "Occupied Operation" and
"Unoccupied Operation – Stand Alone Thermostat
Control" sections be reviewed prior to this section.
The MicroTech III unit controller enters tenant override
mode when the O terminal is energized for 3 seconds during
a period when the Water Source Heat Pump is in unoccupied mode.
Tenant override allows a tenant, returning to the controlled space after the unit has been placed in unoccupied mode, to
activate the tenant override input (O) and place the unit into
occupied mode. Any remote button or switch with momentary dry contacts
can be used for this purpose. During the 2-hour tenant over-
ride period the W2 input will be ignored and the G, Y1, and W1 inputs will be used (see "Occupied Operation" on page
7) for unit operation. If the U terminal is still grounded
after the 2-hour time limit, the unit will return to unoccupied
mode. Refer to "Unoccupied Operation – Stand Alone Ther-
mostat Control" on page 8.
Intelligent Reset (See Table 2)
The Intelligent Reset feature helps to minimize nuisance trips
of automatic lockouts caused by low-temperature faults. This
feature clears faults the rst two times they occur within a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours.
Table 2: Faults
● = Applies – = Does not apply
(Tenant Override) Command or Power)
Invalid Conguration Jumper Setting
Brownout
HP1
LP1 ●*
LT1 (In Heating) ●*
LT1 (In Cooling)
Sensor Room Temperature, LT1, LT2,
Failure EWT (w/Boilerless EH Only)
Condensate Overow
EEPROM Failure
* Auto Recover for the first two occurrences, lockout on the third occurrence within 24 hours, i.e., subject to “Intelligent Reset.”
Fault
Auto Recovery
Remote Reset Reset (Network
OM 931-4 / Page 11 of 28
Page 12

Fan Operation during most Modes, Faults and Shutdowns

The MicroTech III unit controller allows fan operation during most modes, faults and shutdowns to facilitate maximum space comfort and control. However, the fan does not operate during brownout condition. During most modes, faults, or shutdowns the fan will operate under the following condi­tions:
1. In occupied modes, the thermostat inputs G, Y1, or W1 are energized.
2. In unoccupied modes, the thermostat input W2 is energized.
Operation with the High Speed Jumper
■ The MicroTech III unit controller includes a high-speed jumper terminal labeled JP1 to speed system check out
and trouble-shooting. See Figure 2 on page 6 for JP1 location.
Note: This jumper is intended for Daikin McQuay factory unit
testing and should only be used by trained service technicians as several timing functions are reduced to speed system check out.
■ Disconnect power to the unit when installing or removing the high-speed jumper.
■ The high speed jumper should only be used for a short
period of time for testing of the unit’s operation by a
trained service technician. The jumper must be removed
for normal unit operation.
■ If the jumper is left on after system check out, the unit
may be damaged.
Priority of Faults and Modes
The MicroTech III unit controller is congured with mode
and fault priorities. Table 3 illustrates that the lower the prior-
ity level number, the higher the priority of the fault or mode. There are some exceptions to this priority list. For example, tenant override has no affect on occupied modes.
Table 3: Priority Level of Faults and Modes
Priority Level Mode or Fault
1 Emergency Shutdown Mode
2 Brownout
3 High Pressure
4 Low Pressure
5 Low Temperature
6 Tenant Override Mode
7 Unoccupied Heating Mode
8 Occupied Heating Mode
9 Condensate Overow
10 Occupied Cooling Mode
Table 4: MicroTech III Unit Controller Status LED's
Mode / Fault
Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Unoccupied On On Off Energized Condensate Overow On Off Off De-energized
High Pressure 1 Fault Off Off Flash De-energized Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown Off Flash Off De-energized
Room/Return Air or Low
Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM Corrupted
Network “Ofine” Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’s
1
Yellow Green Red Output-Terminal “A”
Off Flash Off De-energized
Flash Flash On De-energized
On On Off De-energized
On On On De-energized
Off Off Off De-energized
Thermostat Alarm Light

