Maytag PRF013840, PRF0138270, PRF013272 Owner's Manual

30" (76.2 CM) AND 36" (91.4 CM) WALL-
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. FOR RESIDENTIAL USE ONL IMPOR POUR UTILISA
.
MOUNT CANOPY RANGE HOOD
Installation Instructions and Use & Care Guide
For questions about features, operation/performance parts, accessories or service, call: 1-800-253-1301
In Canada, for assistance, installation and service, call: 1-800-807-6777
or visit our website at www.whirlpool.com or www.whirlpool.ca
HOTTE D’EXTRACTION À MONTAGE MURAL
DE30" (76,2 CM) ET 36" (91,4 CM)
Pour des questions à propos des caractéristiques, du fonctionnement/rendement, des pièces, accessoires ou service, composez le:
Au Canada, pour assistance, installation ou service, composez le: 1-800-807-6777
or visitez notre site Web au www.whirlpool.com or www.whirlpool.ca
Table of Contents/Table des matières .....................................2
1-800-253-1301
Y.
TANT : LIRE ET CONSERVER CES INSTRUCTIONS.
W11188152B/LIB0138948
TION RÉSIDENTIELLE UNIQUEMENT
TABLE OF CONTENTS TABLE DES MATIÈRES
RANGE HOOD SAFETY .................................................................2
INSTALLATION REQUIREMENTS .................................................4
Tools and Parts .............................................................................4
Location Requirements ................................................................4
Venting Requirements ..................................................................5
Electrical Requirements ...............................................................6
INSTALLATION INSTRUCTIONS ...................................................7
Prepare Location ..........................................................................7
Install Range Hood .......................................................................8
Connect Vent System ..................................................................8
Make Electrical Connection .........................................................9
Install Vent Covers ........................................................................9
Complete Installation ...................................................................9
RANGE HOOD USE ......................................................................10
Range Hood Controls ................................................................10
RANGE HOOD CARE ...................................................................10
Cleaning .....................................................................................10
WIRING DIAGRAM .......................................................................12
ASSISTANCE OR SERVICE .........................................................13
In the U.S.A. ...............................................................................13
In Canada ...................................................................................13
Accessories ................................................................................13
WARRANTY ..................................................................................14
SÉCURITÉ DE LA HOTTE ............................................................15
EXIGENCES D’INSTALLATION ...................................................17
Outils et pièces ...........................................................................17
Exigences d’emplacement .........................................................17
Exigences concernant l’évacuation ...........................................19
Spécifications électriques ..........................................................20
INSTRUCTIONS D’INSTALLATION ............................................. 21
Préparation de l’emplacement ...................................................21
Installation de la hotte ................................................................22
Raccordement du conduit d’évacuation ...................................22
Raccordement électrique ...........................................................23
Installation des cache-conduits .................................................23
Terminer l’installation ..................................................................23
UTILISATION DE LA HOTTE .......................................................24
Commandes de la hotte de cuisinière .......................................24
ENTRETIEN DE LA HOTTE .........................................................24
Nettoyage ...................................................................................24
SCHÉMA DE CÂBLAGE ...............................................................26
ASSISTANCE OU DÉPANNAGE .................................................. 27
Aux É.-U. ....................................................................................27
Au Canada ..................................................................................27
Accessoires ................................................................................27
GARANTIE .....................................................................................28

RANGE HOOD SAFETY

Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
State of California Proposition 65 Warnings: WARNING: This product contains one or more chemicals known to the State of California to cause cancer. WARNING: This product contains one or more chemicals known to the State of California to cause birth defects or other
reproductive harm.
follow instructions.
You
can be killed or seriously injured if you don't
instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
3

