Date of purchase: _________________________________
Date of installation: _______________________________
Installer: ________________________________________
Model number: ___________________________________
Serial number: ___________________________________
W10240579B
W10240583B-SP
1
DRYER SAFETY
You
You can be killed or seriously injured if you don't immediately
can be killed or seriously injured if you don't
follow
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
follow instructions.
instructions.
DANGER
WARNING
2
INSTALLATION REQUIREMENTS
TOOLS AND PARTS
Gather the required tools and parts before starting installation.
Tools needed:
Flat-blade screwdriver#2 Phillips screwdriver
Wire stripper (direct wire
installations)
1/4" nut driver
(recommended)
Tin snips (new vent
installations)
Vent clamps
Parts supplied (all models):
Leveling legs (4)
Parts supplied (steam models):
“Y” connectorShort inlet hose
Long inlet hoseRubber washer
Adjustable wrench that
opens to 1" (25mm) or
hex-head socket wrench
Tape measure
Level
Utility knife
Pliers
Caulking gun and
compound (for installing
new exhaust vent)
Parts package is located in dryer drum. Check that all parts
are included.
NOTE: If installing dryer on pedestal, do not use leveling legs.
Optional Equipment: (Not supplied with dryer)
Refer to your Use and Care Guide for information about
accessories available for your dryer.
Parts needed: (Not supplied with dryer)
Check local codes. Check existing electrical supply and venting.
See “Electrical Requirements” and “Venting Requirements”
before purchasing parts.
Check code requirements. Some codes limit, or do not permit,
installing dryer in garages, closets, mobile homes, or sleeping
quarters. Contact your local building inspector.
3
27"
(686 mm)
38"
(965 mm)
1"
(25 mm)
10
1
/4"
(260 mm)
4
1
/4"
(108 mm)
29"
(736 mm)
36
1
/4"
(921 mm)
1"
(25 mm)
27
1
/
4"
(695 mm)
Left or
right side
exhaust
LOCATION REQUIREMENTS
You will need:
A location allowing for proper exhaust installation. See ■
“Venting Requirements.”
A separate 30 amp circuit.■
If using power supply cord, a grounded electrical outlet ■
located within 2 ft. (610 mm) of either side of dryer. See
“Electrical Requirements.”
Floor must support dryer weight of 200 lbs. (90.7 kg). Also ■
consider weight of companion appliance.
Cold water faucets located within 4 ft. (1.2 m) of the water ll ■
valves, and water pressure of 20-100 psi (137.9-689.6 kPa).
You may use the water supply for your washer using the “Y”
connector and short hose (if needed) which are provided.
20-100 psi (138-690 kPa) for best performance.■
Level oor with maximum slope of 1" (25 mm) under entire ■
dryer. If slope is greater than 1" (25 mm), install Extended
Dryer Feet Kit, Part Number 279810. If not level, clothes
may not tumble properly and automatic sensor cycles may
not operate correctly.
For each arrangement, consider allowing more space for ease
of installation and servicing; spacing for companion appliances
and clearances for walls, doors, and oor moldings. Space
must be large enough to allow door to fully open. Add spacing
on all sides of dryer to reduce noise transfer. If a closet door
or louvered door is installed, top and bottom air openings
in door are required.
DRYER DIMENSIONS
Front view:
* Approx. measurement
Side view:
4
Back view:
6
1
/
4"
(159 mm)
28
3
/
4"
(733 mm)
3
3
/
4
"
(83 mm)
13"
(330 mm)
Electric
24 in.
2
(155 cm2)
48 in.
2
(310 cm2)
1"
(25 mm)
1"
(25 mm)
4"
(102 mm)
3"
(76 mm)
34" recommended
(864 mm)
18" min.
(457 mm)
3"
(76 mm)
1"
(25 mm)
1"
(25 mm)
4"
(102 mm)
7"
(178 mm)
18"
(460 mm)
NOTE: Most installations require a minimum of 5" (127 mm)
clearance behind dryer for exhaust vent with elbow. See “Venting
Requirements.”
IMPORTANT: Do not operate, install, or store dryer where
it will be exposed to water, weather, or at temperatures below
45° F (7° C). Lower temperatures may cause dryer not to
shut off at end of automatic sensor cycles, resulting in longer
drying times.