Troubleshooting the MicroTech III Unit Controller

DANGER
To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s).
Power supply to unit must be disconnected when making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
Page 12 of 28 / OM 931-4
Page 13
Figure 6: MicroTech III Unit Controller LED Status and Faults Troubleshooting Reference
Read Outputs
Check Timers
Yes
Brownout
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
High
Pressure
Low
Pressure
Low Suct
Temp Sensor
Low Suct
Temp
Room Temp
Sensor Failure
R - W 1
R -Y 1
No
No
No
No
No
No
No
Compressor
Time Delay
Request for Water Flow
Start
30 Second
Condensate
Overflow
Stop Compressor
Flash Green LED
Stop Compressor
Flash Red LED
Stop Compressor
Flash Yellow LED Flash Green LED
Solid Red LED
Stop Compressor
Heating Mode
Yes
Flash Yellow LED
Run in Cooling Mode for 1 Min.
Cooling Mode
Yes
Turn on
Yellow LED
No
No
Stop Compressor
Reversing
Valve On
Time Delay
OM 931-4 / Page 13 of 28
Page 14

Troubleshooting the Water Source Heat Pump Unit

Figure 7: Troubleshooting Guide - Unit Operation
Low voltage, check power supply voltage
Check wiring - loose or broken and check for faulty connection
Check relays and contacts, also capacitor and wiring
Check high pressure switch, low pressure switch and low temperature switch to see if unit is cycling on the safety
Check to see if the reversing valve is not hung up and is operating correctly
Check condensate overflow switch in cool mode of operation
Check thermostat for proper location
Fuse may be blown, circuit breaker is open
Neither fan, nor compressor runs and all LED lights are off
Compressor runs in short cycle
Wire may be loose or broken. Replace or tighten wires
Fan operates,
Unit
compressor does not
Unit control, check thermostat for correct wiring or faulty thermostat
Check capacitor
Check wiring - loose or broken and check for bad connection
High or Low pressure lockout A. Cool mode, check water flow B. Heating mode, check air flow C. Check reversing valve for
proper valve position
Check compressor overload - make sure it is closed
Check compressor to ground, or for internal short to ground
Compressor winding may be open. Check continuity with ohm meter
Compressor attempts to start but does not
Check compressor wiring for defective wiring or loose connection
Check for defective compressor internal windings with ohm meter
Check for faulty compressor capacitor
Check for lock rotor amp draw
Insufficient cooling or heating
Check thermostat for improper location
Check for proper air flow ­filter could be dirty
Check blower assembly for dirt or faulty fan motor capacity
Check for low refrigerant charge
Check amp draw on blower assembly
Check for proper water flow and delta T (°F)
Page 14 of 28 / OM 931-4
Page 15

Microtech® III Unit Controller Interface to External Equipment

■ The MicroTech III unit controller’s thermostat input
terminals may be directly interfaced with any standard or night setback thermostat that uses mechanical dry contacts. Power cannot be supplied from the water source heat pump for electronic thermostats that require a separate power supply for their internal operation except
hose provided by Daikin McQuay. Only thermostats
offered by Daikin McQuay are proven to operate properly with the MicroTech III unit controller. Daikin McQuay makes no guarantees about any other thermostat or control device interfaced by the end user with the MicroTech III unit controller.
■ Care must be used to isolate all external power sources
from the MicroTech III unit controller to prevent ground
loops and other unpredictable electrical problems. Only
dry mechanical contacts should be used to operate or interface with the MicroTech III unit controller’s
thermostat and or control inputs. Use mechanical relays
to isolate two power systems when external equipment with its own power supply is used to interface with or control the MicroTech III unit controller’s thermostat and or control inputs. For example, if you have a Building
Automation System (BAS), controller, etc., and you
wish to use a digital output from the building automation system or controller that is internally powered, then you
must use an additional mechanical relay (not supplied by Daikin McQuay) to isolate the MicroTech III unit
controller.
■ Due to the nature of triacs and other solid state devices,
triacs cannot be directly used to operate the MicroTech III’s unit controller’s thermostat or control inputs. To interface triacs or other solid state switching devices to the MicroTech III unit controller inputs, separate them from the board using mechanical relays. To do this, use the
triac or solid state device to drive a mechanical relay (not supplied by Daikin McQuay), then use the mechanical
relay’s dry contacts to drive the desired MicroTech III unit controller input.
■ The MicroTech III unit controller’s valve or pump request terminal {IV/PR (H8)} is an output signal to external devices to allow water ow as required by the heat pump. The IV/PR (H8) terminal follows compressor operation
inversely if connected to the normally open terminal and simultaneously when connected to the normally closed
terminal. The IV/PR (H8) terminal can be used as a signal to an external pump or valve to enable ow to the unit. The compressor start is delayed for 30 seconds after the IV/PR (H8) output is energized.
Table 5: IV/PR(H8) Terminal and Compressor Operation
Compressor Off
IV/PR(H8)
Normally Open
Normally Closed
Compressor On
24 V
0 V
AC
AC
0 V
24 V
AC
AC

