This manual covers two similar product lines:
AGZ-BM, Packaged chiller with the evaporator shipped separately for remote installation, field
piping to the outdoor unit, and interconnection of wiring. The refrigeration specialties are shipped
from the factory for field installation.
Operating instructions are contained in operating manual OM AGZ.
ACZ-BC, Condensing unit with no evaporator included. For use with customer supplied low side
(usually an air-handling unit), field piped and wired to the condensing unit.
Operating instructions are contained in operating manual OM ACZ.
These McQuay air-cooled units are complete, self-contained, automatic refrigerating units. Every
unit is completely assembled, factory wired, tested and provided with a holding charge. Each unit
consists of two air-cooled condenser sections with integral subcooler sections, two tandem or triple
scroll compressors, (brazed-plate or replaceable tube, dual circuit shell-and-tube evaporator and
liquid line components including manual, sight-glass/moisture indicators, solenoid valves, and
thermal expansion valves on AGZ-BM only). Other features include compressor crankcase heaters,
an evaporator heater for chilled water freeze protection (on AGZ-BM only), one-time pumpdown
during “on” or “off” periods, and automatic compressor lead-lag to alternate the compressor starting
sequence.
The electrical control center includes all equipment protection and operating controls necessary for
dependable automatic operation. Condenser fan motors are protected in all three phases and started
by their own three-pole contactors. Model ACZ condensing units require a field-supplied multi-step
thermostat wired to the outdoor unit.
Inspection
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report
shipping damage and file a claim with the carrier. Check the unit nameplate before unloading,
making certain it agrees with the power supply available. McQuay is not responsible for physical
damage after unit leaves the factory.
Note: Unit shipping and operating weights are available in the Physical Data tables
beginning on page 28.
Nomenclature
A G Z - XXX B M
C=Condensing Unit
Scroll Compressor
Air-Cooled
G=Global Chiller
Application
C= Condensing Unit
M= Remote Evaporator
Design Vi ntage
Model Size
(Nominal Tons)
IMM ACZ/AGZ-4 ACZ / AGZ-BM 3
Installation
Note: Installation is to be performed by qualified personnel who are familiar with local
codes and regulations.
Sharp edges on unit and coil surfaces are a potential hazard to personal safety. Avoid
Handling
Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything other than
the base. Block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet
and end frame (see
To lift the unit, 2 1/2" (64mm) diameter lifting tabs are provided on the base of the unit. Arrange
spreader bars and cables to prevent damage to the condenser coils or cabinet (see
Figure 1, Suggested Pushing Arrangement
WARNING
contact with them.
Figure 1).
Figure 2).
Blocking is required
across full width
Figure 2, Suggested Lifting Arrangement
Spreader bars
Spreader bars
required
required
(use caution)
(use caution)
Number of fans may vary
from this diagram. The lifting
method will remain the same.
All rigging locations
must be used.
4 ACZ / AGZ-BM IMM ACZ/AGZ-4
Location
Unit Placement
ACZ/AGZ units are for outdoor applications and can
be mounted either on a roof or at ground level. For
Figure 3, Clearances
SEE TABLE BELOW
DIMENSION “A”
roof mounted applications, install the unit on a steel
channel or I-beam frame to support the unit above the
roof. For ground level applications, install the unit on
a substantial base that will not settle. A one-piece
4 FT. (1220mm)
CLEARANCE FOR
SERVICE ACCESS
concrete slab with footings extended below the frost
line is recommended. Be sure the foundation is level
within 1/2"(13mm) over its length and width. The
foundation must be strong enough to support the
SEE TABLE BELOW
DIMENSION “A”
weights listed in the Physical Data Tables beginning
on page
Do not block the flow of air to and
from the condenser coil. Restricting
airflow or allowing air recirculation
will result in a decrease in unit
performance and efficiency because
discharge pressures are increased.
There must be no obstruction above
the unit that would deflect discharge
air downward where it could be
recirculated back to the inlet of the
condenser coil. The condenser fans are
propeller type and will not operate
with ductwork.
AIR FLOWAIR FLOW
The recommended minimum side clearance between two units
is dimension “B’ in table on this page.