INSTALLATION REQUIREMENTS

Tools and Parts

Gather the required tools and parts before starting installation.Read and follow the instructions provided withanytools listed here.
Tools Needed
■ Level
■ Drill with 1
drillbits
■ Pencil
■ Wire stripper or utility knife
■ Tape measure or ruler
■ Pliers
■ Caulking gun and weatherproof caulking compound
■ Vent clamps
■ Jigsaw or keyhole saw
■ Flat-blade screwdriver
■ Metal snips
■ Phillips screwdriver
■ Metric hex key set
Parts Needed
■ Home power supply cable
■ 1/2" (12.7 mm) UL listed or CSA approved strain relief
■ 3 UL listed wire connectors
For Vented Installations, You Will Also Need:
■ 1 wall or roof cap
■ Metal vent system
For Non-Vented (Recirculating) Installations, YouWillAlsoNeed:
■ Recirculation Kit Part Number W10349327 for non-vented
(recirculating) installations only. See “Assistance or Service” section to order.
■ 6" (15.2 cm) diameter round metal vent duct -
lengthrequiredis determined by ceiling height.
1
/4" (3 cm), 3/8" (9.5 mm), and5/16" (7.9mm)

Location Requirements

IMPORTANT: Observe all governing codes and ordinances. Have a qualied technician install the range hood. It is the
installer's responsibility to comply with installation clearances specied on the model/serial/rating plate. The model/serial/ rating plate is located behind the left lter on the rear wall of the vent hood.
Canopy hood location should be away from strong draft areas, such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance.
Grounded electrical supply is required. See “Electrical Requirements” section.
The canopy hood is factory set for venting through the roof or wall. For non-vented (recirculating) Installation see “For Nonvented (recirculating) Installations Only” in “Connect Vent System” section. Recirculation Kit Part Number W10349327 is available from your dealer or an authorized parts distributor.
NOTE: This product will not comply with Energy Star specications when installed as non-vented (recirculating) with the optional recirculation kit.
All openings in ceiling and wall where canopy hood will be installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local codes.
Product Dimensions
Parts Supplied
Remove parts from packages. Check that all parts are included.
■ Hood canopy assembly with ventilator and light bulbs
installed
■ Vent transition with back draft dampers installed
■ Metal grease lter(s)
■ Vent cover support bracket
■ Mounting template
■ 2-piece vent cover
■ 2 - 3.5 x 9.5 mm screws
■ 2 - 2.9 x 6.5 mm screws
■ 6 - 5 x 45 mm mounting screws
■ 2 - 8 x 40 mm wall anchors
■ 4 - 10 x 50 mm wall anchors
®
■ T20
† Torx® adapter
®
†TORX and T20 are registered trademarks of Acument Intellectual Properties, LLC.
4
(25.4 cm)
30" (76.2 cm) or
36" (91.4 cm)
20" (50.8 cm)
* For non-vented (recirculating) installations ** For vented installations
10"
Cabinet Dimensions
wer
Cooking surface
2" (5.1 cm) min. 6" (15.2 cm) min.*
Vent and po
supply cable
entry location
15" (38.1 cm)
Side cabinet
30" (76.2 cm) or 36" (91.4 cm)
“X”
bottom of
canopy
to cooking
surface
Centerline
* For non-vented (recirculating) installations
IMPORTANT:
Minimum distance “X”: 24" (61 cm) fromelectriccookingsurface
Minimum distance “X”: 27" (68.6 cm) fromgascookingsurface
Suggested maximum distance “X”: 36" (91.4 cm)
The chimneys can be adjusted for different ceiling heights. Seethe following chart.
Vented Installations
Min. ceiling height Max. ceiling height
Electric cooking
7' 5" (2.26 m) 9' 2" (2.79 m)
surface Gas cooking
7' 8" (2.34 m) 9' 2" (2.79 m)
surface
Non-Vented (Recirculating) Installations
Min. ceiling height Max. ceiling height
Electric cooking
7' 5" (2.26 m) 9' 6" (2.9 m)
surface Gas cooking
7' 8" (2.34 m) 9' 6" (2.9 m)
surface
*NOTE: The range hood chimneys are adjustable and designed to meet varying ceiling or soft heights depending on the distance “X” between the bottom of the range hood and the cooking surface. For higher ceilings, a Stainless Steel Chimney Extension Kit Part Number W10337357 is available from your dealer or an authorized parts distributor. The chimney extension replaces the upper chimney shipped with the range hood.
Side cabinet