Appendix A

Operation and Maintenance of I/O Expansion Module

Introduction

The I/O Expansion Module is a eld-installed option. It is an
extension of the main board and provides extra functionality to the MicroTech III control system.
The I/O Expansion Module has 4 main purposes:
■ The MicroTech III unit controller in combination with the I/O Expansion Module will be the standard control system
for two stage Water Source Heat Pump equipment. For example: large vertical units.
■ The I/O Expansion Module has outputs to control electric
heat on a standard Water Source Heat Pump.
■ The I/O Expansion Module has outputs for multi-speed
fans on a standard Water Source Heat Pump.
■ The I/O Expansion Module has an independent LED
annunciator to identify operational fault conditions on second stage equipment.
Adding an I/O Expansion Module (with an interconnect cable) to the main controller allows two stage operation of the
water source heat pump.

Features

Second Circuit
■ High pressure switch
■ Low pressure switch
■ Low suction line temperature sensor
■ Compressor output
■ Reversing valve
Standard Heat Pumps / Single Circuit Units
■ Monitors entering water temperature for boilerless
electric heat control
■ Outputs for medium and high speed fan controls
OM 931-4 / Page 15 of 28
Page 16

Initial Power up

Figure 8: I/O Expansion Board Configuration Jumper Terminals
Table 6: I/O Expansion Board Configuration Jumper Settings
Jumper Description Options
JP1 Number of Compressors
JP2 Hot Gas/Water Reheat
JP3 & JP4 Supplemental Heat Type
JP5 & JP6 Fan Speed Selection
JP7 Compressor Speed Type
JP8 Future Spare
Open for single compressor
Shorted for dual compressor
Open to disable reheat
Shorted to enable reheat
JP3 and JP4 open for no supplemental heat
JP3 open, JP4 shorted for boilerless electric heat.
JP3 shorted and JP4 open for supplemental electric heat
JP3 and JP4 shorted is an invalid setting
JP5 and JP6 open for single-speed fan
JP5 open, JP6 shorted for three-speed fan
JP5 shorted and JP6 open for two-speed fan
JP 5 and JP6 shorted is an invalid setting
Open for single-speed compressor
Shorted for two-speed compressor
Page 16 of 28 / OM 931-4
Page 17

Operation

Dual Circuit Units

• Provides standard lead / lag operation for two compressors
in dual circuit units
• Circuit one will come on rst when there is any call for
heating or cooling at the main board
• The second circuit will be enabled after the interstage timer has expired. The interstage timer defaults to 300
seconds
• HP, LP, SLTS fault for either circuit one or circuit two, will lockout the entire unit and subject for intelligent reset

Thermostat Inputs (Y2, W2)

• The Y2 terminal which is cooling mode stage two, energizes the second compressor
• If Y1 and Y2 thermostat inputs are active at the same time,
interstage timers will be used to stage the compressor up and down
• The W2 terminal which is heating mode stage two, energizes the second reversing valve followed 30 seconds
later by the second compressor
• If W1 and W2 thermostat inputs are active at the
same time, interstage timers will be used to stage the compressors up and down

Electric Heat Controls

Boilerless Heat Coil Control

• Turns on the factory installed heater when the entering water temperature is less than 55°F, the temperature set point is not adjustable
• For geothermal applications the factory installed electric
heater turns on when the entering water temperature is less
than 30°F
Note: In both cases the compressor is shut down.