Closet installation (dryer only):
Cabinet installation (dryer only):
Installation spacing for recessed area or closet
installation
All dimensions show recommended spacing allowed, with tested
spacing of 0" (0 mm) clearance on sides and rear.
Additional spacing should be considered for ease of ■
installation and servicing.
Additional clearances might be required for wall, door, and ■
oor moldings.
Additional spacing should be considered on all sides of the ■
dryer to reduce noise transfer.
For closet installation, with a door, minimum ventilation ■
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilitation openings are
acceptable.
Companion appliance spacing should also be considered.■
5
Closet Installation (stacked washer and dryer):
1"
(25 mm)
1"
(25 mm)
5
1
/2"
(140 mm)
24 in.
2
(155 cm2)
48 in.
2
(310 cm2)
3"
(76 mm)
3"
(76 mm)
6"
(152 mm)
76"
(1930 mm)
1"
(25 mm)
1"
(25 mm)
39" min.
(990 mm)
Custom under counter installation (dryer only):
ELECTRICAL REQUIREMENTS
It is your responsibility:
To contact a qualied electrical installer.■
To be sue that the electrical connection is adequate and in ■
conformance with the National Electrical Code, ANSI/NFPA
70 - latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
To supply the required 3 or 4 wire, single phase, 120/240 ■
volt, 60 Hz, AC only electrical supply (or 3 or 4 wire, 120/208
volt electrical supply, if specied on the serial/rating plate)
on a separate 30-amp circuit, fused on both sides of the line.
Connect to an individual branch circuit. Do not have a fuse in
the neutral or grounding circuit.
Do not use an extension cord.■
If codes permit and a separate ground wire is used, it is ■
recommended that a qualied electrician determine that the
ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
NOTE: Some models not recommended for undercounter
installation.
Mobile home - Additional installation requirements:
This dryer is suitable for mobile home installations. The
installation must conform to the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile home construction
and Safety, Title 24, HUD Part 280) or Standard CAN/CSA-Z240
MH.
Mobile home installations require:
Metal exhaust system hardware, available for purchase from ■
your dealer. For further information, see “Assistance or
Service” section in your Use and Care Guide.
Special provisions must be made in mobile homes to ■
introduce outside air into dryer. Openings (such as a nearby
window) should be at least twice as large as dryer exhaust
opening.
6
This dryer is manufactured ready to install with a 3-wire ■
electrical supply connection. The neutral ground conductor
is permanently connected to the neutral conductor (white
wire) within the dryer. If the dryer is installed with a 4-wire
electrical supply connection, the neutral ground conductor
must be removed from the external ground connector (green
screw), and secured under the neutral terminal (center or
white wire) of the terminal block. When the neutral ground
conductor is secured under the neutral terminal (center or
white wire) of the terminal block, the dryer cabinet is isolated
from the neutral conductor.
If local codes do not permit the connection of a neutral ■
ground wire to the neutral wire, see “Optional 3-wire
connection” section.
A 4-wire power supply connection must be used when the ■
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations,
(2) mobile homes, (3) recreational vehicles, and (4) areas
where local codes prohibit grounding through the neutral
conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL listed 30-amp power supply cord, rated 120/240 volt ■
minimum. The cord should be type SRD or SRDT and be
at least 4 ft. (1.22 m) long. The wires that connect to
the dryer must end in ring terminals or spade terminals
with upturned ends.
A UL listed strain relief.■
If your outlet looks like this:
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
�
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
WARNING
Excessive Weight Hazard
Use two or more people to move and install dryer.
Failure to do so can result in back or other injury.
diamond
m
arking
Then choose a 4-wire power supply cord with
ring or spade terminals and UL listed strain
relief. The 4-wire power supply cord, at least
4 ft. (1.22 m) long, must have four 10-gauge
copper wires and match a 4-wire receptacle of
NEMA Type 14-30R. The ground wire (ground
4-wire receptacle
(14-30R)
If your outlet looks like this:
3-wire receptacle
(10-30R)
conductor) may be either green or bare. The
neutral conductor must be identied by a white
cover.
Then choose a 3-wire power supply cord with
ring or spade terminals and UL listed strain
relief. The 3-wire power supply cord, at least
4 ft. (1.22 m) long, must have three 10-gauge
copper wires and match a 3-wire receptacle of
NEMA Type 10-30R.