Venting Requirements

(vented models only)
■ Vent system must terminate to the outdoors, except for
nonvented (recirculating) installations..
■ Do not terminate the vent system in an attic or other .
enclosed area.
■ Do not use 4" (10.2 cm) laundry-type wall cap.
■ Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
■ The length of vent system and number of elbows should be
kept to a minimum to provide efcient performance.
For the Most Efcient and Quiet Operation:
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61 cm) of straight
ventbetween the elbows if more than 1 elbow is used.
■ Do not install 2 elbows together.
■ Use clamps to seal all joints in the vent system.
■ The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the . range hood.
■ Use caulking to seal exterior wall or roof opening
aroundthecap.
■ The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize backward cold air ow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems when using ventilation systems greater than specied CFM of air movement. The specied CFM varies from locale to locale. Consult your HVAC professional for specic requirements in your area.
Venting Methods
This canopy hood is factory set for venting through the roof orwall.
A 6" (15.2 cm) round vent system is needed for installation (notincluded). The hood exhaust opening is 6" (15.2 cm) round.
NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.
Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.
Rear Discharge
A 90° elbow may be installed immediately above the hood.
5
For Non-Vented (Recirculating) Installations
90 Elbo
Wall cap
If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, using a Recirculation Kit (which includes charcoal lters and a deector). To order, see the “Assistance or Service” section.
The ducting from this fan to the outside of the building has a strong effect on the air ow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airow.
Non-Vented
Roof Venting
Wall Venting
A
C
B
B C
A. Roof cap B. 6" (15.2 cm)
round vent
C Seal duct joints
with duct tape/ caulk
*The recirculating version are neither Energy Star nor HVI certified.
A. Wall cap B. 6" (15.2 cm)
round vent
C Seal duct joints
with duct tape/ caulk
(Recirculating)
C
A
A. Deflector B. 6" (15.2 cm)
round vent
C Seal duct joints
with duct tape/ caulk
A
B
Ensure duct joints and exterior penetrations are sealed with caulk or other similar material to create an air-tight path and to minimize building heat loss and gain and reduce the potential for condensation.
Place/wrap insulation around duct and/or fan in order to minimize possible condensation buildup within the duct, building heat loss and gain.
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft (0.8 m)
90° elbow 5 ft (1.5 m)
Example Vent System
w
2 ft
(0.6 m)
The following example falls within the maximum recommendedvent length of 35 ft (10.7 m).
1 - 90° Elbow = 5 ft (1.5 m) 1 - Wall cap = 0 ft (0 m) 8 ft (2.4 m) straight = 8 ft (2.4 m) Length of system = 13 ft (3.9 m)
6 ft (1.8 m)

Electrical Requirements

Observe all governing codes and ordinances. Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
■ A 120 volt, 60 Hz., AC only, 15-amp, fused electrical
circuitisrequired.
■ If the house has aluminum wiring, follow the
procedurebelow:
1. Connect a section of solid copper wire to the
pigtailleads.
2. Connect the aluminum wiring to the added section
of copper wire using special connectors and/or tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with local codes and industry accepted wiring practices.
■ Wire sizes and connections must conform with the rating of
the appliance as specied on the model/serial/rating plate. The model/serial/rating plate is located behind the left lter on the rear wall of the range hood.
■ Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
Maximum equivalent vent length is 35 ft (10.7 m).
6