Multiple Speed Fan Control

• When the Water Source Heat Pump is equipped with an I/O Expansion Module and factory installed electric heat,
three speed fan control is possible.
• If the thermostat is calling for continuous fan operation
and the compressor is not running the fan motor will run in low speed.
• If there is a call for heating or cooling (compressor is running) the fan motor will run in medium speed.
• If the electric heater is enabled the fan motor does not run
in high speed.
Note: On units with an I/O Expansion Module and no electric
heat, it is possible to congure the I/O Expansion
Module for a two speed fan. If there is a call for continuous fan (compressor off) the fan motor runs in low speed. If there is a call for heating or cooling (compressor on) the fan motor runs at high speed.

Three-Speed Fan Operations

Table 7: Three-Speed Fan
Electric Heat
f
High Speed
Of
Of
f
f
Space Temp Satised Compressor
Heating/Cooling Electric Heat Enabled
Continuous Fan
Low Speed
f
Of
f Off
Of
Compressor On
Of
Med. Speed
Two-Speed Fan Operations
Table 8: Two-Speed Fan
Electric Heat
f
High Speed
Of
Of
f
f
Space Temp Satised Compressor
Heating/Cooling Electric Heat Enabled
Continuous Fan
Low Speed
f
Of
f Off
Of
Compressor On
Of
High Speed

Circuit Two, Additional Operating Modes

The I/O Expansion Module controls the second circuit high
pressure, low pressure, and low suction line temperature operating conditions in the same manner as the main board
controls the rst circuit.
Table 9: I/O Expansion Module LED & Fault Outputs
Terminal “A”
Invalid Conguration Jumper Setting
Base Board Communication Fail
High Pressure #2 Fault Off Off Flash De-energized
Low Pressure #2 Fault Off Off On De-energized
Unoccupied Mode On On Off Energized
Occupied, Bypass, Standby, or Tenant Override Modes
Note: Mode / Faults are listed in order of priority.
1
2
Mode / Fault
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction Low Suction Temp #2, Flash Flash On De-energized
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Yellow Green Red
Boilerless electric heat only Alarm/fault LED indications take precedence over
service test mode LED indication. The controller shall use service test mode if the service test mode jumper
is installed, even if the LED’s indicate an alarm/fault.
Status LED's
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Thermostat Alarm
Light Output
OM 931-4 / Page 17 of 28
Page 18

Second Circuit Faults

With the addition of the second circuit the fault recovery and
reset table has new faults for the second circuit (Table 10).
Table 10: Second Circuit Faults
● = Applies – = Does not apply
(Tenant Override) Command or Power)
Invalid Conguration Jumper Setting
Brownout
HP2
LP1 ●*
LT2 (In Heating) ●*
LT2 (In Cooling)
Sensor Room Temperature, LT1, LT2,
Failure EWT (w/Boilerless EH Only)
Condensate Overow
EEPROM Failure
* Auto Recover for the first two occurrences, lockout on the third occurrence within 24 hours, i.e., subject to “Intelligent Reset.”
Table 11: I/O Expansion Module Connections & Descriptions
H8 Description
Pin 1 Fan high speed normally open output
Pin 2 No connection
Pin 3 24 VAC Common
H3 Pin 1 Pin 2
Pin 3 For future development
Pin 4
Pin 5
Pin 6
H8 Dual compressor: compressor 2 normally
Pin 1 open output, all others fan medium speed
normally open
Pin 2 24 VAC common
Pin 3 No connection
circuit 2, all others electric heat
Pin 5 24 VAC common
H4
Pin 1 Entering water temperature sensor signal
Pin 2 Entering water temperature sensor common
HP6
HP2-1 High pressure switch for circuit 2
HP2-2 High pressure switch for circuit 2
H7 Pin 1 Suction line temperature sensor circuit 2 signal
Pin 2 Suction line temperature sensor circuit 2 common
Pin 3 Low pressure switch circuit 2 signal
Pin 4 Low pressure switch circuit 2 source
H5 LED Annunciator TB1 For future use
Dual compressor: reversing valve for
Pin 4
Fault
Auto Recovery
Remote Reset Reset (Network
Page 18 of 28 / OM 931-4
Page 19