AIR
DISCHARGE
AIR FLOW
“B”
ft. (m)
4 FT. (1220)
CLEARANCE FOR
SERVICE ACCESS
AIR
DISCHARGE
Install the unit with enough side
clearance for air entrance to the coil
AIR FLOWAIR FLOW
AIR
DISCHARGE
and for servicing. Provide service
access to the evaporator, compressors,
electrical control panel and piping
components.
Do not allow debris to accumulate
“C”“C”
near the unit where it could be drawn
into the condenser coil. Keep
condenser coils and fan discharge free
of snow or other obstructions to permit
The unit must not be installed in a pit or enclosure that is
deeper or taller than the height of the unit unless extra space
is provided. The minimum clearance on each
side of the unit is dimension “C” in table on this page.
adequate airflow for proper operation.
IMM ACZ/AGZ-4 ACZ / AGZ-BM 5
Restricted Air Flow
General
The clearances required for design-life operation of ACZ/AGZ air-cooled units are described in the
previous section. Occasionally, these clearances cannot be maintained due to site restrictions, such
as units being too close together, or a fence or wall restricting airflow, or both.
The McQuay ACZ/AGZ units have several features that can mitigate the problems attributable to
restricted airflow.
• The condenser section is configured as shown below. This configuration allows inlet air for
these coils to come in from either side. A vertical coil and its adjacent angled coil are
manifolded together to serve one refrigerant circuit.
• The MicroTech II™ control is proactive in response to “off-design conditions”. In the case of
single or compounded influences restricting airflow to the unit, the microprocessor will act to
keep the compressor(s) running (possibly at reduced capacity) rather than allowing a shut-off on
high discharge pressure.
• The MicroTech II™ control can be programmed to sequence the compressors in the most
advantageous way. For example, in the diagram shown below, it might be desirable to program
circuit #1 to be the lag circuit (last circuit to reach full load) during periods of high ambient
temperatures.
Figure 4, Coil and Fan Arrangement
Building
Circuit #1Circuit #2
NOTE: Models ACZ 030 to 045 and AGZ 026 to 035 do not have an interior slanted coil.
The following sections discuss the most common situations of condenser air restriction and give
capacity and power adjustment factors for each. Note that in unusually severe conditions, the
MicroTech II™ controller would adjust the unit operation to remain online until a less severe
condition is reached.
6 ACZ / AGZ-BM IMM ACZ/AGZ-4
Case 1, Building or Wall on One Side of One Unit
The existence of a screening wall, or the wall of a building, in close proximity to an air-cooled unit is
common in both rooftop and ground level applications. Hot air recirculation on the coils adjoining the wall
will increase compressor discharge pressure, decreasing capacity and increasing power consumption. Only
the compressor(s) connected to these coils will be affected.
When close to a wall, place chillers on the north or east-side of them. Have prevailing winds blowing
parallel to the unit’s long axis. The worst case is to have wind blowing hot discharge air into the wall.
Figure 5, Unit Adjacent to Wall
H
D
Figure 6, Adjustment Factors
3.0
2.0
1.0
.5
ACZ
090-155
AGZ
075-130
4.5 ft.
(1.4m)
6 ft.
(1.8m)
8 ft.
(2.4m)
ACZ
030-080
AGZ
026-070
3.5 ft.
(1.0m)
4 ft.
(1.2m)
6 ft.
(1.8m)
4.0
3.0
2.0
ACZ
ACZ
030-080
090-155
AGZ
AGZ
026-070
075-130
4.5 ft.
3.5 ft.
(1.4m)
(1.0m)
6 ft.
8 ft.
4 ft.
(1.2m)
6 ft.
(1.8m)
(1.8m)
(2.4m)
0
0
IMM ACZ/AGZ-4 ACZ / AGZ-BM 7
Case 2, Two Units Side By Side
Two or more units sited side by side are common. If spaced closer than 12 feet (3.7 meters), or 8 feet
(2.5meters), depending on size, it is necessary to adjust the performance of each unit. Circuits adjoining
each other are affected. NOTE: This case applies only to two units side by side. See Case 3 for three or
more parallel units. If one of the two units also has a wall adjoining it, see Case 1. Add the two adjustment
factors together and apply to the unit located between the wall and the other unit.
Mounting units end to end will not necessitate adjusting performance. Depending on the actual
arrangement, sufficient space must be left between the units for access to the control panel door opening
and/or evaporator tube removal. See “Clearance” section of this guide for requirements for specific units.