INSTALLATION INSTRUCTIONS

A
D

Prepare Location

■ It is recommended that the vent system be installed
beforehood is installed.
■ Before making cutouts, make sure there is proper
clearancewithin the ceiling or wall for exhaust vent.
■ Check your ceiling height and the hood height
maximumbefore you select your hood.
1. Disconnect power.
2. Determine which venting method to use: roof, wall, or
nonvented.
3. Select a at surface for assembling the range hood. Place
covering over that surface.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
4. Using 2 or more people, lift range hood onto
coveredsurface.
Range Hood Mounting Screws Installation
1. Determine and mark the centerline on the wall where
thecanopy hood will be installed.
2. Select a mounting height between a minimum of 24" (61.0
cm) for an electric cooking surface, a minimum of 27" (68.6 cm) for a gas cooking surface, and a suggested maximum of 36" (91.4 cm) above the range to the bottom of the hood. Mark a reference line on the wall.
3. Tape template in place, aligning the template centerline and
bottom of template with hood bottom line and with the centerline marked on the wall.
A
TROPPUS LLAW RAER RO SDUTS HGUORHT SELOH TOLIP "61/3 )OWT( 2 LLIRD
Ver
tical Centerline
LLAW RAER
ETALPMET GNITNUOM
C
L
eniL latnoziroH
thgieH noitallatsnI
B
A. Centerline B. Fastener locations C. Mounting height reference
4. Mark centers of the fastener locations through the template
to the wall. IMPORTANT: All canopy mounting screws must be installed
into wood where possible. If there is no wood to screw into, additional wall framing supports may be required, or use the (4) 10 x 60 mm wall anchors and 5.4 x 75 mm screws. Remove the template.
EGDE MOTTOB NGILA
ENIL LICNEP HTIW
MOTTOB GNITACIDNI
DOOH EHT FO
C
5. For wood, drill 3/16" (4.8 mm) pilot holes at all locations
wherescrews are being installed into wood. For wall anchors, drill 7/16" (10 mm) holes at all locations
where wall anchors are being used.
6. For wood, install (2) 5 x 45 mm mounting screws. Leave
a1/4" (6.4 mm) gap between the wall and the back of the screw head to slide range hood into place.
For wall anchors, install the 10 x 60 mm wall anchors andinstall the 5.4 x 75 mm screws into the wall anchors. Tighten until the wall anchors are secure. Back the screws out 1/4" (6.4 mm).
¹⁄₄"
(6.4 mm)
Vent Cover Support Bracket Installation
Installations using telescoping upper and lower vent coverassembly
1. Position vent cover bracket on wall about 1⁄8" (3.0 mm) away
from the ceiling.
2. Mark the hole locations.
3. Drill (2) 3/8" (9.5 mm) holes for 8 x 40 mm wall anchors
andinsert anchors ush with the wall.
C
B
A. 8 x 40 mm wall anchors B. Centerline on wall C. Vent cover support bracket D. 5 x 45 mm screws
4. Attach vent cover support bracket to wall.
Complete Preparation
1. Determine and make all necessary cuts in the wall for the
vent system. Install the vent system before installing the hood. See “Venting Requirements” section.
2. Determine the required height for the home power supply
cable and drill a 11/4" (3.2 cm) hole at this location.
3. Run the home power supply cable according to the National
Electrical Code or CSA Standards and local codes and ordinances. There must be enough ½" conduit and wires from the fused disconnect (or circuit breaker) box to make the connection in the hood’s electrical terminal box.
NOTE: Do not reconnect power until installation is complete.
4. Use caulk to seal all openings.
7

Install Range Hood

A
B
A
D
B
E
1. Using 2 or more people, hang range hood on 2 mounting
screws through the mounting slots on back of hood.
A
For non-vented (recirculating) installation only:
1. Assemble the air deector with the duct cover bracket with
2assembly screws provided with the Recirculation Kit.
B
B
C
A. Mounting screws B. Mounting slots C. Lower mounting screws
2. Remove the grease lter. See “Range Hood Care” section.
3. Level the range hood and tighten upper mounting screws.
4. Install (2) 5 x 45 mm lower mounting screws and tighten.
Usethe optional wall anchors if needed.

Connect Vent System

1. Install transition on top of hood (if removed for shipping)
with(2) 3.5 x 9.5 mm sheet metal screws.
B C
A. Vent cover bracket B. 2.9 x 6.5 mm screws C. Deflector
2. Measure from the bottom of the air deector to the bottom
ofthe hood outlet.
A
C
X
A. Air deflector B. Vent clamp C. X = length to cut vent duct D. Vent duct E. Exhaust outlet
3. Cut the duct to the measured size “X.”
A. Vent transition B. 3.5 x 9.5 mm screw
For vented installations only:
1. Fit vent system over transition piece.
2. Seal connection with clamps.
3. Check that back draft dampers work properly.
4. Remove the air deector.
5. Slide the duct onto the bottom of the air deector.
6. Place the assembled air deector and duct over
theexhaustoutlet from the hood.
7. Reassemble the air deector to the duct cover bracket
withthe 2 assembly screws.
8. Seal connections with vent clamps.
8