Appendix B

MicroTech III Unit Controller with LonWorks® Communication Module

For installation and operation information on LonWorks Communication Module and other ancillary control compo­nents, see:
■ IM 927 - MicroTech III Water Source Heat Pump
LonWorks Communication Module.
■ IM 933 - LonMaker Integration Plug-in Tool: For use with
the MicroTech III Unit Controller.
■ IM 955 - MicroTech III Wall Sensor for use with
Microtech III Unit Controller
Each Daikin McQuay water source heat pump can be equipped with a LonWorks communication module that is
LonMark 3.4 certied to meet the LonMark Space Com-
fort Control (SCC) prole for heat pumps. The controller is
microprocessor-based and is designed to communicate over a LonWorks communications network. It can be factory or
eld-installed.
The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the Water Source Heat Pump. The unit controller monitors water and air temperatures and passes information to the communication module. The mod­ule communicates with the BAS, to provide network control of the Water Source Heat Pump.
Figure 9: LonWorks Communication Module
MicroTech III Unit Controller with LonWorks Communica-
tion Module orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint based on
a room sensor
Enable fan and compressor operation Monitors all equipment protection controls Monitors room and discharge air temperatures Monitors leaving water temperature Relays status of all vital unit functions
The MicroTech III unit controller with communication module includes:
■ Return Air Temperature sensor (RAT)(eld-installed)
■ Discharge Air Temperature sensor (DAT)(eld-installed)
■ Leaving Water Temperature sensor (LWT)
Note: Refer to IM 956-X for details to install (RAT) & (DAT)
sensors.
CAUTION
When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly.
The communication module provides access to setpoints for operational control Available wall sensors include:
Room sensor with LED status and tenant override button
Room sensor with LED status, tenant override button, and
±3°F setpoint adjustment
Room sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
The MicroTech III unit controller with communication module includes a unit-mounted return air, discharge air and leaving water temperature sensor. Wall mounted temperature
sensors include setpoint adjustment and tenant override. The
user has the capability of substituting the wall sensor with a duct-mounted return air sensor.
OM 931-4 / Page 19 of 28
Page 20