Figure 7, Two Units Side by Side
Figure 8, Adjustment Factor
3.0
2.0
1.0
0
AGZ 075-130
ACZ 090-155
AGZ 026-070
ACZ 030-080
9
(2.7)
6.5
(2.0)
10
(3.0)
7
(2.1)
11
(3.3)
7.5
(2.2)
12
(3.6)
8
(2.4)
AGZ 075-130
ACZ 090-155
AGZ 026-070
ACZ 030-080
6.0
4.0
2.0
0
9
(2.7)
6.5
(2.0)
10
(3.0)
7
(2.1)
11
(3.3)
7.5
(2.2)
12
(3.6)
8
(2.4)
8 ACZ / AGZ-BM IMM ACZ/AGZ-4
Case 3, Three or More Units Side By Side
When three or more units are side by side, the outside units (1 and 3 in this case) are influenced by the
middle unit only on their inside circuits. Their adjustment factors will be the same as Case 2. All inside units
(only number 2 in this case) are influenced on both sides and must be adjusted by the factors shown below.
Figure 9, Three or More Units
Chiller 1Chiller 2Chiller 3
Figure 10, Adjustment Factor
4.0
3.0
2.0
1.0
0
AGZ 075-130
ACZ 090-155
AGZ 026-070
ACZ 030-080
15
(4.6)
11
(3.3)
16
(4.9)
12
(3.7)
17
(5.2)
13
(4.0)
18
(5.5)
14
(4.3)
AGZ 075-130
ACZ 090-155
AGZ 026-070
ACZ 030-080
8.0
6.0
4.0
2.0
0
15
(4.6)
11
(3.3)
16
(4.9)
12
(3.7)
17
(5.2)
13
(4.0)
18
(5.5)
14
(4.3)
IMM ACZ/AGZ-4 ACZ / AGZ-BM 9
Case 4, Open Screening Walls
Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop. These walls
should be designed such that the combination of their open area and distance from the unit do not require
performance adjustment. It is assumed that the wall height is equal to or less than the unit height when
mounted on its base support. This is usually satisfactory for concealment. If the wall height is greater than
the unit height, see Case 5, Pit Installation.
The distance from the ends of the unit to the end walls must be sufficient for service, opening control panel
doors, and pulling evaporator tubes, as applicable.
If each side wall is a different distance from the unit, the distances can be averaged, providing either wall is
not less than 8 feet (2.4 meters) from the unit. For example, do not average 4 feet and 20 feet to equal 12
feet.
Figure 11, Open Screening Walls
Figure 12, Wall Free Area vs. Distance
AGZ 026-070
ACZ 030-080
4
(1.2)
3.5
(1.0)
3.0
(0.9)
2.5
(0.7)
AGZ 075-130
ACZ 090-155
6
(1.8)
5
(2.0)
4
(1.2)
3
(0.9)
01020304050
10 ACZ / AGZ-BM IMM ACZ/AGZ-4
Case 5, Pit/Solid Wall Installation
Pit installations can cause operating problems and great care should be exercised if they are to be used on
an installation. Recirculation and restriction can both occur. A solid wall surrounding a unit is
substantially the same as a pit and the data presented here should be used.
Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The grating
material and installation design must be strong enough to prevent such accidents, yet provide abundant
open area or serious recirculation problems will occur. Have any pit installation reviewed by McQuay
application engineers prior to installation for air-flow characteristics. The installation design engineer
must approve the work to avoid an unreasonable risk of accident and is responsible for final design
criteria.
Figure 13, Pit Installation
Figure 14, Adjustment Factor
AGZ 026-070
ACZ 030-080
AGZ 075-130
ACZ 090-155
D=4
(1.4)
D=6
(1.8)
D=5
(2.0)
D=8
(2.4)
AGZ
075-130
ACZ
090-155
D=10
(3.1)
AGZ
026-070
ACZ
030-080
D=7
(2.1)
D=4
AGZ 026-070
ACZ 030-080
AGZ 075-130
ACZ 090-155
(1.4)
D=6
(1.8)
D=5
(2.0)
D=8
(2.4)
AGZ
075-130
ACZ
090-155
D=10
(3.1)
AGZ
026-070
ACZ
030-080
D=7
(2.1)
IMM ACZ/AGZ-4 ACZ / AGZ-BM 11
Sound Isolation
The low sound level of the ACZ/AGZ units is suitable for most applications. When additional sound
reduction is necessary, locate the unit away from sound sensitive areas. Avoid locations beneath
windows, or between structures where normal operating sounds can be objectionable. Reduce
structurally transmitted sound by isolating refrigerant lines, electrical conduit and the unit itself. Use
wall sleeves and rubber isolated piping hangers to reduce transmission of water, refrigerant, or pump
noise into occupied spaces. Use flexible electrical conduit to isolate sound transmission through
electrical conduit. Spring isolators are effective in reducing the low amplitude sound generated by
scroll compressors and for unit isolation in sound sensitive areas.