Choose a standard power supply cord connector:
INSTALL LEVELING LEGS
1.
Prepare dryer for leveling legs
Flanged spade connectors Ring connectors
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic sheathed copper cable ■
(with ground wire), protected with exible metallic conduit. All
current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum) at least ■
5 ft. (1.52 m) long.
To avoid damaging oor, use a large at piece of cardboard
from dryer carton; place under entire back edge of dryer.
Firmly grasp dryer body (not console panel) and gently lay
dryer down on cardboard.
2.
Screw in leveling legs
Examine leveling legs, nd diamond marking. Screw legs into
leg holes by hand, use a wrench to nish turning legs until
diamond marking is no longer visible.
Now stand the dryer on its feet. Slide the dryer until it is
close to its nal location. Leave enough room for electrical
connection and to connect the exhaust vent.
7
WARNING
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to
green ground connector.
Connect remaining 2 supply wires to remaining
2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, re, or
electrical shock.
ELECTRICAL CONNECTION
WARNING
Fire Hazard
Use a new UL listed 30 amp power supply cord.
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to
green ground connector.
Connect remaining 2 supply wires to remaining
2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, re, or
electrical shock.
Power Supply Cord
Direct Wire
ELECTRICAL CONNECTION
OPTIONS
3.Choose electrical connection type
Power supply cord 4-wire receptacle
(NEMA Type 14-30R):
Follow steps 4-6 and 7-10.
Then, go to Venting Requirements.
Power supply cord 3-wire receptacle
(NEMA Type 10-30R):
Follow steps 4-6 and 11-13.
Then go to Venting Requirements.
4-wire direct connection:
Follow steps 4 and 14-21.
Then go to Venting Requirements.
NOTE: If local codes do not permit connection of a
cabinet-ground conductor to neutral wire, go to “Optional
3-wire connection” and follow steps 4, 14-15, and 27-30.
This connection may be used with either a power supply
cord or a direct wire connection.
8
3-wire direct connection:
Follow steps 4, 14-15, and 22-26.
Then go to Venting Requirements.
4.Remove terminal block cover
Before you start, disconnect power. Remove hold-down screw
and terminal block cover.
A
B
C
D
Power supply cord strain relief:
A
BF
E
G
D
C
Attach power supply cord
5.
strain relief
A. Strain relief tab pointing up
B. Hole below terminal block opening
C. Clamp section
D. Strain relief tab pointing down
Remove screws from 3/4" (19 mm) UL listed strain relief (UL
marking on strain relief). Put two clamp section tabs into hole
below terminal block opening with one tab pointing up and
one pointing down. Hold in place and tighten strain relief
screws enough to hold two clamp sections together.
4-WIRE POWER SUPPLY CORD
CONNECTION
IMPORTANT:A 4-wire connection is required for mobile
homes and where local codes do not permit the use of 3-wire
connections.
A. 4-wire receptacle (NEMA type 14-30R)
B. 4-prong plug
C. Ground prong
D. Neutral prong
E. Spade terminals with upturned ends
F. 3/4" (19 mm) UL listed strain relief
G. Ring terminals
Prepare to connect neutral
7.
ground wire and neutral wire.
E
B
Attach power supply cord
6.
to strain relief
Put power supply cord through strain relief. Be sure that wire
insulation on power cord is inside strain relief. Strain relief
should be a tight t with dryer cabinet and be in a horizontal
position. Do not tighten strain relief screws at this point.
Now go to step 5 for 4-wire power supply cord
connection or step 9 for 3-wire power supply cord
connection.
Remove center, silver-colored terminal block screw (B).
Remove neutral ground wire (E) from external ground
conductor screw (A).
8.
Connect neutral ground wire
and neutral wire
C
E
Connect neutral ground wire (E) and neutral wire (white or
center wire) (C) of power supply cord under center, silvercolored terminal block screw (B). Tighten screw.
A
B
9
A
B
D
C
E
F
G
9.Connect ground wire
F
11.Remove center screw
B
A
Connect ground wire (F) (green or bare) of power supply cord
to external ground conductor screw (A). Tighten screw.
10.
Connect remaining wires
Connect remaining wires to outer terminal block screws.
Tighten screws. Finally, reinsert tab of terminal block cover
into slot of dryer rear panel. Secure cover with hold-down
screw. Now, go to Venting Requirements.