MicroTech III Controller with BACnet® Communication Module

For installation and operation information on MicroTech III unit controller and other ancillary components, see:
■ IM 928 - MicroTech III Water Source Heat Pump BACnet
Communication Module
■ IM 955 - MicroTech III Wall Sensor For use with
Microtech III Unit Controller
Daikin McQuay water source heat pumps are available with Daikin McQuay BACnet MS/TP communication module that is designed to communicate over a BACnet MS/TP commu-
nications network to a building automation system (BAS). It can be factory or eld-installed.
The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the water source heat pump. The unit controller monitors water and air temperatures and passes information to the communication module. The mod­ule communicates with the BAS, to provide network control of the water source heat pump.
The module makes operational data and commands available
on a communications network using BACnet objects and
properties:
■ The network cable is a shielded twisted-pair cable
■ Network communications run up to 76.8 Kbps
■ DIP switches on the controller enable the MS/TP MAC
address to be set in the range 0-127
■ Four green status LEDs on the communication module
indicate communication activity on the MS/TP communication network and with the unit controller
Figure 10: MicroTech III BACnet MS/TP Snap-in Communication Module
MicroTech III Unit Controller with BACnet MS/TP Commu­nication Module orchestrates the following unit operations:
■ Enable heating and cooling to maintain setpoint based on
a room sensor
■ Enable fan and compressor operation
■ Monitors all equipment protection controls
■ Monitors room and discharge air temperatures
■ Monitors leaving water temperature
■ Relays status of all vital unit functions
The MicroTech III unit controller with communication module includes:
■ Return Air Temperature sensor (RAT)(eld-installed)
■ Discharge Air Temperature sensor (DAT)(eld-installed)
■ Leaving Water Temperature sensor (LWT)
Note: Refer to IM 956-X for details to install (RAT) & (DAT)
sensors.
CAUTION
When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly.
The communication module provides access to setpoints for operational control
Available wall sensors include:
■ Room sensor with LED status and tenant override button
■ Room sensor with LED status, tenant override button, and ±3°F setpoint adjustment
■ Room sensor with LED status, tenant override
button, 55° to 90°F setpoint adjustment
Page 20 of 28 / OM 931-4
Page 21

Appendix C – Typical Wiring Diagrams

MicroTech III Unit Controller (Standalone) – 208/230/460/575/60Hz/3-Phase

able B
T
RED
208V 230V
*Drawing No. 668991201 Shown with optional desuperheater
pump wiring.
ORG
Legend
Description
Item
Capacitor-Compressor
C1
Capacitor-Fan
C2
Compressor - Contactor
CC
Compressor - Motor
CM
Condensate Overow Sensor
CDS DA EWT
HTR IOEXP ISO-NC ISO-NO LED1 LED2 LP
SL
LWT MIII R1 R2 RA RV TB1 X1
_____ _ _ _ _
Discharge Air Temp Sensor
T
Entering Water Temp Sensor High Pressure Switch
HP
Electric Heater Cartridge I/O Expansion Board / Harness Isolation V Isolation V
Annunciator / Harness
LED
Annunciator / Harness
LED Low Pressure Switch
Suction Line
TS
Leaving W MicroT Relay - Fan Motor Relay - Electric Heat Return
T
Reversing V Power
ransformer
T Standard Unit Wiring Optional Wiring (by others)
alve - Normally Closed alve - Normally Open
Temp Sensor
ater Temp Sensor
ech III Main Board
Air Temp Sensor
alve Solenoid
Terminal Block
Notes:
1.
Main board jumpers: No jumpers shorted.
2.
I/O expansion board jumpers: Jumper JP4 shorted.
T
ransformer:
Unused wire to be capped.
Desuperheater only available on 1
15-208-230V applications.
All open.
Note: The gray tinted areas in the wiring diagram; Leaving Water (L WT), Discharge Air (DAT) and Return Air (RA T) Temperature
sensors are shipped or are eld installed on units congured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
OM 931-4 / Page 21 of 28
Page 22

MicroTech III Unit Controller with Optional ECM Motor, Desuperheater and I/O Expansion Module – 208/230/265/277/60 Hz/1-Phase

able B
T
RED
208V 230V 265V 277V
*Drawing No. 668991501
ORG BRN BRN
Legend
Description
Item
Capacitor-Compressor
C1
Capacitor-Fan
C2
Compressor - Contactor
CC
Compressor - Motor
CM
Condensate Overow Sensor
CDS
DA
EWT
HP
HTR IOEXP ISO-NC ISO-NO LED1 LED2 LP
SL
LWT MIII R1 R2 RA RV TB1 X1
_____ _ _ _ _
Discharge Air Temp Sensor
T
Entering Water Temp Sensor High Pressure Switch Electric Heater Cartridge I/O Expansion Board / Harness Isolation V Isolation V LED LED Low Pressure Switch
Suction Line
TS
Leaving W MicroT Relay - Fan Motor Relay - Electric Heat Return
T
Reversing V Power
ransformer
T Standard Unit Wiring Optional Wiring (by others)
alve - Normally Closed
alve - Normally Open Annunciator / Harness Annunciator / Harness
Temp Sensor
ater Temp Sensor
ech III Main Board
Air Temp Sensor
alve Solenoid
Terminal Block
Notes:
1.
Main board jumpers: No jumpers shorted.
2.
I/O expansion board jumpers: Jumper JP4 shorted.
T
ransformer:
Unused wire to be capped.
Desuperheater only available on 1
15-208-230V applications.
All open.
Note: The gray tinted areas in the wiring diagram; Leaving Water (L WT), Discharge Air (DAT) and Return Air (RA T) Temperature
sensors are shipped or are eld installed on units congured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Page 22 of 28 / OM 931-4
Page 23

MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, Electric Heat Coil and I/O Expansion Module – 208/230/460/60 Hz/3-Phase

able B
T
RED
208V 230V 460V
*Drawing No. 668991301
BLK/RED
ORG
Legend
Description
Item
Capacitor-Compressor
C1
Capacitor-Fan
C2
Compressor - Contactor
CC
Compressor - Motor
CM
Condensate Overow Sensor
CDS
DA
EWT
HTR IOEXP ISO-NC ISO-NO LED1 LED2 LP
SL
LWT MIII R1 R2 RA RV TB1 X1
_____ _ _ _ _
Discharge Air Temp Sensor
T
Entering Water Temp Sensor High Pressure Switch
HP
Electric Heater Cartridge I/O Expansion Board / Harness Isolation V Isolation V LED LED Low Pressure Switch
Suction Line
TS
Leaving W MicroT Relay - Fan Motor Relay - Electric Heat
Return
T
Reversing V Power
ransformer
T Standard Unit Wiring Optional Wiring (by others)
alve - Normally Closed
alve - Normally Open Annunciator / Harness Annunciator / Harness
ater Temp Sensor
ech III Main Board
Air Temp Sensor
Terminal Block
Temp Sensor
alve Solenoid
Notes:
1.
Main board jumpers: No jumpers shorted.
2.
I/O expansion board jumpers: Jumper JP4 shorted.
T
ransformer:
Unused wire to be capped.
Desuperheater only available on 1
15-208-230V applications.
All open.
Note: The gray tinted areas in the wiring diagram; Leaving Water (L WT), Discharge Air (DAT) and Return Air (RAT) T emperature
sensors are shipped or are eld installed on units congured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
OM 931-4 / Page 23 of 28
Page 24

MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, and I/O Expansion Module 208/230/460/60/3-Phase

able B
T
RED
208V 230V 460V
*Drawing No. 668991401
BLK/RED
ORG
Legend
Description
Item
Capacitor-Compressor
C1
Capacitor-Fan
C2
Compressor - Contactor
CC
Compressor - Motor
CM
Condensate Overow Sensor
CDS
DA
EWT
HTR IOEXP ISO-NC ISO-NO LED1 LED2 LP
SL
LWT MIII R1 R2 RA RV TB1 X1
_____ _ _ _ _
Discharge Air Temp Sensor
T
Entering Water Temp Sensor High Pressure Switch
HP
Electric Heater Cartridge I/O Expansion Board / Harness Isolation V Isolation V LED LED Low Pressure Switch
Suction Line
TS
Leaving W MicroT Relay - Fan Motor Relay - Electric Heat Return
T
Reversing V Power
ransformer
T Standard Unit Wiring Optional Wiring (by others)
alve - Normally Closed
alve - Normally Open Annunciator / Harness Annunciator / Harness
ater Temp Sensor
ech III Main Board
Air Temp Sensor
Terminal Block
Temp Sensor
alve Solenoid
Notes:
1.
Main board jumpers: No jumpers shorted.
2.
I/O expansion board jumpers: Jumper JP4 shorted.
T
ransformer:
Unused wire to be capped.
Desuperheater only available on 1
15-208-230V applications.
All open.
Note: The gray tinted areas in the wiring diagram; Leaving Water (L WT), Discharge Air (DAT) and Return Air (RA T) Temperature
sensors are shipped or are eld installed on units congured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
Page 24 of 28 / OM 931-4
Page 25