Vibration Isolators
Vibration isolator springs are recommended for all roof-mounted installations, or wherever vibration
transmission is a consideration. Some form of isolator is also recommended for slab installations,
primarily to keep the unit base from resting its entire length directly on the slab.
Table 2 and Table 3 list isolator point loads for all unit sizes. Figure 15 and 16 shows isolator
locations. See Dimensional Data for detailed mounting hole location.
Isolator Installation
The unit should be initially installed on shims or blocks at the listed free height. When all piping,
wiring, flushing, charging, etc., is completed, adjust the springs upward to load them and to provide
clearance to remove the shims or blocks.
Installation of spring isolators requires flexible piping connections and at least three feet of conduit
flex tie-ins. Piping and conduit must be supported independently of the unit.
Bolting: if the chiller base is to be bolted to the isolators, it is recommended that the short threaded studs
usually found on isolators be replaced with eight-inch threaded rod that can extend through the holes on
the top of the base and then be bolted. Washers will be required.
Figure 15, RP-4, Neoprene-in-Shear Isolators CP-2, Spring Isolators
Figure 16, Isolator Locations,
4/6 FAN UNIT8 FAN UNIT
34
45
6
CONTROL
PANEL
12
12ACZ / AGZ-BM IMM ACZ/AGZ-4
CONTROL
PANEL
12
3
Table 2, Isolator Loads At Each Mounting Location (With Aluminum Fins)
ACZ-B
Model
ACZ 030 AGZ 026
ACZ 035 AGZ 030
ACZ 040 AGZ 035
ACZ 045 AGZ 040
ACZ 050 AGZ 045
ACZ 055 AGZ 050
ACZ 060 AGZ 055
ACZ 065 AGZ 060
ACZ 070 AGZ 065
ACZ 080 AGZ 070
AGZ-BM
Model
Shipping
lbs 3550 3600 1227 901 849 623 3600 72
kg 1608 1631 556 408 385 282 1631 32
lbs 3550 3600 1227 901 849 623 3600 72
kg 1608 1631 556 408 385 282 1631 32
lbs 3550 3600 1227 901 849 623 3600 72
kg 1608 1631 556 408 385 282 1631 32
lbs 3550 3610 1261 872 873 604 3610 72
kg 1608 1635 571 395 395 274 1635 32
lbs 3590 3650 1275 881 883 611 3650 72
kg 1626 1653 578 399 400 277 1653 32
lbs 3730 3800 1295 951 896 658 3800 119
kg 1690 1721 587 431 406 298 1721 54
lbs 3780 3850 1303 1016 860 671 3850 119
kg 1712 1744 590 460 390 304 1744 54
lbs 3820 4040 1367 1066 903 704 4040 142
kg 1730 1830 619 483 409 319 1830 65
lbs 3970 4070 1305 1146 862 757 4070 142
kg 1798 1844 591 519 390 343 1844 65
lbs 4080 4180 1278 1192 885 825 4180 217
kg 1848 1894 579 540 401 374 1894 99
Wt
Operating.
Wt
Loc. 1 Loc. 2 Loc. 3 Loc. 4 Total
NOTE (1): Additional weight for copper coils is per mounting location.
(1) Add’l for
Copper Fins
Table 3, Isolator Loads At Each Mounting Location (With Aluminum Fins)
ACZ
Model
ACZ090 AGZ 075
ACZ100 AGZ 085
ACZ110 AGZ 090
ACZ120 AGZ 100
ACZ130 AGZ 110
ACZ140 AGZ 120
ACZ155 AGZ 130
NOTE (1): Additional weight for copper coils is per mounting location.