Make Electrical Connection

A
E
D
WARNING
Electrical Shock Hazard Disconnect power before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Remove terminal box cover.
3. Remove the knockout in the terminal box and install
aULlisted or CSA approved 1/2" strain relief.
4. Run home power supply wiring through 1/2" strain relief
intoterminal box.
7. Connect green (or bare) ground wire from home power
supply to the 2 yellow-green ground wires (D) in terminal boxusing UL listed wire connectors.
8. Tighten strain relief screw.
9. Install terminal box cover.
10. Reconnect power.

Install Vent Covers

1. When using both upper and lower vent covers, push lower
coverdown onto hood and lift upper cover to ceiling and installwith (2) 2.9 x 6.5 mm screws.
NOTE: For vented installations, the upper vent cover may be reversed to hide slots.
C
C
A
B
D
C
B
A UL listed wire connectors B. White wires C. Black wires D. Green (or bare) wire connected to yellow-green wires E. Home power supply
5. Use UL listed wire connectors and connect white
wires(B)together.
6. Use UL listed wire connectors and connect black
wires(C)together.
WARNING
Electrically ground blower.
Connect ground wire to green and yellow ground wire in terminal box.
Failure to do so can result in death or electrical shock.
Electrical Shock Hazard
A. Upper vent cover B. Lower vent cover C. 2.9 x 6.5 mm screws D. Bracket

Complete Installation

1. For non-vented (recirculating) installations only, install
charcoal lters over the grease lters, using the clips provided in the kit. See the “Range Hood Care” section.
2. Install metal lters. See the “Range Hood Care” section.
3. Check the operation of the range hood blower and light.
Seethe “Range Hood Use” section.
NOTE: To get the most efcient use from your new range hood,read the “Range Hood Use” section.
9

RANGE HOOD USE

B
D
A

RANGE HOOD CARE

The range hood is designed to remove smoke, cooking vapors and odors from the cooktop area. For best results, start the hood before cooking and allow it to operate several minutes after the cooking is complete to clear all smoke and odors from the kitchen.
The hood controls are located on the front panel on the right side of the range hood.
A
C
D
A. LED lamps B. Blower and light controls C. Grease filter handle D. Grease filter

Range Hood Controls

Cleaning

IMPORTANT: Clean the hood and grease lters frequently according to the following instructions. Replace grease lters before operating hood.
Exterior Surfaces:
IMPORTANT: Do not use soap-lled scouring pads, abrasive cleaners, Cooktop Polishing Creme, steel wool, gritty washcloths or paper towels.
To avoid damage to the stainless steel, do not use cleaners that contain chlorine.
Cleaning Method:
■ Rub in direction of grain to avoid scratching or damaging the
surface.
■ Stainless Steel Cleaner and Polish Part Number 31462A (not
included): See “Assistance or Service” section to order.
■ Liquid detergent or all-purpose cleaner: Rinse with clean
water and dry with soft, lint-free cloth.
■ Glass cleaner to remove ngerprints.
Metal Grease Filter
1. Remove each lter by pulling the spring release handle
andthen pulling down the lter.
A
A. On/Off light button B. Blower off and speed minimum button C. Blower speed medium button D. Blower speed maximum button
B
C
Operating the light
The On/Off light button controls both lights. Press once forONand again for OFF.
Operating the blower
The Blower Speed buttons turn the blower On and control the blower speed and sound level for quiet operation. The speed can be changed anytime during fan operation by pressing the desired blower speed button.
Press the Blower Off button a second time to turn the blower
OFF.
A. Spring release handle
2. Wash metal lters as needed in dishwasher or hot
detergentsolution.
3. Reinstall the lter by making sure the spring release handles
are toward the front. Insert aluminum lter into upper track.
4. Push in spring release handle.
5. Push up on metal lter and release handle to latch into place.
6. Repeat steps 1-5 for the other lter.
10
Loading...
+ 22 hidden pages