3-WIRE POWER SUPPLY CORD
CONNECTION
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
Remove center, silver-colored terminal block screw (B).
12.Connect neutral wire
C
Connect neutral wire (white or center wire) (C) of power supply
cord to center, silver-colored terminal block screw (B). Tighten
screw.
B
13.Connect remaining wires
A. 3-wire receptacle (NEMA type 10-30R)
B. 3-wire plug
C. Neutral prong
D. Spade terminals with upturned ends
E. 3/4" (19 mm) UL listed strain relief
F. Ring terminals
G. Neutral (white or center wire)
10
Connect remaining wires to outer terminal block screws.
Tighten screws. Finally, reinsert tab of terminal block cover
into slot of dryer rear panel. Secure cover with hold-down
screw. Now, go to Venting Requirements.
Direct wire strain relief:
1"
(25 mm)
5"
(127 mm)
14.Attach direct wire strain relief
Unscrew removable conduit connector and any screws from
a 3/4" (19 mm) UL listed strain relief (UL marking on strain
relief). Put threaded section of strain relief through hole below
terminal block opening, screw removable conduit connector
onto strain relief threads.
15.Attach direct wire cable
to strain relief
4-WIRE DIRECT WIRE
CONNECTION
Prepare your 4-wire cable for direct connection:
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit 3-wire
connections.
16.Prepare your 4-wire cable for
direct connection
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer may be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable,
leaving bare ground wire at 5" (127 mm). Cut 11/2" (38 mm)
from remaining 3 wires. Strip insulation back 1" (25 mm).
Shape ends of wires into hooks.
Put direct wire cable through strain relief. Strain relief should
be a tight t with dryer cabinet and be in a horizontal position.
Tighten strain relief screw against direct wire cable. Now
go to step 14 for 4-wire direct wire connection, step 20
for 3-wire direct wire connection, or step 25 for optional
3-wire connection.
17.Connect wires to terminal block
To connect wires to terminal block, place hooked end of
wire under terminal block screw, facing to the right, squeeze
hooked end together and tighten screw.
18.Prepare to connect neutral
ground wire and neutral wire
E
A
B
Remove center, silver-colored terminal block screw (B).
Remove neutral ground wire (E) from external ground
conductor screw (A).
11
19.Connect neutral ground wire
1"
(25 mm)
3½"
(89 mm)
and neutral wire
3-WIRE DIRECT WIRE
CONNECTION
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
C
Connect neutral ground wire (E) and place hooked end (hook
facing right) of neutral wire (white or center wire) (C) of direct
wire cable under center screw of terminal block (B). Squeeze
hooked ends together and tighten screw.
B
E
20.Connect ground wire
F
A
22.Prepare your 3-wire cable for
direct connection
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer may be moved if needed.
Strip 31/2" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape wire ends
into hooks.
23.Connect wires to terminal block
Connect ground wire (green or bare) (F) of direct wire cable
to external ground conductor screw (A). Tighten screw.
21.Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze
hooked ends together and tighten screws. Finally, reinsert tab
of terminal block cover into slot of dryer rear panel. Secure
cover with hold-down screw. Now, go to Venting
Requirements.
To connect wires to terminal block, place hooked end of wire
under terminal block screw, facing to the right, squeeze
hooked end together and tighten screw.
24.Remove center screw
B
Remove center, silver-colored terminal block screw (B).
12
25.Connect neutral wire
28.
Connect neutral ground wire
and neutral wire
C
Place hooked end of neutral wire (white or center wire) (C)
of direct wire cable under center terminal block screw (B).
Squeeze hooked end together. Tighten screw.
26.
Connect remaining wires
B
C
Connect neutral ground wire (E) and neutral wire (white or
center wire) (C) of power supply cord or cable under center,
silver-colored terminal block screw (B). Tighten screw.
29.
Connect remaining wires
B
E
Place hooked ends of remaining direct wire cable wires
under outer terminal block screws (hooks facing right).
Squeeze hooked ends together and tighten screws. Finally,
reinsert tab of terminal block cover into slot of dryer rear
panel. Secure cover with hold-down screw. Now, go to
Venting Requirements.
OPTIONAL 3-WIRE CONNECTION
You must verify with a qualied electrician that this
grounding method is acceptable before connecting.