3600 1631 Black Gray Gray Green- - Orange Purple Red Orange
3600 1631 Black Gray Gray Green- - Orange Purple Red Orange- 3600 1631 Black Gray Gray Green- - Orange Purple Red Orange- 3610 1635 Black Gray Gray Green- - Orange Purple Purple Orange- 3650 1653 Black Gray Gray Green- - Orange Purple Purple Orange- 3800 1721 Black Gray Gray Green- - Orange Purple Purple Orange- 3850 1744 Black Gray Gray Green- - Orange Purple Purple Orange- 4040 1830 Black Gray Gray Green- - Orange Purple Purple Orange- 4070 1844 Black BlackGray Gray - - Orange Purple Purple Red - 4180 1894 Black BlackGray Gray - - Orange Orange Purple Red - 5630 2550 Red BlackRed Black - - Green Orange Green Orange- 5790 2623 Red BlackRed Black - - Green Orange Green Orange- 5950 2695 Red BlackRed Black - - Green Orange Green Orange- 6970 3157 Black Black Black Black Black Black Orange Orange Purple Orange Orange Purple
7230 3275 Black Black Black Black Black Black Orange Orange Purple Orange Orange Purple
7480 3388 Red Black BlackRed Black Black Green Orange Purple Green Orange Purple
7760 3515 Red Black BlackRed Black Black Green Orange Purple Green Orange Purple
spring.
Neoprene-In-Shear Mountings Spring-Flex Mountings
Ambient Temperature and Water Flow Limitations
ACZ/AGZ units are designed to operate in ambient temperatures as shown in the following table.
Table 6, Unit Maximum Operating Ambient Temperature
Unit Model Standard Controls
AGZ 026B – 130B
ACZ 030B – 155B
115°F 105°F 125°F
w/ Low Ambient VFD
Control Option
The VFD Low Ambient Control Option imposes an additional heat load on the control panel limiting
operation to 105°F ambient temperature. The addition of the High Ambient Panel Option allows
operation to 125°F ambient temperature.
Compressor loading and unloading is adaptively determined by system load, ambient air temperature,
and other inputs to the MicroTech control algorithms. An optional low ambient fan VFD option allows
operation down to 0°F (-18°C). The minimum ambient temperature is based on still conditions where
the wind is not greater than five mph. Greater wind velocities will result in reduced discharge pressure,
increasing the minimum operating ambient temperature. Field-installed hail/wind guards are available
to allow the chiller to operate effectively down to the ambient temperature for which it was designed.
Evaporator flow rates can be found on page
25. Operation below the minimum values can result in
laminar flow causing freeze-up problems, scaling and poor control. Flow rates above the maximum
values will result in unacceptable pressure drops and can cause excessive erosion, potentially leading to
failure.
w/ Low Ambient VFD Control
Plus High Ambient Panel Option
Water Piping (Model AGZ-BM)
Local authorities can supply the installer with the proper building and safety codes required for safe and
proper installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop. The following
issues must be considered when designing and installing water piping:
14 ACZ / AGZ-BM IMM ACZ/AGZ-4
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves are required to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Drains must be installed
at the lowest points in the system.
4. Adequate system water pressure must be maintained (expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit are required to aid in unit servicing.
6. A strainer or other means of removing foreign matter from the water before it enters the pump
be installed. Place the strainer far enough upstream to prevent cavitation at the pump
must
inlet (consult pump manufacturer for recommendations). The use of a strainer will prolong
pump life and keep system performance up.
7. A strainer must
be installed in the water line before the inlet of the evaporator. This will help
prevent foreign material from entering and decreasing the evaporator performance.
8. If the unit is used as a replacement chiller, flush the system thoroughly before unit
installation. Regular water analysis and chemical water treatment for the evaporator loop is
recommended immediately at equipment start-up.
9. The total water volume in the system should be sufficient to prevent frequent “on-off”
cycling. Turnover rate should not be less than 4 minutes for normal variable cooling loads.
10. When glycol is added to the water system for freeze protection, the refrigerant suction
pressure will be lower, cooling performance less, and water side pressure drop greater. If the
percentage of glycol is high, or if propylene is used instead of ethylene glycol, the added
pressure drop and loss of performance could be substantial. When Glycol or Ice are selected
as Unit Mode, the MicroTech controller will automatically reset the available range for the
Leaving Water Temperature, Freezestat and Evaporator Pressure settings.