MicroTech III Unit Controller with PSC Motor, Desuperheater and I/O Expansion Module for Hot Gas Reheat Control (Unit Sizes 019-070) 208/230/60/1-Phase

able B
T
RED
208V 230V
*Drawing No. 669007101A
ORG
Legend
Description
Item
Capacitor-Compressor
C1
Capacitor-Fan
C2
Compressor - Contactor
CC
Compressor - Motor
CM
COS Condensate Overow Sensor
DA
EWT
HTR IOEXP ISO-NC ISO-NO
DSHP
HGRH P1 LED1 LED2 LP
SL
LWT MIII R1 R2 RA RV TB1 X1 X2
_____ _ _ _ _
Discharge Air Temp Sensor
T
Entering Water Temp Sensor High Pressure Switch
HP
Electric Heater Cartridge I/O Expansion Board / Harness Isolation V Isolation V
Desuperheater Pump
3-W 24 V LED LED Low Pressure Switch
Suction Line
TS
Leaving W MicroT Relay - Fan Motor Relay - Electric Heat Return
T
Reversing V Power Primary 24 V Secondary 24 V Standard Unit Wiring Optional Wiring (by others)
alve - Normally Closed alve - Normally Open
ay Valve Solenoid
AC Supply I/O Expansion Brd.
Annunciator / Harness Annunciator / Harness
ater Temp Sensor
ech III Main Board
Air Temp Sensor
alve Solenoid
Terminal Block
Temp Sensor
AC Transformer
AC Transformer
Notes:
1.
Main Board Jumpers: JP3 Geothermal.
2.
I/O Expansion Board Jumpers: JP4 Hot Gas Reheat. JP3 Supplemental EH. JP4 Boilerless EH. JP5 2-Speed Fan
T
ransformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature
sensors are shipped or are eld installed on units congured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.
OM 931-4 / Page 25 of 28
Page 26

Controller Comparison

Note: The Mark IV, MicroTech 2000, Alerton and MicroTech III boards are NOT interchangeable. Table 12: Control Boards and Features
● = Applies – = Does not apply
Mark IV
MicroTech 2000
Alerton MicroTech III
DC Power
AC Power
Terminal Connection 1/4″ Push-on
IDC Connection
Fault Indicators
Thermostatic Controls
Room Sensor
LONmark Capable
LonWorks Capable BACnet Capable
Motorized Valve Capability
Short Cycle Protection & Random Start
Unoccupied Mode
Override Mode
Pump Restart
Loadshed
Brownout Protection
Unit Shutdown
Condensate Overow Protection
Remote Reset
Intelligent Reset
Dual Circuit Capability
Adjustable Set Points Through Software
Adjustable Fan Speed
Electric Heat Availability
Service Tools Needed at Start up
Dipswitch Settings
Programmable Front-end Settings
Switching Line Voltage
Note:
(1) Alerton BACnet requires Alerton service tools for commissioning (1) Alerton dipswitch settings must be configured during commissioning (1) See Remote Reset and Intelligent Reset information under section: Additional Operating Modes
Features
(1)
(1)
(1)
Page 26 of 28 / OM 931-4
Page 27
This page left blank intentionally
OM 931-4 / Page 27 of 28
Page 28
Daikin McQuay Training and Development
Now that you have made an investment in modern, efficient Daikin McQuay equipment, its care should be a high priority. For training information on all Daikin McQuay HVAC products, please visit us at www. daikinmcquay.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin McQuay Representative, go to www.daikinmcquay.com.
Aftermarket Services
To find your local parts office, visit www.daikinmcquay.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.daikinmcquay.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.daikinmcquay.com.
Products manufactured in an ISO certified facility.
©2012 McQuay International • www.daikinmcquay.com • 800.432.1342 OM 931-4 Page 28 of 28 (8/12)
Loading...