27.Prepare to connect neutral
ground wire and neutral wire
B
E
A
Place hooked ends of remaining wires under outer terminal
block screws (hooks facing right). Tighten screws.
30.
Connect a separate copper ground wire (G) from the external
ground conductor screw (A) to an adequate ground. Finally,
reinsert tab of terminal block cover into slot of dryer rear
panel. Secure cover with hold-down screw. Now, go to
Venting Requirements.
Connect external ground wire
A
G
Remove center, silver-colored terminal block screw (B).
Remove neutral ground wire (E) from external ground
conductor screw (A).
13
4"
(102 mm)
4"
(102 mm)
B
A
4"
(102 mm)
2½"
C
VENTING REQUIREMENTS
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in death
or re.
Exhaust hoods:
Must be at least 12" (305 mm) from ground or any object that ■
may obstruct exhaust (such as owers, rocks, bushes, or
snow).
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or exible metal vent shall be used for
exhausting.
■
Only a 4" (102 mm) heavy metal exhaust
vent and clamps may be used.
■
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid ■
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
Must be fully extended and supported in nal dryer location.■
Remove excess to avoid sagging and kinking that may result ■
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.■
The total length should not exceed 7■
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not plugged
with lint. Replace plastic or metal foil vents with rigid metal or
exible metal vents. Review Vent system chart and if necessary,
modify existing vent system to achieve best drying performance.
3
/4 ft. (2.4 m).
Recommended styles:
A. Louvered hood
B. Box hood
An exhaust hood should cap vent to keep rodents and ■
insects from entering home.
Do not use exhaust hood with a magnetic latch.■
Acceptable styles:
C. Angled hood
Elbows:
45° elbows provide better airow than 90° elbows.■
GoodBetter
Clamps:
Use clamps to seal all joints.■
Exhaust vent must not be connected or secured with screws ■
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
14
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in death
or re.
Improper venting can cause moisture and lint to collect
indoors, which may result in:
Moisture damage to woodwork, furniture, paint, wallpaper,
carpets, etc.
Housecleaning problems and health problems.
Vent products can be purchased from your dealer. For further
information, see “Assistance or Service” section in your Use
and Care Guide.
PLAN VENT SYSTEM
Choose your exhaust installation type
Recommended exhaust installation:
Alternate exhaust installations (for close clearance):
Over-the-top installation
(also available with one offset elbow)
Optional exhaust installations:
If you prefer, dryer may be converted to exhaust out right side,
left side, or through bottom. You must contact your local dealer
to have dryer converted.
Periscope installation
Special provisions for mobile homes:
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath the
mobile home. Terminate exhaust vent outside.
Bottom exhaust installation
Determine vent path:
Select route that will provide straightest and most direct ■
path outdoors.
Plan installation to use fewest number of elbows and turns.■
15
12" min.
(305 mm)
12" min.
(305 mm)
When using elbows or making turns, allow as much room ■
as possible.
Bend vent gradually to avoid kinking.■
Use as few 90° turns as possible.■
Determine vent length and elbows needed for best
drying performance:
Use following Vent system chart to determine type of vent ■
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied
in Vent system chart.
Exhaust systems longer than those specied will:
Shorten life of dryer.■
Reduce performance, resulting in longer drying times ■
and increased energy usage.
The Vent system chart provides venting requirements that will
help achieve best drying performance.
NOTE: Side and bottom exhaust installation have a 90° turn
inside the dryer. To determine maximum exhaust length, add on
90° turn to the chart.
NOTE: If exible transition vent is used, the length must be
subtracted from the total exhaust length in the vent system chart.
Vent system chart
Number of
90° elbows
Type
of vent
Box/louvered
hoods
Angled
hoods
32.
Vent must t over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location
using straightest path possible. Avoid 90° turns. Use clamps
to seal all joints. Do not use duct tape, screws, or other
fastening devices that extend into interior of vent to secure
vent, because they can catch lint.
Connect vent to exhaust hood
CONNECT INLET HOSE
The dryer must be connected to the cold water faucet using the
new inlet hoses. Do not use old hoses.
Turn cold water off, remove and
33.
replace rubber washer
0
1
2
3
4
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
64 ft. (20 m)
54 ft. (16.5 m)
44 ft. (13.4 m)
35 ft. (10.7 m)
27 ft. (8.2 m)
58 ft. (17.7 m)
48 ft. (14.6 m)
38 ft. (11.6 m)
29 ft. (8.8 m)
21 ft. (6.4 m)
INSTALL VENT SYSTEM
31.