Reset the freezestat setting to approximately 4 to 5 degrees F (2.3 to 2.8 degrees C) below the
leaving chilled water setpoint temperature. See the section titled “Glycol Solutions” for
additional information concerning glycol.
11. Perform a preliminary leak check before insulating the piping and filling the system.
12. Piping insulation should include a vapor barrier to prevent condensation and possible damage
to the building structure from water dripping.
Figure 17, AGZ 075BM – AGZ 130BM, Typical Field Evaporator Water Piping
THERMOWELL
T
INLET
T
IMM ACZ/AGZ-4 ACZ / AGZ-BM 15
Figure 18, AGZ 026BM - AGZ 070BM, Typical Field Evaporator Water Piping
Air
T
Inlet
Outlet
T
Thermowell
Vent
P
Drain
Vibration
Eliminators
Strainer
Isolation
Valves
Flow
Switch
Flow Switch (Model AGZ-BM)
Mount a water flow switch in the leaving water line of the remote water chiller to shut down the unit
when water flow is interrupted. A flow switch is an equipment protection control and should never
be used to cycle a unit.
A flow switch is available from McQuay (part number 017503300). It is a “paddle” type switch and
adaptable to any pipe size from 2” (51 mm) to 6” (152 mm) nominal. Certain minimum flow rates
are required to close the switch and are listed in
19. Connect the normally open contacts of the flow switch in the unit control center at terminals 44
and 61. There is also a set of normally closed contacts on the switch that can be used for an indicator
light or an alarm to indicate when a “no flow” condition exists. Freeze protect any flow switch that
is installed outdoors. Manufacturer’s instructions included with the switch should be followed.
NOTE: Differential pressure switches are not recommended for outdoor installation.
Table 7. Installation should be as shown in Figure
Note: See pressure drop table on page 25 for minimum and maximum flow through the evaporator.
Minimum Required Flow To
Activate Switch - gpm (l/m)
Maximum Flow Rate
gpm (l/m)
Figure 19, Flow Switch Installation
Flow direction marked on switch
1" (25mm) NPT flow switch connection
Tee
Water Connections
Bring water piping to the evaporator through the side between the vertical supports. Provide taps for
the connection of pressure gauges and thermometers in the inlet and outlet lines. Check the inlet and
outlet labels on the unit against the certified drawings supplied on the job and be sure the water
piping is hooked up correctly. Contact the McQuay sales office if any discrepancies exist.
16 ACZ / AGZ-BM IMM ACZ/AGZ-4
Variable Speed Pumping
Variable water flow involves lowering the water flow through the evaporator as the load decreases.
McQuay chillers are designed for this duty provided that the rate of change in water flow is slow and
the minimum and maximum flow rates for the vessel are not exceeded.
The recommended maximum change in water flow is 10 percent of the change per minute.
The water flow through the vessel must remain between the minimum and maximum values listed on
25. If flow drops below the minimum allowable, large reductions in heat transfer can occur. If
page
the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.
System Water Volume Considerations
All chillers need adequate time to recognize a load change, respond to the change and stabilize
without short cycling the compressor. The water volume in the system and the size of the piping
loop is a critical consideration. Good engineering practice is to have a minimum water volume of
four times the flow rate (GPM) for comfort cooling applications. For process applications where the
load can change quickly, contact the local McQuay sales office for recommendations. A water
storage tank (provided by others) can be required to increase the system water volume in some
systems.
Since there are many other factors that can influence performance, systems can successfully operate
below these suggestions. However, as the water volume decreases below these suggestions, the
possibility of problems increases. We believe that these guidelines should be an industry standard
and not just recommendations from McQuay.
Glycol Solutions
The use of a glycol/water mixture in the evaporator to prevent freezing will reduce system capacity
and efficiency and increase pressure drop. The system capacity, required glycol solution flow rate,
and pressure drop with glycol can be calculated using the following formulas and tables.
1. Capacity – Multiply the capacity based on water by the Capacity correction factor from
through
2. Flow – Multiply the water evaporator flow by the Flow correction factor from
Table 11.
Table 8 through
Table 8
Table 11 to determine the increased evaporator flow due to glycol.
If the flow is unknown, it can be calculated from the following equation:
(gpm) Flow Glycol
−
TDelta
×
=
3. Pressure drop -- Multiply the water pressure drop from page
factor from
Table 8 through Table 11. High concentrations of propylene glycol at low
)(24
glycolCapacityTons
×
FactorCorrectionFlow
25 by Pressure Drop correction
temperatures can cause unacceptably high-pressure drops.
4. Power -- Multiply the water system power by Power correction factor from
Table 8 through
Table 11.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service
stations) to determine the freezing point. Obtain percent glycol from the freezing point table below.
It is recommended that a minimum of 25% solution by weight be used for protection against
corrosion or that additional compatible inhibitors be added.
IMM ACZ/AGZ-4 ACZ / AGZ-BM 17
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be used.
Automotive antifreeze contains inhibitors which will cause plating on the copper tubes
within the chiller evaporator. The type and handling of glycol used must be consistent with
local codes.
Table 8, Ethylene Glycol Factors for Models AGZ 026BM to 070BM
Performance tables are based at sea level. Elevations other than sea level affect the performance of
the unit. The decreased air density will reduce condenser capacity, consequently reducing the unit's
performance. For performance at elevations other than sea level refer to
Table 12 or Table 13.
18 ACZ / AGZ-BM IMM ACZ/AGZ-4
Evaporator Temperature Drop Factors
Performance tables are based on a 10 degree F (5 degree C) temperature drop through the evaporator.
Adjustment factors for applications with temperature ranges from 6 degree F to 16 degree F (3.3
degree C to 8.9 degree C) are found in
Table 12 and Table 13. Ranges outside these temperatures
can affect the control system's capability to maintain acceptable control and must not be used.
The maximum water temperature that can be circulated through the evaporator in a non-operating
mode is 100°F (37.8°C).
Fouling Factor
Performance tables are based on water with a fouling factor of:
As fouling is increased, performance decreases. For performance at other than 0.0001 (0.0176)
fouling factor, refer to
Table 12 and Table 13. Foreign matter in the chilled water system will
adversely affect the heat transfer capability of the evaporator and could increase the pressure drop
and reduce the water flow. Maintain proper water treatment to provide optimum unit operation.
Table 12, Capacity and Power Derates, Models AGZ 026 to 070
All ACZ units have two circuits, each with either two compressors, or three compressors on models
ACZ 120 through 155. These circuits must be kept separated throughout the entire refrigerant piping
system. Each unit refrigerant circuit must be piped to a separate coil or to a separate air handler
(with a single coil).
Temperature control for each evaporator coil is provided by the installer through field-supplied and
wired temperature controllers. The field-supplied staging signals are field-wired to the Microtech II
controller that correspondingly activates and deactivates the scroll compressors. The MicroTech II
controller has a menu screen (See operating manual OM AGZ) that allows selection between “Unit’
and “Circuit”.
Select “Unit” for a single air handler with row control where it does not matter which circuit starts
first. When the controller gets a signal to start Stage 1 of cooling, it will start the compressor, on
either circuit, with the fewest number of starts, so either circuit can start first. Energizing stage 2
will start the compressor with the fewest starts on the other circuit. Further staging requests will
continue to start alternate compressors between the two circuits.
For applications where the staging must be associated with a particular circuit (face-split coils or
separate air handlers), select “Circuit”. In this mode, stages 1, 2, and 3 are connected to refrigerant
circuit #1 and stages 4, 5,and 6 to refrigerant circuit #2. As the thermostat for coil #1 stages up, the
microprocessor will start the compressors on circuit # 1 (compressors 1, 3 and 5). Compressors 5
and 6 are found only on the six compressor units.
The field supplied temperature controller is required to close normally open 24-volt contacts on a
demand for cooling. These closure signals are field wired to the terminal strip (TB3) in the
condensing unit. Refer to the field wiring diagram (page
staging is required:
51) for details. The following control
Condensing Unit Model
ACZ-030B through 110B 4 4
ACZ-120B through 155B 6 6
Number of
Capacity Steps
Number of Required
Contact Closure Signals
In summary:
• Evaporator coil #1 must be piped to the condensing unit circuit #1. See dimension drawings
beginning on page
dimension drawings beginning on page
52. Evaporator coil #2 must be piped to the condensing unit circuit #2. See
52 for circuit locations.
• Evaporator staging thermostat for coil #1 must be wired to the unit terminal board TB3, stages 1,
and 2 (and 3 on models 120 through 155). Evaporator staging thermostat for coil #222 must be
wired to the unit terminal board TB3, stages 4, and 5 (and 6 on models 120 through 155).