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
Install exhaust hood
Turn cold water faucet off and remove washer inlet hose.
Check and see if rubber washer is in the “Y” connector.
Remove old rubber washer from inlet hose and replace with
new rubber washer provided.
16
Attach short hose and
34.
“Y” connector
AB
If space permits, attach the brass female end of the “Y”
connector to the cold water faucet. See gure A.
If “Y” connector cannot be attached directly to the cold water
faucet, the short hose must be used. See gure B. Attach
short hose to cold water faucet. Screw on coupling by hand
until it is seated on faucet. Then attach “Y” connector to
brass male end of the short hose. Screw on coupling by hand
until it is seated on connector.
Tighten couplings
35.
Attach long hose to “Y”
36.
connector and tighten couplings
One end of the long hose has a wire mesh strainer inside the
coupling. Attach this end to the “Y” connector. Attach washer
cold inlet hose to other side of “Y” connector. Screw on
coupling by hand until it is seated on connector. Using pliers,
tighten the couplings an additional two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can
result.
AB
Using pliers, tighten the couplings with additional
two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can
result.
Attach long hose to dryer ll
37.
valve and tighten coupling
Attach other end of long hose to ll valve at bottom of dryer
back panel. Screw on coupling by hand until it is seated on
ll valve connector. Using pliers, tighten the couplings an
additional two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can
result.
17
Turn on cold water faucet
38.
Check that the water faucets are turned on.
Check for leaks
39.
41.
Move dryer to nal location, taking care not to crush or kink
vent.
After dryer is in place, remove corner posts and cardboard
from under dryer.
Move dryer to nal location
LEVEL DRYER
Check for leaks around “Y” connector, faucet, and hoses.
CONNECT VENT
40.
Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure vent is
clean. Dryer vent must t over dryer exhaust outlet and inside
exhaust hood. Check that vent is secured to exhaust hood
with a 4" (102 mm) clamp.
Connect vent to exhaust outlet
42.
Check levelness of dryer from side to side. Repeat from
front to back.
NOTE: The dryer must be level for the moisture sensing system
to operate correctly.
Not Level LEVEL Not Level
Level Dryer
Place
level here
18
Tighten and adjust leveling legs
43.
If dryer is not level, prop up using a wood block, use wrench
to adjust legs up or down, and check again for levelness.
Once legs are level, make sure all four legs are snug against
the oor before tightening them.
•Householdfuseisintactandtight,orcircuitbreaker has not tripped.
•Dryerdoorisclosed.
This dryer automatically runs an installation diagnostic routine
at the start of its rst cycle.
NOTE: You may notice an odor when dryer is rst heated. This
odor is common when heating element is rst used. The odor
will go away.
DOOR REVERSAL
If you prefer to reverse the door swing on your dryer:
COMPLETE INSTALLATION
CHECKLIST
Check that all parts are now installed. If there is an extra
q
part, go back through steps to see what was skipped.
Check that you have all of your tools.
q
Dispose of/recycle all packaging materials.
q
Be sure the water faucets are on.
q
Check for leaks around “Y” connector, faucet, and hoses.
q
Check dryer’s nal location. Be sure vent is not crushed
q
or kinked.
Check that dryer is level. See “Level Dryer”.
q
Remove lm on console and any tape remaining on dryer.
q
Wipe dryer drum interior thoroughly with a damp cloth to
q
remove any dust.
Read “Dryer Use” in your Use and Care Guide.
q
For power supply cord installation, plug into a grounded
q
outlet. For direct wire installation, turn on Power.
If you live in a hard water area, use of a water softener is
q
recommended to control the buildup of scale through the
water system in the dryer. Over time, the buildup of lime
scale may clog different parts of the water system, which will
reduce product performance. Excessive scale buildup may
lead to the need for certain part replacement or repair.
Select a Time Dry heated cycle, and start dryer. Do not select
q
Air Only Temperature setting.
A door reversal kit, Part Number W10277499 is available ■
to order. For further information, see “Assistance or Service”
section in your Use and Care Guide.
TROUBLESHOOTING
See the Use and Care Guide for troubleshooting information.