AGZ-BM Remote Evaporator Chillers: Refrigerant specialties including the expansion valves,
solenoid valves, filter-drier and sight glasses for use with the AGZ-BM remote evaporator models are
supplied by McQuay but require field installation. The remaining components including fittings and
Schrader valves are provided and piped by the installer.
The hot gas bypass valve with solenoid valve option can be provided as a field-installed or factory
installed option.
ACZ-B Condensing Units:
variety of evaporator types, other than a water chiller as shown in the above diagram, may be used.
Very often these may be air handlers with multiple-circuited coils. If multiple evaporator circuits and
expansion valves are used, they must be piped so that only two circuits end up being piped back to
the condensing unit, matching the unit’s two refrigerant circuits. Each circuit must have a solenoid
valve with a filter-drier installed ahead of it installed close to the evaporator.
The hot gas bypass valve with solenoid valve option can be provided as a field-installed or factory
installed option.
Unit-Mounted Valves:
valve and a suction shutoff valve factory mounted as standard.
No Refrigerant specialties are furnished on the ACZ condensing units. A
Both the ACZ-B and the AGZ-BM outdoor sections have a liquid line shutoff
22 ACZ / AGZ-BM IMM ACZ/AGZ-4
Refrigerant Piping
All field piping, wiring, and procedures must be performed in accordance with ASHRAE, EPA, and
industry standards. Proper refrigerant piping can make the difference between a reliable system and
an inefficient, problematic system.
The primary concerns related to piping are refrigerant pressure drop, a solid liquid feed to the
expansion valves, continuous oil return and properly sized refrigerant specialties.
Insulate the suction line to reduce excessive superheat build-up. Insulate the liquid line, where
located in areas above ambient temperature, to prevent loss of subcooling and consequent liquid
flashing.
A holding charge of R-22 is provided for the evaporator (AGZ-BM) and the outdoor section. The
installer must properly evacuate the piping system and provide the operating charge of R22. Refer to
the piping schematic drawing on page
The recommended source for refrigerant piping techniques and sizing is the ASHRAE 2002
Refrigeration Handbook, chapter 2.
Although conflicting piping recommendations can be found in different sources, McQuay offers the
following recommendations for these controversial issues.
The use of double risers for vertical gas risers is generally not required and should be used only as a
last resort to maintain the minimum refrigerant flow to carry oil up the vertical risers. Slightly
downsizing the vertical riser is a preferable option to providing double risers.
Slope the refrigerant lines 1” per 10 feet of horizontal run in the direction of refrigerant flow to assist
oil return.
22 for additional details.
Resist using hot gas bypass for applications when operation in ambient temperature below 40
degrees is expected. This recommendation helps to maintain adequate condensing pressures and
liquid refrigerant at the expansion valve when condenser capacities are at their maximum.
Pressure drops in the refrigerant lines should be maintained at or below the ASHRAE
recommendations and line lengths should be made as short as possible. Exceeding these
recommendations will decrease performance and could impact reliability.
Small traps should be provided at the base of each major vertical gas riser to assist in the collection
of oil. If vertical risers exceed more than 25 feet, install a small trap at the midpoint and at a
maximum of 20 foot intervals.
Use caution in sizing the liquid line in applications where the evaporator is above the outdoor
section. The weight of the liquid refrigerant in the vertical column will decrease the pressure at the
top of the riser (approximately 0.5 psi per foot of vertical rise) allowing some of the refrigerant to
flash to a gas. Adequate refrigerant subcooling is needed at the outdoor section to prevent large
volumes of refrigerant gas at the expansion valve.
The piping systems should always extend above the highest component in the refrigeration system
before dropping down to make the final refrigerant connections to components. This practice will
hinder the draining of condensed refrigerant to the lower component when normal shutdown
procedures do not occur (such as a power failure).
NOTE: Do not run refrigerant piping underground.
Pumpdown
The pumpdown capacity of ACZ/AGZ units is given in the Physical Data Tables. Care should be
exercised to include all equipment and lines when calculating the system charge relative to the unit’s
pumpdown capacity. The AGZ-BM remote evaporators have an insignificant operating charge.
IMM ACZ/AGZ-4 ACZ / AGZ-BM 23
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.